Transformer Neutral CT Sizing
Home
Transformer Neutral CT Sizing
Transformer Neutral CT SizingFull description...
Author:
Pramod B.Wankhade
26 downloads
451 Views
69KB Size
Report
DOWNLOAD .PDF
Recommend Documents
CT Sizing
Siemens 7SD5 CT sizingFull description
CT sizing
InstrumentationFull description
CT sizing
CT SizingFull description
Transformer Sizing
Full description
CT Sizing
CT sizingFull description
CT-Sizing
CT SizingFull description
CT Sizing
CT sizing
Transformer Sizing
Full description
CT Sizing
CT sizingFull description
Transformer Sizing
Typical Transformer sizing CalculationsFull description
Ct Sizing XL
ctFull description
Technical CT Sizing
CT sizing Technical dataFull description
CT VT Sizing
mFull description
184306471-CT-Sizing
vsdgfsdf
CT wire sizing
CT wire sizingFull description
CT Sizing Calculations
xfgSFFull description
CT Sizing Calculation
Full description
CT wire sizing
CT wire sizingFull description
Transformer Sizing Calculation
Trafo calc.Full description
Transformer Ngr Sizing Calculation
Full description
CT Sizing Claculation
CT Sizing XLS fileFull description
184306471-CT-Sizing
vsdgfsdfFull description
CT SIZING FOR MALAWI.xls
Full description
CT Sizing Guideline
Guide Line to Size a Current Transformer from Siemens. This is good presentation of the CT applications and CT sizing guideline.Full description
DOC NO : HZL-BTN-ELE-D HZL-BTN-ELE-DS-SY-031 S-SY-031
TRANSFORMER LV NEUTRAL CT
Core I : 1.0 CT sizing calculation for 132kV ‐ Definite Time Ground O/C Protection 1.1 Basic Data: 800 /
A
Ratio
=
1
Accuracy class
= 5P10
Burden ( VA )
= 15
VA
IDMT Overcurrent Relay
= 0.1
VA
Cable Length ( m )
= 150
m
Lead resistance at 70ºC for 4mm copper ( Ω/km )
= 5.54
Ω/km
Loop Resistance ( R L) (Ω)
= 1.66
((Ω Ω)
Loop Burden ( VA )
= 1.66
VA
Total Meter Burden ( VA )
= 0.1
VA
Total Burden on CT ( VA )
= 1.76
VA
1.2 Burdens of relays of relays connected :
2
1.3 Selected burden is more than requ requir ired ed..
HENC HENCE E SAFE.
Core II : 1.0 CT sizing calculation for132kV ‐ Restricted Earth Fault Protection Fault Protection (64R) 1.1 Basic Data: Ratio
= 1000 /
Voltage ( kV )
= 6.6
Accuracy Class
= PS
Transformer rating
= 7.5
MVA
Impedence of transformer
= 8.35
%
Maximum through fault, MVA
= 7.5 x 100/8.35 = 89.82 MVA
Through Fault current at primary
I f
Through Fault current at secondary I fs
1 of 18
1 A
kV
= 89.820359281437 89.8203592814371 1 x 1000/(1.732 1000/(1.732 x6.6 = 7857.5 A = 7.857
A
DOC NO : HZL-BTN-ELE-D HZL-BTN-ELE-DS-SY-031 S-SY-031
TRANSFORMER LV NEUTRAL CT 1.2 Burdens of relays of relays connected : Restricted Earth Fault Relay lay
= 1.00
VA
Cable Length ( m )
= 100
m
2 Lead resistance at 70ºC for 4 mm copper ( Ω/km ) = 5.54
Ω/km
Loop Resistance ( R L) (Ω)
= 1.1080
Ω
= 1.1080
VA
= 2
Ω
Loop Burden ( VA )
R
Inte Intern rna al resi resist sta ance nce of CT seco secon ndary dary ( Ω) 1.3 Required Knee point Voltage point Voltage Vk
Ifs(Rct+2RL)) volt ≥ (2 x Ifs(Rct+2R ≥ 2 x7.86 x (2+ 2x1.108) ≥ 66.26
V
≥ 500
V
2 of 18
L
×
Report "Transformer Neutral CT Sizing"
Your name
Email
Reason
-Select Reason-
Pornographic
Defamatory
Illegal/Unlawful
Spam
Other Terms Of Service Violation
File a copyright complaint
Description
×
Sign In
Email
Password
Remember me
Forgot password?
Sign In
Our partners will collect data and use cookies for ad personalization and measurement.
Learn how we and our ad partner Google, collect and use data
.
Agree & close