Generator Protection
GENERATOR CONTROL AND PROTECTION
Generator Protection •
Introduction
• • • • • •
Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F)
•
Stator Ground Fault (87N, 51N, 59N, 27-3N)
GENERATOR CONTROL AND PROTECTION
Generator Protection • • • • • • • • •
Loss of Field (40Q, 40Z) Over/Under Frequency (81O/81U) Overexcitation and Overvoltage (24, 59) Out of Step (78) Negative Sequence (Current Unbalance) (46) Inadvertent Energization (27, 50, 60, 81, 62, 86) Loss of Voltage Transformer (60) System Backup (51V, 21) Conclusion
GENERATOR CONTROL AND PROTECTION
Generator Protection 63
49
25 G 51N
64F
51 60
87G
REG
62
47
27
81U
59
32-1
59N
87T
24
32-2
51
81O
40
51V
50 IE
46
273N
51GN
GENERATOR CONTROL AND PROTECTION
Steam Generator Stator Windings
GENERATOR CONTROL AND PROTECTION
Hydraulic Generator Stator / Rotor
GENERATOR CONTROL AND PROTECTION
Hydraulic Generator Stator Core
GENERATOR CONTROL AND PROTECTION
Generator Protection
GENERATOR CONTROL AND PROTECTION
Split Phase Relaying CT
GENERATOR CONTROL AND PROTECTION
Cylindrical Rotor in Need of Repair
GENERATOR CONTROL AND PROTECTION
Generator Protection
GENERATOR CONTROL AND PROTECTION
Generator Protection
GENERATOR CONTROL AND PROTECTION
Symmetrical Components •
Positive Sequence –
A set of three phasors that have the same magnitude, are equally displaced from each other by 120º, and have the same phase sequence as the system under study (ex ABC)
•
Negative Sequence –
•
A set of three phasors that have the same magnitude, are equally displaced from each other by 120º, and have the opposite phase sequence as the system under study (ex ACB)
Zero Sequence –
A set of three phasors of equal magnitude that are all in phase or have zero displacement from each other
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Symmetrical Components Example Problem •
One conductor of a three phase line is open. The current flowing to the delta connected load thru line a is 10A. With the current in line a as reference and assuming that line c is open, find the symmetrical components of the line currents.
GENERATOR CONTROL AND PROTECTION
Symmetrical Components Example Problem • Ia = 10/0° A, I b = 10/180° A, I c = 0 A • I = (1/3)(I + I + I ) a0 a b c • Ia0 = (1/3)(10/0° + 10/180° + 0) = 0 • Ia1 = (1/3)(Ia + αIb + α2 Ic ) • Ia1 = (1/3)(10/0° + 10/180+120° + 0) • Ia1 = 5.78 /-30° • Ia2 = (1/3)(Ia + α2 Ib + αIc ) • Ia2 = (1/3)(10/0° + 10/180+240° + 0) • Ia2 = 5.78 /30°
GENERATOR CONTROL AND PROTECTION
Symmetrical Components Example Problem •
Ib0 = 0
•
Ib1 = 5.78 /-150°
•
Ib2 = 5.78 /150°
•
Ic0 = 0
•
Ic1 = 5.78 /90°
•
I = 5.78 /-90° c2
GENERATOR CONTROL AND PROTECTION
Symmetrical Components Example Problem •
Ia0 = 0, Ib0 = 0, Ic0 = 0
•
Ia1 = 5.78 /-30° , I b1 = 5.78 /-150° , I c1 = 5.78 /90°
•
Ia2 = 5.78 /30° , I b2 = 5.78 /150° , I c2 = 5.78 /-90°
GENERATOR CONTROL AND PROTECTION
Symmetrical Components Example Problem •
Note: the components I c1 and Ic2 have definite values although line c is open and can carry no net current. As expected, the sum of these currents is zero.
•
The sum of the currents in line a is 10/0°
•
The sum of the currents in line b is 10/180°
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
Single Phase Line to Ground Fault GENERATOR CONTROL AND PROTECTION
Symmetrical Components
Generator Sequence Networks GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Symmetrical Components
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a Synchronous Generator
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a Synchronous Generator
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a Synchronous Generator
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a Synchronous Generator
Max DC Offset
No DC Offset
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a Synchronous Generator
GENERATOR CONTROL AND PROTECTION
Fault Current Behavior of a Synchronous Generator
GENERATOR CONTROL AND PROTECTION
Generator Grounding
GENERATOR CONTROL AND PROTECTION
Generator Grounding •Low Impedance Grounding •Single phase to ground fault current between 200A and 150% •High Impedance Grounding •Single phase to ground fault current between 5 and 20A
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault Protection (87G)
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault Protection (87G) •87G used to protect for: •3 phase line to line •1 phase line to line •multi-phase line to ground •May not be able to detect a 1 phase to ground fault on high impedance grounded generators •Restraint or Percentage Differential Trip Characteristic •Used to improve sensitivity for detecting small levels of fault current •Also maintains security against inadvertent tripping due to thru faults GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault Protection (87G)
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault Protection (87G)
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault Protection (87G) •Split-phase protection scheme •Able to detect turn-turn faults •Windings for each phase split into equal groups •Individual winding currents are vector summed •Any difference in winding current results in a output from CT •Overcurrent relay (50/51) can be used to monitor difference current •Setting must be above any normal unbalances that may exist
GENERATOR CONTROL AND PROTECTION
Generator Stator Phase Fault Protection (87G)
GENERATOR CONTROL AND PROTECTION
Generator Field Ground Fault Protection (64F)
GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault Protection (87N, 51N, 59N & 27-3N)
For Low Impedance Grounded Generators GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault Protection (87N, 51N, 59N & 27-3N)
For Low Impedance Grounded Generators GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault Protection (87N, 51N, 59N & 27-3N)
External Generator Phase-Ground Fault GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault Protection (87N, 51N, 59N & 27-3N)
External Generator Phase-Ground Fault GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault Protection (87N, 51N, 59N & 27-3N)
Internal Generator Phase-Ground Fault GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault Protection (87N, 51N, 59N & 27-3N)
Internal Generator Phase-Ground Fault GENERATOR CONTROL AND PROTECTION
Generator Stator Ground Fault Protection (87N, 51N, 59N & 27-3N)
High Impedance Grounded 50MVA, 13.2kV Generator Xc = 10,610Ω for 0.25uf @ 60Hz Rpri = 10,610/3 = 3537 Ω GENERATOR CONTROL AND PROTECTION
Loss of Field Protection (40Q, 40Z)
GENERATOR CONTROL AND PROTECTION
Loss of Field Protection (40Q, 40Z)
GENERATOR CONTROL AND PROTECTION
Loss of Field Protection (40Q, 40Z)
GENERATOR CONTROL AND PROTECTION
Over/Under Frequency Protection (81O/U) •Causes: •Significant load addition •Sudden reduction in mechanical input power •Loss of generation •Loss of load •Underfrequency can cause: •Higher generator load currents •Overexcitation •Turbine blade fatigue •Overfrequency can cause: •Overvoltage on hydro turbines GENERATOR CONTROL AND PROTECTION
Overexcitation and Overvoltage Protection (24, 59) •Modern Excitation Systems include over excitation limiting and protection, but it may take several seconds to limit •Overexcitation occurs when the V/Hz ratio exceeds 105% at FL and 110% at no load •V/Hz relays set at 110% with a 5 – 10 sec delay •Generator overvoltage can occur without exceeding V/Hz relay setting due to large over speed on hydro generator •Generator overvoltage relay, 59 may be used
GENERATOR CONTROL AND PROTECTION
Out of Step Protection (78) •High peak currents and off-frequency operation can occur when a generator losses synchronism •Causes winding stress, high rotor iron currents, pulsating torques and mechanical resonances •Conventional relaying approach – analyzing variations in apparent impedance as viewed at generator terminals •Variation in impedance can be detected by impedance relaying and generator separated before the completion of one slip cycle
GENERATOR CONTROL AND PROTECTION
Out of Step Protection (78) EA
EB ZA
ZT
ZB
A
B
Generator
Transformer
System
+X EA/EB>1
B
EA/EB=1
ZB
Q EA/EB<1
ZT -R
+R
δ
ZA A -X
GENERATOR CONTROL AND PROTECTION
P
Out of Step Protection (78) A
B X
System R Trans
P
M Gen X'd
A B Element Element Pickup Pickup
Blinder Elements
GENERATOR CONTROL AND PROTECTION
Mho Element
Negative Sequence Protection (46) •Protects generator from excessive heating in the rotor due to unbalanced stator currents •Negative sequence component of stator current induces double frequency current in rotor, causing heating •Rotor temperature rise proportion to I22t •Negative sequence relays provide settings for this relationship in the form of a constant, k = I22t •Minimum permissible continuous unbalance currents are specified (ANSI/IEEE C50.13)
GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection (27, 50, 60, 81U, 62 and 86) •Protects against closing of the generator breaker while machine is not spinning / on turning gear •Caused by operator error, breaker flash-over, control circuit malfunction •Two schemes illustrated: •Frequency supervised overcurrent •Voltage supervised overcurrent
GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection Frequency Supervised Overcurrent +DC
50 (3-phase)
G
81U 62 60
50
60 81U
86 0.5sec Pickup 0.1sec Dropout
62
86
-DC
GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection Frequency Supervised Overcurrent • Uses an underfrequency instantaneous overcurrentrelay relay(81U) (50) to enable a sensitive • Overcurrent relay picks up at 50% or less of expected inadvertent energizing current • Frequency relay contacts must remain closed if sensing voltage goes to zero • Voltage balance relay (60) protects against loss of sensing • Time delay relay (62) protects against sudden application of nominal voltage during inadvertent energization, allowing overcurrent to trip lockout relay (86) • Lockout relay must be manually reset GENERATOR CONTROL AND PROTECTION
Inadvertent Energization Protection Voltage Supervised Overcurrent •Same illustration as frequency supervised overcurrent except 81U replaced by 27 •Undervoltage setpoint of 85% of the lowest expected emergency operating level
GENERATOR CONTROL AND PROTECTION
Loss of Voltage Transformer Protection (60) •• • • • •
Common large systems to use two or more VTs One used practice for relaysonand metering The other used for AVR VTs normally fused Most common cause of failure is fuse failure Loss of VT protection blocks voltage based protective functions (21, 32, 40 … etc) • Loss of VT protection measure voltage unbalance, typical setting is 15%
GENERATOR CONTROL AND PROTECTION
Loss of Voltage Transformer Protection (60) G vt
60
To Protective Relays
To Excitation Controller
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
• Common practice to provide protection for faults outside of the generator zone of protection • Voltage supervised time-overcurrent (51V) or distance relaying (21) may be used • Distance relay set to include generator step up transformer and reach beyond, into the system • Time delays must be coordinated with those of the system protection to assure that system protection will operate before back up • CTs on neutral side of generator will also provide backup protection for the generator GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
G
21 51V
a.) Neutral Connected ct's GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21)
• For medium and smalltime sized generators, voltage-restrained or voltage controlled overcurrent relays (51V) are often applied • Control or restraining function used to prevent or desensitize the overcurrent relay from tripping until the generator voltage is reduced by a fault
GENERATOR CONTROL AND PROTECTION
System Backup Protection (51V, 21) Enable
100% p u k ic P r o f
e l b a n E /t i ib h n I p u k c i P
e lu a V t e S t n e c r e P
Inhibit
25%
25%
Percent Nominal Volts
100%
a.) Voltage-Restrained Overcurrent
Percent Nominal Volts
80%
100%
b.) Voltage-Contolled O vercurrent
GENERATOR CONTROL AND PROTECTION
Conclusion
• Generators be protected from electrical faults, mechanical must problem and adverse system conditions • Some faults require immediate attention (shutdown) while others just require alarming or transfer to redundant controllers • Design of these systems requires extensive understanding of generator protection • Further study – IEEE C37.102 Guide for AC Generator Protective Relaying
GENERATOR CONTROL AND PROTECTION