This guide instructs that how to configur BTS3900 in the BSC6000.also that how to implement BTS swap.All the operations is based on the LMT and MML. The content of this guide is as below: 1, Main process of BTS configuration 2, Alarm configuration for BTS 3, Data configuration for BTS swap
2009-7-2
Page2, Total17
BTS3900 Configuration
Level: internal
1. Main process of BTS configuration Keep the same configuartion with site “Batna CCLT 05503” in the Batna. Step1: add site
Step2: add cell
2009-7-2
Page3, Total17
BTS3900 Configuration
Level: internal
Step3: set attributes
2009-7-2
Page4, Total17
BTS3900 Configuration
Level: internal
Step4: add FMU and GATM board (Each BTS3900 is configured with 6 DRFU.1 FMU.1 GATM.1 BBU.) Add FMU in slot 8 and GATM in slot 17, because the monitor signal cable of FMU and GATM are connected to “MON0” and “MON1” of UPEU separately.which keeps the confiuration same with the practical installation.
2009-7-2
Page5, Total17
BTS3900 Configuration
Level: internal
Step5: add RXU Chain
2009-7-2
Page6, Total17
BTS3900 Configuration
Level: internal
Use the RF cable connection tool to generate the connection. For the site 05503(S4/4/4) is as below:
2009-7-2
Page7, Total17
BTS3900 Configuration
Level: internal
Step6: add RXU (RFU) Principia for RXU’s name: PortX_SlotX_PosX. PortX: Port No. X of GTMU SlotX: Slot No. X of DRFU PosX: Position No.X of the DRFU in the chain.
Keep confiuration same with the practical connection.Finally the RXU chain topo is as below.
2009-7-2
Page8, Total17
BTS3900 Configuration
Level: internal
Step7: bind logical TRX From Trx No.0 to Trx No.11
Step8: Set TRX attributes (Send Receive Mode)
2009-7-2
Page9, Total17
BTS3900 Configuration
Level: internal
Set the “Send Receive Mode” due to pratical situation. Because just one ANT port of DRFU is used, the “Single Antenna Double Receiver” is chosen.
Step9: Set cell attributes Almost the configuration process is same with BSC32. One parameter should be cared, which is”Power Type”. “20W” is chosen due to the Send Receive Mode.
2009-7-2
Page10, Total17
BTS3900 Configuration
Level: internal
2. Alarm configuration for BTS3900 The BBU can support 2 RS485 bus and 16 line of on-off alarm maximally. There are just 1 UPEU configured in BTS3900 in the packeting list. The No. of on-off alarm for UPEU is as below.
The monitor signal of DCDU-01 is connected to No.8 alarm of EXT-ALM0 of UPEU. Step1: set site attributes
Step2: set Alarm Shield Flag 2 (Hex) The 8 bits (from low to high) of alarm sheild flag 2 determines the No.8-15 on-off alarm. 0 means “shield”, 1 means “non-shield”. The alarm sheild flag 2 is set as “01” to enable the DCDU-01 arlarm.
2009-7-2
Page11, Total17
BTS3900 Configuration
Level: internal
Step3: set Alarm Voltage Definition
2009-7-2
Page12, Total17
BTS3900 Configuration
Level: internal
Step4: set external alarm port Set the external alarm port for the on-off alarm of the UPEU as below.
Step5: name the external alarm Click the “Alarm Matintenance” in the LMT mean
Find the No.5048 alarm.then right-click it.choose as below.
2009-7-2
Page13, Total17
BTS3900 Configuration
Level: internal
Set the Alarm name.
2009-7-2
Page14, Total17
BTS3900 Configuration
Level: internal
3. Data configuration for BTS swap Step1: configure the site with LMT in offline mode Note: Configure the site on the same slot and port as the site to be swapped.
Step2: export the site data in offline mode
It will take about 5 minutes to export one site data. Step3: backup the data of the swapped site in online mode Note: do this after blocking the site.
2009-7-2
Page15, Total17
BTS3900 Configuration
Level: internal
The exported result is the format of text as above, which will be used to edit the adjacent cell for BTS3900 later. Step4: delete the swapped site in online mode
Step5: import the data in online mode
2009-7-2
Page16, Total17
BTS3900 Configuration
Level: internal
The log above indicates that importing is successful. Step6: edit the MML script Use the “UltraEdit” tool to edit the exported file named”BTS3900 adjacent cell” above. Comman”ADD CELL2GNC” will be used to add adjacent cell. It’s very to edit the MML script with the “UltraEdit” tool in column mode. Take care the”Bidirectional Adjacent Cell”and”Single directional Adjacent Cell”! For the the”Bidirectional Adjacent Cell”, command” ADD CELL2GNC” should be executed twice to add adjacent cell in both cell. Step7: execute the MML script in batch Log in the MML and execute the script”BTS3900 adjacent cell” in batch.