Two comparators of a quad OPAMP IC is used to form a window comparator for sensing low / high input voltage while their 'OR' logic wired output drives a relay to cut-off the load beyond a specified...Full description
Bullah Piling rate analysisFull description
Two comparators of a quad OPAMP IC is used to form a window comparator for sensing low / high input voltage while their 'OR' logic wired output drives a relay to cut-off the load beyond a specified...
test voltagesDescription complète
Another book from ARAMCO series of Engineering Desktop Standards encyclopedia.Descripción completa
notesFull description
Full description
test voltagesDescripción completa
test voltagesFull description
fire safety risk analysisDeskripsi lengkap
Engineering Summary ReportFull description
Full description
kmbFull description
descripyion check valve
Descripción completa
As of late, as disseminated age, new loads and new FACTS gadgets generally utilized, the current voltage control innovation of network have been not able meet the new necessities under the new circumstance on the control goals, control methodology an
elektrikalDeskripsi lengkap
elektrikal
Topic:
REL316*4 Technology and Solutions Protection and Substation Automation
On several auto-reclosing cycle, only the first cycle can be single pole tripping with fast auto-reclosing Following auto-reclosing cycles must be three phase tripping and reclosing The line protection must provide single phase trip for the first fault, following faults must be tripped three phase RE.316_AR_Syn / 2003-10-01 / RW
The closing command always goes to all three phases
ABB
REL316*4
79 - Rules / Facts
No synchro check is needed for fast single phase reclosing (Sychro-check by-pass) The system will not loose synchronity: 3 of 4 conductors (2 phases and ground) are still in service During the pause time the line still transmits more than 50% of the maximum power
If AR is not ready for a single cycle, the tripping circuit must be prepared or switched to 3-phase tripping Reasons for AR not ready: - AR blocked or switched off - AR blocked with t inhibit after reclosing (CB recovery time) - Fast AR dead time expired - No 1- pole AR permitted
ABB
REL316*4
79 - Rules / Facts
During the 1-pole dead time (one pole from the breaker is open) all other functions who react on unsymmetry and have a shorter tripping time then t-dead-1P-setting must be blocked Example: - Directional earth fault with tripping scheme POTT
1-pole dead time (t dead 1P) 3-pole dead time (t dead 3P) Operating time (t oper) Discrimination time (t discrim.1P, t discrim.3P) Blocking time (t AR Block)
One pole opens and closes after t-dead -1P Typical dead time: 0.3 – 0.5 s in high voltage systems All 3 pole open and close after t-dead-3P Typical dead time: 0.5 s – sev. minutes Prevents an AR for a long during fault (eg. in the 2nd zone) Decision about 1-pole AR, 3 pole AR or definitive trip after evolving fault Prolongation of the AR blocking after a manual close command or after close command from the control system
Blocking of the AR for 5 ….. 180 s after an unsuccessful AR attempt.t inhibit is also called recovery time. The breaker needs time to be ready for a new AR cycle Must be long enough to make sure the breaker closes properly. The close pulse is reset direct after an unsuccessful AR attempt.
Open circuit breaker blocks the AR device. During a running AR cycle the position of the breaker is not interrogated. This prevents under all circumstances an AR for a switched off CB The breaker is able to switch on to a fault and to open again. This information is interrogated direct before re-closing The breaker is able to do a complete AR cycle This input is not interrogated during a running AR cycle.
If the AR function operates two breakers the supervision signals are needed from both breakers.
With the opening of the breaker the voltage which supplies the arc is switched off ⇒ the arc will extinguish The dead time is set as short as possible. So the line can be back in normal service as fast as possible. If the arc is not extinguished with the first AR attempt (tree, bamboo) a second attempt with a longer dead time will be started (2nd and 3rd attempt are 3-phase cycles) This attempt is just an automatic voltage check One side will be switched on. An immediate trip occurs if the fault is still present. The opposite station will only reclose if the line was successful energized from the own station (Synchro- & V - Check) normally not applied in high voltage systems
ABB
REL316*4
79 - Function of the operating time t-oper
Supervision of the fault duration is important in distance protection
Fault duration < operating time Example: Trip in zone 1 initates an AR cycle
Fault duration > operating time Example: Trip in a higher zone stops the a fast AR cycle Starting
AR Mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase fault Example: - fast AR not successful, - slow AR successful
Starting 1-phase Tripping 1-pole Discrimination time 1-pole On-pulse, interrupted with second tripping Dead time fast AR 1-pole, Starting 1-phase Tripping 3-pole
Mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase fault Example: - Evolving fault before expiring of discrimination time - fast AR not successful, slow AR successful Starting 1-phase Tripping 1-pole Discrimination time 1-pole Dead time 1-pole, interrupted with 2nd fault before expiring of 3-pole discrimination time Starting 1-phase(other phase) Tripping 3-pole Discrimination time 3-pole On-pulse, interrupted with tripping Dead time fast AR 3-pole Starting 1-phase
Dead time slow AR Q0 Phase R Q0 Phase S Q0 Phase T
fast AR 1-pole interrupted
fast AR 3-pole
Slow AR
ABB
REL316*4
79 - Examples
AR mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase fault Example: - Evolving fault after expiring of discrimination time of fast AR - Definitive tripping
Starting 1-phase Tripping 1-pole Discrimination time 1-pole
The Follower re-closes only after successful re-closing of the Master. In case the master is not ready for an ARcycle a signal will be send to the follower. The follower will now re-close in the set dead time.
• Only one phase to phase voltage is used for the synchro-check Reasons: • A three phase measuring is not needed because the synchro-check is only needed for 3-phase faults
• For 1-phase AR the synchro-check is bypassed • Phase to ground voltage should not be used. The natural zero sequence voltage disturbs in the medium voltage system the sychro-check measuring