Power Transformer Design Aspect
Didik Susilo Widianto Technical Director
PT UNINDO – AREVA
Contents
1.
Introduction
2. Transformer core 3.
Inrush Current
4. Transformer Winding 5.
Insulation and Cooling Medium
6.
Transformer Losses
7.
Insulation Structure & Dielectric Withstand
8.
Transformer Thermal Aspect
9.
Short Circuit Analysis
10. Engineering 11. Manufacturing Process 12. Accessories, Protection & control 13. Final Acceptance Test 14. Technology Application 3
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
3
1. Introduction
4
> Title of presentation - Date - References
4
Basic Theory Faraday ’ ’s law The electromotive force ( e.m.f ) is proportional to e.m.f the rate of linked flux changes
E = - N x dΦ/dt E = Electro motive force N = Number of turn dΦ/dt = Change the flux against time
Lenz ’ ’s law The e.m.f is such any current produced acts to opposite the linked flux. Current Flux Current Counter Flux
5
> Title of presentation - Date - References
5
NO LOAD Condition
E = - N dΦ/dt = - N d(Φm Sin(ωt))/ dt = - Nω. ΦmSin(ωt – π/2) At f = 50 Hz, Φ = Β.Α E = 222.14 . Ν.Β.Α At f = 60 Hz, E = 222.14 .N.B.A.(f/50)
E1
E = e.m.f (electromotive force) in Volt Φ = Flux in Weber B = Peak Induction in Tesla A = Core cross section in
I0
Ip
Φ
m2
I0 = No load current in Amp.
Im
I0
Im = Magnetizing current in Amp. Ip = Losses current in Amp.
E2
E1
E2 N1 6
> Title of presentation - Date - References
N2 6
ON LOAD Condition
V1 I2
I0 + I1
R2
I 1.X 1
X2
I 1.R 1
X1
R1
V1
E1 E2
E1 N1
V2
I1 Ip
N2
E 1 : N 1 = E 2 : N 2 I 1 x N 1 = I 2 x N 2
I1 + I0 I0
I2
Im
Φ
Θ Θ
V2 I 2 R 2
Θ 7
= the load power factor
> Title of presentation - Date - References
I 2 .X 2
E2 7
Power Transformer Main Parts Oil Preservation
Bushing Core Transformer Tank Winding Control Cubicle
Cooler 8
> Title of presentation - Date - References
Transformer Liquid 8
Transformer Power Rating Transformer power rating is expressed by MVA as a product of
rating voltage and rating current. The power rating [S] is a product of reactive power [Q] and
active power [P];
S [MVA] = S(Q2 [MVAR] + P2 [MW] ) Referring to IEC 60076 – 1;
S [MVA] = S S3 x E2[kV] x I2[Amp] 10-3 Referring to ANSI/IEEE C57.12.00;
S [MVA] = S S3 x V2[kV] x I2[Amp] 10-3 = S S3 x (E2 + ∆V)[kV] x I2[Amp] 10-3 Hence, in ANSI/IEEE standard the power rating has considered voltage drop at stated power factor
9
> Title of presentation - Date - References
9
Voltage Drop/Rise
∆V = V 2 – V 1 R2
I2
I1
X2
X1
R1
V1
E2
E1 N1
V2
N2
∆V = K (VR.CosΘ + VX.SinΘ) + K2/200 x (VR.Sin Θ – VX.CosΘ)
V Z
V X
Θ Θ
∆V K V R V X V Z Θ Θ
= Voltage drop/rise [%] = Loading factor = Transformer resistance [%] = Transformer reactance [%] = Transformer impedance [%] = Load power factor
V R 10
> Title of presentation - Date - References
10
Tap Regulation Tap Regulation ; the required voltage ratio to control the
fluctuated voltage of network to deliver the expected constant voltage. Two type of tap regulator = Tap Changer ;
1.OLTC (On Load Tap Changer) = Tap regulation when the transformer energized/under loading. 2.OCTC (Off Circuit Tap Changer) = Tap regulation when the transformer de-energized (no transformer terminal is connected to any network/generator) Tap regulation is expressed by the number of step & the
percentage of nominal voltage for each step regulation. Example = 150 kV + 7 x 1.5% / -10 x 1.5%
11
> Title of presentation - Date - References
11
Flux Behavior Due To Tap Regulation Two type of tap regulation ; CFVV = Constant Flux Variable Voltage
The transformer volt/turn as well as the core flux will constant along the tap regulated positions. This is the most common tap regulation system.
VFVV = Variable Flux Variable Voltage
12
The transformer volt/turn as well as the core flux will vary referring to the tap regulated positions. This is used due to high current tap regulation at furnace application or booster type regulation.
> Title of presentation - Date - References
12
Position Of Tap Changer
Normally, the most optimum solution for tap changer
location is the neutral end of winding for STAR connected winding. For DELTA connected winding with insulation class of
72.5 kV and lower, the line end location of tap changer is normally the most optimum solution. For DELTA connected winding with insulation class
higher than 72.5 kV class, the middle electrical location of tap changer will be the optimum. The electrically as well as geometrically location of tap
changer will also determine the impedance & losses behavior.
13
> Title of presentation - Date - References
13
Tap Regulation vs Power Rating There are two kinds of power rating; CONSTANT Power Rating;
The power is constant for all tap regulation position. REDUCED Power Rating;
The power is reduced with constant current rating from a certain tap regulation position.
Constant Power S V
Tap 1
14
Reduced Power from tap n V
I
n
> Title of presentation - Date - References
p
Tap 1
S I
n
p
14
Autotransformer Concept Seri Winding
I2 = Is
Ns = N2 – N1
Tap Changer I1 V2 V1
I1, I2
N1 = Nc
Ic = I1 – I2
Common Winding
= Current primary (1) & secondary (2)
V1, V2 = Voltage primary (1) & secondary (2) Common Winding = N1 x (I1 – I2) Seri Winding = (N2 – N1) x I2 15
> Title of presentation - Date - References
15
On Load Tap Changer
ON TANK OLTC
16
> Title of presentation - Date - References
IN TANK OLTC
16
ACTIVE PART - Areva definitions Upper Yoke
Frame Insulation
Top Frame
Tank Location Cup
Coil Clamping Block Cross Brace Top Platform
Tie Rod
Bottom Platform
Flux Packet Coil Support Blocks Oil Diaphragm Tank Base 17
> Title of presentation - Date - References
17
2. Transformer Core
18
> Title of presentation - Date - References
18
CORE Purpose :
the path for the flux lines with low magnetic reluctance
Core material in power transformer ; Cold Rolled Grain Oriented Silicon Steel. Available thickness = 0.23 mm, 0.27 mm, 0.30 mm Lamination insulation = CARLITE 0.012 mm Grade ; Conventional Grain Oriented = High losses. Hi-B Grain Oriented
= Medium losses.
Laser/plasma refinement GO = Low losses.
19
> Title of presentation - Date - References
19
Induction vs Core Loss
20
> Title of presentation - Date - References
20
Core Stacking - Mitred Joints
But Lap Joint
Step Lap Joint
21
> Title of presentation - Date - References
21
Core Cutting
Three Legs Core
½ W
W
Five Legs Core (3 wounds + 2 return) 22
> Title of presentation - Date - References
22
Bandaged Core
23
> Title of presentation - Date - References
23
Core Determination Factors No Load Loss (and No Load Current) ;
No load loss is independent with the loading of the transformer, but it is
dependent with the applied voltage per turn of the winding. It has more significant economical component cost in capitalization than other
losses due to it’s appearance independency with the cyclic loading. IEC standard tolerance for no load loss = +15%, no load current = +30%. Over excitation capability ;
For generator application, the transformer shall be designed for over excitation
up to 140% in 5 second during load rejection. For distribution application (and general purpose), the transformer has to be
designed by considering
Over voltage up to 110% continuous at no load condition.
Over voltage up to 105% continuous at full load condition.
Core temperature limit at required maximum ambient temperature (Design limit < 140oC at center, < 105oC at surface to avoid gassing).
Sound power / sound pressure level.
The local regulation for sound pressure/sound power limit. Installation location ; populated area, remote area. 24
> Title of presentation - Date - References
24
Core Saturation Capability For Load Rejection
145 140 n135 o i t a130 t i c x 125 E t n e120 c r e P 115
110 105 0.1
25
> Title of presentation - Date - References
1
Time - Minutes
10
100
25
3. Inrush Current
26
> Title of presentation - Date - References
26
Definition Inrush Current is the excitation current that will occur due to the existence of magnetic flux remnant when the transformer is first switched into the service.
The inrush current can have the peak value up to 5 times the nominal current. The most unfavorable inrush current arises when switching in take place at a zero voltage transition.
Due to the magnitude of the inrush current, the over current relay may interpret this current as the failure current to open the circuit breaker on the system.
27
> Title of presentation - Date - References
27
Inrush Current Calculation Maximum Inrush Current can be estimated with the some
empirical factors referring to the core stacking method, gap between core and the first excited winding, primary winding connection, network & transformer impedance and transformer core behavior. This is an important information to determine the over current and differential relays setting point. The actual inrush current is difficult to be estimated as this will
be dependent to the existence of remanence flux due to previous system cut out at certain voltage angle. Maximum inrush current estimation method;
Empirical formula. Electromagnetic transient computer software;
28
EMTP (Electro Magnetic Transient Program), CANADA.
SLIM – electromagnetic function, AREVA
> Title of presentation - Date - References
28
Estimating Inrush Current Empirical formula to calculate the peak of inrush current is as followings; S2.U
I peak = Z . Sin(ωt – y) – e-(t-t0)/τ.SinQ). K t Where;
29
K
= Constanta value referring to the transformer connection (Grounded STAR, DELTA) and other circumstantial.
U
= Applied voltage (rms)
Zt
= Transformer + network impedance.
y
= Energization angle.
τ
= Transformer time constant.
t
= Core saturation time referring to maximum, remnant & saturation induction behaviour.
Q
= Angle function of core induction.
> Title of presentation - Date - References
29
Some Aspect Effecting Inrush Current Transformer number of phases and primary winding
connections; Single phase transformer and/or shell type has higher inrush current than three phase transformer and/or core type. DELTA connection of primary winding three phase transformer has lower inrush current than grounded STAR. Transformer capacity; Higher transformer MVA rating has lower ratio between inrush current and primary nominal current, but longer decay time. Transformer core steel, core design and nominal induction; HiB core steel has lower inrush current than CRGO material. But lap joint has lower inrush current than Step lap joint. Lower impedance transformer normally has lower air core reactance and then higher inrush current.
30
> Title of presentation - Date - References
30
B
Flux nominal + remnant
Φrem
H
time Flux nominal nomina l
Inrush current Excitation current
31
> Title of presentation - Date - References
e m i t
31
4. Transformer Windings
32
> Title of presentation - Date - References
32
Winding
Type of winding; Layer winding;
Single layer.
Multilayer.
Helical winding. Disc winding.
Plain/continuous disc
Intershielded disc.
Interleaved disc.
Multistart winding. 33
> Title of presentation - Date - References
33
Winding Conductor Type of material conductor; Electrolytic copper. Aluminum.
Form of conductor; Round wire.( for small distribution transformer) Rectangular wire. Twin/Tripple/Quadrople conductor. CTC (Continuous Transposed Cable). Netting-CTC/Paper less CTC 34
> Title of presentation - Date - References
34
Winding – Areva terminology Axial/Radial Packing for transposition
Directed Oil Flow washers External DOF washer Internal DOF washer Transposition set Segment Spacer
35
> Title of presentation - Date - References
35
Disc Winding
PROTECTION FOR SCISSOR EFFECT
Extra paper = 2 layers overlapped of Clupack
36
> Title of presentation - Date - References
36
CTCs winding
Epoxy bonded
Try to use CTC with max. 55 strands per cable. Epoxy bonded in low chip type is recommended for force capability. Strand thickness 1.2 mm to 2.6 mm. Strand width 5.0 mm to 12.5 mm. Insulation increase of each strand = 0.10 PVA + 0.05 low chip epoxy. Insulation increase of bundle, minimum 0.50 mm. Minimum key spacer thickness for ZIG-ZAG cooling = 4.0 mm.
37
> Title of presentation - Date - References
37
Soft Cross Over for CTC – DISC winding Missing turn block = 1 cable thick
Inside cross over protection
Cross over block = thick pressboard
38
> Title of presentation - Date - References
38
Heavy current helical winding
39
> Title of presentation - Date - References
39
Intershielded Disc Winding
Provide the best controllable high frequency dielectric voltage distribution 40
> Title of presentation - Date - References
40
Intershield Disc Winding Technology Research
In 2007 : To Tests Models ISDW With Few Turns/Disc With Results To Be
Used As Input For The Design Of A Full Size 800 kV UHVDC ISDW Prototype
To Design With EDT&PD Team; To Build And To Test A Full Size 800 kV
UHVDC ISDW Prototype
41
> Title of presentation - Date - References
41
Intershielded Disc Winding
42
> Title of presentation - Date - References
42
5. Insulation and Cooling Medium
43
> Title of presentation - Date - References
43
Cooling Medium
INTERNAL COOLING MEDIUM
Besides the thermal absorption, the internal cooling medium also functions as the insulation medium.
Class A;
44
Mineral oil (Inhibited or Un -inhibited oil).
Class K;
Silicon oil
Synthetic ester
Hi-Temp natural liquid (seeds).
> Title of presentation - Date - References
44
Oil Molecules
45
> Title of presentation - Date - References
45
Oil Specification
46
> Title of presentation - Date - References
46
Oil Finger Print
47
> Title of presentation - Date - References
47
Oil ’ ’s Aromatic Check (Sulphur Content and other)
48
> Title of presentation - Date - References
48
Future – Environmental Friendly Liquid Environmental liquid
= Enviro-Temp FR3 by COOPER
Inhibited oil
= Nitro 10XT by NYNAS
Property – typical values
Inhibited oil
FR3
0.08% per Wt
n.a.
500 hours
continuous
25%
100%
80 ppm
1200 ppm
60/65/78 K
80/110/130 K
Flash point
145oC
330oC
Pour point
-57oC
-18oC
Antioxidant, phenols Oxidation stability by 120oC Biodegradable in 21 days Saturated moisture at 25oC Temp. rise for unity life time *)
49
> Title of presentation - Date - References
49
Natural ester dielectric behavior Dielectric Strength versus Water Content 80
) V k ( n w o d k a e r B c i r t c e l e i D 6 1 8 1 D
70 60 50 40 30 Envirotemp FR3 fluid conventional transformer oil
20 10 0 0
100
200
300
400
500
600
Water Content (ppm)
50
> Title of presentation - Date - References
50
Eco - -Design/vegetable D esign/vegetable oil transformer History ; ;
2005: order for joint development with customers of vegetable oil transformers 2006: oil characteristics review and prototype transformers design, manufacture and test 2007 Q1: commissioning and monitoring of 90MVA 132kV transformer in UK 2007 : devel of PTR design rules book, oil specification , manufacturing and filling process , maintenance rules and nominal parameters 2007 : commercial agreement with oil supplier Cooper for local vegetable oil distribution.
Achievement Environmentally friendly transformers and reactors
filled with vegetable oil
Vegetable oil totally biodegradable , with higher fire point
than mineral oil (envirotempFR3 oil from COOPER) transformers and reactors up to 245kV, and rated power up to 100 MVA (existing new references) Application for Higher ratings to be evaluated if potential for joint development with customers
51
> Title of presentation - Date - References
51
6. Transformer Losses
52
> Title of presentation - Date - References
52
Power Transformer Losses Losses is the active energy component
to be absorbed by the transformer and associated component such as fan, pump, control circuit. Mainly this losses will become the heat energy. Losses contain; Core loss = No load loss. Load loss Auxiliary loss
53
> Title of presentation - Date - References
53
Core Loss Core Loss = No Load Loss ; is the loss of the
energy when the transformer under no load condition (the primary terminal is connected to the power source, the secondary/tertiary etc are open). This loss is expressed by Watt or kWatt. Core loss contains; Hysteresis loss; The magnetic power that inherently
absorbed due to the magnetic behavior of the transformer core material. This energy is required to realign the magnetic domain for the flux at certain time.
Eddy-current loss; The loss of active power caused by
the circulating current as the result from the perpendicular flux into the core plate with it’s resistive component characteristic. Thinner plate will give lower eddy-current loss of core material.
54
> Title of presentation - Date - References
54
Hysteresis Core Loss
B max [T] P h = k h .f.B max n k h = Hysteresis constant depend on the 3 to 20x10 - 3 3 ) core material (3x10 - 3
n = Exponent varies from 0.5 to 2.3 dependent on the core material
δ δB B
H peak [A/m]
55
> Title of presentation - Date - References
55
Eddy - -Current C urrent core loss
P e = k e .f 2 .t 2 .B max 2 k e = Constant depends on the core grade, typical values = 200 to 1000 t = core plate thickness [m]
B
t
56
> Title of presentation - Date - References
56
Load Loss The current flowing through the windings
of a loaded transformer will create loss energy in the form of heat. The load loss is normally expressed at
75oC or 85oC. 85oC shall use thermally upgraded paper
This load loss is containing DC losses = the dominant component loss is caused by
the product of current to the DC resistance of winding conductor
Stray losses = the loss is caused by the leakage
magnetic impinging on the winding conductor and other internal conductive material inside the transformer.
57
> Title of presentation - Date - References
57
DC loss
1
2
3
DC losses = I 12 R dc1 + I 2 2 (R dc2 + R dc3 ) R dc = ρ . L/A I1, I2 = current flowing in winding 1,2,3 [A] Rdc = DC resistance of each winding. [Ω] ρ = winding conductor resistivity. [Ωm] L = Length of winding conductor. [m] A = Winding conductor cross section. [m 2] 58
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
58
Winding Conductor Property
Propeties
Unit
Copper
Aluminum
Conductivity
% IACS
100
60.97
Resistivity@20oC
ρ (Ω.m)
1.7241 x 10-8
2.8280 x 10-8
K
235
225
Kg/m3
8890
2703
Temperature reference
Specific mass
59
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
59
Conductivity vs temperature For Copper at temperature T1 and T2
ρ2 = ρ1 x (235 + T2) / (235 + T1) Resistivity at 75oC = 2.1 x 10-8 Ωm. DC loss at 75oC in Watt = 2.36 x 10-12.τ2.M
τ = curr current ent den density sity [A/m2]
M = conductor mass [kg]
For Aluminum at temperature T1 and T2
ρ2 = ρ1 x (225 + T2) / (225 + T1) Resistivity at 75oC = 3.46 x 10-8 Ωm. DC loss at 75oC in Watt = 12.8 x 10-12.τ2.M
60
current ent den density sity [A/m2] τ = curr M = conductor mass [kg]
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
60
Eddy Current Loss in AC system When the winding is AC (Alternating Current) loaded, the
leakage flux impinges on the winding conductors and as a consequence eddy currents are generated in these conductors. This eddy current will push the distributed current on the skin area of conductor. This phenomena is known as SKIN EFFECT.
Conductor
Flux line
AC current line 61
> Title of presentation - Date - References
61
Eddy loss distribution
The eddy loss distribution is not uniform along the winding. Normally the eddy losses at winding end is higher than at winding middle. It is important to control the eddy loss at top end winding to avoid very high hot spot gradient temperature. Brad B rad
Brad
1
2
1 62
> Title of presentation - Date - References
2 62
Stray losses of inside metallic parts & tank Inside tank of a power transformer is containing a lot
number of leakage flux. The higher transformer impedance will result the bigger
number of leakage flux. Leakage flux impinging onto metallic structural parts and
tank wall + cover will contribute the additional load loss. This loss is normally controlled between 5% to 15% of the total load losses. This additional loss due to leakage flux is controlled by
the following methods; Magnetic shunt panel to collect the leakage flux. Copper or aluminum flux rejecter. A-magnetic metallic part. Splitting the wide plate width.
63
> Title of presentation - Date - References
63
Infra Red Thermal Investigation
Infra Red Thermal Check To avoid local hot spot > 125oC
64
> Title of presentation - Date - References
64
7. Insulation Structure & Dielectric Withstand
65
> Title of presentation - Date - References
65
Dielectric Voltage Withstand Test International standard reference; SPLN IEC 60076 part 3. ANSI/IEEE C57.12.00 & C57.12.10
Continuous over voltage up to 110% no load, 105% full load
condition. Applied voltage withstand = the over voltage withstand between
each winding to other part in the transformer for one minute. Induced voltage withstand = the over voltage withstand between
each turn and/or disc of each winding and the winding to earth for few seconds dependent on the testing frequency 120 x fnetwork /ftesting [seconds]. This over voltage may have magnitude up to twice of nominal voltage. Transient over voltage withstand = the over voltage withstand due
to switching and /or lightning. The wave shape has duration up to few microseconds with it’s instantaneous peak over voltage withstand may have magnitude up to 3.5 times the nominal peak voltage for
66
> Title of presentation - Date - References
66
IEC Standard Insulation Level
67
Highest voltage
Power frequency
(kV r.m.s)
(kV r.m.s)
7.2
Full wave impulse (kV peak)
Minimum air clearance (mm)
20
60
90
12
28
75
110
17.5
38
95
170
24
50
125
210
36
70
170
280
72.5
140
325
630
115
185
450
830
123
230
550
900
170
275
650
1250
325
750
1450
245
395
950
1900
2250
300
460
1050
2300
2650
362
510
1175
2700
3100
> Title of presentation - Date - References
67
Voltage Withstand Criterium No Flash over (puncture and creepage) Partial Discharge under requirements; Less than 100 pC at 110% voltage. Less than 300 pC at 130% voltage. Less than 500 pC at 150% voltage.
FREE PARTIAL DISCHARGE ;
68
Less than 50 pC at 150% voltage.
> Title of presentation - Date - References
68
INSULATION Coordination
»The
Radial and Axial stresses between windings and to Earth have to be managed by an insulation structure which considers the combined individual stresses.
»This
structure has to consider both electrical requirements and thermal requirements for oil flow
»It
has to consider the effects of voltage transients and the problems of manufacture and processing
»It
has to be economic using minimum clearances and minimum of expensive components.
69
> Title of presentation - Date - References
69
Oil Strength Behavior
70
> Title of presentation - Date - References
70
Water Content in Paper
»0.5% dryness PD PD inception voltage is 83% induced voltage. »1.0% dryness PD PD inception voltage is 41% induced volatge .
71
> Title of presentation - Date - References
71
Water Content Equilibrium
72
> Title of presentation - Date - References
72
Dryness of insulation vs voltage withstand Water Content in paper shall be less than 0.5% (from 17% originally). Oil breakdown shall be greater than 60 kVrms/2.5 mm (IEC) from 30 kV/2.5 mm.
73
> Title of presentation - Date - References
73
Transformer Active Part Insulation: a. MINOR INSULATION : Insulation between individual sections and pairs of discs in a winding or inter turn of layer winding. b. MAJOR INSULATION : Insulation between windings c. END INSULATION : Insulation between windings and the core. d. LEAD INSULATION : Insulation on exit leads. e. CLEAT BAR : Insulation on interconnecting leads 74
> Title of presentation - Date - References
74
Top End Insulation
Optimised number of angle rings Stress Ring Profile
Standard Block thickness
Standard Oil Ducts
75
> Title of presentation - Date - References
75
Cleat bar clearances
A = Cylinder to Plane OR treat as Tie Rod profile for analysis. B = Cylinder to Plane. C = Cylinder to plane. D & E will affect calculation limits. F = Point to Plane ?
76
> Title of presentation - Date - References
76
FEM Models
High Voltage Stress Detection 77
> Title of presentation - Date - References
77
Insulation Structures Validation Criteria
Peak Stress in paper coverings Peak Stress in Oil adjacent to covered electrodes Peak and Average Stress in Oil ducts Cumulative Stress in Oil Bulk Oil Volume Stresses Peak and Cumulative Creep Stress Failure Probability of small oil volumes at peak
stress
78
> Title of presentation - Date - References
78
608 series (4% grading): Bulk oil stress critical path from HV winding to LV winding 100
] m m / V 10 k [ | E |
²
stress (absolute value) cumulative stress Strength gas saturated oil Strength degassed oil 1 0
5
10
15
20
25
30
35
40
45
50
path [mm]
Stress in duct next to HV Stress Ring 79
> Title of presentation - Date - References
79
ACTIVE PART - clearances Creep is an electrical failure using a solid object as a path Electrical Creep = Y
Y
80
> Title of presentation - Date - References
80
ACTIVE PART (coil erection cleat bar) Tap changer (or Tap switch)
HV Line Lead T&D
Tap lead connections
Tap lead connections 81 PTR Quality
> Title of presentation - Date - References
Cable Run/Channel 81
Bus Bar Connection For High Current Lead Exit 82
> Title of presentation - Date - References
82
Tap Changer Connection 83
> Title of presentation - Date - References
83
Inside CT Connection Lead Exit = Ground Level
84
> Title of presentation - Date - References
84
Flash Over To Sharp Edge Of Metal Steel Flash is the distance between two objects, using Oil or Gas as a path (sharp edges, corners e.t.c. are high risk) Consider the closest point is not always the RISK! Electrical Clearance checks
- FLASH
X x = FLASH DISTANCE 85
> Title of presentation - Date - References
85
PARTIAL DISCHARGES > 1000 nano Coulomb A track path can display a “tree” shaped pattern
86
> Title of presentation - Date - References
86
CREEPAGE - FAILURES Creep from HV to tank wall along the support board
87
> Title of presentation - Date - References
Creep from HV wdg to LV leads during Impulse tests
87
FLASH OVER / BREAKDOWN - FAILURE
88
> Title of presentation - Date - References
88
8. Transformer Thermal Aspect
89
> Title of presentation - Date - References
89
Thermal Aspect To Control Ageing & Lifetime
90
> Title of presentation - Date - References
90
Transformer Life Time Transformer life time is mostly determined by the life time of winding conductor insulation paper.
Cellulose insulation paper is built of several chain of glucose molecules. The number of glucose molecule in the cellulose paper is known as DEGREE POLIMERIZATION. New insulation paper Degree polymerization > 850. End life of insulation paper Degree polymerization < 200. At DP < 200 paper will be brittle as it has the tensile strength of HALF of new paper tensile strength.
THERMAL ASPECT has significantly contributed in the reducing of glucose chains on paper.
91
> Title of presentation - Date - References
91
Glucose Molecule Of Cellulose Insulation
92
> Title of presentation - Date - References
92
HEAT Source
Total Active Losses in kiloWATT
»(A) »(B) »(C) »(D)
I2R + Eddy losses (Max Loss > Minimum Tap) Stray Losses (Steel Structure + Tank) Core Losses Sun Radiation
TOTAL Losses to be evacuated = A + B + C + D
93
> Title of presentation - Date - References
93
COOLING MEDIUM
INTERNAL COOLING MEDIUM
The internal cooling medium has function also as internal insulation medium.
Mineral oil (Inhibited or Un-inhibited oil)
Silicon oil
Synthetic ester
Hi-Temp natural liquid (seeds).
EXTERNAL COOLING MEDIUM
94
Air
Water
> Title of presentation - Date - References
94
Directed Cooling
»Convection
»Conduction
»Fan
95
> Title of presentation - Date - References
95
Temperature Identification 1.3 x gradient
core
cooler
gradient
winding
l i o m o t t o B
96
> Title of presentation - Date - References
l i o n a e M
l i o p o T
g n i d n i w e g a r e v A
t o p s t o H
96
Temperature Rise and Driven Factors Temperature Rise for Class A (IEC / ANSI C57); Top oil rise ; = 60K / 55 K or 65 K. Average oil rise ; = 65 K / 55 K or 65 K (By resistance method) Hot spot rise ; = 78 K / 65K or 80K. Site elevation height; The standard elevation height is 1000 m above sea level. Climatic temperature behaviors; Yearly average ambient temperature (IEC std = 20oC) transformer life time. Hot monthly average ambient temperature (IEC std = 30 oC) Maximum ambient temperature (IEC std = 40 oC) transformer loading capability Insulation class Operating temperature 97
> Title of presentation - Date - References
A
E
B
F
H
105oC
120oC
125oC
145oC
220oC 97
Class A Temperature Design Limits
*) suitable for thermally up graded paper insulation
Oil
Winding
Metal part
Consequences
Annual average
80
98 / 110 *
110
Life time
Cyclic load
105
120 / 130 *
130
Gas generation
Emergency
115
140
140
Gas generation
Short emergency
115
160
160
Gas generation
1.Copper
115
250
160
Conductor softening
2.Aluminum
115
200
160
Maximum temperature design limit [oC]
Thermal short circuit
98
> Title of presentation - Date - References
98
Cooling Method – Oil Immersed
Oil circulation
External cooling
IEC 60076
ANSI C57
BS 171
Natural flow
Air Natural flow
ONAN
OA
ON
Natural flow
Air Forced flow
ONAF
FA
OB
Forced/Blasted
Air Natural flow
OFAN
*)
*)
Forced/Blasted
Air Forced flow
OFAF
FOA
OFB
Forced & Directed
Air Forced flow
ODAF
FOA
OFB
Forced & Directed
Water Forced flow
OF(D)WF
FOW
OFW
*) not specifically indicated
99
> Title of presentation - Date - References
99
Rules Reference List Material Properties Material Paper Pressboard Nomex PVA Enamel
Thermal Conductivities of Solid Dielectric Materials Thermal Conductivity (W/ m/ K) 0.17 0.21 0.125 0.16
Thermal Conductivities of the Core Direction Thermal Conductivity (W/ m/ K) In the plane of the laminations 21 Perpendicular to the plane of the laminations 3.3
Thermodynamic Properties of Cooling Liquids Property (units) Oil Ester Synthetic Oil Cubic Expansivity (/ K) 0.000795 0.000750 0.000700 Density (kg/ m3) 849 931 810 Dynamic Viscosity (kg/ m/ s) 0.00399 0.009589 0.01500 Specific Heat Capacity (J/ kg/ K) 2080 2216 2400 Thermal Conductivity (W/ m/ K) 0.1272 0.1535 0.1000
100
> Title of presentation - Date - References
Silicone 0.001040 912 0.02052 1525 0.1500
100
Directed Oil Flow Examples of washer applications (External) :
Duct maintained with sticks
Duct maintained with segments
101
> Title of presentation - Date - References
101
dire rect cted ed oi oill flo flow w PRE-ASSEMBLY - di Directed Oil Flow arrangements arrangements may may not be present in TX designs, designs, dependa dependant nt upon local Design influences
Bottom Oil Annulus (Ring) Directed Oil Flow entry point
Check that the Oil path is clear & free from leaks
102
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
102
Future Material Insulation
103
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
103
Alternative Insulation - Hybrid Design
CALENDERED KRAFT BOARD CALENDERED KRAFT BOARD NOMEX® NOME X® T-9 T-993 93 Creped NOMEX® CALENDERED KRAFT BOARD
Support Washers Static Rings Cylinders
NOME NO MEX® X® T-4 T-410 10
Conductor Insulation
NOME NO MEX® X® T-9 T-994 94
Axial & Radial Spacers
PRECOMPRESSED KRAFT BOARD
104
Angle Rings and Caps
Clamping Rings, Blocks
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
104
Transformer life Time
105
> Title of presentation - Date - References
105
106
> Title of presentation - Date - References
106
107
> Title of presentation - Date - References
107
108
> Title of presentation - Date - References
108
9. Short Circuit Analysis
109
> Title of presentation - Date - References
109
Definition Short circuit current is the current flowing thru the transformer part at the condition that the secondary side of power flowing from primary to secondary has been short circuited. Since the power transformer is the reactive apparatus, the short circuit current will be limited by this transformer impedance inherently. There are two kind of short circuit analysis; Symmetrical short circuit analysis such as three phases short circuit. Asymmetrical short circuit such as single phase to ground or two phases short circuit and/or to ground. Symmetrical short circuit current will be the biggest short circuit current for all loaded winding with all the winding terminals are brought out. For unloaded winding such as stabilizing winding, the single phase short circuit as well as the two phases short circuit shall be analyzed. 110
> Title of presentation - Date - References
110
Short Circuit Withstand A). Thermal capability. The transformer conductor shall be designed to limit the produced heat due to short circuit below the temperature where the conductor material will start to loose it’s designed tensile strength for certain period of time. This clearance time will be used as the protection coordination reference. 1. Thermal limit for Copper conductor
250 o C .
2. Thermal limit for Aluminum conductor
200 o C .
B). Dynamic capability. Each part inside the power transformer has to be supported and clamped sufficiently to anticipate the forces happen due to the result of the peak of short circuit current and the leakage induction. 111
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
111
IEC 60076 – 5 ; Minimum Short Circuit Impedances Impedances
112
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
112
Oscillogram Showing The SC Current and Forces
113
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
113
Short Circuit Current
Ipeak = S 2 x Iccrms
DC Offset K = 1 + e
x Π r + r 2 x
− arctan
× sin arctan x
U
x r
r
Icc
Clearance time = 3 seconds 114
> Title of presentation - Date - References
114
Short Circuit - Thermal Thermal Withstand For Copper Conductor, Θ1 shall be less than 250oC Θ1 = Θ0 +
2 x ( Θ0 + 235) 106000 J2
xt
-1
For Aluminum Conductor, Θ1 shall be less than 200oC Θ1 = Θ0 +
2 x ( Θ0 + 225) 45700 J2
-1
xt
Θo = Initial temperature in oC Θ1 = Average winding temperature at certain time in oC
J = RMS short circuit current density in A/m2 t = Clearance time in second, max. 10 seconds 115
> Title of presentation - Date - References
115
Short Circuit - Dynamic Withstand
A moving charge q, at the speed V, in a magnetic field B, is subject to a force F according to LAPLACE' s law
V q r
r
r
F = qV ∧ B
B F
116
> Title of presentation - Date - References
116
Axial & Radial Stresses Axial Stresses come from radial component of the
leakage field. This axial stresses can be minimized by an adequate balancing of the magneto motive forces on the whole height of the winding. The clamping device through flitch plate, tie rod,
clamping beam are pre-loaded with the bigger force than axial short circuit force to anticipate any movement and deformation due dynamic short circuit force. Radial Stresses come from axial component of the
leakage field. This type of force can not be minimized as this is directly dependent on the magneto motive force of inner and outer side windings. The concentrically winding shape is the best geometry
to resist the radial stresses. The inherently conductor tensile/compressive strength
shall be higher than the available short circuit forces. Sometime the reinforced material (e.g. CPR) is required. 117
> Title of presentation - Date - References
117
B RADIAL FORCES Frad
mmf
I
I
Frad
F = I dl x B core
AXIAL FORCES
I Fax
118
> Title of presentation - Date - References
I Fax
118
Mean Hoop Stress dl
α
p Leakage/flux
σS Rav
e
I
2B
α
e
F
B Rav
119
σS
> Title of presentation - Date - References
Y
119
Hoop Stresses Of Multilayers leakage field in the middle of the layer
J −1 ni I i 12 n J I J B = µ 0 µ r ∑ + H J i H i
Hi = electrical height of the layer
W1
B k
W2 F
Wn
F
F F
H
F
Electromagnetic pressure
F
R1
R2
B2
r r
r
p = I ∧ B
120
> Title of presentation - Date - References
R2
120
Self Supporting / Counter Pressure
Layer type winding: self supporting reaction equivalent
counterpressure with the thin cylinder hypothesis (R J>>eJ)
σ =
P J . R J e J
Hooke’s law ⇒ σ = E.I = E.
PJ
pJ
E= Young modulus of material
as
i=
∆(2.Π. R J ) 2.Π. R J
=
∆ R J R J
Internal counterpressure
P J = e J . E .
RJ ∆RJ 121
> Title of presentation - Date - References
∆ R J 2
R J
121
Bending Stress Between Supports
Layer type winding : Bending stress ; reaction of support
F tJ = ( p J R J − F nJ )
Ft
d bs RJ
+ 0
-
d bs
2 R J
or
x
F tJ = −
dMf dx
-Ft and Hook law : EIy’’=-Mf
122
> Title of presentation - Date - References
E
: Young modulus
I
: inertia
Mf
: bending torque
122
Buckling Stress
123
> Title of presentation - Date - References
123
Axial Forces
124
> Title of presentation - Date - References
124
Tilting Stress
125
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
125
Compressive Stress On Radial Spacer
e
e1
e2
en
Swidth 126
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
126
Shearing Stress on CTC
Epoxy cab cable le : shea shearin ring g stres stress s on ep epoxy oxy Epoxy
F τ
with epoxy without epoxy Epoxy avoid any relative movement from one strand to another
127
> Title Title of presen presentat tation ion - Date Date - Refere Reference nces s
127
Clamping Forces
Clamping forces : reduction of number of elements
F4,0
F3,1= F4,0
F3,0
F2,1= F3,0
F2,n = F2,n-1 + F3,n-1
F2,0 F1,1= F1,0 + F2,0
F1,0 initial nb of elements : 4
128
step 1 nb of elements : 3
> Title of presentation - Date - References
F1,n = F1,n-1
step n nb of elements : 2
128
Clamping Structure
Clamping structure reactions Rt= -F2,n
Rt= 0
if F2,n > F1,n Rt= 0
if F1,n > F2,n Rt= - (F1,n -F2,n )
F2,n
F2,n
F1,n
F1,n
F1,n
Rb= 0
Rb= - (F2,n -F1,n )
Rb= 0
Rt= - (F1,n + F2,n )
F2,n F2,n
F1,n
F2,n
F1,n
Rb= -F1,n Rb = - (F1,n + F2,n )
Clamping forces ≥ Σ of reactions on each layer
129
> Title of presentation - Date - References
129
Axial Clamping System Clamping the winding assembly with pre -compressed load >
the axial force per phase & active part weight/3
130
> Title of presentation - Date - References
130
Maximum Allowed Forces And Stresses
131
> Title of presentation - Date - References
131
10. Engineering
132
> Title of presentation - Date - References
132
Mechanical Design
kV 1200
H-Range 220
N-Range 110
E-Range 25
75
2500
MVA
Mechanical Design standardize the best practice 133
> Title of presentation - Date - References
133
Transformer Tank TOP BEAM TOP END WEDGE
TIE-ROD CRADLE
E RANGE Maximum Voltage ≤ 170 kV Weight of core steel sheet, max 20 Ton Center-center distance max 1350 mm
UPPER CLAMPRINGS
LOWER CLAMPRINGS
134
> Title of presentation - Date - References
134
Transformer Tank TOP BEAM
N RANGE Maximum Voltage ≤ 275
FLITCH PLATE
kV
UPPER CLAMPRINGS
Weight of core steel
sheet, max 40 Ton
LOWER CLAMPRINGS
Weight of Part active max
80 Ton
Center-center distance
max 1600 mm
YOKE SUPPORT
135
> Title of presentation - Date - References
135
Engineering Tools Full integrated engineering program : TARGET (Transformer Architecture Generating Tools)
136
As Main Program to design main variable of transformer part active, optimation tools for choosing design vs Price level Link (export/import) to verification tools
> Title of presentation - Date - References
136
Vérification Tools Verification tools : Overload capability of overloaded Invodat capacitance network and voltage distribution Corecalc Core losses and temp Annuli Force oil entry evaluation ASC Detailed core Design Program Choc Transient impulse voltage Analysis Clearstress Voltage Stress Evaluation DOF Direct Oil Flow Evaluation Fluxshunt Dimensional analysis for flux within tank shunt Gradcalc Winding Gradient Evaluation Radinsulation Lead clearances, thermal performances RothFEM Forces, stresses, impedances and flux ploting
137
> Title of presentation - Date - References
137
Vérification Analyses
TRANSFORMERLEAKAGE FLUX (GRID-FLUX LINES)
U
Example of impulse wave 1.2µs / 50µs 50 µs Breaking time
100%
Full wave
50%
Wave chopped on the tail 0% 1.2 µs
Falling time
times in µs Undershoot Voltage
30%
138
> Title of presentation - Date - References
138
11. Manufacturing Process
139
> Title of presentation - Date - References
139
Manufacturing Process
Core cutting
Winding
Core stacking
Insulation
Active part assembly
Drying Repack
Assembly Testing 140
> Title of presentation - Date - References
140
Core Stacking
141
> Title of presentation - Date - References
141
Winding Manufacturing
142
> Title of presentation - Date - References
142
Check Cross Over Of Winding
143
> Title of presentation - Date - References
143
Connection & Insulation
144
> Title of presentation - Date - References
144
Active Part Tanking After Repack
145
> Title of presentation - Date - References
145
146
> Title of presentation - Date - References
146
Single Phase Reactor: New Design
147
> Title of presentation - Date - References
147
Single Phase Autotransformer 240 / 3 MVA 250 / 150 kV 148
> Title of presentation - Date - References
148
Yoke Shield for reactor
149
> Title of presentation - Date - References
149
12. Accessories, Protection & Control
150
> Title of presentation - Date - References
150
Protection and Additional Accessories A. PROTECTION DEVICE - Protective Relay (Bucholz) Function : to trip out the trafo if there is a release of gas arising from the decomposition of the solid and liquid insulating material due to the action of heat or electric arcing.
Principal Of Operation - During normal operation, the relay is completely filled with oil. - When gas forms inside the transformer, it tends to flow towards the conservator - it accumulated progressively inside the relay there by LOWERING the oil level. - If gas continues to form, the oil level will affect the lower float B and relative switch which is connected to the circuit and causes disconnection of the transformer power supply.
151
> Title of presentation - Date - References
A. Upper Float B. Lower Flat
151
Protection and Additional Accessories
- Protective Relay (Bucholz)
152
> Title of presentation - Date - References
152
Protection and Additional Accessories
- RS 2001 relay for OLTC Function : to protect tap changer and transformer from any damage if a defect arises in the tap changer . This relay operates to put the trafo off circuit Principal Operation: It responds only if oil flows occur from tap changer head to the oil conservator
153
> Title of presentation - Date - References
1. Flap Valve 2. Permanent Magnet 3. Reed Switch
153
Protection and Additional Accessories - Winding
Temperature Indicator
Function : to measure temperature
the
winding
Principal Of Operation: measure the winding temperature by means of a special bulb surrounded by heating resistance through which passes a current proportional to the current passing through the transformer winding subject to a given load and immersed in insulating oil at temperature
1. Case
9. Microsw. Setting Pointer
2. Locking Glass Ring
10. Junction Box
3. Fixing Rear Flange 4. Air Hole 5. Capillary Output 6. Dial
11.Glass or polycarbo-nate window 12. Potentiometer for heating resistance adjustment
7.Microsw. Setting Dial 8. Max. indicating pointer
154
> Title of presentation - Date - References
154
Protection and Additional Accessories - Oil Temperature Indicator
Function : to measure the oil temperature inside power transformer tank
1. Case
8. Max. indicating pointer
2. Locking Glass Ring
9. Microsw. Setting Pointer
3. Fixing Rear Flange 4. Air Hole 5. Capillary Output
10. Junction Box 11.Glass or polycarbonate window
6. Dial 7.Microsw. Setting Dial
155
> Title of presentation - Date - References
155
Protection and Additional Accessories - Oil Level Indicator Function : to measure the level reached by the oil in a transformer conservator Principal Of Operation - The changing oil level in the conservator is detected by a float attached to a suitably – long rod which is connected to the magnetic transmission axle - A permanent magnet, whose flux passes through attachment flange 2.0, is coupled to the pin turned by the float-carrying arm. The aforementioned parts fitted to flange 2.0 are placed inside the conservator through a hole made in a suitable position which is perfectly sealed by the flange it self. - A second permanent magnet inside instrument gauge 1.0, dragged round by the first magnet, moves a second shaft on which the optical level- indicator pointer and a cam are fitted. The cam trips the microswitch (Es) which electrically indicate that the oil has reached a certain level.
156
> Title of presentation - Date - References
156
Protection and Additional Accessories - Pressure Relief Device
Function : an equipment to relieve large volumes of gas or insulating fluid rapidly when the pressure inside a transformer reaches a pre-determined limit.
157
> Title of presentation - Date - References
157
Protection and Additional Accessories B. ACCESSORIES - Oil Sampling Valve
- Butterfly Valve
F=close position O=open position
158
> Title of presentation - Date - References
158
Automatic Voltage Regulator - KVGC
159
> Title of presentation - Date - References
159
Fibre Optic Temperature monitor 1 - 8 Channels Cooling/Alarms/Protection -30°C to +200°C Programmable relays Analog output
0–1ma or 4–20ma
Ring Lug Terminals Memory Retention
90 days at 1/minute – factory set
Power Input
Universal AC/DC
Self Diagnostics Applications
Small to Large Power Transformers
RS 232 Port Options for RS 485 and Protocol Converter 160
> Title of presentation - Date - References
160
Protection and Additional Accessories
- Screw and Globe Type Valve
161
> Title of presentation - Date - References
161
13. Final Acceptance Test
162
> Title of presentation - Date - References
162
Definition Final Acceptance Test is the crucial moment for a
transformer , verifying the manufactured transformer has met the guaranteed performances and is ready to function under specified circumstance. Purpose of testing is to ensure that the transformer has
fulfilled the quality performance and to validate the specific contractual requirements. Validate the design Validate the manufacturing process. Compare the measurements with the technical data specification. Establish a finger print of the transformer, useful for comparison with the future/on site measurement such as SFRA, capacitance, insulation resistance etc.
163
> Title of presentation - Date - References
163
Testing Procedures The testing procedures are divided in three parts as followings; 1. Routine Tests; These tests are subjected to be performed on each individual transformer prior to delivery. 2. Type Tests (IEC) / Design Tests (ANSI/IEEE); These kind of tests are performed on one transformer representing the other transformers with the similar design. 3. Special Tests (IEC) / Other Tests (ANSI/IEEE); These tests are non-mandatory tests and have to be agreed between the manufacturer and the purchaser. 164
> Title of presentation - Date - References
164
Routine Tests Routine Test is containing the following tests; 1. Insulation resistance measurement. 2. The electric strength of the transformer liquid. 3. Winding resistance measurement. 4. Voltage ratio & polarity/vector group checks. 5. Load loss & impedance measurement. 6. No load loss & no load current measurement. 7. Dielectric – routine tests (induced & applied tests) 8. Tap changer test (OLTC and/or DETC). 9. Functional tests on control devices, CT ratio checks.
165
> Title of presentation - Date - References
165
Type/Design & Special/Other Tests Type tests (IEC) /Design tests (ANSI/IEEE); 1. Temperature rise test. 2. Dielectric – type test (lightning impulse test) Special tests (IEC) /Other tests (ANSI/IEEE); 1. Dielectric – special test (PD measurement) 2. Zero sequence impedance measurement. 3. Sound level measurement. 4. Capacitance and power factor. 5. Harmonic measurement of no load condition. 6. Fans and/or oil pump power consumption measurement. 7. SFRA (Swept Frequency Response Analysis). 8. DGA (Dissolved Gas Analysis) measurement. 9. Tank destructive test. 10. Transformer short circuit.
166
> Title of presentation - Date - References
166
Insulation Resistance Measurement This insulation is normally known as MEGGER insulation
test. This measures the DC insulation value containing the oil or other transformer liquid, cellulose pressboard, insulation paper and other insulation material between windings and winding to core. The power supply is DC voltage source 1000 VDC up to
5000 VDC. Due to capacitance of different insulation medium, the insulation value of combined materials will take some times prior to get the stabilized result. The acceptance criterium ; Interwinding insulation = minimum 500 Ohm. Winding to core = minimum 200 Ohm. The wet insulation material may result very low insulation
resistance.
167
> Title of presentation - Date - References
167
Winding DC Resistance Measurement Winding DC resistance is measured thru two bushings for
each winding. The measurement is performed with bridge connection of VOLT – Ampere meters or high accuracy digital multimeter. Care shall be taken for the effect of self-inductance. Hence
the oil temperature shall be recorded. Anomalous result can detect bad connection joint within
the winding, inter winding or winding to bottom terminal of bushing. R std
V 2 DC power supply
x
R 1 V
R x = R std x V 1 /V 2 168
> Title of presentation - Date - References
168
Load loss & impedance measurement This test will measure the load loss and impedance referring to the rated current at some of tap changer positions. The AC 3 phases supply is normally injected on the HV side of the transformer. The power supply voltage is increased until the nominal current is reached. The voltage giving the rated current is the impedance voltage. This is normally expressed as percentage of the rated voltage at particular tap changer position. If the rated current can not be reached due to testing limitation or other reasons, the following correction factor will be used. The minimum test current is 50% rated current Pextrapolation = Ptest x (Irated : Itest)2 During test, the transformer oil has to measured to correct the copper temperature as ambient temperature reference. The measured resistance has to be extrapolated to 75 oC (85oC for ANSI/IEEE with 65oC rise). 169
> Title of presentation - Date - References
169
Correction factor for load loss due to temperature The load loss [Pcu/Pal] is containing I2Rdc + stray loss and guaranteed at 75 oC for IEC standard transformer and ANSI/IEEE standard transformer with 55 oC temperature rise. For ANSI/IEEE standard transformer with 65 oC temperature rise, the temperature reference for load loss is 85 oC. The DC resistance & load loss are measured at testing laboratory ambient temperature ( Θambient). For in case the oil temperature during load loss measurement has exceeded 3oC different with the actual ambient temperature, this oil temperature shall be used for measurement ambient temperature.
K CU =
[235 + 75 (or 85)] [235 + Θ ] Θambient
K AL =
[225 + 75 (or 85)] [225 + Θ ] Θambient
P cu(al) 75 o C (or 85 o C) = I 2 R dc x K + Stray loss / K 170
> Title of presentation - Date - References
170
No Load loss and Current The 3 phase, AC, power supply at 90%, 100%, 110% of
rated voltage is connected to the LV winding to induced the nominal voltage on HV as well as the other winding. The total (3 phases) losses & injected current to reach the rated voltage are known as no load loss, no loda current respectively. Correction factor for no load losses;
P0 = Pm x ( 1 +
171
U’-U ) U’
P0
= Corrected no load loss
Pm
= Measured no load loss
U’
= Mean Voltage
U
= RMS voltage
> Title of presentation - Date - References
171
Applied Over Voltage Test Purpose ; to check the voltage withstand between the tested winding to other separated windings (not in series/parallel connection), core, steel structure and tank. The test is made of single phase AC voltage at rated frequency for 60 seconds duration applied to one winding while other windings & core are grounded. The test is successful if no collapse of the test voltage occurs.
V HVN
172
> Title of presentation - Date - References
172
Induced Over Voltage Withstand Test Purpose; To ensure that the insulation between turns, between
discs, inter windings, winding to core/steel structure, cleat bars withstand the over voltage switching referring to guaranteed power frequency insulation class. Two type of induced test; Short duration Over Voltage Test (ACSD);
AC single phases power supply for STAR connection non-uniform insulation. For ANSI/IEEE standard and some customer requirements are requiring the three phases power supply for STAR connection non-uniform insulation. AC three phase power supply for WYE or DELTA connection of uniform insulation.
rated frequency Time (seconds) =
test frequency
x 120 , but no less than 15 seconds
Long duration Over Voltage Test (ACLD); Over voltage up to 130% or 150% Um for 30 minutes with partial discharge measurement. 173
> Title of presentation - Date - References
173
Time Duration For ACSD & ACLD Induced Test U1 tinduced
U2 1.1Um
5 min
5 min
5 min
5 min
ACSD
U1 = induced voltage U2 = 1.3 Um for < 300 pC = 1.5 Um for < 500 pC 1.1Um < 100 pC For phase to earth Um : S 3
U1 tinduced
U2 1.1Um
5 min 5 min
30 min 5 min
ACLD 174
> Title of presentation - Date - References
174
Partial Discharge Measurement Partial Discharge Measurement is measuring the small discharge activity inside as well as outside around the transformer prior to flash over occurrence. This measurement is a good tool to ensure the transformer quality. •
Corona discharges occurs due to the sharp edge electrode.
•
Surface discharges (creepage) occurs due to overstress component parallel to the dielectric medium surface.
•
Internal discharges occurs due to the non-homogenous dielectric medium.
•
Electric trees due to the particle or cavity in the solid insulation.
•
Floating discharging occurs due to badly grounded component.
•
Contact noise occur in case bad contact terminal.
175
> Title of presentation - Date - References
175
Single Phase Induced Voltage Vectorial HV = WYE non - -uniform uniform U 1
2/3 U Induced LV = DELTA
U Induced
v 2 = 1/2u 2 U supply
N
u 2
1 phase
w 2 = 1/2u 2
1/3 U Induced
V 1 & W 1
176
> Title of presentation - Date - References
176
Three Phases Induced Voltage Vectorial HV = WYE uniform U 1 LV = DELTA u 2 UInduced :S S3
v 2
w 2
e d c d u n I U
N
U supply 3 phase
W 1 177
> Title of presentation - Date - References
V 1 177
Temperature Rise Test Purpose : to check the temperature rises (top oil, average
winding & hot spot) do not exceed the guaranteed temperature rises. The test can be performed by BACK TO BACK test or SHORT
CIRCUIT methods. The short circuit method is mostly used for this temperature rise test. In the short circuit method, all three phases low voltage
windings are short circuited to generated the total losses as well as the current, Principally the test is performed by supplying the current to provide the total losses (no load + load losses) for oil temperature check and then to provide the rated current for winding temperature check. Since the oil time constant is very long (it can take several
hours) while the conductor time constant is practically only few minutes, the injected current for total losses is performed first to get stabilized oil temperature then followed by reduced current to rated current to get winding temperature at rated capacity one hour prior to shut down. 178
> Title of presentation - Date - References
178
DC Resistance For Temperature Analysis Oil temperature can be detected by direct measurement
referring to oil temperature indicator. Winding temperature at rated capacity is calculated by
comparing the DC resistance value at cold condition with known ambient temperature and the DC resistance value at rated current just prior to shut down. The transformer has to be cleared for any capacitive
charge before taking the hot DC resistance measurement by using charging stick. The charging time has to be kept as short as possible to keep measurement accuracy, but this period may need several minutes. The hot DC resistance is extrapolated from several
measured DC resistance values after shut down and cleared charging. If there is tap changer with several tap positions, the tap
position with highest load loss is taken as reference for temperature analysis. 179
> Title of presentation - Date - References
179
Some Of Equations For Temperature Rise Analysis 1. Power Supply is provided on HV tap pos. with highest load los s. I injected = I rated x
(P load loss + P no load ) P load loss
V injected = V rated x Z(%) x
I injected I rated
2. Top Oil Rise and Average Oil Rise at Rated Capacity DToil = (max. {T cover , ,T top rad ’ } – T amb ) x
DAOT = ½ x (T top rad + T bot rad ) – T amb ) x
180
> Title of presentation - Date - References
(P load loss + P no load )
x
P load loss (P load loss + P no load )
x
P load loss 180
Some Of Equations For Temperature Rise Analysis 3. Winding Temperature Gradient at Rated Current.
GR CU =
GR AL =
R 2 R 1 R 2 R 1
x (234.5 + T 1 ) – (234.5 + T 2 ) – DAOT x
x (228.1 + T 1 ) – (228.1 + T 2 ) – DAOT x
I rated
y
I inject I rated
y
I inject
4. Average Winding Temperature Rise and Hot Spot Rise.
181
DT CU = DAOT + GR CU
DT AL = DAOT+ GR AL
HS CU = DT oil + HSF x GR CU
HS AL = DT oil + HSF x GR AL
> Title of presentation - Date - References
181
Some Of Equations For Temperature Rise Analysis Definitions; 1. Iinjected 2. Irated 3. Vinjected 4. Pload loss 5. Pno load loss 6. T1, T2 7. Tcover 8. Ttop rad 9. Tbot rad 10. DToil 11. DAOT 12. DT 13. GR 14. x
= Injected current [A] = Rated current at stated tap [A] = Testing Voltage [kV] = Maximum load loss [kW] =Measured no load loss [kW] = Ambient temperature at condition 1,2 respect.[oC] = Oil temperature on top cover [oC] = Oil temperature on top radiator [oC] = Oil temperature on bottom radiator [ oC] = Top oil temperature rise [K] = Mean oil temperature rise [K] = Average winding temperature rise [K] = Winding gradient temperature [K] = Exponent for oil temperature due to losses.
0.8 for ON cooling of < 2500 kVA. 0.9 for ON cooling 1.0 for OF or OD cooling
15. Y
= Exponent for winding gradient due to current.
1.6 for ON or OF cooling 2.0 for OD cooling
182
> Title of presentation - Date - References
182
Lightning Impulse Tests Purpose ; To check the transformer capability against
the fronted over voltage caused by atmospheric discharge with time peak between 0.1 ms to 20 ms and tail duration of less than 300 ms. Considering the transformer as a complex network of
RLC component, the distribution of such very high frequency over voltage such as lightning impulse will be highly influenced by the capacitive component of transformer. The lightning impulse test is performed by comparing
the result of 100% impulse test against the 50% and/or 75% impulse test result. If there is failure, the voltage wave form as well as the current wave form will have different shape as the wave of reduced level.
183
> Title of presentation - Date - References
183
Full Wave Impulse 100%
50%
front time
tail time
Front time = 1.2 ms + 30% Tail time = 20 ms + 20% Peak value + 3% 184
> Title of presentation - Date - References
184
Voltage Wave
Current Wave
50% impulse
100% impulse
185
> Title of presentation - Date - References
185
14. Technology Application
186
> Title of presentation - Date - References
186
Single Phase Solution
187
> Title of presentation - Date - References
187
Single Phase Reactor: Original Design
188
> Title of presentation - Date - References
188
Less Maintenance
189
> Title of presentation - Date - References
189
ATT expérience in Industrial Transformers Electrolysis Industry
=> Rectifier Transformers
(Aluminium, Zinc, Copper, Chlorine)
Chemical, Oil&Gas Industry => Converter Transformers
Steel Industry
190
> Title of presentation - Date - References
=> Electrical Arc Furnace (EAF)Transformers
190
Furnace transformer on UTR SLN LE-NICKEL 3 x 1 PHASE 33.3 MVA 50 Hz, 63 Kv / 300 ~ 1800 Volt OLTC ± 16 x 750 Volt ODWF
191
> Title of presentation - Date - References
191