INTRODUCTION Alarm’s are used to monitor the site in case of any fault occur then alarm panel automatically generate the alarm for corresponding fault occurred at site.
AMIT MISHRA
2
Why alarm’s are used at site?
External alarm is important at BTS site because in case of any fault occur then as a maintenance engineer it will be easier for us to identify the problem and rectify it accordingly. We can check at DDF, where termination of alarm is done. It provide security and stability to whole BTS site.
AMIT MISHRA
3
TYPES OF ALARM AT BTS SITE BTS SITE
ALARM INTERNAL
EXTERNAL
ALARM
ALARM
AMIT MISHRA
4
PARAMETER OF EXTERNAL ALARM These are parameter which may differ according to manufacturer. ALARM NAME OR SYNTAX OR TITLE
ALARM NO
ALARM SEVERITY
COLOUR CODE
ALARM TYPE(NO/NC)
ALARM PORT NO/PIN NO
ROUTE OF ALARM
ROOT CAUSE OF ALARM
AMIT MISHRA
CAUSE OF ALARM
5
ALARM NAME OR SYNTAX OR TITLE
It define the name of the alarm at BTS site. It may differ according to the operator. Depending upon BTS used syntax or title can change. Some of the example of name of alarm operator are as follow’s..
BTS NAME
ALARM NAME
NOKIA FLEXI BTS
DG FAIL’S TO START MAIN’S FAILURE
ERICSSION RBS 2964
DG FAIL’S TO STOP DOOR OPEN
AMIT MISHRA
6
PARAMETER DESCRIPTION CONTINUED ALARM NO Every operator decide a particular alarm no for it’s BTS site and accordingly series of alarm is decided. for eg-7401 in NOKIA flexi BTS case.
ALARM TYPE Type of alarm mean’s that either alarm will be normally Closed or normally open. Normally open mean’s that state of alarm in normal condition is OPEN. Normally closed mean’s that state of alarm in normal condition is closed.
NORMALLY OPEN
NORMALLY CLOSED
ALARM TYPE AMIT MISHRA
7
CRITICAL Critical mean’s that ,it require immediate attention, if on BTS site any alarm is critical defined that mean’s that level of alarm severity is high. for eg : LLOP- low lubricant oil pressure.
SEVERITY
PARAMETER DESCRIPTION
CRITICAL MAJOR
MINOR
MAJOR Major mean’s that ,it’s severity level is lesser than critical but it is also needed attention as soon as possible. for eg: low fuel level
MINOR Minor mean’s that ,it’s severity level is lesser in compare to other alarm and site may not get affected as much as in case of critical and major. for eg- site on DG.
AMIT MISHRA
8
ALARM PORT Alarm port or pin no is decided by operator itself .
COLOUR CODE
PORT NO/PIN NO
OPERATOR SPECIFIC COLOUR CODE
The colour code of alarm wire is decided by operator itself. Always it will exist in pair for PCM cable’s used.
AMIT MISHRA
9
ROUTE OF ALARM It decide the route of alarm or we can say that where alarm connection start till termination of that alarm.
ROOT CAUSE Root cause mean’s the exact cause of fault which led to the alarm at the site.
ROUTE of ALARM
• IT DECIDE ROUTE OF ALARM
ROOT CAUSE
• IT DECIDE THE CAUSE OF ALARM
AMIT MISHRA
10
ALARM CABLE CONNECTION
Alarm cable are PCM cable. They exist in pair’s. Each alarm will be connected to ddf with these cable.(two wire is one pair) 37 pin D-type connector. Alarm ddf installed on shelter wall. Alarm’s are connected to sensor’s.
25 PAIR PCM CABLE
AMIT MISHRA
11
For connection of alarm these are needed.
D TYPE 37 PIN
DDF ALARM CONNECTION AMIT MISHRA
12
TYPE OF EXTERNAL ALARM’S
1. DOOR OPEN 2. HIGH TEMPERATURE 3. DG FAIL’S TO START 4. DG FAIL’S TO STOP 5. LOW FUEL LEVEL 6. FIRE OR SMOKE 7. LOW LUBRICATION OIL PRESSURE 8. LOAD ON DG 9. AC FAIL’S TO START(AC-1/AC-2) 10.RECTIFIER MODULE PAIR FAIL’S 11.LOW BATTERY VOLTAGE 12.SITE ON DG 13.AC -1 FAIL’S 14.AC-2 FAIL’S 15.DG RUNNING WITHOUT LOAD
AMIT MISHRA
13
TO ELABORATE ABOVE DESCRIPTION TAKE EXAMPLE OF NOKIA FLEXI BTS
There are 12 external alarm for nokia flexi BTS. For 12 alarm connection ,we need 37 pin D connector in which 24 pin’s will be used. For each alarm , we require one pair E1 cable having two wire. Termination of these cable is done on DDF i.e from BTS to DDF and from alarm sensor to DDF.
AMIT MISHRA
14
SYNTAXMAIN’S FAILURE
ALARM NO7401/ALARM NO1
PIN NO-7/25
COLOR CODEGREEN& GREEN/WHITE
ROUTE OF ALARM
ROOT CAUSE
PIU/AMF
ALARM TYPENORMALY OPEN
DDF
SEVERITYMINOR
BTS
-MAIN’S FAILURE
AMIT MISHRA
15
ALARM CONFIGURATION CONTINUED SYNTAXRECTIFIER MODULE FAILURE
PIN NO-8/26
ALARM NO7402/ALARM NO2
SEVERITYMINOR
COLOR CODE-BLUE& BLUE/WHITE
ROUTE OF ALARM
ROOT CAUSE
ALARM TYPENORMALY OPEN
POWER PLANT
DDF
BTS
-RECTIFIER FAILURE
AMIT MISHRA
16
ALARM CONFIGURATION CONTINUED
SYNTAX-BATTERY AT 47V/LOW BATTERY VOLTAGE
PIN NO-9/27
ROUTE OF ALARM
ROOT CAUSE
ALARM NO7403/ALARM NO3
ALARM TYPENORMALY OPEN
SEVERITYCRITICAL
COLOR CODEVOILET& WHITE VOILET
POWER PLANT
DDF
BTS
-BATTERY VOLTAGE IS BELOW -48V
AMIT MISHRA
17
ALARM CONFIGURATION CONTINUED SYNTAXLOAD ON BATTERY
ALARM CONFIGURATION CONTINUED SYNTAX-LOW FUEL LEVEL
ALARM NO7407/ALARM NO7
PIN NO13/31
COLOR CODE-LIGHT BLUE&BLACK
ROUTE OF ALARM
FUEL SENSOR
ALARM TYPENORMALY OPEN
PIU/AMF
SEVERITYMINOR
DDF
BTS
ROOT CAUSE -WHEN THE FUEL IN TANK GOES BELOW 40%.
AMIT MISHRA
21
ALARM CONFIGURATION CONTINUED SYNTAX-DG FAIL TO START
ALARM NO7408/ALARM NO8
PIN NO14/32
COLOR CODE-WHITE BLACK/WHITE
ROUTE OF ALARM
PIU/ AMF
ALARM TYPENORMALY OPEN
SEVERITYMAJOR
DDF
BTS
ROOT CAUSE-DG DOESN’T START AFTER 3 ATTEMPT’S BY PIU/AMF
AMIT MISHRA
22
ALARM CONFIGURATION CONTINUED SYNTAX-AC FAIL’S
PIN NO15/33
ALARM NO7409/ALARM NO9
ALARM TYPENORMALY OPEN
SEVERITYMAJOR
DDF
BTS
COLOR CODELIGHT GREY& LIGHT GREY /BLACK
ROUTE OF ALARM-
MICRO CONTROLLER
ROOT CAUSE-BOTH AC FAIL’S
AMIT MISHRA
23
ALARM CONFIGURATION CONTINUED SYNTAXDOOR OPEN
ALARM N07410/ALARM NO10
PIN NO16/34
COLOR CODEGREEN& GREEN/WHITE
ROUTE OF ALARM-
DOOR SENSOR
ALARM TYPENORMALY CLOSED
PIU/AMF
SEVERITYMINOR
DDF
BTS
ROOT CAUSE -WHEN SHELTER DOOR IS OPEN.
AMIT MISHRA
24
ALARM CONFIGURATION CONTINUED SYNTAXHIGH TEMPERATUR -E PIN NO17/35
ALARM NO7411/ALARM NO11
ALARM TYPENORMALY OPEN
SEVERITYMAJOR
COLOR CODEORANGE/ RED&ORANGE/LI GHT GREY
ROUTE OF ALARM-
MICRO CONTROLLER
DDF
BTS
ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.
AMIT MISHRA
25
ALARM CONFIGURATION CONTINUED
SYNTAXFIRE/SMOKE
PIN NO18/36
ALARM NO7412/ALARM NO12
ALARM TYPENORMALY OPEN
SEVERITYCRITICAL
COLOR CODEORANGE /BLACK&ORANGE/GREEN
ROUTE OF ALARM-
FUEL SENSOR
PIU/AMF
DDF
BTS
ROOT CAUSE -WHEN TEMPERATURE REACHES ALARMING LEVEL.
AMIT MISHRA
26
APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S
SYNTAX-DG FAIL’S TO STOP
ALARM NOOPERATOR SPECIFIC
PIN NOOPERATOR SPECIFIC
ROUTE OF ALARM-
ALARM TYPENORMALLY CLOSED
SEVERITYMINOR
COLOUR CODEOPERATOR SPECIFIC PIU/AMF
DDF
BTS
ROOT CAUSE-WHEN PIU OR AMF NOT ABLE TO STOP DG AFTER 3 ATTEMPT.
AMIT MISHRA
27
APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S
SYNTAX-AC1 FAIL’S
PIN NO – OPERATOR SPECIFIC
ALARM NOOPERATOR SPECIFIC
ALARM TYPENORMALLY OPEN
SEVERITYMINOR
COLOUR CODEOPERATOR SPECIFIC
ROUTE OF ALARM-
MICRO CONTROLLER
DDF
BTS
ROOT CAUSE-WHEN AC-1 FAIL’S
AMIT MISHRA
28
APART FROM THESE ALARM’S OF NOKIA FLEXI BTS WE HAVE FEW MORE AS FOLLOW’S
SYNTAX-AC2 FAIL’S
PIN NO – OPERATOR SPECIFIC
ALARM NOOPERATOR SPECIFIC
ALARM TYPENORMALLY OPEN
SEVERITYMINOR
COLOUR CODEOPERATOR SPECIFIC
ROUTE OF ALARM-
MICRO CONTROLLER
DDF
BTS
ROOT CAUSE-WHEN AC-2 FAIL’S
AMIT MISHRA
29
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM Ericsson RBS2954
DG on DG fail’s to start Main fail’s DG fuel level LLOP DG fails to stop Cabinet temperature Fire & smoke Door smoke BFU fault Spare SMPS input fail Battery low voltage DC disconnected alarm Battery breaker off Battery disconnected
AMIT MISHRA
30
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM Ericsson RBS2964
DG on DG fail’s to start Main fail’s DG fuel level LLOP DG fails to stop Cabinet temperature Fire & smoke Door open BFU fault Spare SMPS input fail Battery low voltage DC disconnected alarm Battery breaker off Battery disconnected
AMIT MISHRA
31
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM HUAWEI 3900
Intruder A/C failure High room temperature Fire alarm Fire fighting Main’s failure Generator failure Generator run Rectifier high voltage Tower light failure Rectifier 2/more failure Tower amplifier fail Rectifier low voltage Rectifier common alarm GN auto mode Low fuel in main tank
AMIT MISHRA
32
LIST OF DIFFERENT OPERATOR EXTERNAL ALARM ZTE ZXG 10
AMIT MISHRA
33
ALARM DEFINED IN ERICSSON SITES:
Sl. No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
External Alarms ID DG ON DG fail to Start Mains Fail High Shelter Temperature DG Fuel Level Low LLOP DG Fail to Stop Fire and Smoke Door Open AC 1 - OFF AC 2 – OFF Spare Battery Fuse Fail Rectifier Fail Battery Low Voltage SMPS Input Fail
After we connect the cable on krone block we will give loop with krone tool one by one and check weather alarm get disappear in OMCR or not. Same way we have to check for all the 8 ports.
AMIT MISHRA
36
EXTERNAL ALARM IN HUAWEI 3900 BTS AND COLOUR CODEKRONE NO:1
KRONE NO:2
NO:
port
SLOT
DDF
ALARM
NO:
port
SLOT
DDF
1
0
18
1
INTRUDER
9
0
19
1
2
1
18
2
A/C FAILURE
10
1
19
2
11
2
19
3
ALARM RECTIFIER HIGH VOLTAGE TOWER LIGHT FAILURE
3
2
18
3
HIGH ROOM TEMPERA TURE
4
3
18
4
FIRE ALARM
12
3
19
4
5
4
18
5
FIRE FIGHTING
13
4
19
5
6
5
18
6
MAINS FAILURE
14
5
19
6
7
6
18
7
GENERAT OR FAILURE
15
6
19
7
GN AUTO MODE
8
GENERAT OR RUN
8
LOW FUEL IN MAIN TANK
8
7
18
16
AMIT MISHRA
7
19
RECTIFIER 2/MORE FAILURE TOWER AMPLIFIE R FAIL RECTIFIER LOW VOLTAGE RECTIFIER COMMON ALARM
37
HUAWEI EXTERNAL ALARMS(COLOURS)
EXTERNAL ALARM COLOUR CODES CABLE NO:
PAIR
1
1
2
1
3
2
4
2
5
3
6
3
7
4
8
4
COLOUR WHITE ORANGE ORANGE WHITE GREEN GREEN WHITE BLUE BLUE WHITE BROWN BROWN
AMIT MISHRA
38
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE
LIST OF ALARM’S
(1)RECTIFIER & BTS DOOR CABINET ALARM (2)RECTIFIER MAJOR ALARM (3)RECTIFIER MINOR ALARM (4)LOW DC VOLTAGE (5)HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY) (6)TEMPERATURE ALARM(FOR FAN COOL CABINE ONLY)
CORRESPONDING ALARM NO-
ALARM ALARM ALARM ALARM ALARM ALARM
NO1 NO2 NO3 NO4 N05 NO7
AMIT MISHRA
39
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE
LIST OF COLOUR CODE OF ABOVE ALARM NO1-RECTIFIER & BTS DOOR CABINET ALARM- GREEN & WHITE GREEN NO2-RECTIFIER MAJOR ALARM-BLUE & WHITE BLUE NO3-RECTIFIER MINOR ALARM-VIOLET & WHITE VIOLET NO4-LOW DC VOLTAGE-GREY & WHITE GREY NO5-HEAT MANAGEMENT ALARM(FOR AC CABINET ONLY)-BLUE/BLACK &BLACK BLUE ALARM NO7-TEMPERATURE ALARM(FOR FAN COOLED CABINET ONLY)-LIGHTBLUE &LIGHT BLUE/ BLACK
ALARM ALARM ALARM ALARM ALARM
AMIT MISHRA
40
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE MATERIAL REQUIREMENT-
ALARM CABLE KRONE RACK CAT-5 CABLE 7-9 METER SOLDERING IRON OTHRE BASIC TOOL’S
AMIT MISHRA
41
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE INSTALLATION PROCESS-
Initial step before installation-
(1)Alarm cable is too long so cut it into two pieces. (2)1st cable will be used to take alarm from rectifier smart pack i/o ports to crone.
(3)2nd cable with connector at one end will be used for taking alarms from krone to BTS EAC port(2G cabinet).
AMIT MISHRA
42
INSTALLATION OF ALARM AT OUTDOOR (AC/FAN COOLED) NOKIA BTS SITE INSTALLATION PROCESS CONTINUE STEP-1 KRONE INSTALLATION Install the krone on rack and fix this rack in rectifier cabinet. Use proper size bolt’s and washer.
Connect the alarm cable connector on EAC port at BTS(2G cabinet) Bring the other end of alarm cable to rectifier through roxtec. Punch the alarm cable on the lower side of krone according to the alarm’s sequence. The alarm cable should be fixed properly with ties and properly routed.
AMIT MISHRA
44
INSTALLATION PROCESS CONTINUE-
Route this cable properly with ties and fix it near the Rectifier I/O ports •
Connect Green & White Green (Alarm nu 1) with Pins 8 & 9 of CON1 (X1)
•
Connect Grey & White Grey (Alarm nu 4) with Pins 9 & 10 of CON2 (X2)
•
Connect Violet & White Violet (Alarm nu 3) with Pins 15 & 16 of CON2 (X2)
•
Connect Blue & White Blue (Alarm nu 2) with Pins 18 & 19 of CON2 (X2)
•
Connect Light Blue & Light Blue Black (Alarm nu 7) with Pins 12 & 13 of CON2 (X2)
(Only for Fan Cool Rectifier Cabinets) AMIT MISHRA
45
CON 2 ( X2 ) CON 1 ( X1 )
AMIT MISHRA
46
INSTALLATION PROCESS CONTINUE HEAT MANAGEMENT ALARM
Air condition in the door usually has Red & Yellow cable for Air Condition Alarm. This cable is connected to Pins 3 & 4 on CON1. Remove this cable from there & punch it on Krone.
AIR CON ALARM CABLE
AMIT MISHRA
47
INSTALLATION PROCESS CONTINUE-
Remove this cable from pins & punch it on Krone as shown
Air Con Alarm cable
AMIT MISHRA
48
INSTALLATION PROCESS CONTINUE TESTING HEAT MANAGEMENT ALARM-
To test Heat Management Alarm cover the AC from outside with plastic so that no air can go through as shown below
Air Condition covered with plastic sheet
AMIT MISHRA
49
INSTALLATION PROCESS CONTINUE 900 BTS CABINET DOOR SENSOR The BTS Cabinet door sensor cable is very small so we have to extend it • Take 1 pair from CAT-5 Cable and solder it with the sensor wires in BTS (900 Cabinet) • Route this cable properly and fix it near Smart Pack I/O ports • Connect this pair with pins 3 & 4 of CON 2
BTS Cabinet door Sensor
AMIT MISHRA
50
INSTALLATION PROCESS CONTINUE RECTIFIER CABINET DOOR SENSOR
Rectifier Door Sensor
Usually Rectifier door Sensor cables are already connected to the CON 1 (X1)•
If it is not connected then connect Rectifier Door Alarm Cable with pins 1 & 2 of CON 1 (X1) Rectifier Door cable connected to pins 1 & 2 of CON 1
AMIT MISHRA
51
SUMMARY
Overall summary is that on any BTS site external alarm’s are important. Alarm’s make fault finding easy. External alarm’s make BTS site safer and easy to maintain. Each alarm has it’s own importance cannot be neglected.