ACS 1000 Medium voltage drives
Troubleshoot rou bleshooting ing manual manual Software version: MSAH44xx classic Release date: 05/21/2013 3BHS539545 ZAB E40 Rev.-
Troubleshooting manual
Table of cont c onte ents
Troub Tro ubles les hoot ho ot in g manu al ..................... ................................ ...................... ...................... ...................... ...................... ...................... ...................... .............. ... 5 Fault s ..................... ................................ ...................... ...................... ...................... ...................... ...................... ...................... ...................... ...................... ...................... ............. 7 Al arm s .................... ........................... ............. ........................... .......................... .......................... .......................... ........................... ........................... ............. 105
Troubleshooting manual
Troubleshootin roub leshootin g manual manual If information is required beyond the instructions in this manual, contact ABB as follows:
ABB Switzerland Ltd Ltd Medium Voltage Drives CH-5300 Turgi, Switzerland
Phone:+41 844 845 845 Fax: +41 58 589 58 9 2984 298 4 E-mail
[email protected]
Troubleshooting manual
Faults Panel Panel text
AnIn pCali b
Meaning Meaning of message
Possible causes
Analog input calibration: calibration: Automatic Automatic calibration calibration of analog calibration of analog inputs was not inputs could not be carried out successful. successfully because one of the analog input values is higher than 0.5 mA.
Hints for rectification
Fault class ARU
Fault class INU
Analog input wires have to be disconnected for the calibration. Retry calibration.
Parameter
Bit
9.07
B12
9.07
B02
Defective IOEC.
Aut oRest art
Drive trip because auto-restart sequence takes too long.
Depends on the fault that initiated the auto-restart sequence.
The auto-restart function function is enabled with P31.01.
Wrong parameter setting
Check reason for auto restart attempts. Check related parameters.
Not Appl.
FC2
Panel Panel text
Aux Fan 1/2
Troubleshooting manual
Meaning Meaning of message
Auxiliary fans of water water cooling system: auxiliary fan 1/2 failure. For details see P41.06 RedAuxFanInstall.
Possible causes
Auxiliary fan thermal thermal protection relay has been tripped.
Hints for rectification
Faults
Fault class ARU
Fault class INU
Check thermal relay setting.
Parameter
Bit
9.05
B05
9.02
B08
Check fan phase currents. Faulty components or wiring. Check components and wiring.
Affected internal connections: D13- Auxiliary fan M13 has a thermal IOEC1 (X11/5, X11/6) for AuxFan1, protection relay Q13 with a DI9-IOEC4 (X12/7, X12/8) for normally closed auxiliary contact. AuxFan2.
This supervision cannot be deactivated in the SW.
Behavior of redundant cooling fan is set with P41.06 RedAuxFanInstall: 0 = no redundant fan is installed 1 = redundant fan is installed Default setting is 0 BChopDiscr
BCU was switched on but no feedback was received
Fiber optic link INT to BCU IGCT interrupted.
The status of the signal can be read from - P09.02, Bit08 (FaultWord2)
Fiber optic link CDU to INT interrupted.
Check fiber optic links. Check IGCT status LEDs on GUSP. Check current setting of CDU.
BCU IGCT (-V4501, -V4504) not switching. Wrong current setting on CDU.
Not Appl.
FC2
Troubleshooting manual
Panel Panel text
Meaning Meaning of message
BChopGUSP
BCU GUSP3 failure.
BChopShort
Possible causes
Aux power failure.
Hints for rectification
Faults
Fault class ARU
Fault class INU
Check auxiliary supply, batteries and fuses.
The status of the signal can be read from - P09.02, Bit06 (FaultWord2)
Faulty fiber optic link.
Check auxiliary supply wiring.
GUSP failure.
Check fiber optic cables and connections.
Short circuit in BCU circuit
Short circuit inside the BCU.
Check diodes and IGCTs.
The status of the signal can be read from - P09.02, Bit07 (FaultWord2)
Short circuit on braking resistor.
Check braking resistor.
Incorrect setting on CDU.
Check CDU settings.
Not Appl.
FT
Parameter
Bit
9.02
B06
9.02
B07
Troubleshooting manual
Panel Panel text
Meaning Meaning of message
Possible causes
Brg DE Mlos
Motor bearing temperature Loss of measurement signal. measurement at driven end: loss of analog input. Defective temperature probe.
Hints for rectification
Check measurement circuit, refer to the electrical diagram for terminal identification. Check components and wiring.
Motor bearing temperature is a 4...20 mA analog input signal. BrgDE Mlos alarm is activated when measuring signal drops below 2 mA. Connection: AI02-IOEC3 (X31.3, X32.3) (IOEC3 has to be activated by setting P75.01 to YES). Actual bearing temperature temperature can be read from P80.02 BEARING TEMP DE (via AI02-IOEC3). Measurement loss detection is activated only if P81.10 AI2 MINIMUM IO3 is set to 1 (1 = 4 mA / 2 V). Reaction to measurement loss can be set to NONE, ALARM or SOFT STOP with P35.01 BEARING BEARING TEMP PROTECTION DE.
Faulty components or wiring. Check parameter settings. Communication problem with IOEC3.
Check the analog inputs on IOEC3. Check IOEC3 DIP-switch setting according to wiring diagram.
Faults
Fault class ARU
Fault class INU
Parameter
Bit
9.01
B10