Directional protection and directional zone selectivity
Index
1. Generalities 1.1 Directional Protection: dierent dierent trip times according to the direction o the ault ....2 ....2 1.2 Directional Zone Selectivity: the combination combination o Zone Selectivity and Directional Protection ..................... ............................... ..................... ...................... ..................... ..................... ...................... .................3 ......3
2. Application Description 2.1 Theoretical introduction.......................... .................................... ..................... ...................... ..................... ..................... .....................4 ..........4 2.2 An outline o D .......................... ..................................... ...................... ..................... ..................... ...................... ..................... ..................... ............4 .4 2.3 An outline o SdZ D...................... ................................ ..................... ...................... ..................... ..................... ...................... ...................5 ........5 2.4 D application example: Two Two generators linked to the same busbar ............. .......................6 ..........6 2.5 SdZ application example 1: MV/LV MV/LV transormer substation with bus tie.................8 .................8 2.6 SdZ application example 2: Presence o low voltage generators. ..................... ........................10 ...10
3. Reerences 3.1 Reerence or D........... D...................... ..................... ..................... ...................... ..................... ..................... ...................... ..................... .............12 ...12 3.2 Reerences or SdZ.......................... ..................................... ...................... ..................... ..................... ...................... ..................... .............14 ...14 3.2.1 Marine electrical plant (civilian) ..................... ............................... ..................... ...................... ..................... .............14 ...14 3.2.2 Military naval electrical plant................. plant........................... ..................... ...................... ..................... ..................... ............17 .17 3.2.3 High reliability military electrical plant ..................... ............................... ..................... ...................... ...............17 ....17
4. Practical Guide 4.1 About SdZ............................. ....................................... ..................... ...................... ..................... ..................... ...................... ..................... .............19 ...19 4.1.1 An Overview .................... ............................... ...................... ..................... ..................... ...................... ..................... ....................19 ..........19 4.1.2 “Shopping list” section................ section........................... ..................... ..................... ...................... ..................... ....................20 ..........20 4.1.3 Testing eld ...............................................................................................24 4.1.3.1 Testing with the PR123 Test Function ...........................................................24 4.1.3.2 Testing with Ts3 unit ......................................................................................24 4.2 About D............................. ........................................ ..................... ..................... ...................... ..................... ..................... ...................... .................25 ......25
5. Index o abbreviations ...................... ................................ ..................... ...................... ..................... ..................... ...................26 ........26 6. Bibliography .......................................................................................................27
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
1 1SXU210200G0201
Generalities
1. Generalities This White Paper describes the potential and the use o directional protection and directional zone selectivity unctions, hereater called “D” and “SdZ D”.
1.1 Directional Protection: dierent trip times according to the direction o the ault • DirectionalProtectionisanadvancedfunctionoftripunitsPR123/Pand PR333/P • DirectionalProtectionisusefulincaseswhenthereismorethanone power supply source • DirectionalProtectiondoesnotneedanauxiliarypowersupplyoritsown specic cabling The PR123/P and the PR333/P trip units oer excludable directional protection (“D”) against short-circuits with adjustable xed time. This p rotection unction is very similar to protection “S” with xed time, with the capacity to recognize the current direction during the ault period as well. The “D” makes it possible to determine whether the ault is on the supply side or load side o the circuit breaker, and then to obtain selectivity (“directional time selectivity”, see Application Paper, “Low voltage selectivity with ABB circuit breakers”).
2 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Generalities
In order to use the D unction, you have to set a reerence direction or the current. Then it is possible to set two dierent trip times on the trip unit: •time(t7FW)inthesamedirectionasthereferencedirectionset; •time(t7BW)inadifferentdirectionasthereferencedirectionset. These times are enabled only when the current threshold (I7) set on the relay is exceeded.
1.2 Directional Zone Selectivity: the combination o Zone Selectivity and Directional Protection • DirectionalZoneSelectivityisanadvancedfunctionofthePR123/Pand PR333/P trip units • BymeansofDirectionalZoneSelectivity,selectivitycanbeobtainedinmesh and ring networks • ImplementingtheDirectionalZoneSelectivityissimple:youdonotneed special external devices The SdZ D unction is useul in ring and grid type systems in addition to its zone where it is essential to dene the d irection o the power fow that supplies the ault. This unction is available exclusively on PR123/P and PR333/P trip units and can be only set to “on” when zone selectivity S and G are set to “o” and there is an auxiliary power supply (at 24 V DC). To dene the zone and the power fow, each relay has two inputs (DFin and DBin: i. e. Directional Forward in and Directional Backward in) and two outputs (DFout and DBout: i. e. Directional Forward out and Directional Backward out) that must be suitably connected to the other trip units. Each output is a “block” signal. The breaker that receives the signal will open within the time set; the breaker that doesn’t receive a block signal will op en within a set time t7s. Thus the trip units will behave in two dierent ways, depending on the direction o the power fowing across them.
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
3 1SXU210200G0201
Application description
2. Application Description 2.1 Theoretical introduction The denition o selectivity is given by the ANSI C37.17 Standard, “American National Standard or Trip Devices or AC and General Purpose DC Low voltage Power Circuit Breakers”. Zone protective interlocking provides a selective trip system which obtains shorter tripping times or upstream circuit breakers or aults loca ted between two or more circuit breakers, while providing coordination o upstream and downstream circuit breakers or through aults. Zone protective interlocking may operate on the short-time-delay trip unction and/ or the ground ault trip unction. It requires communication between the direct-acting trip devices comprising the zone protective interlocking system. Selection o the protection system o the electrical installation is undamental both to guarantee correct economical and unctional service o the whole installation and to reduce to a minimum the problems caused by abnormal service conditions or actual aults. Particularly, a good protection system must be able to: • sensewhathashappenedandwhere,discriminatingbetweenabnormalbuttolerable situations and ault situations within its zone o competence, a voiding unwanted trips that cause unjustied stoppage o an undamaged part o the installation. • actasrapidlyaspossibletolimitthedamage(destruction,acceleratedageing, etc.) saeguarding power supply continuity and stability.
2.2 An outline of D
G1 Trip unit
Reference direction inverted through software
Direction set by ABB
There is a deault power fow reerence direction on the circuit breaker, indicated by a red arrow. I it is necessary, it is possible to invert the reerence direction through the sotware o the trip unit. Working in this way all the values measured with the PR123 and PR333 trip units will be assessed as they actually fow in the installation.
CB V
I Inductive/resistive load
Z
Once the power fow reerence direction has be en chosen, the fow o the positive reactive power towards the load (reer to the picture above) is the dened “orward” direction. On the contrary, the fow o the negative reactive power towards the load is the dened “backward direction”. In this manner, because o the bond between reactive p ower and current, the orward and the backward directions are also de ned or the current. 4 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Application description
With the D activated, i the direction o the power cannot be established, the trip unit takes eect considering the shorter programmed times between t7Fw and t7Bw. To determine the direction o the current the value o the phase reactive power has to be higher than 2% o the nominal phase power.
Generator
Trip unit 4
Trip unit 3 DFout4
DFin3
DBin4
DBout3
DFin4 DBout4
DBin3 DFout3
LoadB
LoadC
DFout1 DBin1
DBout2 DFin2
DBout1 DBout1 DFin1
DBin2 DFout2
Trip unit 1
Forward power ow
: Output enabled = 1
Trip unit 2
LoadA
Backward power ow
Fault
2.3 An outline of SdZ D Even in mesh networks and ring networks, in order to obtain selectivity it is necessary to use a protection that combines zone and directional selectivity: the SdZ D. An example conguration or which the SdZ D is likely to be used is illustrated in the above gure. I a ault is detected in one section o the system (Load A), the nal circuit breakers o the interested section (trip unit 1 and trip unit 2), communicate the presence o the ault to the connected circuit breakers (trip unit 3 and trip unit 4) by setting the output signals DFout or DBout, depending on the direction o the current (in our case both DFout o trip unit 1 and DBout o trip unit 2 are on). So the circuit breaker trip unit 1 and trip unit 2, conning the section aected by the ault, are tripped with the set selectivity time t7s, while the circuit breakers urther away rom the ault count down the delay time set, t7FW (trip unit 4) and t7BW (trip unit 3), beore opening. In this way the system is isolated within the time t7s to e xclude only the part aected by the ault.
I one o the circuit breakers required to open does not operate, a specic unction will activate the opening o the rst circuit breaker immediately upstream o it, ater another approx. 100 ms. In this example, i the circuit breaker does not open with the trip unit 1, only the circuit breaker with trip unit 4 will open ater a time t7s+100 ms.
In the event o a lack o auxiliary power supply, the breakers will open in t7w or t7bw times (i.e. SdZ is reduced to being a simple D: this act must be considered by plant designers).
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
5 1SXU210200G0201
Application description
2.4 D application example: Two generators linked at the same busbar G1
G2
-CB1
-CB2
-B1
-CB3
-CB4
M -MS1
Other passive loads
Consider an electrical scheme like the one above. The contribution o the motor to the maximum short circuit current is about 5 kA . The contribution to the short circuit by each generator is about 10 kA. As a consequence, it is not sure that CB1 and CB2 will be able to distinguish between an upstream and a downstream ault. In order to guarantee selectivity between CB1 and CB2 in the event o a ault and to maintain the supply to the other passive loads, it is necessary to use D. Hereunder, an analysis o the two aults on the supply sides taken into consideration: G2
G1
A Reference direction
B Reference direction
CB1
C
D
CB2
E QF3
Other passive loads
CB4 M
Let’s chose reerence directions or CB1, CB2 and CB4 breakers. In this rst case (ault on the supply side o CB1), only CB1 must trip: 1 CB1 detects a current rom 10 kA to 15 kA dierent rom with its reerence direction, and thereore shall trip in t7BW1 time 2 CB2 detects a current o 10 kA the same as its reerence direction, and thereore shall trip in t7FW2 time. 3 CB3 does not detect any ault current 4 CB4 detects a current o maximum 5 kA dierent rom with its reerence direction, and thereore shall trip in the t7BW4 time. 6 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Application description
G2
G1
A Reference direction
B Reference direction
CB1
CB2
C D
E QF3
CB4
Other passive loads
M
In this second case (ault on the supply side o CB2), only CB2 must trip: 1
CB1 detects a current o 10 kA in the same direction as its reerence direction, and thereore shall trip in t7FW1 time
2
CB2 detects a current rom 10 kA to 15 kA dierent rom its reerence direction, and thereore shall trip in t7BW2 time.
3
CB3 does not detect any ault current
4
CB4 detects a current o maximum 5 kA dierent rom its reerence direction, and thereore shall trip in the t7BW4 time.
By repeating the consideration above or any other possible ault, it is possible to give an example o settings (protection S, D and I) or the installation in question (where I7 is the current threshold or D). Protection functions CB
S I2
I
D t2
I7
t7FW
t7BW
I3
CB1
OFF
3 kA
300 ms
200 ms
OFF
CB2
OFF
3 kA
300 ms
200 ms
OFF
CB3 CB4
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
3 kA
200 ms OFF
-
-
-
OFF
3 kA
200 ms
300 ms
OFF
7 1SXU210200G0201
Application description
2.5 SdZ application example 1: MV/LV transormer substation with bus tie substation with bus tie
-TM2
-TM1
IN Fw
IN Bw
CB1 +
OUT Fw
Fw
Fw
OUT
PR123
Bw
IN
CB2 + PR123
Bw
Fw
Bw
OUT Bw
Fw
Bw
-B1
-B2 IN Fw
Bw
IN
CB5 + PR123
Fw
PR123
OUT Fw
CB3 + PR123
CB4 +
Bw
OUT
Bw
Fw
L
Bw
M
Reference direction
The presence o two or more MV/LV transormers and a bus tie closed on the LV busbars in a transormer substation allows the network to be managed with the transormers in parallel. This kind o conguration has the main advantage o allowing power supply even in the case o outage o one transormer. Thanks to SdZ D it is possible to keep hal the busbar supplied with voltage even in the case o a ault on the other hal o the busbar. This example also shows which procedure must be used to determine the cabling required between the various releases. The aults now analyzed are: Fault in B1, Fault in B2
Fault in B1 Only CB1 and CB3 circuit breakers must interrupt the ault: in particular the CB3 circuit breaker is passed through by a current in the same direction as the one set; the DFout sends a lock signal to the DFin o CB2 circuit breaker and to the DBin o CB5 circuit breaker. Direction (OUT -IN) Fw
Fw
Fw
Bw
Bw Bw
Fw Bw
Arrow
-TM1
Refer ence dir ection
IN
CB1+ PR123
Fw Bw OUT Fw
Bw
-TM2 IN Fw Bw OUT Fw
IN
CB2+ PR123
Fw Bw OUT
Bw
Fw
Bw
-B1
-B2 IN
CB4+ PR123
Fw Bw OUT Fw
1SXU210200G0201
IN
CB5+ PR123
Fw Bw OUT
Bw
Fw
L
8
CB3+ PR123
Bw
M
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Application description
Fault in B2 CB2 and CB3 and CB5 circuit breakers must interrupt the ault: in particular the CB3 circuit breaker is passed through by a current coming rom busbar B1 (thereore in the opposite direction rom the one set); the DBout sends a lock signal to the DFin o CB1 circuit breaker. Direction (OUT -IN) Fw
Fw
Fw
Bw
Bw Bw
Fw Bw
Arrow
-TM1
Refer ence dir ection
IN
IN
CB1+ PR123
Fw Bw OUT Fw
-TM2
Fw Bw OUT
Bw
Fw
IN
CB2+ PR123
Fw Bw OUT
Bw
Fw
Bw
-B1
-B2 IN
CB4+ PR123
Fw Bw OUT Fw
CB3+ PR123
IN
CB5+ PR123
Fw Bw OUT
Bw
Fw
Bw
M
L
The remarks described above are summarized in the ollowing table on the cabling o the system: OUT Cabling
CB1 FW
CB1 CB2 IN
CB3 CB4 CB5
CB2 BW
FW
CB3 BW
FW
CB4 BW
FW
CB5 BW
FW
BW
FW BW FW BW FW BW FW BW FW BW
Repeating this reasoning or the our other kinds o possible ault (load side o CB4, load side o CB5, supply side o CB1 and supply side o CB2), it is possible to establish a global table or the system: OUT Cabling
CB1 FW
CB1 CB2 IN
CB3 CB4 CB5
BW
FW
CB4
CB3 BW
FW
BW
FW
CB5 BW
FW
BW
FW BW FW BW FW BW FW BW FW BW
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
CB2
9 1SXU210200G0201
Application description
An example o settings (protection S, D and I) or the installation in question is given where I7 is the current threshold or SdZ D protection and IK the minimum short circuit current calculated. Protection function
CB
S
I2
I
D
t2
I7
t7FW
t7BW
Selectivity time
I3
CB1 CB2 CB3
OFF OFF OFF
350 ms 350 ms 300 ms
250 ms 250 ms 300 ms
150 ms 150 ms 150 ms
OFF OFF OFF
CB4 CB5
OFF OFF
250 ms 250 ms
350 ms 350 ms
150 ms 150 ms
OFF OFF
Selectivity time t7s can be adjusted rom 130 to 500 ms, while t7FW/BW is to be adjusted rom 200 to 800 ms to comply with the relationship: t7FW/BW>t7s+70 ms. That is because 70 ms is the minimum dierence between the trip times o two circuit breakers in series in auxiliary power supply, to guarantee that the circuit breaker on the supply side does not trip. It is important to consider that i the unction I is enabled, and the short circuit current exceeds the value set I3, the circuit breaker will open instantaneously and regardless o directions and signals received. Moreover, even i the unction I is disabled, the line protection is always enabled, the auto-protection o the circuit breaker. In the same way, i the unction S is enabled and the short circuit current exceeds the value set I2, the circuit breaker will op en in the t2 time i this is shorter than the other time s, regardless o the directions and signals received.
2.6 SdZ application example 2: Presence o low voltage generators SdZ D may be very useul when generators are present in the low voltage network. This is a situation that will happen more and more requently in the uture, due to the diusion o distributed energy resources. Let TM1 be the MV/LV transormer, CB1 its LV protection, G1 the low voltage generator, CB2 its protection, B1 the low voltage busbar, M a motor load, CB3 its protection. In the case o ault in A, circuit breaker CB1 is passed through by a current that fows in a direction against with the one set (black arrow). The DBout o CB1 “blocks” the DFin o CB2 and the DBin o CB3. Current fows through CB2 in the same direction as the setting,
10 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Application description
whereas CB3 is passed through by a current against the setting (the active “block” signals are indicated by wider arrows).
-TM1
G1
A
B IN
CB1 + PR123
Fw
OUT Fw
IN
CB2 + PR123
Bw
Fw
Bw
OUT
Bw
Fw
Bw
C
B1 IN Fw
CB3 + PR123
Bw
OUT Fw
Bw
D
M
In the case o a ault in B, the circuit breaker CB2 is passed through by a current rom busbar B1. This current fows in a direction against the one set. The DBout o CB2 “blocks” the DFin o CB1 and the DBin o CB3. In act, current fows through CB1 in the same direction as the setting, whereas CB3 is passed through by a current opposite rom the setting. G1
-TM1 A
B IN
CB1 + PR123
Fw
OUT Fw
IN
CB2 + PR123
Bw
Fw
Bw
OUT
Bw
Fw
Bw
C
B1 IN Fw
CB3 + PR123
Bw
OUT Fw
Bw
D
M
In case o ault in C, CB1 and CB2 are passed through by a current fowing in the same direction as the one set, whereas CB3 is passed through by a current with the opposite direction. No circuit breaker is blocked and consequently all the circuit breakers aected b y the ault will trip according to the time settings o the protection S or I. -TM1
G1
A CB1 + PR123
B IN Fw
CB2 + PR123
Bw
OUT Fw
Bw
IN Fw Fw
C
Bw
OUT Bw
B1 IN Fw
CB3 + PR123
Bw
OUT Fw
Bw
D
M
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
11 1SXU210200G0201
Reerences
3. References 3.1 Reference for D D is commonly used in order to guarantee selectivity between air circuit breakers in substations with two transormers which operate in p arallel on the same busbar.
V
-V1 Vrif = 20000V LLL/IT->TT P = 885kW Q = 462 kvar
-TM1 Vn2 = 480V Sn = 630kVA Sec.: LLLN/TT
-TM2 Vn2 = 480V Sn = 630kVA Sec.: LLLN/TT
A
B -CB1 E1B 1000 PR123/P-LSIG In=1000A RCQ
-CB3 T5N 600 PR221DS-LS/I RCQ
-CB4 T5N 600 PR221DS-LS/I RCQ
-L1 Sn = 350 kWA Cosphi = 0.90
-L2 Sn = 350 kWA Cosphi = 0.90
-CB2 E1B 1000 PR123/P-LSIG In=1000A RCQ
M
-MS1 M3GP 315 MLA 8 - 110 kW T4N350 PR221-I
-MS2 M2BAT 315 SMB 2 - 132 kW T5N400 PR221-I
Cont. LD A210 Relay E320DU Pn = 110.00 kW Cosphi = 0.83
Cont. LD A260 Relay E320DU Pn = 132.00 kW Cosphi = 0.887
-M1
M
-M2
Plant main features Operating voltage
480 V
Rated frequency
60 HZ
Installed power
850 kW
Busbar short-circuit current
28 kA
Above is a sketch o an electrical plant or a ood plant. Assume reerence direction as in the picture above (red arrows). From each transormer a contribution to the short circuit current equal to about 13 kA fows to the low voltage busbar. The two motors together give a contribution to maximum short circuit current o about 2 kA. We have two possible aults near the sources, a ault at load side o TM1 and a ault at load side o TM2.
12 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Reerences
In the rst case (ault in A), CB1 is passed through by a current o a value included between 13 kA and 15 kA, while CB2 is passed through by a current o about 13 kA. Only CB1 must trip: in this manner, shedding the low priority load L2, it is possible to keep on load L1, M1 and M2. Because there may be no dierence between the two short circuit values, it is not possible to use a protection S setting in order to guarantee selectivity between CB1 and CB2. The second case (ault in B) is exactly the same. So, only using D (with t7FW times longer than t7BW times) selectivity between CB1 and CB2 is always saved. Hereunder, the setting o the protection unctions, values o I threshold guaranteed as multiple o In. Protection function
CB
S
D
I2
t2
I
I7
t7FW
t7BW
I3
CB1
OFF
4
300 ms
200 ms
OFF
CB2
OFF
4
300 ms
200 ms
OFF
CB3
4.5
100 ms
-
-
-
OFF
CB4
4.5
100 ms
-
-
-
OFF
MS1
-
-
-
-
-
9
MS2
-
-
-
-
-
9
To be sure that everything unctions as oreseen in case o a ault, i. e. the circuit breakers set with D protection always trip with D protection, the choice o the circuit breakers and the relevant settings has been established ollowing these three simple rules: 1. The circuit breakers must have a short withstand current value higher than the maximum prospective short circuit current that can occ ur at the point where they are installed: Icw>Ikmax 2. The trip threshold o D protection must be set at a lower value than the minimum prospective short circuit current which can occur at the point where that release is installed: I7
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
13 1SXU210200G0201
Reerences
3.2 References for SdZ SdZ D has just been implemented in several applications, three o these are listed below.
3.2.1 Marine electrical plant (civilian) An IEC electrical plant o a large erryboat: -GS1 G
-GS2
Vn = 480 V Vrif = 480 V Cosphi = 0.80 P = 625 kW Q = 604 kvar LLL/IT->TT
G
-WC1
-GS3 G
Vn = 480 V Vrif = 480 V Cosphi = 0.80 P = 888 kW Q = 302 kvar LLL/IT->TT -WC2
10x4G300/150 Ib = 1009.9 A Iz = 1695.0 A dV = 0.02% L=6m -CB1
-WC3
14x4G300/150 Ib = 1230.8 A Iz = 2373.0 A dV = 0.02 % L=8m
-CB6
-CB7
E2S 1600 PR122/P-LSI
E2S 1600 PR122/P-LSI
T7L 1600 PR332/P LSI
-B2
V = 460 V Ib = 2216.5 A Cosphi = 0.90 I’’k LLL = 76.0kA T2L 160
-CB4
T7L 1600 PR332/P LSI
-B1
-CB5
10x4G300/150 Ib = 1010.0 A Iz = 1695.0 A dV = 0.02 % L=6m
-CB3
T7L 1600 PR332/P LSI
Vn = 480 V Vrif = 480 V Cosphi = 0.80 P = 625 kW Q = 605 kvar LLL/IT->TT -WC4
10x4G300/150 Ib = 1010.0 A Iz = 1695.0 A dV = 0.02 % L=6m
-CB2
T7L 1600 PR332/P LSI
-GS4 G
Vn = 480 V Vrif = 480 V Cosphi = 0.80 P = 625 kW Q = 605 kvar LLL/IT->TT
-CB8
V = 460 V Ib = 2216.6 A Cosphi = 0.89 I’’k LLL = 76.0kA -CB9
E1B 1250 PR 123/P-LSI Bus Tie
-CB10
E1B 1250 PR 123/P-LSI Bus Tie
T2L 160
-CB11
-CB12
E2S 1600 PR122/P-LSI
E2S 1600 PR122/P-LSI
-B3
-WC5 4G10 Ib = 27.6 A Iz = 46.0 A dV = 0.14 % L=7m -TM1
Vn2 = 240 V M Sn = 50 kV A
-WC7 4G95/50 Ib = 55.3 A Iz = 179.0 A dV = 0.07 % L=7m
-BW1
-BW2
SC 1200 A 4 cond. AI L = 30 m dV = 0.59 % Ib = 860.0 A Iz = 1260,0 A
-MS1 M2JA 400 MB 4 Pn = 700 HP Cosphi = 0.89 FU = 100 % dV = 0.62 %
SC 1200 A 4 cond. AI L = 10 m dV = 0.22 % Ib = 950.2 A Iz = 1260,0 A
M
-CB13
V = 439.9 V Ib = 756.0 A Cosphi = 0.90 I’’k LLL = 76.0kA
-WC6 4G10 Ib = 29.4 A Iz = 46.0 A dV = 0.14 % L=7m
E2S 1250 PR122/P-LSI
-TM2
-MS2
-BW5
M2JA 400 LKA 4 Pn = 750 HP Cosphi = 0.86 Cosphi = 0.90 FU = 100 % dV = 0.24 %
-MS5 M3KP 355 MLB 4 Pn = 650 HP Cosphi = 0.87 Cosphi = 0.90 FU = 100 % dV = 0.28 %
-CB14
-CB15
T1B 160
T1B 160
-MS6 M
M3AA 180 L 6 Pn = 25 HP Cosphi = 0.79 Cosphi = 0.90 FU = 100 % dV = 1.90 %
14 1SXU210200G0201
-BW2
SC 1200 A 4 cond. AI L = 30 m dV = 0.59 % Ib = 860.0 A Iz = 1260,0 A
-MS3
Vn2 = 240 V M M2JA 400 MB 4 Sn = 50 kV A Pn = 700 HP Cosphi = 0.89 FU = 100 % -WC8 dV = 0.62 % 4G95/50 Ib = 55.8 A Iz = 179.0 A dV = 0.07 % L=7m
MR 1000 A 4 cond. Cu L = 10 m dV = 0.26 % Ib = 756.0 A Iz = 1050,0 A
M
-BW3
SC 1200 A 4 cond. AI L = 10 m dV = 0.22 % Ib = 950.2 A Iz = 1260,0 A
M
-MS2 M3KP 400 LKA 4 Pn = 750 HP Cosphi = 0.86 Cosphi = 0.90 FU = 100 % dV = 0.24 %
-MS7 M
M2BA 100 L2 A Pn = 25 HP Cosphi = 0.79 Cosphi = 0.85 FU = 100 % dV = 1.98 %
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Reerences
Main plant features
Operating voltage
480 V
Rated requency
60 HZ
Installed power
3 MW
Busbar short circuit current
76 kA
There are two bus ties that connect the central 3-phase 500 kW MS5 motor to the two LV busbars. This motor shall be supplied both in the event o a ault on busbar B1 (red one) and o a ault on busbar B2 (green one). Deault directions or the two Emax E1 bus-ties are indicated in the picture be low:
-CB8
-CB9
E1B 1250 PR123/P-LSI Bus Ti e
E1B 1250 PR123/P-LSI Bus Ti e
-CB13 E2S 1250 PR122/P-LSI
-BW5 MR 1000A 4 cond. Cu L = 10 m
-MS5 MRKP 355 MLB Pn = 650 HP
M
G -GS1
G -GS2
Vn = 480 V
B1
OUT
G -GS3
Vn = 480 V
-CB1 IN
-CB2
T7L 1600 PR332/P-LSI
IN OUT
IN
T7L 1600 PR332/P-LSI
Fw
-CB6 E2S 1600 PR122/P-LSI
-CB7 E2S 1600 PR122/P-LSI
Fw
OUT
E1B 1250 PR123/P-LSI Bus Tie
Bw
OUT
Bw
Fw
Vn = 480 V
-CB3
IN Bw
-CB8
-CB5
-GS4
G
Vn = 480 V
Fw
T2L 160
4
IN
T7L 1600 PR332/P-LSI
OUT
-CB4 IN OUT
T7L 1600 PR332/P-LSI
B2
Bw
-CB9 E1B 1250 PR123/P-LSI Bus Tie
-CB10 T2L 160
-CB11 E2S 1600 PR122/P-LSI
-CB12 E2S 1600 PR122/P-LSI
-CB13 E2S 1250 PR122/P LSI
In the event o a ault on the busbar B2 the bus tie o busbar B1 must remain closed, while bus tie B2 must trip so that the ault is isolated. Moreover, CB1 and CB2 breakers must also remain closed and not trip even i they are passed through by a considerable current. Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
15 1SXU210200G0201
Reerences
At the same time, CB1 and CB2 must suitably protect the generators, and their S protection unction has to intercept the curve o the generator in the event o a ault on busbar B1. Because o these two opposing issues, CB1 and CB2 have been equipped with PR332/P trip units, with which it is possible to implem ent the zone selectivity. In the event o a ault on the busbar B2, CB8 will block CB1 and CB2, which will open in S time t2 (set at 0.25 s). However, in the event o a ault on the busbar B1 they will quickly open in t7s time (set at 0.15 s, so that it intercepts the decreasing curve o the generator). In this manner both the issues are respected (see the diagram and the table in the next page). In the event o ault on the busbar B1, it is necessary to act in a similar way. In the picture above, the plant logic is summarized, hinged on the two PR123/P trip units with SdZ D. Time-Curr ent Curve LLL 1E5s
1E4s
1E3s
100s
10s
1s
0.1s
1E-2s
1E-3s
1E-3kA
1E-2kA
0.1kA
1kA
10kA
100kA
1E3kA
Here above, the set time-current curves or generator GS2 (black line), generator protection CB2 (red), motor protection CB7 (blue) and bus tie CB8 (green) are indicated. This brie table shows the chosen settings o the breakers considered in the time-current graph. Protection function
S
D
I
CB
I2
t2
t7FW
t7BW
t7SEL
I3
CB2
1.8
250 ms
-
-
150 ms
OFF
CB7
OFF
OFF
-
-
-
8
CB8
OFF
OFF
250 ms
-
150 ms
OFF
16 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Reerences
3.2.2 Military naval electrical plant -GS1 Vn = 600V Cosφ = 0.80 LLL/IT ->TT
G
-GS2 Vn = 600V Cosφ = 0.80 LLL/IT ->TT
G
-CB2
-CB1
-CB3
-CB4
-CB5
-CB6
-CB7
-CB8
Load @ 480 V
-GS3 Vn = 600V Cosφ = 0.80 LLL/IT ->TT
Load @ 480 V
-TM1
-TM2
-CB9
Load @ 480 V
G
-CB10
-CB11
-TM3
-CB12
Main plant features Operating voltage
480 V
Rated frequency
60 HZ
Installed power
7.5 MVA
Ring short-circuit current
65 kA
Above is a simplied sketch o a part o a ship electrical plant. The topology o the plant is characterized by the presence o a ring which the loads are linked to. In this case, only by using SdZ D it is possible to reach selectivity (see paragraph 2.1).
3.2.3 High reliability military electrical plant G
G
G
OUT
ET1
ET2
IN OUT IN
EG1
OUT
OUT
IN
IN
EG2
OUT IN OUT
IN
EG3
EG4
IN
IN
EG-AB
OUT IN
BW
OUT FW
OUT
BW OUT
IN
IN FW
E01-1 OUT IN
E01-3 E01-2
Low Voltage Products & Systems
IN
ET-AB
FW
B
IN BW
OUT
OUT
E01-4 E01-5
ABB Inc. • www.abb.us/lowvoltage
ET4
OUT
FW
A
ET3
G
BW
E02-1
E02-2 OUT IN
E02-3
OUT IN
E02-5 E02-4
17 1SXU210200G0201
Reerences
Main plant features
Operating voltage
480 V
Rated requency
60 HZ
Installed apparent power
7.5 MVA
Max busbar short circuit current
65 kA
EMAX
Number of breakers
All EMAX
20
With PR123/P relay and SdZ D
2
With PR122/P relay and SdZ
14
With PR121/P relay
4
Withdrawable version
20
With interblock
4
Let’s ocus on the ET-AB bus tie. The plant layout oresees that it is not possible to have more than two transormers parallel connected on the same busbar, thereore: • ET-ABwillbealwaysopenwhenET1,ET2,ET3andET4areallclosed • ET-ABwillbeclosedonlyifoneamongthecoupleET1/ET2andoneamong the couple ET3/ET4 are closed at the same time. Moreover, the generators cannot operate in parallel with the transormer, except or ew minutes.
Let’s analyze two dierent ault types: 1) Fault in the main switchboard A with only TR1 and TR3 on duty In this case:
2) Fault in the main switchboard B with only TR1 and TR3 on duty In this case:
• ET1andET3close
• ET1andET3close
• ET2andET4open
• ET2andET4open
• ET-ABclose
• ET-ABclose
• E01-3open
• E02-3open
• E01-2close
• E02-2close
• E01-4close(E01-5open)
• E02-4close(E02-5open)
The ault path aects E01-2, ET1, ET-AB, ET3 breakers.
The ault path aects the E02-2, ET3, ET-AB, ET1 breakers.
E01-2 senses the ault and blocks ET1 and ET-AB (simple zone selectivity); ET-AB is passed through by a current coming rom the busbar supplied by TR3 (thereore in the same direction as the one set, see the blue arrow), so the DFout sends a lock signal to the DFin o ET3.
E02-2 eels the ault and blocks ET3 and ET-AB (simple zone selectivity); ET-AB is passed through by a current coming rom the busbar ed by TR1 (thereore in the opposite direction as the one set), so the DFout sends a lock signal to the DFin o ET1. It is quite clear that only using a SdZ D or the ET-AB relay it is possible to reach a good degree o selectivity in this plant.
18 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Practical guide
4. Practical Guide 4.1 About SdZ 4.1.1 An overview To set up the SdZ D unction you must suitably connect the K11 – K15 terminals on EMAX terminal box. For example, i you have a system like the ollowing (sketch o a part o a real electrical plant o an electronic equipment actory):
1
1
AT12S 5000/5A
3
A-V-Hz-cosphi Wh-V ARh VA-W-V AR
3 AT12S ASC10 5000/5A 5+5+5/5A
RS485 Mod-Bus RTU
4
A-V-Hz-cosphi Wh-V ARh VA-W-V AR
3
Voltmetric
24 V DC
24 V DC
E6H-5000 600V 5000A 100kA
E6-2 PR123/P L-S-S2-I-G-RC-D-U OT-UV-OV-RV-RP-UF-DF A-V-Hz-cosphi Wh-VARh-VA-W-VAR DF in DB out
In = 5000A
E6H-5000 60 0V 5000A 100kA
E6-3 PR123/ P L-S-S2-IG-RC-D-U OT-UV-OV-R V-RP-UF-DF A-V-Hz-cosphi Wh-VARh-V A-W-V AR DF in DB out
3
RS485 Mod-Bus RTU
4
I 3
24 V DC
3 In = 5000A
AT12S 5000/5A
Voltmetric
I 3
PFI E6H-5000 600V 5000A 100kA
E6-1
RS485 Mod-Bus RTU
4
Voltmetric
I 3
1
TR-3
A-V-Hz-cosphi Wh-V ARh VA-W-V AR
PR123/P L-S-S2-I-G-RC-D-U OT-UV-OV-RV-RP-UF-DF A-V-Hz-cosphi Wh-VARh-VA-W-VAR DF in DB out
3 In = 5000A
Block signal fr om TR1 to TR2
Block signal fr om TR1 to TR3
Block signal fr om TR2 to TR1
Block signal fr om TR2 to TR3
Block signal fr om TR3 to TR1
Block signal fr om TR3 to TR2
in this illustrative scheme you can nd the cabling: *F)
Uoux. 24V K1 K1 1 K
Uoux. 24V K2 K2
K15 K15 5 1 K
1 K
K14 K14 4 1 K
K13 K13 3 1 K
K12 K12 2 1 K
K1 K1
Q/26 3 6
X K2
1 X K2 2
1 6
K51
K51
*N) *V) 3 XK2
3 W
5
4 W
W3 W3
W4 W4
XK3
3
X K2
1 X K2 2
K13 K13 3 1 K
K12 K12 2 1 K
K1 K1
Q/26
1 K
Q/27 4 6
1 6
K51
PR122/ P PR123/ P 3 XK2
5
4 W
E6-1
W4 W4
XK3
5 1 K
1 K
X K2
1 X K2 2
K51
*N) *V) 3
3 1 K
K12 K12 2 1 K
Q/26
Q/27 4 6
1 6
2 6
X K3 1 XK3 2 X K3 5 X K3 4 X K4 1 XK 4 2 X K4 5 XK 4 6
K51
K51
PR122/ P PR123/ P
K51
*N) *V) 3 XK2
5
4 W
W3 W3
E6-2 (A)(B) W2
4 1 K
K13 K13
SZin(DFin) SZout(DFout) GZin(DBin) GZout(DBout)
3 W
K11 K11
K14 K14
K51 K51
XK2
1 1 W
K15 K15
3 6
X K3 1 XK3 2 X K3 5 X K3 4 X K4 1 XK 4 2 X K4 5 XK 4 6
K51
K2 K2
2 6
SZin(DFin) SZout(DFout) GZin(DBin) GZout(DBout)
W3 W3
(A)(B) W2
4 1 K
K51 K51
3 W
K11 K11
K14 K14
3 6
XK2
1 1 W
K15 K15 5 1 K
1 K
K51
SZin(DFin) SZout(DFout) GZin(DBin) GZout(DBout)
XK2
K2 K2
2 6
X K3 1 XK3 2 XK 3 5 XK 3 4 X K4 1 XK 4 2 X K4 5 XK 4 6
K51 K51
1 K
Q/27 4 6
Uoux. 24V
W4 W4
XK3
PR122/ P PR123/ P
3
1 1 W
K11 K11
E6-3 (A)(B) W2
Star connected K11 terminals, not grounded
K51
K51
K51
K51
SZin(DFin) SZout(DFout) GZin(DBin) GZout(DBout)
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
19 1SXU210200G0201
Practical guide
The terminals that must be connected are physically present (and clearly identied) in EMAX terminal box.
4.1.2 “Shopping list” section To use SdZ D the ollowing is needed: 1) An EMAX ACB with PR123/P or an EMAX X1 with PR333/P
All EMAX rames can be used to realize SdZ D. 20 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Practical guide
2) A cable
A two-wire shielded corded cable can be used to carry out the cabling. A cable that can be used or the application is the “Belden 3105A”, manuactured by BELDEN. The conductor diameter is 0.30 inch, characteristic impedance is 120 Ohm, max. operating voltage-UL 300 V RMS, max. recommend current 2.7 A per conductor @ 25°C). The shield o the cable must only be connected to ground in correspondence with one o the two trip units. When it is possible to nd an additional circuit breaker “on the supply side” between the two, it is advisable to connect the shield to ground in correspondence with the trip unit o the circuit breaker. The maximum length o cabling between two units or zone selectivity is 300 meters. This limit can be increased using a special mechanism.
3) A power pack
The external auxiliary power supply is provided using a galvanically-separated power pack. You may use an ABB CP-24 power supply unit (supply voltage: max. 260 V). It is recommended to provide an output current o 0.5 A per circuit breaker supplied.
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
21 1SXU210200G0201
Practical guide
4) Some special devices for some particular applications 4a) Zone Selectivity Array With reerence to the gures below, in a specic ca se o current fow: C must lock A and B D must only lock B With the cabling in the gure below, it would not be possible to obtain the desired solution.
A B
C
D
In act, the lock signal coming rom D would also be transmitted to A by means o the electrical continuity which is created between the dierent B-C and C-A interlocking connections. By means o suitable cabling o the Zone Selectivity Array module (ZSA). Cabling is carried out by ABB on customer’s request. The lock signal is made one-way so that a signal coming orm D towards B is not transmitted to A as well. See the picture below.
A
B
ZSA C
22 1SXU210200G0201
D
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Practical guide
In act, ZSA is a diode matrix that allows distributing the input blocking signal to the correct output without undesired signal returns. Look at the example below: 1
IN
2
IN
3
IN
4
IN
11
OUT
12
OUT
13
OUT
11
12
13
1 2 3 4
Blocking signal
11
12
13
1
X
X
X
2
X
X
3
X
4
X X
X
1 blocks 11,12 and 13, 2 blocks 11 and 12.... and so on. The maximum number o circuit breakers which can be connected to the outputs o a trip unit is 20, or PR123 that blocks other PR123s. I you have old devices type PR113, there are less connections available: 3 in the case o a PR123 that blocks PR113s; 3 in the case o PR113 that blocks other PR113s. The maximum number o circuit breakers which can be connected to the inputs o a PR123 trip unit is indenitely high.
4b) Zone Selectivity Buer As above, the maximum number o circuit breakers which can be connected to the outputs o a trip unit is 3 in the case o a PR113 that blocks PR113s. I it is necessary to block 4 or more PR113, it is possible to use a Zone Selectivity Buer (ZSB) unit. ZSB is an amplier and needs to be supplied with auxiliary voltage.
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
23 1SXU210200G0201
Practical guide
4.1.3 Testing eld There are two dierent kinds o tests that can be perormed in order to veriy the correct unctioning o the SdZ D. The rst one (see clause 4.1.3.1) shall be perormed when the electrical system is working under normal operating conditions, while the second one (see clause 4.1.3.2) simulates a ault in the plant. Between the two, only the rst one can be carried out by the customer: the other one is carried out by ABB technicians.
4.1.3.1 Testing with the PR123 test unction Testing SdZ D using the PR 123 test unction is simple. In order to test whether the implemented system works properly, it is possible to orce the output signals DFout and DBout o one breaker and then proceed to veriy the status o the breakers connected. This specic unction may be activated under the trip unit’s Test Menu selecting the “Zone selectivity” menu. Menu
4/6
Password
Test
1/6
CB status
Measures Settings Test
Enter
0***
Enter
Auto test Trip test (disabled)
Device test
Enter password
CB open
4.1.3.2 Testing with the Ts3 unit By using the special Ts3 testing unit, it is possible to simulate short circuit current on several breakers, and then to test the correct working o the SdZ D unction. To simulate the test, the Ts3 unit applies a suitable current to the secondary o the PR113/P CS or sets a suitable voltage in the Rogowski coil o the PR123/P, so that the PR1x3/P sees a ault current.
24 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Practical guide
4.2 About D D does not need a terminal connection or a n external power supply. Once the customer has decided to use D, they just have to choose the power fow direction.
Modules
1/4
MEASURING module Voltage Transf
MEASURING module COM module SIGNALLING module
1/4
Enter
Rated voltage Positive Power ow
Communication parameters
Absent
Choosing the power fow direction is simple. Entering in the measuring module menu (you can nd it in the settings menu) and selecting “positive power fow” is possible to make a choice between Bottom -> Top Or Top -> Bottom. It is only possible to test D protection using the Ts3 unit (see paragraph 4.1.3.2).
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
25 1SXU210200G0201
Index o abbreviations
5. Index o abbreviations D
Directional protection
SdZ D Directional zone selectivity function t7FW
Trip time in a direction concordant with the reference direction set
t7BW
Trip time in a direction discordant with the reference direction set
I7
Current threshold for D and SdZ D
DFin
Directional Forward input
DBin
Directional Backward input
DFout Directional Forward output DBout Directional Backward output t7s
Selectivity time, i. e. the trip time of the “unlocked” circuit breakers
26 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Practical guide
6. Bibliography Technical Application Paper, “Low voltage selectivity with ABB circuit breakers”, May 2008, code 1SDC007100G0204. ANSI C37.17 “American National Standard or Trip Devices or AC and General Purpose DC Low Voltage Power Circuit Breakers” Electrical Installation Handbook volume 1, “Protection and control device”, March 2007, code 1SDC008001D0205 Electrical Installation Handbook volume 2, “Electrical device”, March 2007, code 1SDC010001D0205.
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
27 1SXU210200G0201
Notes
28 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Notes
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
29 1SXU210200G0201
Notes
30 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage
Notes
Low Voltage Products & Systems ABB Inc. • www.abb.us/lowvoltage
31 1SXU210200G0201
Notes
32 1SXU210200G0201
Low Voltage Products & Systems ABB Inc. •
www.abb.us/lowvoltage