Powerware® 9355 20-30 kVA UNINTERRUPTIBLE POWER SUPPLY
Service Manual
July 2006 164201621 Revision A02
Notice of Proprietary Information The equipment discussed herein is capable of causing great harm to life, limb and/or property. Installation, maintenance, and/or repair, of the equipment referenced herein must be performed by Eaton Electrical duly authorized or trained certified personnel. Notwithstanding the foregoing, Eaton Electrical assumes NO responsibility for any damage or injury to any persons or property which may be caused to any extent by reliance on the information provided herein except to the extent such damage or injury results solely and directly from the willful negligence of Eaton Electrical, it’s agents or employees. Additionally, Eaton Electrical shall not be liable for any indirect, special incidental or consequential damages, such as, but not limited to, loss of anticipated profits, good will or other economic loss in connection with or arising out of the existence of, the furnishing of, or the use of the information provided for in this agreement, whether or not the possibility of damage was disclosed to or could have been reasonably foreseen by Eaton Electrical. The information contained herein is proprietary to Eaton Electrical and may be used or copied only in accordance with written agreement with Eaton Electrical. It is UNLAWFUL TO COPY OR REPRODUCE THIS DOCUMENT OR ANY PART THEREOF IN ANY MEDIA OR TO USE OR REFERENCE SAME EXCEPT FOR THOSE PURPOSES IN THE MEANS AND QUANTITIES SPECIFIED BY WRITTEN AGREEMENT WITH EATON ELECTRICAL. Periodically, changes are made to the contents herein. Please contact Eaton Electrical or your original source for any modification, updates or new additions. Due to the possibility of such changes, RELIABILITY ON THE CONTENTS HEREIN IS AT RECIPIENT’S/USERS’S OWN RISK. The equipment provided by Eaton Electrical contains areas that conduct lethal voltages. The maintenance of Eaton Electrical equipment requires factory trained personnel that are aware of the potential danger areas.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Table of Contents
Table of Contents Chapter 1 System Overview 1.1 System Description 1.1.1 Single Module Systems 1.2 Single Module–Reverse Transfer (RT) Modes of Operation 1.2.1 NORMAL Mode 1.2.2 BATTERY Mode 1.2.3 Power Share Operation 1.2.4 BYPASS Mode 1.3 Parameter Settings 1.3.1 Parameter List 1.4 Input Isolation Transformer (60 Hz Only) 1.4.1 PW 9355 1.5 Seismic Capability 1.6 External Battery Cabinets 1.7 Remote Emergency Power Off (REPO) 1.8 Environmental Monitoring Probe (EMP) 1.9 Parallel Tie Cabinet with System Bypass
1-1 1-1 1-4 1-4 1-6 1-8 1-8 1-12 1-12 1-16 1-16 1-16 1-16 1-16 1-16 1-17
Chapter 2 Safety 2.1 General Safety Considerations 2.1.1 Tools, Equipment, and Expendable Field Service Supplies 2.1.2 General Safety Rules 2.2 Environmental Safety 2.3 Electrical Safety 2.4 Mechanical Safety 2.5 Eye Safety 2.6 UPS Safety 2.6.1 Operating Environment 2.6.2 Normal Operation 2.6.3 Maintenance/Service 2.6.4 Batteries 2.7 Site Safety 2.8 Summary 2.9 Electrostatic Discharge (ESD) Procedure And Equipment Requirements 2.9.1 Purpose 2.9.2 Objective 2.9.3 Applicable Documents and Materials 2.9.4 Definitions 2.9.5 Procedure 2.9.6 Removal of Boards 2.9.7 Packaging of Boards 2.9.8 General Handling Guidelines for ESD Protection
2-1 2-1 2-1 2-2 2-3 2-4 2-4 2-5 2-5 2-5 2-5 2-6 2-7 2-8 2-8 2-8 2-8 2-8 2-9 2-9 2-10 2-11 2-11
Chapter 3 Installation and Startup 3.1 MODEL 9355 20 – 30kVA SINGLE MODULE (RT) 3.1.1 Mechanical Inspection 3.1.2 Electrical Inspection © 2006 - Eaton Corporation
3-1 3-1 3-5 i
Table of Contents
ii
9355 20 – 30 kVA
Operational Inspection 3.2 MODEL 9355 20 – 30kVA Parallel (PC/PR) 3.2.1 Mechanical Inspection 3.2.2 Electrical Inspection 3.2.3 Operational Inspection 3.2.4 Inspection Completion
3-7 3-10 3-10 3-16 3-19 3-21
Chapter 4 Functional Descriptions 4.1 Model 9355 20 – 30kVA 4.1.1 Overview 4.1.2 X-Slot Connections 4.1.3 Native RS Port 4.2 Electronics Module Functional Sections 4.2.1 Display Panel 4.2.2 Control Board 4.2.3 Power Module Boards 4.2.4 Bypass Control Board 4.2.5 I/O Board 4.2.6 EMI / Surge Board 4.2.7 Contactors 4.2.8 Internal Battery 4.2.9 External Battery 4.2.10 Battery Circuit Breaker 4.2.11 Ferrite Toroids 4.2.12 Chokes 4.2.13 Fans 4.3 LCD Display Panel 4.3.1 Overview 4.3.2 Detailed Description of Settings 4.3.3 User Settings 4.3.4 Service Settings 4.4 CONTROL BOARD (PCB) 4.4.1 Firmware Description and Operation 4.4.2 Shutdown State 4.4.3 Startup State 4.4.4 Battery Starting State 4.4.5 Utility Starting State 4.4.6 Inverter Starting State 4.4.7 Standby State 4.4.8 User Interface & XCP 4.4.9 On Inverter State 4.4.10 On Bypass State 4.4.11 The Bleeding State 4.4.12 Bypass-Locked State 4.4.13 Failure Shutdown State 4.4.14 Methods of Turning the UPS Off 4.4.15 XCP Command Codes 4.4.16 Hardware Signals 4.5 POWER MODULE BOARD (PCB)
4-1 4-1 4-2 4-2 4-3 4-3 4-3 4-3 4-3 4-3 4-3 4-4 4-4 4-4 4-4 4-4 4-5 4-5 4-5 4-5 4-6 4-6 4-9 4-11 4-11 4-12 4-13 4-15 4-16 4-18 4-19 4-20 4-20 4-21 4-25 4-26 4-27 4-28 4-28 4-29 4-31
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Table of Contents
4.5.1 Introduction & Overview 4.5.2 Description and Operation 4.5.3 Other Connector Descriptions 4.6 Power Board Functional Blocks 4.6.1 Voltage Sensing 4.6.2 Rectifier 4.6.3 Battery Converter 4.6.4 Inverter 4.6.5 IGBT Gate Drives 4.7 Advanced Battery Management 4.7.1 Introduction 4.7.2 Purpose 4.7.3 General Terms 4.7.4 Charging Cycles 4.7.5 Temperature Compensation 4.7.6 Forcing on Rest Mode 4.7.7 User Disabling of ABM Charging Cycles 4.7.8 Battery Failure Testing 4.8 Battery Lifetime 4.8.1 Introduction 4.8.2 Operational Sequence 4.8.3 Battery Discharge 4.8.4 Run-Time and Temperature 4.9 Battery Test 4.9.1 Introduction 4.9.2 Battery Test 1 4.9.3 Battery Test 2 4.9.4 Battery Test Calculations 4.10 I/O BOARD (PCB) 4.10.1 Overview 4.10.2 I/O Connector Descriptions 4.11 I / O Board Functional Sections 4.11.1 Auxiliary Power Supply 4.11.2 Rail Precharge 4.11.3 Voltage Sensing 4.12 Current Measurements and Hardware Current limits 4.12.1 Output Current Measurement 4.12.2 Input and Output Filtering Scheme 4.12.3 Inverter/Rectifier Fault Methodology 4.12.4 Single Feed/Dual Feed Input Contactors 4.12.5 Battery Relay, Battery Start and Current Measurement 4.12.6 Balancer Relays and Drive 4.12.7 Battery CB Trip 4.12.8 Input/Output CB Trip 4.12.9 Other Sensing 4.12.10 X-Slots 4.12.11 AC Fans 4.12.12 Chassis GND 4.12.13 Troubleshooting © 2006 - Eaton Corporation
4-31 4-32 4-32 4-33 4-33 4-33 4-33 4-34 4-34 4-35 4-35 4-35 4-36 4-38 4-39 4-40 4-41 4-42 4-44 4-44 4-44 4-44 4-45 4-45 4-45 4-45 4-45 4-46 4-49 4-49 4-50 4-59 4-59 4-59 4-59 4-60 4-60 4-60 4-61 4-61 4-61 4-62 4-62 4-62 4-62 4-62 4-63 4-63 4-63 iii
Table of Contents
iv
9355 20 – 30 kVA
4.13 Bypass Board System Overview 4.14 Bypass Board Functional Blocks 4.14.1 BAUX Power Supply 4.14.2 Voltage Sensing 4.14.3 Input Contactor 4.14.4 Alarm Supply 4.14.5 EPO Alarm 4.14.6 Building Alarms 4.14.7 RS-232 4.14.8 NO/NC Relay Contacts 4.15 Bypass SCR Gate Drive and SCRs 4.15.1 Standalone Bypass Functionality 4.15.2 Bypass State Machine 4.15.3 AC Fans 4.16 ELECTRO-MAGNETIC INTERFERENCE (EMI) BOARD (PCB) 4.16.1 Introduction 4.16.2 EMI Board Functional Sections
4-64 4-66 4-66 4-66 4-67 4-67 4-67 4-67 4-67 4-67 4-67 4-68 4-68 4-72 4-73 4-73 4-73
Chapter 5 Connectivity and Communications 5.1 9355 GENERAL CONNECTIVITY DEVICES 5.1.1 Basic Serial Communication 5.1.2 Relay Signaling 5.1.3 Building Alarm Inputs 5.1.4 Additional Connectivity & Software 5.2 9355 X-SLOT CONNECTIVITY DEVICES 5.2.1 Modem Handling 5.2.2 Modem Operation 5.2.3 Modem Call Handling States 5.2.4 Communication During a Modem Session 5.3 9355 COMMUNICATION 5.3.1 Default Communication Access Passwords 5.3.2 Signal Inputs & Programmable Functions 5.3.3 Programmable Functions 5.3.4 Signal Inputs on Front Panel Display 5.3.5 Configuration Fields 5.3.6 HyperTerminal
5-1 5-1 5-1 5-1 5-1 5-2 5-2 5-4 5-8 5-16 5-19 5-19 5-19 5-19 5-22 5-23 5-27
Chapter 6 Options 6.1 Communications and Connectivity Options 6.1.1 Single Port RS-232 Serial or AS/400 Signal Card 6.1.2 Multi-Port/Multi-Server Card 6.1.3 Low Voltage (LV) Relay Interface Card 6.1.4 High Voltage (HV) Industrial Relay / RMP Interface Card 6.1.5 ConnectUPS Network Adapters 6.1.6 MODBUS Communications Card 6.1.7 Modem Card 6.1.8 USB Module 6.1.9 CAN Bridge Card 6.1.10 Remote Monitor 6.2 Options Cabinet
6-2 6-2 6-3 6-5 6-7 6-8 6-9 6-10 6-13 6-14 6-14 6-15
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Table of Contents
6.3 Power Distribution Unit (PDU) 6.4 Remote Power Panel (RPP) 6.4.1 IQ 100 Series RPP 6.4.2 IQ 200 Series RPP
6-18 6-19 6-19 6-19
Chapter 7 Troubleshooting and Maintenance 7.1 Troubleshooting Charts 7.1.1 Action Levels 7.1.2 Alarm, Notice, Status & Flag Definitions 7.1.3 Detailed Definitions 7.1.4 Failure Analysis 7.1.5 Electronics Module and Other Failures
7-1 7-1 7-3 7-22 7-27 7-36
Chapter 8 Removal and Replacement 8.1.1 Removal Preparation 8.1.2 Removing the L3 Power Module 8.1.3 Replacing the L3 Power Module 8.1.4 Removing the L2 Power Module 8.1.5 Replacing the L2 Power Module 8.1.6 Removing the L1 Power Module and Bypass Board 8.1.7 Replacing the L1 Power Module / Static Switch Assembly 8.1.8 Removing the I/O Board Assembly 8.1.9 Replacing the I/O Board 8.2 TECHNICAL SUPPORT KNOWLEDGE BASE
8-1 8-1 8-4 8-6 8-7 8-8 8-12 8-13 8-19 8-21
Chapter 9 9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.1.6 9.1.7 9.1.8 9.1.9 9.1.10 9.1.11
9-4 9-5 9-7 9-8 9-9 9-10 9-11 9-12 9-14 9-15 9-16
Calibration Calibrate Bypass AC Input Voltage Calibrate Utility AC Input Voltage Calibrate Battery Voltage Calibrate DC Link Voltage Calibrate UPS AC Output Voltage Calibrate Inverter AC Output Voltage Calibrate Inverter DC Output Voltage Calibrate Bypass Current (Output) Calibrate Utility Current Calibrate Battery Current Calibrate Inverter Current
Chapter 10 Parts 10.1 PW 9355 30kVA SPARE PARTS LISTINGS 10.1.1 Low Voltage PW 9355 30kVA Spare Parts Kit “A” P/ N 106711170 10.1.2 High Voltage PW 9355 30kVA Spare Parts Kit “A” P/ N 10.2 PW 9355 30kVA UPS Subassemblies 10.2.1 LV Electronic Module 10.2.2 HV Electronic Module 10.3 Parts Break-down / Look-up Procedure 10.3.1 Requirements: 10.3.2 Procedure
10-1 10-1 10-2 10-2 10-2 10-3 10-4 10-4 10-4
Chapter 11 Prints
© 2006 - Eaton Corporation
v
Figure List
9355 20 – 30 kVA
Figure List Figure 1. Figure 2. Figure 3. Figure 4. Figure 5. Figure 6. Figure 7. Figure 8. Figure 9. Figure 10. Figure 11. Figure 12. Figure 13. Figure 14. Figure 15. Figure 16. Figure 17. Figure 18. Figure 19. Figure 20. Figure 21. Figure 22. Figure 23. Figure 24. Figure 25. Figure 26. Figure 27. Figure 28. Figure 29. Figure 30. Figure 31. Figure 32. Figure 33. Figure 34. Figure 35. Figure 36. Figure 37. Figure 38. Figure 39. Figure 40. Figure 41. Figure 42. Figure 43. Figure 44. Figure 45. Figure 46. Figure 47. vi
EATON-Powerware® 9355 20–30kVA UPS .............................................. 1-1 PW9355 30kVA Basic Single Module System............................................ 1-2 PW 9355 NORMAL Mode (single feed)...................................................... 1-4 PW 9355 NORMAL Mode (dual feed) ........................................................ 1-5 PW 9355 BATTERY Mode (single feed)..................................................... 1-6 PW 9355 BATTERY Mode (dual feed) ....................................................... 1-7 PW 9355 BYPASS Mode (single feed)...................................................... 1-9 PW 9355 BYPASS Mode (dual feed) ........................................................ 1-9 PW9355 Service Position ......................................................................... 1-11 PW9355 Maintenance Bypass Position ................................................ 1-11 Parallel Tie Cabinet with System Bypass.............................................. 1-17 Front door panel removed...................................................................... 3-1 Right side skin panel removed................................................................ 3-2 Wiring Access After Dead Front Panel Removal .................................... 3-2 XCP Tool Battery Toggle Positions......................................................... 3-6 Front door panel removed..................................................................... 3-10 Right side skin panel removed.............................................................. 3-10 Wiring Access After Dead Front Panel Removal .................................. 3-11 CAN Bridge Board Jumper Settings ..................................................... 3-13 Parallel Control Wiring .......................................................................... 3-13 XCP Tool Battery Toggle Positions....................................................... 3-17 Display Panel.......................................................................................... 4-5 9355 Control Board............................................................................... 4-11 9355 Control Board Machine States ..................................................... 4-12 9355 Power Board ................................................................................ 4-31 Typical Battery Charging Cycle............................................................. 4-38 PW 9355 I/O Board............................................................................... 4-49 Bypass Control Board ........................................................................... 4-64 State Diagram....................................................................................... 4-68 Modem Call Handling States .................................................................. 5-8 No Modem State..................................................................................... 5-9 Modem Idle State.................................................................................. 5-11 Modem Dialing State ............................................................................ 5-13 Modem Session State........................................................................... 5-14 Hanging Up State ................................................................................. 5-15 Path to HyperTerminal Application ....................................................... 5-27 HyperTerminal Opening Screen Selections .......................................... 5-27 Select COM1 or COM2 from the drop-down menu ............................... 5-28 Port Parameter Setup ........................................................................... 5-28 File, Properties menu options, Settings tab, Emulation drop-down....... 5-29 Font Settings menu............................................................................... 5-29 Single Port Serial Card ........................................................................... 6-2 Multi-Port Serial Card.............................................................................. 6-3 Low Voltage Relay Interface Card .......................................................... 6-5 High Voltage Industrial Relay Card......................................................... 6-7 10 Megabyte SNMP/Web 10/100 Megabyte SNMP/Web/Hub........ 6-8 SNMP / Web / Hub Card Components.................................................... 6-8 © 2006 - Eaton Corporation
9355 20 – 30 kVA
Figure 48. Figure 49. Figure 50. Figure 51. Figure 52. Figure 53. Figure 54. Figure 55. Figure 56. Figure 57. Figure 58. Figure 59. Figure 60. Figure 61. Figure 62. Figure 63. Figure 64. Figure 65. Figure 66. Figure 67. Figure 68. Figure 69. Figure 70. Figure 71. Figure 72. Figure 73. Figure 74. Figure 75. Figure 76. Figure 77. Figure 78. Figure 79. Figure 80. Figure 81.
Figure List
MODBUS Communications Card............................................................ 6-9 MODBUS Communications Card Components ...................................... 6-9 Modem Card ......................................................................................... 6-10 X-Slot Modem Functional Parts ............................................................ 6-11 USB Module.......................................................................................... 6-13 CAN Bridge Card .................................................................................. 6-14 CAN Bridge Card J3 Terminals............................................................. 6-14 Options Cabinet with MBS Wiring ......................................................... 6-15 Options Cabinet with Dual-Feed Wiring ................................................ 6-16 Options Cabinet with Output Transformer Wiring ................................. 6-17 Remote Power Panels Series 100 and 200 .......................................... 6-20 Damage Sustained by the IGBTs Due to Severed Wiring....................... 8-2 Top Fan Dead Front and Bracket Plates................................................. 8-2 L3 and Fan Removal Points on the I/O Board ........................................ 8-3 Bypass Board Silk Screen ...................................................................... 8-3 L3 PM Shelf Insertion.............................................................................. 8-4 L2 Removal Points on the I/O Board ...................................................... 8-6 Positive Battery String Wires .................................................................. 8-8 Bypass Static Switch Connections.......................................................... 8-9 I/O Board Wiring Connections to Static Switch ..................................... 8-10 Static Switch Housing and SCRs.......................................................... 8-11 DC Link Check Points ........................................................................... 8-13 Removing the control board from the I/O board.................................... 8-14 Wiring Locations ................................................................................... 8-15 Wiring Removal Diagram ...................................................................... 8-16 TB5 ....................................................................................................... 8-17 Bus bar and neutral bolts ...................................................................... 8-17 Chassis Screws .................................................................................... 8-18 Analog Potentiometer Diagram............................................................... 9-1 Analog to Digital Circuit........................................................................... 9-1 Digital Potentiometer Diagram ................................................................ 9-2 9355 Front Calibration Points ................................................................. 9-5 I/O Board Bypass Phase A, B and C .................................................... 9-12 208V DC Link Voltage Calibration test points ....................................... 9-13
© 2006 - Eaton Corporation
vii
Figure List
9355 20 – 30 kVA
164201621 Change sheet Revision
A001
A002
viii
Item
Section(s)
Change
Table of Contents
Accommodates new pages
Figure List
Accommodates new figures 8-3
Figure 62 added for procedure elaboration
8-9
Figure 66 added for procedure elaboration
Prints
Page 9
110720639 TOPS Rev B00
Chapter 1 (System Overview)
Section 1.3
“Parameter Settings” added.
Chapter 3 (Installation and Startup)
Section 3.1.1
Elucidated item 1.e. under module inspection — check ALL wiring.
Chapter 9 (Calibration)
All
Emphasis placed on XCP software tool use
Prints
CTO charts
Added to hard copy
Chapter 8 (Removal and Replacement)
© 2006 - Eaton Corporation
1 System Overview 1.1 System Description Refer to Figure 1, EATON-Powerware® 9355 20–30 kVA UPS and Figure 2, Basic Single Module System.
1.1.1
Single Module Systems
The EATON-Powerware® 9355 UPS is intended to be an Online Double Conversion Uninterruptible Power Supply rated at 20kVA–30kVA, 3-phase in/3phase out, with 4 basic models: •
20kVA — 30kVA 230/400
•
20 or 30kVA 120/208
The power-train topology is unique to the PW9355 design but uses the same control board as the PW9155 and PW9355-15kVA.
Figure 1.
EATON-Powerware® 9355 20–30kVA UPS © 2006 - Eaton Corporation
1-1
System Overview
Figure 2.
9355 20 – 30 kVA
PW9355 30kVA Basic Single Module System
A digital signal processor (DSP) is used to provide all software functionality (that is, analog metering, digital signal sampling, power-train control including Pulse Width Modulated (PWM) gate signals, serial communications, and user interface processing). The UPS incorporates Flash ROM for upgrades to DSP firmware using the PW Flash Utility (via serial port communication). For more information on the Control board, see paragraph 4.4. These systems are designed to be one of the most enhanced and improved EATON-Powerware® UPS products, using a compilation of the most successful features found in previous products. The basic system consists of:
1-2
•
a rectifier
•
battery converter
•
inverter
•
monitoring / operation control panel
•
integrated communications server
•
and microprocessor controlled (DSP) logic.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
System Overview
A single module operates independently, providing conditioned and uninterruptible AC power to support an applied critical load. During an outage, the module continues to operate, supporting power to the critical load from the batteries. If the module requires service, critical loads can be manually transferred to internal maintenance bypass. No additional cabinets or equipment are required. UPS input is derived from a power factor corrected, current controlled, and half bridge boost rectifier. The conditioned output comes from a current controlled half bridge buck inverter. The battery converter is a current controlled boost converter, and the charger is a current controlled buck converter. Power Share mode limits the utility current and provides DC link rail voltage regulation. Internal batteries within the UPS are replaceable and can be hot swapped by a qualified service technician without affecting the critical load (the UPS will not have battery back-up available during the swap out). Frequency / phase converter operation is possible with a de-rated output load capacity to 80%. Frequency / phase converter mode can be configured from the front panel or through the XCP configuration command. With default frequency converter configuration, bypass will not be available. Integral bypass can perform an automatic transfer (0 msec, no break) of attached critical loads from the UPS to a bypass source if required. The unit will recover from automatic bypass without dropping the critical load if the unit does not indicate damage.
© 2006 - Eaton Corporation
1-3
System Overview
9355 20 – 30 kVA
1.2 Single Module–Reverse Transfer (RT) Modes of Operation The EATON–Powerware® 9355 UPS will support a critical load in three different modes of operation: 1.
NORMAL
2.
BATTERY
3.
BYPASS
The UPS can automatically use all three modes without operator intervention. To achieve this, sophisticated detection and control logic is used to ensure that any change in operating mode is automatic and transparent. Internal monitoring systems indicate the current mode of operation. A more detailed explanation of the three modes of operation, using block diagrams, will follow.
1.2.1
NORMAL Mode
Refer to Figure 3 and Figure 4 NORMAL Mode. During normal UPS operation, power for the system is delivered from a utility input source to the rectifier input breaker CB-1. The rectifier converts the incoming AC (alternating current) power to DC (direct current) using IGBT (Isolated Gate Bipolar Transistor) devices to produce a regulated DC voltage for the inverter, while the battery is charged through a buck / boost DC converter. S ervice
B ypass
UP S
B ypass
S ervice
UP S
S ervice
Input TB
B ypass
Bypass Input
UP S
MBS
Single feed jumper Output TB
Rectifier Input
CB-3
CB-1
Optional
Static Switch K-5
K-3
K-1
Rectifier
Inverter
Battery Converter
CB-2
<
Remote External Battery
Figure 3.
1-4
Up and Match < Line External Battery
PW 9355 NORMAL Mode (single feed)
© 2006 - Eaton Corporation
LOAD
S er vice
B ypa ss
UP S
B ypa ss
UP S
S er vice
MBS
B ypa ss
Input TB
S er vice
System Overview
UP S
9355 20 – 30 kVA
Bypass Input Output TB
LOAD
Rectifier Input
CB-3
CB-1
Optional
Static Switch K-5
K-3
K-1
Rectifier
Inverter
Battery Converter
CB-2
<
Remote External Battery
Figure 4.
<
Line Up and Match External Battery
PW 9355 NORMAL Mode (dual feed)
The DC converter derives its input from the regulated DC output of the rectifier and provides a regulated, boosted DC voltage charge to the battery. The battery charge condition is monitored by the UPS and reported by status indicators located on the LCD monitor panel. The battery is always connected to the UPS and ready to support the inverter should the utility input become unavailable. The system has a shunt trip for the battery and can disconnect the battery under a fault condition or Remote Emergency Power Off (REPO) activation, see paragraph 1.7 for details. The neutral from the system input is connected to the neutral throughout the system.
CAUTION The output neutral of the system is connected with the required neutral for the customer’s critical load and should never be bonded to ground at the module output.
The inverter produces three phase AC output to a customer’s critical load without the use of a transformer. The inverter derives regulated DC from the DC Link and uses IGBT devices and PWM (pulse-width modulation) to produce a regulated and filtered AC output. The AC output of the inverter is delivered to the system output by way of the inverter output contactor K-3. “NORMAL” appears on the module front panel to indicate that the system is providing clean and protected power to the connected critical loads. © 2006 - Eaton Corporation
1-5
System Overview
1.2.2
9355 20 – 30 kVA
BATTERY Mode
Refer to Figure 5 and Figure 6 BATTERY Mode. The UPS enters into BATTERY mode automatically during a utility power failure, when the input power to the rectifier is out of specification (refer to the specifications in your generator manual), and in some cases during a noncatastrophic rectifier failure. During a utility power failure, the rectifier no longer has an AC utility source to supply the DC output power required by the inverter. When the rectifier is turned off, the supply of DC current to the inverter is drawn from the awaiting charged batteries. When the rectifier is partially operational, Power Share mode is implemented.
Bypass
Service
UPS
Bypass
UPS
Service
MBS Bypass
Bypass Input Input TB
Service
UPS
Power Share mode provides DC link rail voltage by drawing supplemental power from the batteries (that is, Power Share mode apportions energy jointly from the batteries and from the rectifier to supply adequate energy to the inverter to maintain the critical load). See paragraph 1.2.3 on for more details about Power Share.
Single feed jumper Output TB
Rectifier Input
CB-3
CB-1 Static Switch K-5
K-3
K-1
Rectifier
Inverter
Battery Converter
CB-2
Figure 5.
1-6
<
Remote External Battery
<
Line Up and Match External Battery
PW 9355 BATTERY Mode (single feed)
© 2006 - Eaton Corporation
LOAD
Optional
9355 20 – 30 kVA
System Overview
Bypass Input
Bypass
Service
UPS
Bypass
Service
UPS
Bypass
Input TB
Service
UPS
MBS
Output TB
Rectifier Input
LOAD
CB-3
CB-1
Static Switch K-5
K-3
K-1
Rectifier
Inverter
Battery Converter
<
Remote External Battery
CB-2
<
Figure 6.
Line Up and Match External Battery
PW 9355 BATTERY Mode (dual feed)
When the rectifier can no longer supply energy to the inverter, energy stored in the battery is supplied instantaneously to the DC converter and is boosted so that the inverter can support the customer’s critical load without interruption. To prevent battery output from back-feeding, the rectifier contactor (K-1) opens on separate feed, but this is not true of a dual fed system when the UPS goes to battery. Opening K-1 on a single fed system prevents static system voltages from bleeding backwards through the rectifier “snubber” components and reentering the input source. For more information on the Battery Boost Converter, refer to paragraph 4.6.3. While in BATTERY mode, the UPS will annunciate an audible horn, light a visual indicator lamp on the front panel (ON BATTERY), and make an entry into the alarm event history. As the battery discharges, the converter and inverter constantly make minute adjustments to maintain steady output. The UPS will remain in this operating mode until the input power to the rectifier is again within specification. If the input power fails to return, or is not within the acceptance window required for normal operation, the battery will continue discharging until a DC voltage level is reached and the inverter output can no longer support the critical load. When this occurs, the UPS will issue another set of audible and visual alarms indicating SHUTDOWN IMMINENT. Unless the rectifier has an immediate valid input, the output will only be supported for approximately one (1) minute before the UPS shuts down, dropping the critical load.
© 2006 - Eaton Corporation
1-7
System Overview
9355 20 – 30 kVA
If the input power becomes available during battery discharge, the rectifier contactor (K-1) is closed; the rectifier turns on and provides power to the DC Link for the inverter, and begins recharging the battery. At this point, the unit returns to NORMAL operation. Depending on the amount of load on the system and the duration of the battery discharge, battery and rectifier input current limit alarms might be seen for a short time due to the current required to recharge the battery. The UPS total operating time on battery will depend on many factors. Some factors that affect battery support are battery type and capacity, the number of parallel strings, environmental temperatures, battery age, and fluctuations in load demand during battery discharge. The greater the load, the less support time the battery can sustain; as the load decreases, the battery support time generally increases.
1.2.3
Power Share Operation
Power Share mode pulls energy from the batteries and from the rectifier to supply energy to the inverter. Two conditions that cause the unit to enter power share mode are: 1.
A scheduled battery test and
2.
The rectifier exceeds the maximum input current
The utility voltage determines the maximum power that the rectifier may provide and the maximum input current allowed. If the power required by the inverter exceeds the maximum rectifier power, the rectifier is run in a constant power mode, and the battery converter is turned on to make up the deficit. In this way, the UPS draws maximum power from the rectifier while supplementing the power shortfall as efficiently as possible using the batteries. When the battery test is running, rectifier power is regulated so that the power required for testing is drawn from the batteries. For more details on Advanced Battery Management, refer to paragraph 4.7.
1.2.4
BYPASS Mode
Refer to Figure 7 and Figure 8, BYPASS Mode. When the inverter is unable to support the critical load, the UPS will transfer the load to the internal bypass to ensure the critical load remains energized. In BYPASS mode, the output of the system is provided with three-phase AC power directly from the system input (or utility source). While in this mode, the output of the system is not protected from voltage, frequency fluctuations or power outages. Some power line filtering and spike protection is provided to the critical load, but no active power conditioning or battery support is available to the critical load during the bypass mode of operation.
1-8
© 2006 - Eaton Corporation
9355 20 – 30 kVA
System Overview Bypass
Service
UPS
Bypass
Service
UPS
Bypass
Input TB
Bypass Input
Service
UPS
MBS
Single feed jumper Output TB
Rectifier Input
CB-3
CB-1
LOAD
Optional
Static Switch K-5
K-3
K-1
Rectifier
Inverter
Battery Converter CB-2
<
Remote External Battery
Figure 7.
<
Line Up and Match External Battery
PW 9355 BYPASS Mode (single feed)
Bypass Input
Bypass
Service
UPS
Bypass
Service
UPS
Bypass
Input TB
Service
UPS
MBS
Single feed jumper Output TB
Rectifier Input
CB-3
CB-1
LOAD
Optional
Static Switch K-5
K-3
K-1
Rectifier
Inverter
Battery Converter CB-2
Figure 8.
<
Remote External Battery
<
Line Up and Match External Battery
PW 9355 BYPASS Mode (dual feed) © 2006 - Eaton Corporation
1-9
System Overview
9355 20 – 30 kVA
The internal bypass is comprised of a solid-state Silicon Controlled Rectifier (SCR) static switch. The (SCR) static switch is rated as a continuous duty device that is used anytime the inverter is unable to support the applied critical load. The bypass static switch is an electronically controlled device, so if a system fault occurs necessitating an emergency transfer to bypass, the static switch can be turned on immediately to pick up the critical load from the inverter, while the inverter output contactor (K-3) automatically opens to isolate the inverter. During an outage, transfers to BYPASS are prohibited with single feed input. For the safety of those who may be working on the power lines upstream from the UPS, back-feed protection is provided by opening the bypass contactor (K-5), which prevents system output voltage from bleeding across the bypass static switch (SCR) components to the input source. The output of the system will be transferred automatically to the internal bypass if any of the following abnormal conditions occur on the output of the system: •
the output of the system exceeds acceptable voltage or frequency tolerances.
•
the system is overloaded.
•
there is an inverter failure.
The transfer is initiated by turning on the bypass static switch (SCR) and by opening the inverter output contactor (K-3). This kind of transfer is normally referred to as a “make-before-break” transfer, or emergency transfer to bypass. The transfer should take place in less than 4 msec (one-quarter cycle) to ensure critical loads on the system output are not interrupted. The bypass static switch (SCR) remains on until either the inverter is able to support the system output, or until the unit is placed in maintenance configuration to facilitate repairs. If the UPS automatically initiates transfer to bypass without operator intervention, the UPS will attempt to automatically restart the inverter, and to transfer the UPS back to on-line status to support the system output. Three attempts will be made automatically within ten minutes to bring the inverter back on-line before the UPS will lock out any further attempts. After three (3) attempts have been made, the UPS will remain in BYPASS and an alarm condition will be annunciated. The UPS can also be manually transferred to BYPASS using the front panel controls. A Maintenance Bypass Switch (MBS) is installed on all units. When the switch is in the “UPS” position it operates as discussed in the previous paragraphs. When the switch is in the “Service” position the critical load is powered by utility, and the UPS has power available for troubleshooting and maintenance (see Figure 9). When the switch is in the “Bypass” position power to internal bypass is secured and the critical load is supplied by utility (see Figure 10). CB-1 controls the input power to the rectifier in a single or dual feed UPS. For more information on Bypass Mode, refer to paragraph 4.4.10. 1-10
© 2006 - Eaton Corporation
Byp ass
Se rvi ce
U PS
Byp ass
UPS
Se rvi ce
MBS Byp ass
Input TB
Se rvi ce
System Overview
UPS
9355 20 – 30 kVA
Bypass Input Single feed jumper Output TB
Rectifier Input
CB CB-3
CB-1
LOAD
Optional
Static Switch K-5
K-3
K-1
Rectifier
Inverter
Battery Converter
CB-2
<
<
Bypass Input
Byp ass
Se rvice
UPS
Bypass
Se rvice
MBS UPS
Se rvice
Input TB
Line Up and Match External Battery
PW9355 Service Position
UPS
Figure 9.
Byp ass
Remote External Battery
Single feed jumper Output TB
Rectifier Input
CB-3
CB-1
LOAD
Optional
Static Switch K-5
K-3
K-1 Rectifier
Inverter
Battery Converter CB-2
<
Remote External Battery
Figure 10.
<
Line Up and Match External Battery
PW9355 Maintenance Bypass Position © 2006 - Eaton Corporation
1-11
System Overview
9355 20 – 30 kVA
1.3 Parameter Settings This section describes the parameters list option in the 9X55 service menu. This menu is intended so that a service technician can change UPS settings without serial communication. This list is correct for 9X55 ESW version 1.06.xx for the 9355.
1.3.1
Parameter List
Note: Send over CAN means that in a parallel system, updating 1 unit will update all units in the parallel system that are connected to the CAN network. Numbers missing in numerical sequence either apply to 9155 units exclusively or the setting has been disabled. Table 1. Parameters List Setting for the 9X55 LV Service Menu Param Num
0 1
3 4 5 6
7
8 9
1-12
Description Start Screen Language
Horn enable
Default
Options
0
0
Power ware logo
1
Mimic Screen
0
English
1
French
2
Spanish
0
Horn is disabled
1
Horn is enabled
0
Transfer to bypass immediately
1
Transfer to bypass after a delay
0
Synchronization is not required
1
Synchronization is required
0
Synchronization to bypass is enabled
1
Synchronization to bypass is disabled
0
Transfer to bypass is allowed
1
Transfer to bypass is not allowed
0
Site fault is enabled
1
Site fault is disabled
0
REPO is enabled
1
REPO is disabled
0
1
Overload transfer to bypass
1
Sync required for bypass transfer
1
Sync disable
0
Bypass disable
Site fault disable REPO disable
0
0 0
Option description
© 2006 - Eaton Corporation
Send over CAN No No
No YES YES YES
YES
No YES
9355 20 – 30 kVA
10
11
12
13
14
15
System Overview
Disable control commands from X-Slot1
0
Disable control commands from X-Slot1/Service port
0
Automatically schedule battery test
1
ABM disable
0
Charger temp. compensation disable
0
Modem installed
0
0
Control commands from X-Slot1 are allowed
1
Control commands from X-Slot1 are not allowed
0
Control commands from XSlot1/ service port are allowed
1
Control commands from XSlot2/ service port are not allowed
0
Battery test will only run when requested from LCD or XCP
1
Battery test will run every ABM cycle without user intervention
0
ABM cycling is disabled (constant float)
1
ABM cycling is enabled
0
Temperature compensation is enabled
1
Temperature compensation is disabled
0
No modem is installed
1
Modem is installed in X-Slot1
2
Modem is installed in X-Slot2
No
No
No
No
No
No
16
On battery delay
5
0-99
Time in seconds before “UPS on Battery “ alarm is activated
YES
17
XCP Auto-on delay
0
0-32767
XCP auto-on delay in seconds
YES
-1
Restart through LCD or remote only
XCP Auto-off delay
-1
0-32767
XCP auto-off delay in seconds
18
-1
YES
Disabled
19
Input signal shutdown delay
120
0-65535
Used if input signal is programmed for delayed shutdown
20
X-Slot signal input activation delay
5
0-65
After the set time delay, the RS323 pin is recognized to be an active signal (3-12 Vdc). Refers to function of signal inputs
No
21
Number of internal battery strings
Model specific
0-22
Number of parallel strings of internal batteries
No
23
Internal battery capacity
34
1-32767
Capacity, in W/cell of internal batteries at 15min rate
No
© 2006 - Eaton Corporation
YES
1-13
System Overview
9355 20 – 30 kVA
24
Battery low alarm level
1880
17501950
Voltage, in mV/cell, that sets the “Battery Low” alarm
YES
25
Constant float voltage
2300
21502335
Battery float voltage, in mV/cell when ABM cycling is disabled
No
26
Max charge current
340
50-3400
Maximum battery charge current, in mA * 100, per battery string
No
27
Nominal Output voltage
1200
1200
Nominal output voltage is 120Vac to neutral
1270
Nominal output voltage is 127Vac to neutral
YES
28
Bypass voltage high limit
10
1-20
Upper voltage window for bypass, in percent nominal voltage
YES
29
Bypass voltage low limit
-15
(-1)- (20)
Lower voltage window for bypass, in percent nominal voltage
YES
30
Sync window
2000
10003000
Frequency window around nominal that inverter will sync to bypass in mHz
YES
31
Utility sync window
2000
10003000
Frequency window around nominal that inverter will sync to utility in mHz
YES
32
Nominal output frequency
60000
50000
Nominal output frequency is 50Hz
YES
60000
Nominal output frequency is 60Hz
35
Reset Modem
NA
1
Causes the UPS to send a reset command to the modem
No
36
Reset History
NA
1
Clears the UPS event history
No
37
Reset to factory defaults
NA
1
Resets all parameters on this list to factory default
No
38
Lock X-Slot2 to service port
0
0
X-Slot2/service port are multiplexed
No
1
X-Slot2 is disabled, service port only is usable
NA
1
Requests battery commissioning test to run
No
1
0
UPS is not allowed to back feed utility during battery test
No
1
UPS is allowed to back feed utility during battery test
40
Scheduled battery commissioning test
41
Enable full power battery test
1-14
© 2006 - Eaton Corporation
9355 20 – 30 kVA
42
43
46
Auto-sense input frequency
System Overview 1
Parallel UPM number
0
Parallel mode
0
0
Do not auto-sense input frequency, get inverter frequency configuration from eeprom
1
On next power-up, auto-sense input frequency and configure inverter to match, then clear this bit. (One time only)
0
Single unit configuration
1-4
YES
No
Parallel system configuration. Each UPM in parallel system must have a different UPM number
0
Parallel redundant system
1
Parallel capacity system
YES
47
Start parallel auto-calibration
NA
1
Initiates parallel system autocalibration
YES
48
Start No-load/full load
NA
1
Initiates no load/full load test
No
49
Error state reset
NA
1
Clears parallel comm errors. Also resets 0xC9 encryption lock out
YES
50
Remove offset
NA
1
Initiates offset auto-calibration
51
Force xcp subunit
0
0
Parallel unit accepts system and sub-module commands
1
Forces parallel unit to submodule mode always
53
Number of external battery strings
56
Reset battery alarms
0
0-65535
Number of external battery strings of different capacity than internal batteries
NA
1
Clears “Battery needs service” and “battery test failed” alarms
© 2006 - Eaton Corporation
No
No
1-15
System Overview
9355 20 – 30 kVA
1.4 Input Isolation Transformer (60 Hz Only) 1.4.1
PW 9355
The input isolation transformer is contained in the Options Cabinet and can come in various configurations. See chapter 6.
1.5 Seismic Capability Seismic stands will be provided as necessary. A non-operating seismic test will derive test methods from NEBS GR-63-CORE, ANSI T1 329, or EN 60068-2, as appropriate.
1.6 External Battery Cabinets The UPS will operate with up to three (3) External Battery Cabinets (EBCs), containing four battery strings in each cabinet. The EBCs can increase battery capacity to a maximum of 18 battery strings, Including the internal batteries: a maximum of twelve (12) strings of 24 ampere-hour batteries in the EBCs and six (6) internal battery strings of 9 ampere-hour batteries.
1.7 Remote Emergency Power Off (REPO) The remote emergency power off (REPO) switch is a provision for powering down the customers critical load when rapid shutdown is required. The REPO function is activated by an external contact. Both normally open and normally closed REPO contacts are provided. The REPO control can be used in conjunction with a room or building REPO, so that the utility can be removed no matter what position the UPS Maintenance Bypass Switch (MBS) is in.
WARNING AN ACTIVE REPO SIGNAL WILL DE-ENERGIZE THE CRITICAL LOAD. When REPO is activated with utility present or on battery, the load is deenergized immediately. The UPS will shut down all converters, de-energize all system contactors, trip the CB-1 and CB-2 breakers, and fully power down the UPS within 10 to 15 seconds. Note: If the REPO switch is not connected to the feeder breaker, the Customer critical load will maintain power in the Maintenance Bypass position.
1.8 Environmental Monitoring Probe (EMP) The Environmental Monitoring Probe is used only with a Web/SNMP Card. Refer to the Supporting Documents for information on installation and for additional information. 1-16
© 2006 - Eaton Corporation
9355 20 – 30 kVA
System Overview
1.9 Parallel Tie Cabinet with System Bypass The Parallel Tie Cabinet is capable of paralleling up to 4 UPMs. It has a maintenance bypass switch and auxiliary contacts to force the UPS to bypass mode when the UPS maintenance output breakers (MOBs) are closed and the UPS in normal operating mode.
CB1
UPM#1 Input Breaker
CB1
UTILITY INPUT
UPM#2
#1
#2
#3
#4
Input Breaker CB1
Input Breaker
UPM#3 CB1
TO LOAD
Input Breaker
UPM#4
Figure 11.
Parallel Tie Cabinet with System Bypass
© 2006 - Eaton Corporation
1-17
System Overview
9355 20 – 30 kVA
This page was left blank intentionally.
1-18
© 2006 - Eaton Corporation
2 Safety 2.1 General Safety Considerations 2.1.1
Tools, Equipment, and Expendable Field Service Supplies
When performing service calls or procedures on Eaton Electrical equipment, the following rules must be observed. These rules pertain to tools, testers, solvents, adhesives, and lubricants: •
Ensure that electrical hand tools, such as power drills, are inspected regularly.
•
Replace worn and broken tools and test equipment with new tools and equipment.
2.1.2
General Safety Rules
Adhere to the following safety rules for working with electrical and mechanical equipment in the maintenance and repair procedures: •
The UPS must be used as intended. Follow the instructions given in the user guide and installation manual.
•
Installation and use of the UPS must comply with all national and local safety regulations and procedures.
•
All primary power switches installed downstream from the UPS must be labeled as follows: “ISOLATE UPS (Uninterrupted Power Supply) before working on this circuit.”
© 2006 - Eaton Corporation
2-1
Safety
9355 20 – 30 kVA
2.2 Environmental Safety Observe the following rules:
WARNING DO NOT WORK ALONE AS DANGEROUS VOLTAGES ARE PRESENT INSIDE THE UNIT. THE UPS MUST BE INSTALLED AND SERVICED ONLY BY SERVICE PERSONNEL FROM THE MANUFACTURER OR FROM AN AGENT AUTHORIZED BY THE MANUFACTURER. 1.
Always inform the appropriate supervisor/manager of conditions or voltages that might pose a threat to safety. Take all steps necessary to maximize safety.
2.
Always look for possible hazards, such as moist floors, nongrounded extension cables, power supplies, and missing safety grounds.
3.
Do not make un-authorized changes or modifications to the equipment. This creates a hazard and unsafe equipment.
4.
Before starting the equipment, ensure that other service and customer personnel are not exposed to any unsafe conditions.
5.
Do not wear loose clothing that can be trapped in the moving parts of a machine. Ensure sleeves are fastened or rolled above the elbow.
6.
If wearing a necktie or scarf insert it into the clothing or fasten it with a nonconductive clip at approximately 8 centimeters (3 inches) from its end. This prevents the tie from being caught by a moving part of the equipment.
7.
If your hair is worn long, fasten it to make it safe.
8.
Lift the equipment or parts by using your leg muscles to prevent back strain. Do not lift any heavy equipment or parts that cannot be lifted comfortably.
9.
Always keep tool kits away from walk areas to prevent a tripping hazard. If possible, keep all tools and tool kits on or under a table.
10. Observe good housekeeping practices in the area of the UPS while performing maintenance and after completing the job. 11. Place removed UPS covers in a safe place while servicing the UPS. Reinstall the covers before returning the UPS to the customer. 12. Reinstall all safety devices, such as guards, shields, and ground wires. Replace safety devices that are worn or defective with new ones. Remember that safety devices protect personnel from a hazard. Ensure all safety devices are reinstalled when the maintenance/service has been completed. 2-2
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Safety
2.3 Electrical Safety Observe the following rules when working on electrical machinery: 1.
2.
Follow the manual shut down and maintenance bypass procedures to prevent loss of power to the customers load. Switch input and logic power off if recommended in the service manual and: •
before removing or assembling the main units of the equipment.
•
before working near power supplies.
•
before inspecting power supplies.
•
before installing changes in machine circuits.
Unless the maintenance documents specifically instruct otherwise:
WARNING DO NOT SERVICE INPUT, OUTPUT, OR BYPASS CIRCUIT BREAKERS, TRANSFORMERS, CTS, OR PTS WITH POWER ON. 3.
If working on equipment that has exposed live electric circuits, OBSERVE the following precautions: •
To protect against high leakage current; connect protective earth (PE or ground) before connecting power supply cables.
•
Ensure another person who is properly trained in the power-off controls is in a close proximity at all times to switch off power, if necessary.
•
Remove jewelry, chains, metal frame eyeglasses, or other personal metal objects.
•
Use only insulated probe tips or extenders.
•
Use one hand while working on or near energized equipment. Keep one hand in your pocket or behind your back to prevent electric current flow across the heart.
•
Do not touch objects that are grounded, such as metal floor strips, machine frames, or other conductors. Use suitable rubber mats. Obtain the mats locally, if necessary.
When using test equipment, set the controls as referenced in the operator’s, or service, manual. Use only properly insulated probes. 4.
When working with machines having voltages more than 30 VAC or 42.4 VDC, observe special safety instructions (referenced in the service manual). © 2006 - Eaton Corporation
2-3
Safety
9355 20 – 30 kVA
5.
The output neutral of the system is connected with the required neutral for the customers load and should never be bonded to ground at the module output.
6.
Ensure ALL battery breakers, and EBMs, are open before checking voltages.
WARNING NEVER ASSUME THAT POWER HAS BEEN REMOVED FROM A CIRCUIT. CHECK AND ENSURE THAT POWER HAS BEEN REMOVED BY USING A VOLTMETER. 7.
Do not touch live electric circuits with the surface of a dental mirror. The mirror handle is conductive and can cause equipment damage and/or personal injury.
8.
If an electrical accident occurs: •
Instruct another person to get medical aid
2.4 Mechanical Safety
CAUTION Do not touch moving mechanical parts at any time (Including fans). To prevent overheating, do not obstruct the air flow or block the ventilation openings to the unit.
2.5 Eye Safety
CAUTION Safety glasses shall be worn at all times.
Use additional caution when using the following equipment or when performing procedures listed below:
2-4
•
Using a hammer
•
Using a power drill
•
Using a spring hook
•
Soldering parts
•
Cutting wire or removing steel bands
•
Using solvents, chemicals, or cleaners to clean parts
•
Working in any other condition that might cause eye injury (that is, a UPS module under power, input or bypass)
© 2006 - Eaton Corporation
9355 20 – 30 kVA
•
Safety
Do not wear soft contact lenses when working on or around electrical equipment.
2.6 UPS Safety
WARNING THE OSCILLOSCOPE MUST BE ISOLATED BY USING AN ADAPTER THAT ISOLATES THE SCOPE AND EARTH GROUND. USE EXTREME CAUTION; THE SCOPE WILL HAVE POTENTIAL BETWEEN THE UPS FRAME AND THE SCOPE. DO NOT TOUCH THE UPS AND THE SCOPE AT THE SAME TIME.
2.6.1
2.6.2
Operating Environment 1.
Keep surroundings clean and free from excess moisture.
2.
Do not operate in close proximity to gas or electric heat sources.
3.
The system is not intended for outdoor use.
4.
The operating environment should be within the parameters listed in Chapter 1.
Normal Operation 1.
Keep equipment doors closed to ensure proper cooling airflow, and to protect you from dangerous voltages within the unit.
2.
Ensure all conduit knockouts and/or unnecessary openings are sealed.
3.
Do not make any assumptions about the electrical state of the UPS. CHECK THE ELECTRICAL STATUS WITH A VOLTMETER!
WARNING THIS UPS CONTAINS LETHAL VOLTAGES. ALL REPAIRS AND SERVICE SHOULD BE PERFORMED BY AUTHORIZED SERVICE PERSONNEL ONLY. THERE ARE NO USER SERVICEABLE PARTS INSIDE THE UPS. The following safety cautions are intended to provide important specific information about the safe operation of the UPS. Violation of these precautions could result in serious damage to the UPS and/or injury or death.
2.6.3
Maintenance/Service 1.
Always wear appropriate eye protection.
2.
Remove restrictive clothing and remove all jewelry.
3.
Use correct documentation and appropriate tools as outlined in this manual. © 2006 - Eaton Corporation
2-5
Safety
9355 20 – 30 kVA
2.6.4
4.
Use static secured work area and procedures when performing component replacement or modifications.
5.
Ensure power is disconnected before performing installation or service when possible.
6.
Observe all CAUTIONS, WARNINGS, and DANGER notices fixed to the inside and/or outside of the equipment.
7.
Always comply with more detailed safety precautions described at the appropriate paragraph later in this manual.
Batteries 1.
The lead-acid batteries are maintenance-free sealed batteries. No electrolyte/water can be added. Lead-acid batteries must be disposed of correctly in compliance with the local regulations.
CAUTION The battery breaker on the rear of the electronic module or Extended Battery Module (EBM) shall be in the OFF position prior to connecting or disconnecting batteries. The RED wires from the electronics module must be connected to the POSITIVE (+) terminal of the battery trays and the BLACK wires from the electronics module must be connected to the NEGATIVE (-) terminal of the battery trays. There is a risk of explosion if a battery or batteries are replaced by an incorrect type.
2.
Dangerous voltage is always present at battery terminals.
WARNING BATTERIES CAN PRESENT A RISK OF ELECTRICAL SHOCK OR BURN FROM HIGH SHORT CIRCUIT CURRENT AND HIGH VOLTAGE. OBSERVE PROPER PRECAUTIONS. INCORRECT CONNECTION OF BATTERIES MAY CAUSE ELECTRICAL SHOCK, FIRE, INJURY, OR DEATH. 3.
The battery contains sulfuric acid. If any spillage occurs, take the following precautions:
If acid comes in contact with skin: •
Wash immediately with soap and water
•
Contact a physician if any burn results
If acid is splashed in the eyes: • 4.
2-6
Wash for 20 minutes under running water
Contact a physician.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Safety
2.7 Site Safety Personnel associated with the UPS should be aware of the presence of potentially lethal voltages. Observe the following precautions to ensure personnel safety and continued equipment operation. 1.
Keep surroundings clean and free from excess moisture.
2.
Do not operate in close proximity to gas or electric heat sources.
3.
The system is not intended for outdoor use.
4.
The operating environment should be within the parameters listed in Chapter 1.
WARNING VOLTAGES ACROSS CHARGED CAPACITORS CAN BE IN EXCESS OF 300 VDC. BE CERTAIN THE FILTER CAPACITORS ARE FULLY DISCHARGED AND INPUT POWER IS OFF BEFORE PERFORMING ANY MAINTENANCE OR TROUBLESHOOTING. 5.
Ensure the site is safe.
6.
Inspect power cables and plugs; check for loose, damaged, or worn parts.
7.
Review all procedures in the maintenance documents before removing a part that can hold an electric charge. Carefully discharge the parts exactly as instructed by the procedures.
8.
Do not use a normal light (for example, a table lamp) for illumination when performing maintenance on the UPS. Use a flashlight with a nonconductive case.
NOTICE Never assume that a UPS or a circuit is safe. Follow all procedures and safety precautions in the maintenance documents and all other applicable manufacturers publications.
© 2006 - Eaton Corporation
2-7
Safety
9355 20 – 30 kVA
9.
Always be aware of the following potentially hazardous conditions. Take the necessary safety steps to protect against the existence of these potential hazards. At the minimum inspect the following: •
Power receptacles wired incorrectly.
•
Safety devices or features missing or defective.
•
Maintenance or change history that is wrong or incomplete.
•
A UPS design problem.
•
A UPS that has shipping damage.
•
An unsafe change or attachment installed in the UPS.
•
An engineering change or a sales change installed Incorrectly.
•
A defective part.
•
A potentially unsafe old UPS or one that has been operated in an extreme environment.
2.8 Summary Prevention is the key and main aid to electrical safety. Always think about electrical safety and use good preventive practices before performing any work on equipment. These are some of the ways that the condition of the UPS that could affect safety. Before starting maintenance or repair procedures, USE GOOD PREVENTIVE JUDGMENT and USE CAUTION. SAFETY COMES FIRST!
2.9 Electrostatic Discharge (ESD) Procedure And Equipment Requirements 2.9.1
Purpose
To provide guidelines on handling electrostatic sensitive materials.
2.9.2
Objective
To provide a procedure which specifies ESD criteria when handling electrostatic sensitive materials.
2.9.3
2-8
Applicable Documents and Materials
•
3M Product catalog 1986/1987
•
3M Series 2100 bags or better
•
Wrist strap 3M 2221-2223 or better
•
Table mats (grounded) 3M 8200 series or better
•
Antistatic (pink poly) © 2006 - Eaton Corporation
9355 20 – 30 kVA
Safety
•
3M Dissipative mats (field kits) or better
•
Tables (grounded) with equivalent or better than surface of mat
2.9.4
Definitions
Antistatic material: Material that neither generates static electricity nor does it provide protection against a static field, and typically has a surface resistance of 109 to 1014 ohm/cm. Conductive material: Material that provides a Faraday cage effect and protects against static generation and a static field with a surface resistance of <105 Ω per cm. Dissipative material: Material that provides some protection against a static field and typically has a surface resistance of 105 to 109 Ω per cm. Faraday Cage or Faraday Shield: A conductive enclosure capable of protecting its contents from any outside static charge or electrostatic field. An example would be an ESD bag that is closed. Frame ground: Any unpainted surface of a unit or subassembly to which a wrist strap may be firmly connected. Ground: Building/earth ground. Static safeguard stations: Any area with provisions for controlling electrostatic discharge. Static sensitive material: Any static sensitive component/device (semiconductors, film resistors and capacitors, and so on) or boards with such components/devices mounted on them. Static shield: Must be capable of providing a Faraday cage (protective from static discharge as well as electrostatic fields). Static Protective equipment/tools: Must include as a minimum, but not be limited to, a wrist strap with 1 meg ohm resistor, a conductive table mat or grounded work surface and dissipative mats for field engineers.
WARNING 100% ESD PREVENTION REQUIRES REMOVAL OF ALL POWER FROM THE UPS (THAT IS, INPUT, BYPASS, AND LOAD) CAUSING A LOAD INTERRUPTION. THE FOLLOWING RECOMMENDATIONS ARE MADE TO ENSURE THE BOARDS AND OTHER STATIC SENSITIVE COMPONENTS WILL NOT BE DAMAGED.
2.9.5
Procedure 1.
All static sensitive material shall be packaged in approved antistatic protective packaging.
2.
Wrist straps and grounded mats, or a grounded surface with equivalent or better ground than the surface of the mat, shall be used when handling static sensitive material. © 2006 - Eaton Corporation
2-9
Safety
9355 20 – 30 kVA
2.9.6
3.
When removing or installing boards in a unit or subassembly, a wrist strap shall be used and it shall be connected to the frame of the unit or subassembly.
4.
Rejected boards (returned to factory/rework center) equally sensitive to electrostatic discharge and shall be handled with the same protection as good/accepted boards (that is, in a static protected environment).
5.
All static sensitive devices and boards with such devices shall be stored/handled in their static protected tubes and bags that provide a complete Faraday cage. The protection for both is required at all times.
6.
All sales and field engineering personnel are required to use a portable static controlled field service kit when handling static sensitive material.
Removal of Boards
CAUTION When removing a board without pull out tabs, handle the board on the edges. Lethal voltage may be present on the traces of the board.
Use the correct removal procedure to remove all boards from the unit. If the board has pull out tabs, remove the board with the use of these tabs. For boards without pull out tabs, pull the board by grabbing the edge of the board. Do not touch any static sensitive component/device (semiconductors, film resistors, and capacitors, and so on). The following procedure provides guidelines on handling electrostatic sensitive materials.
2-10
1.
All static sensitive material shall be packaged in approved antistatic protective packaging.
2.
Wrist straps and grounded mats, or a table with a surface ground equivalent or better than that of a mat, shall be used when handling static sensitive material.
3.
When removing or installing boards in a unit or subassembly, a wrist strap shall be used and it shall be connected to the frame ground of the unit or subassembly.
4.
Rejected boards (returned to factory/rework center) are just as sensitive to electrostatic discharge and shall be handled with the same protection as good/accepted boards (that is, in a static protected environment).
5.
All static sensitive devices and boards with such devices shall be stored/handled in their static protected tubes and bags. The protection for both is required at all times.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Safety
6.
2.9.7
All CSEs are required to use a portable static controlled field service kit when handling static sensitive material.
Packaging of Boards
NOTICE Packaging of boards, unless otherwise specified, will be packaged in egg-crate type cartons, separating each board with partitions.
2.9.8
General Handling Guidelines for ESD Protection
All printed circuit boards without static sensitive components must, as a minimum, have a pink poly wrap for static protection. Boards with semiconductor devices must be in ESD shielded bags. Boards with on-board batteries must be wrapped with pink poly (for protection against battery discharge) prior to insertion into standard shielded bags. 1.
The packing material used is designed to protect static sensitive components and assemblies from both internal and external static charge during transfer between static safe work areas.
2.
Protective bag construction must provide protection inside against static buildup from movement of devices, outside against electrostatic fields and must insulate against a direct static discharge.
3.
Resistance requirements are as follows: •
Interior (anti-static) 109 to 1014 W per square.
NOTICE The resistance will be the same for any size square. 144 x 144 x 144 will have the same resistance as a 244 x 244 x 244 square. •
Inter-layer resistance (insulating and direct discharge protection) greater than 1014 W per square.
•
Exterior resistance (conductive) less than or equal to 105 W per square.
•
Total thickness of static bags (including all layers) must be 3 MILS minimum.
•
Static bags must be sealed in some manner.
© 2006 - Eaton Corporation
2-11
Safety
9355 20 – 30 kVA
HANDLING FLOWCHART Handling of Boards
Handling of Components
Handling for Field Engineers and Sales Personnel
| |
| |
| |
Wrist straps and grounded mats, or tables with an equivalent surface will be used when handling all static sensitive material.
Wrist straps and grounded mats, or tables with an equivalent surface will be used when handling all static sensitive material.
Dissipative mats are to be used by field engineers and sales personnel.
| |
| |
| |
Boards without static sensitive material, as a minimum, must be in pink poly wrap for protection.
All static sensitive components must arrive in antistatic tubes or shielding packages.
Field engineering personnel shall be equipped with portable static controlled field service kits.
| |
| |
| |
Boards with static sensitive material must be in static shield bags. | | All boards with on-board batteries must be placed in pink poly wrap prior to insertion in static shielding bag.
Static sensitive components shall be handled at a static safe-guard station only | | Transport static sensitive components in a static shielding bag or container.
| | Rejected boards are to be handled with the same care as accepted boards.
2-12
© 2006 - Eaton Corporation
All other ESD procedures for boards and components will be observed by field personnel.
3 Installation and Startup 3.1 MODEL 9355 20 – 30kVA SINGLE MODULE (RT) 3.1.1
Mechanical Inspection 1.
Visually inspect the module for any shipping damage: a.
Remove the front right side door and battery dead front panels.
Figure 12. b.
Front door panel removed
If possible, remove the right side skin panel, see Figure 17.
© 2006 - Eaton Corporation
3-1
Installation and Startup
9355 20 – 30 kVA
Figure 13. c.
Figure 14.
3-2
Right side skin panel removed
Remove bolts from the dead front panel for wiring access.
Wiring Access After Dead Front Panel Removal
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
d.
Perform an external and internal inspection (no dents, paint blemishes, frame is straight).
e.
Inspect to ensure that all internal subassemblies are secure and ALL wiring connections are secure: - Check input/output connections on the I/O Board, (see Figure 71 and Figure 72). - Check K1 and K3 contactor wiring connections (see below).
Ensure wiring is secure
2.
f.
Remove the protective film from the unit front panel (use a ground strap while removing the protective film) if installed.
g.
Inspect the auxiliary cabinets for shipping damage. (transformer, battery, or other cabinets)
Visually inspect the module for proper installation: a.
Check for properly rated feeder-breaker and wire size (reference the installation and operation manual for recommended breaker and wire sizes).
b.
The UPS label matches the application (voltage, kVA, frequency, power).
c.
Ensure that the input and bypass connections are properly wired and torqued (refer to users manual).
d.
The system neutral must be supplied by the utility input power source.
CAUTION Do NOT bond neutral to ground internally in the UPS module.
3.
Verify all options are installed and wired properly: a.
X-Slot Connectivity Devices: - Connect the UPS SNMP / Web adapter © 2006 - Eaton Corporation
3-3
Installation and Startup
9355 20 – 30 kVA
- Inspect the multi-port serial card - Inspect the relay card (isolated form C contacts, AS400 type status) - Inspect the single port serial card (RS-232 and AS400 signal levels) - Inspect the USB module / card - Inspect the X-Slot modem card (either V.34 or V.90) (XSlot-1 only) b.
External Maintenance Bypass Switch (If provided)
c.
Remote Emergency Power Off (REPO)
d.
External Power Distribution (PDM module or customer provided)
e.
External Transformers (optional cabinet or customer provided)
f.
Remote Monitoring Panel (RMP)
WARNING STEP 4. CANNOT BE PERFORMED IF THE UPS INPUT IS ENERGIZED. 4.
Verify there are no installation ground faults using a properly functioning DVM (this includes the UPS module and any optional cabinets): Note: The MBS should be in the UPS position. - Neutral may have to be lifted removing the input source neutral to ground bond a.
Verify there are no faults on the main inputs, phase to phase and phase to ground
b.
Verify there are no faults on themain outputs, phase to phase and phase to ground - All readings should be 2Meg Ω or greater. - Output Phase “A” to GND should be 80 Ω
c.
Reconnect neutral if removed previously.
CAUTION The battery circuit breaker on the UPS and/or EBC must be in the OFF position prior to connecting or disconnecting batteries. The RED wires from the electronics module must be connected to the POSITIVE (+) terminal of the battery trays and the BLACK wires from the electronics module must be connected to the NEGATIVE (-) terminal of the battery trays
3-4
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
5.
6.
7.
3.1.2
Verify that the Internal and External Battery Cabinet (EBC) battery strings have been properly assembled and attached to the UPS: a.
Verify CB-2 is open.
b.
Verify Inter-tray connections (Red to Black, Black to Red) for batteries in series (use the diagram on the battery cabinet and/or the UPS).
c.
Verify inner-cabinet connections for strings in parallel.
d.
Using a DVM, verify that the polarity of all parallel strings match BEFORE making final connections.
Verify each string in the UPS, and EBC if installed. (Open cell voltage for any string should be >210 VDC.) a.
Connect all black connectors, leaving the red connectors on each string disconnected.
b.
Verify each individual string prior to making final connections.
c.
The battery must NOT be ground referenced (either pole tied to ground).
d.
If a string doesn’t indicate > 210 VDC, verify the inner connections and recheck.
Verify battery strings, each pole to ground < 1 VDC.
Electrical Inspection
WARNING BE AWARE THAT THE FOLLOWING STEPS WILL ENERGIZE THE UPS MODULE AND ITS OUTPUT! IF CUSTOMER LOADS ARE NOT TO BE ENERGIZED AT THIS TIME, ENSURE DOWN STREAM BREAKERS ARE OPEN AND LOADS ARE DISCONNECTED OR UNPLUGGED BEFORE PROCEEDING.
NOTICE Use Startup Worksheets and Checksheet found at the end of this chapter.
1.
Verify CB-1 is open and the MBS is in the UPS position.
2.
Apply utility power to the UPS. (If dual feed also apply bypass input power) Note:
The bypass control board will have power applied to it but it will not energize logic power in the remainder of the UPS. © 2006 - Eaton Corporation
3-5
Installation and Startup
3.
9355 20 – 30 kVA
Using a DVM, verify the system has correct input voltages a.
Using a DVM, verify AC voltages: phase-to-phase, phase-toneutral, phase-to-ground
b.
Using a DVM, verify voltage neutral to ground is less than 5 VAC RMS (Root-mean square).
4.
Using an oscilloscope or phase rotation meter, verify phase rotation at the rectifier and bypass inputs.
5.
Energize the system input, close CB-1. The following events occur:
6.
a.
Logic power starts
b.
The display energizes
c.
The ALARM lamp on the front panel is lit
d.
The active event for the batteries is disconnected
e.
Horn sounds once every 3 seconds (pushing any button silences the horn)
Using the XCP Service Software Tool, verify the unit setup: a.
Using the CTO (Configuration to Order) tab, verify that the unit CTO number and power ratings correspond to the unit labeling and installation - You may have to enter the CTO the first time you connect.
b.
Using the Battery Setup tab, configure the UPS for the connected battery
The battery vendor’s data sheet or the battery label may be required. If there are only internal batteries, enter the total number of strings and watts per cell on the Battery 1 Battery Selection toggle switch if it is not already set, see Figure 21. If the external batteries are the same type as the internal batteries then include both on the Battery 1 Battery Selection toggle switch if it is not already set on the XCP Service Tool, see Figure 21. If the external battery is different from the internal battery, enter the number of strings and watts per cell on the Battery 2 Battery Selection toggle switch on the XCP Service Tool, see Figure 21.
Figure 15.
XCP Tool Battery Toggle Positions
To clear the setup required bit: 3-6
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
- After verifying the battery setup push the “Battery Setup Complete” button. This will clear the setup required bit. - A pop up will appear, click on the “Battery Configuration Complete” to continue. As soon as the setup bit is cleared the unit will start precharge, K5 will close, K1 will close after precharging is complete (approx. 1 minute), The front inverter fans will start. c.
Using the OPTIONS tab, verify the availability of customer options. - Verify that the required setups for the Configure To Order (CTO) type are enabled
d.
Using the MODEM tab, configure the unit for outcall operations (if applicable)
Refer to the outcall setup procedures for specific instructions 7.
Confirm the status of the following indicators: a.
The LCD display indicates the following active event messages: - Batteries Disconnected
b. 8.
The ALARM LED is lit.
Verify the following front panel operations: a.
The time and date are set correctly (the clock is a 24 hour clock)
b.
All screens correctly show the current operating status
c.
All buttons are in working order
d.
Status in the “UPS STATUS” window displays: - UPS is OFF - BATTERY NOT CONNECTED
Note: Auto-Frequency detection is enabled from the factory when input power is first applied. Once the system has initialized, the auto-frequency detection is disabled. It can be reenabled using the XCP Service Tool.
Operational Inspection 1.
Start the UPS: a.
Close battery breaker CB-2.
b.
Close output breaker CB-3 if installed.
c.
Select “UPS ON/OFF”, cycle to select “TURN UPS ON,” and hold the enter key until the beeping stops.” © 2006 - Eaton Corporation
3-7
Installation and Startup
2.
3.
9355 20 – 30 kVA
d.
The output contactor closes; the NORMAL lamp on the front panel is lit, the output fans energize and the rear fans energize.
e.
Verify the output voltage
f.
Investigate and resolve any alarms or notices before continuing.
Verify BATTERY operation: a.
Open utility input breaker for 30 seconds.
b.
Using a DVM, verify stable output voltage & frequency, the battery screen shows discharge.
c.
Using the front panel meter screen, verify that NORMAL, BATTERY, and NOTICE lamps are lit on the front panel, and the horn sounds every 3 seconds.
d.
Close the utility input breaker, verify battery recharge, and that the system indicates NORMAL.
e.
Review the module event history queue for expected events.
f.
Investigate and resolve any unexpected events.
Verify the operation of all applied equipment options (where applicable) for External Maintenance Bypass, and so on. The module must be in bypass. a.
External and / or Internal Maintenance Bypass: - The UPS must be in bypass or standby mode. - Check voltage across external MBP, it should be <1VAC. - Check the voltage across the input terminal block and the output terminal block for internal MBP, it should be <1VAC - UPS output should be recorded using a scope during transfers.
b.
X-Slot connectivity \ communication options: - Refer to specific product instructions for setup and verification.
c.
Remote monitoring panels or status relays: - Refer to specific product instructions for setup and verification.
d.
Eaton - Powerware Remote Monitoring (if applicable): - Refer to specific instructions for setup and testing.
WARNING IF THE CUSTOMER’S EPO IS A BUILDING EPO AND THE UPS EPO IS CONNECTED TO THE BUILDING EPO, A BUILDING LOAD DUMP COULD OCCUR DURING UPS REPO TESTING. 3-8
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
e.
Remote Emergency Power Off (REPO): - Exercised while the module is operating in NORMAL operation. - The UPS battery breaker will open. - The input contactor will open. - CB-1 will open. - The Inverter / rectifier will turn off. - After testing REPO — restart the UPS.
f.
Check building alarm inputs (if used) - After REPO the display and LEDs will sound and flash until the UPS bleeds down.
© 2006 - Eaton Corporation
3-9
Installation and Startup
9355 20 – 30 kVA
3.2 MODEL 9355 20 – 30kVA Parallel (PC/PR)
NOTICE This process for converting a 9355 RT to a Parallel Unit is described in document #164700576.
3.2.1
Mechanical Inspection 1.
Visually inspect the module for any shipping damage: a.
Remove the front right side door and battery dead front panels.
Figure 16. b.
Remove the right side skin panel, see Figure 17.
Figure 17. c. 3-10
Front door panel removed
Right side skin panel removed
Remove bolts from the dead front panel for wiring access. © 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
Figure 18.
2.
Wiring Access After Dead Front Panel Removal
d.
Perform an external and internal inspection (no dents, paint blemishes, frame is straight).
e.
Inspect to ensure that all internal subassemblies are secure and ALL wiring connections are secure.
f.
Remove the protective film from the unit front panel (use a ground strap while removing the protective film) if installed.
g.
Inspect the auxiliary cabinets for shipping damage. (transformer, battery, or other cabinets)
Visually inspect the module for proper installation: a.
Check for properly rated feeder-breaker and wire size (reference the installation and operation manual for recommended breaker and wire sizes).
b.
The UPS label matches the application (voltage, kVA, frequency, power).
c.
Ensure that the input and bypass connections are properly wired and torqued (refer to users manual).
d.
The system neutral must be supplied by the utility input power source.
e.
Check the phase rotation on all connection points. This is extremely critical, failure to have all phase connections correct WILL result in damage to all UPMs. © 2006 - Eaton Corporation
3-11
Installation and Startup
9355 20 – 30 kVA
CAUTION Do NOT bond neutral to ground internally in the UPS module.
WARNING IF CHECKING THE ACROSS MOBS FOR PROPER PHASE ROTATION WHEN THE CUSTOMERS LOAD IS ON EXTERNAL BYPASS THERE WILL BE VOLTAGE PRESENT ON THE MOBS. CLOSING THE MOBS WILL RESULT IN THE UPM BEING BACKFED. MAINTAIN ELECTRICAL SAFETY PRECAUTIONS HIGH VOLTAGE IS PRESENT.
WARNING IF THE TERMINAL CONNECTIONS, PHASE “A”, “B”, AND “C”, ARE SWAPPED, RESULTING IN A MISMATCH IN PHASES WHEN PARALLELING, IT COULD RESULT IN DAMAGE TO ALL UPMS. SPECIAL ATTENTION SHOULD BE GIVEN TO ENSURE THE CONNECTIONS ARE CORRECT. 3.
Inspect Parallel Wiring Configuration a.
3-12
Remove the CAN Bridge card and verify jumpers are set correctly on the CAN Bridge Board in accordance with Figure 19 and re-install in each UPM. Set jumpers on first and last UPM CAN Bridge Board J7 to Pins 1 and 2. On middle UPM(s), set jumper on J7 to Pins 2 and 3. If only two UPMs are being paralleled, then both cards should be set to Pins 1 and 2.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
Figure 19. b.
CAN Bridge Board Jumper Settings
Verify all parallel control wiring is connected in accordance with Figure 20. The CAN connections should be a maximum of 18 gauge twisted pair with optional shield. It’s recommended a shielded wire bundle be used. CAN Bridge boards can be installed in X-Slot one or two. Note:
A modem card can only be used in X-Slot 1. If both a modem and CAN Bridge board are used the CAN Bridge board must go into X-Slot 2.
Figure 20.
Parallel Control Wiring
© 2006 - Eaton Corporation
3-13
Installation and Startup
4.
9355 20 – 30 kVA
Verify all options are installed and wired properly: a.
X-Slot Connectivity Devices: -
Connect the UPS SNMP / Web adapter Inspect the multi-port serial card Inspect the relay card Inspect the single port serial card Inspect the USB module / card Inspect the X-Slot modem card (X-Slot-1 only)
b.
External Maintenance Bypass Switch (If provided)
c.
Remote Emergency Power Off (REPO)
d.
External Power Distribution (PDM module or customer provided)
e.
External Transformers (optional cabinet or customer provided)
f.
Remote Monitoring Panel (RMP)
g.
Internal MBS should always remaining the UPS position - Only operate during maintenance when the MOB is open and all parallel control wiring is disconnected.
WARNING STEP 4. CANNOT BE PERFORMED IF THE UPS INPUT IS ENERGIZED. 5.
Verify there are no installation ground faults using a properly functioning DVM (this includes the UPM and any optional cabinets): - Neutral may have to be lifted removing the input source neutral to ground bond
CAUTION If the unit has external maintenance bypass you may also have to lift the output neutral.
a.
Main inputs, phase to phase and phase to ground
b.
Main outputs, phase to phase and phase to ground - All readings should be 2Meg Ω or greater. - Output Phase “A” to GND should be 80 Ω due to the rear fan.
c.
3-14
Reconnect neutral if removed previously.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
CAUTION The battery circuit breaker on the UPM and/or EBC must be in the OFF position prior to connecting or disconnecting batteries. The RED wires from the electronics module must be connected to the POSITIVE (+) terminal of the battery trays and the BLACK wires from the electronics module must be connected to the NEGATIVE (-) terminal of the battery trays
6.
7.
8.
Verify that the Internal and External Battery Cabinet (EBC) battery strings have been properly assembled and attached to the UPS: a.
Verify CB-2 is open.
b.
Verify Inter-tray connections (Red to Black, Black to Red) for batteries in series (use the diagram on the battery cabinet and/or the UPMs).
c.
Verify inter-cabinet connections for strings in parallel.
d.
Using a DVM verify the polarity of all parallel strings match BEFORE making final connections.
Connect the Positive (red) wire to each string from the UPM or EBC a.
Open cell voltage for any string should be >210 VDC.
b.
Verify each individual string prior to making final connections.
c.
The battery must NOT be ground referenced (either pole tied to ground).
Verify battery strings, each pole to ground < 1 VDC.
© 2006 - Eaton Corporation
3-15
Installation and Startup
3.2.2
9355 20 – 30 kVA
Electrical Inspection
WARNING BE AWARE THAT THE FOLLOWING STEPS WILL ENERGIZE THE UPS MODULE AND ITS OUTPUT! IF CUSTOMER LOADS ARE NOT TO BE ENERGIZED AT THIS TIME, ENSURE DOWN STREAM BREAKERS ARE OPEN AND LOADS ARE DISCONNECTED OR UNPLUGGED BEFORE PROCEEDING.
NOTICE Use Startup Worksheets and Checksheet found at the end of this chapter.
1.
Verify CB-1 is open and the MBS is in the UPS position.
2.
Apply utility power to one UPM at a time. (If dual feed also apply bypass input power). DO NOT CLOSE CB-1. Note:
The bypass control board will have power applied to it but it will not energize logic power in the remainder of the UPS. 3.
4.
Using a DVM, verify the system has correct input voltages a.
Using a DVM, verify AC voltages: phase-to-phase, phase-toneutral, phase-to-ground
b.
Using a DVM, verify voltage neutral to ground is less than 5 VAC rms.
Using an oscilloscope or phase rotation meter, verify phase rotation at the rectifier and bypass inputs. •
3-16
Secure power to the UPM and repeat Steps 1-4 for each additional UPM.
5.
Apply utility power to all UPMs:
6.
Perform steps 7 through 11 on one UPM at-a-time ensuring that the previous UPM is off before starting the next UPM.
7.
Close CB-1; the following will occur: a.
Alarm will sound (press any key to silence)
b.
Alarm light is lit
c.
“UPS status = OFF” on the UPS status screen
d.
“BATTERIES DISCONNECTED” appears on the UPS battery status screen
e.
Within 30 seconds K-5 will close with an audible “click.” © 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
8.
Using the XCP Service Software Tool, verify the unit setup: a.
Using the CTO (Configuration to Order) tab, verify that the unit CTO number and power ratings correspond to the unit labeling and installation - You may have to enter the CTO the first time you connect.
b.
Using the Battery Setup tab, configure the UPS for the connected battery
If there are only internal batteries, enter the total number of strings and watts per cell on the Battery 1 Battery Selection toggle switch if it is not already set, see Figure 21. If the external batteries are the same type as the internal batteries then include both on the Battery 1 Battery Selection toggle switch if it is not already set on the XCP Service Tool, see Figure 21. If the external battery is different from the internal battery, enter the number of strings and watts per cell on the Battery 2 Battery Selection toggle switch on the XCP Service Tool, see Figure 21.
Figure 21.
XCP Tool Battery Toggle Positions
To clear the setup required bit: - After verifying the battery setup push the “Battery Setup Complete” button. This will clear the setup required bit. - A pop up will appear, click on the “Battery Configuration Complete” to continue. As soon as the setup bit is cleared the unit will start precharge, K1 will close after precharging is complete (approx. 1 minute), The front inverter fans will start. c.
Using the OPTIONS tab, verify the availability of customer options. - Verify that the required setups for the Configure To Order (CTO) type are enabled
d.
Using the MODEM tab, configure the unit for outcall operations (if applicable) - Refer to the outcall setup procedures for specific instructions © 2006 - Eaton Corporation
3-17
Installation and Startup
9.
9355 20 – 30 kVA
Confirm the status of the following indicators: a.
The LCD display indicates the following active event messages: - Batteries Disconnected
b.
The ALARM LED is lit.
c.
The alarm was previously silenced when acknowledged in previous step 7a.
10. Verify the following front panel operations: a.
The time and date are set correctly (the clock is a 24 hour clock)
b.
All screens correctly show the current operating status
c.
All buttons are in working order
d.
Status in the “UPS STATUS” window displays: - UPS is OFF - BATTERY NOT CONNECTED
11. Set up Parallel System (you cannot have the same UPM ID on multiple UPMs) a.
Using the XCP Service Tool Option (IF THIS OPTION IS USED YOU DO NOT NEED TO PERFORM THE FRONT DISPLAY OPTION) Connect to each UPM and on the PCB Tab select - UPM ID = Unit #1, Unit #2, Unit #3 or Unit #4 - Slide bar to Parallel Redundant or Parallel Capacity (Must be the same for all UPMs)
b.
Using the Front Display Option (IF THIS OPTION IS USED YOU DO NOT NEED TO PERFORM THE XCP SERVICE TOOL OPTION) - On the XCP Service Tool Options Tab enable the service menu option. - For each UPM select ID number in parallel system: UPM #1, UPM #2, UPM #3 or UPM #4. Select: SETTINGS -> SERVICE SETTINGS -> PARALLEL OPERATION SETTINGS -> PARALLEL UNIT NUMBER. - Select parallel operation “Redundant or Capacity”: Select: SETTINGS -> USER SETTINGS -> PARALLEL OPERATION SETTINGS -> PARALLEL OPERATION MODE.
Note: For a reverse transfer UPM the ID will be zero (0); if the UPM ID is changed to zero (0) the UPM will act as an RT UPS. 12. Repeat Steps 7 through 11 on each UPM.
3-18
© 2006 - Eaton Corporation
9355 20 – 30 kVA
3.2.3
Installation and Startup
Operational Inspection 1.
Close CB-1 input breakers on all UPMs:
2.
After all UPMs are in standby (fans running): a.
Close battery breaker CB-2. - The LED should turn off.
3.
b.
Close output breaker CB-3 if installed.
c.
Close the MOBs to all UPMs.
On any UPM turn the SYSTEM ON.
Note: After the first startup, the load sharing of the system needs to be calibrated. For best results No Load is preferred for auto-calibration; however, the system can still be calibrated on load. 4.
Select: Settings->Service Settings->PARALLEL OPERATION ->SETTINGS->START AUTO CALIBRATION
5.
After completing the parallel calibration allow 10 minutes for the UPMs to stabilize and verify that they share the load equally. If load share is lop-sided, perform the parallel calibration again. (With smaller loads the system may not load share equally).
6.
Verify BATTERY operation: a.
Open CB-1 input breaker for 30 seconds on each UPM (only perform on one UPM at-a-time) and verify the following: - Using a DVM, verify stable output voltage and frequency, the battery screen shows discharge. - Using the front panel meter screen, verify that NORMAL, BATTERY, and NOTICE lamps are lit on the front panel, and the horn sounds every 3 seconds.
b.
Close the CB-1 input breaker, verify battery recharge, and that the UPM indicates NORMAL.
c.
Review the module event history queue for expected events.
d.
Investigate and resolve any unexpected events.
7.
Repeat Step 6 as a system test by opening CB-1 on all UPMs at the same time.
8.
Verify the operation of all applied equipment options (where applicable). a.
External Maintenance Bypass only: - The UPS must be in bypass or standby mode. - Check voltage across external MBP, it should be <1VAC. - UPS output should be recorded using a scope during transfers.
b.
Test MBP/Tie Cabinet AUX contents: © 2006 - Eaton Corporation
3-19
Installation and Startup
9355 20 – 30 kVA
c.
With UPMs in NORMAL, close the external MBS UPMs should go to BYPASS Open MBS UPMs should go back to NORMAL
X-Slot connectivity \ communication options: - Refer to specific product instructions for setup and verification.
d.
Remote monitoring panels or status relays: - Refer to specific product instructions for setup and verification.
e.
Eaton - Powerware Remote Monitoring (if applicable): - Refer to specific instructions for setup and testing.
WARNING IF THE CUSTOMER’S EPO IS A BUILDING EPO AND THE UPS EPO IS CONNECTED TO THE BUILDING EPO, A BUILDING LOAD DUMP COULD OCCUR DURING UPM REPO TESTING. f.
Remote Emergency Power Off (REPO):
Note: Unless all REPOs are paralleled only one UPM will shut down. If UPMs are paralleled, all UPMs will shut down. - Exercised while the module is operating in NORMAL operation. - The UPM battery breaker will open. - The input contactor (K-1) and out (K-3) will open. - CB-1 will open (and CB-3 if installed). - The inverter / rectifier will turn off. - After testing REPO — restart the UPM. Note: UPMs will alarm and turn completely off after the capacitors are drained. g.
Check building alarm inputs (if used) - After REPO the display and LEDs will sound and flash until the UPS bleeds down.
3-20
© 2006 - Eaton Corporation
9355 20 – 30 kVA
3.2.4
Installation and Startup
Inspection Completion 1.
Temporarily apply the customer’s load, if available, or load bank to the system and using a DVM verify all measured values against the values that are displayed by both the unit front panel and the XCP Service Software Tool meters tab. a.
Use the provided work sheet as needed.
b.
Perform calibration of those parameters that are outside of tolerances. (Refer to Chapter 8 for calibrations)
c.
Shut down the unit, reinstall all panels and restore unit to normal condition.
d.
Restart the unit and place it online.
e.
With the XCP Service Tool enable battery commissioning.
Note: Do not cycle logic power after the battery commissioning button is selected (it will reset it). 2.
Unit Data and Customer Reports
3.
Download Setup Values
4.
a.
Download Unit History
b.
Download Alarm / Event Nodes (if applicable)
Installation Acceptance Completion: a.
Conduct unit operation training for the customer.
b.
If logic power cycles before battery testing, battery commissioning must be re-enabled.
c.
Provide a signed copy of the installation and startup check sheet and a hardcopy of the unit setup values to the customer.
© 2006 - Eaton Corporation
3-21
Installation and Startup
9355 20 – 30 kVA
Installation and Startup CHECKsheet (the linked CD MSWord form can be filled-out and saved) Powerware® 9355 (20 - 30 kVA) 1.
Apply customers load before final readings / measurements
2.
Using a DVM verify all measurements and readings are within 1%
3.
Make copies of this worksheet and fill one out for each UPM.
Single Module (RT) Parallel Redundant / Capacity
UPM#
SN
IP Address
Location
Recorded Values
Expected
AC VOLTAGE MEASUREMENTS Measured
XCP Tool
A-B
V
B-C
V
A-C
V
(L1 = Phase “A”)
A-N
V
V
(L2 = Phase “B”)
B-N
V
(L3 = Phase “C”)
C-N
V
(N = Neutral)
A-G
V
(G = Ground)
B-G
V
C-G
V
Neutral to Ground
N-G
V
UPS Output
A-B
V
B-C
V
C-A
V
A-N
V
V
(L2 = Phase “B”)
B-N
V
(L3 = Phase “C”)
C-N
V
(N = Neutral)
A-G
V
(G = Ground)
B-G
V
C-G
V
Input
3-22
LCD V V V V
OK(√ ) 208
400
208
400
208
400
V
120
230
V
V
120
230
V
V
120
230
120
230
120
230
120
230
V V V V V V V V V V
<5 208
400
208
400
208
400
V
120
230
V
V
120
230
V
V
120
230
120
230
120
230
120
230
V V V V
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Installation and Startup
AC CURRENT MEASUREMENTS Location
Recorded Values Measured
XCP Tool
OK (√ )
LCD
UPS Input (L1)
ØA
A
A
A
UPS Input (L2)
ØB
A
A
A
UPS Input (L3)
ØC
A
A
A
UPS Input (L1)
ØA
A
A
A
UPS Input (L2)
ØB
A
A
A
UPS Input (L3)
ØC
A
A
A
DC MEASUREMENTS Location
Recorded Values Measured
XCP Tool
LCD
DC Link Voltage
VDC
V
V
V
Battery Voltage
VDC
V
V
V
Battery Current
ADC
A
A
A
%
%
Expected Values
OK (√ )
% Batt. Time Remaining
Mins.
Battery Charge Level
%
POWER Location
Recorded Values Measured
Input Power
XCP Tool
LCD
OK (√ )
kVA KW Hz PF
Output Power
kVA KW Hz PF
© 2006 - Eaton Corporation
3-23
Installation and Startup
9355 20 – 30 kVA
Powerware® 9355 (20 - 30 kVA) Single Module (RT) Parallel Redundant / Capacity DATE: CUSTOMER SITE
PHONE
UPS
S/N:
REQUEST/ORD
CTO
Installation Inspection
OK
Mechanical Inspection
OK
Electrical Inspection
OK
Operational Inspection
OK
Environmental Evaluation
OK
Installation Notes / Comments / Recommendations:
CUSTOMER ACCEPTANCE:
SERVICE REPRESENTATIVE:
DATE:
CUSTOMER SIGNATURE: DATE:
3-24
© 2006 - Eaton Corporation
4 Functional Descriptions This chapter provides a functional description for the Powerware® 9355 20kVA to 30 kVA power train and the printed circuit boards.
4.1 Model 9355 20 – 30kVA 4.1.1
Overview
Reference Documents: 110720639 Electronics Module Schematic in the Prints chapter at the end of this document. The power-train topology is common among all 9355 UPS models and is developed using common control and display boards. The three phase low volt Electronics Module (EM) contains the I/O, EMI, control, bypass and power module boards. The I/O board provides interconnections to the control board. The power module boards contain the system power-train components. The control board contains the microprocessor and controls the entire UPS. The EMI Board handles surge protection and EMI.
© 2006 - Eaton Corporation
4-1
Functional Descriptions
4.1.2
9355 20 – 30 kVA
X-Slot Connections X-Slot One
X-Slot Two
Reference Designator
Description
Reference Designator
Description
X55-1
GND
X55-1
GND
X55-2
GND
X55-2
GND
X55-3
GND
X55-3
GND
X55-4
GND
X55-4
GND
X55-5
PAR RED1
X55-5
PAR RED1
X55-6
TX
X55-6
TX
X55-7
PAR RED2
X55-7
PAR RED2
X55-8
RX
X55-8
RX
X55-9
K3 DRV
X55-9
K3 DRV
X55-10
K1 DRV
X55-10
K1 DRV
X55-11
GND
X55-11
GND
X55-12
DTR
X55-12
DTR
X55-13
GND
X55-13
GND
X55-14
K4 DRV
X55-14
K4 DRV
X55-15
CAN HI
X55-15
CAN HI
X55-16
K2 DRV
X55-16
K2 DRV
X55-17
NC
X55-17
NC
X55-18
+12VDC
X55-18
+12VDC
X55-19
CAN LO
X55-19
CAN LO
X55-20
+12VDC
X55-20
+12VDC
4.1.3
Native RS Port Reference Designator
Description
X53-1
DCD
X53-2
RXD
X53-3
TXD
X53-4
DTR
X53-5
GND
X53-6
DSR
X53-7
RTS
X53-8
CTS
X53-9
4-2
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.2 Electronics Module Functional Sections 4.2.1
Display Panel
Refer to paragraph 4.3 Display Panel. The Display Panel is the user interface. It has an LCD for displaying system information and buttons for navigating through the menus. The Display Board communicates with the control board over the CAN network via a PIC18F448 Micro Controller and provides the user interface.
4.2.2
Control Board
Refer to paragraph 4.4 Control Board. The Control Board contains the DSP micro-controllers and is responsible for overall operation of the UPS except for certain bypass functions. The Control Board contains a Texas Instruments (TI) TMS320F2812A Digital Signal Processor (DSP). The 150 MIPS TI DSP provides software functionality, that is: analog sensing, digital signal sampling, power-train control including Pulse Width Modulated gate signals, serial communications, serial EEPROM, and a CAN 2.0B network.
4.2.3
Power Module Boards
Refer to paragraph 4.5 PW9355 Power Board. The Power Board Assembly (1024049) contains IGBT modules for the converters, IGBT gate drives, and for additional sensing.
4.2.4
Bypass Control Board
Refer to paragraph 4.13 PW9355 Bypass Control Board. The Bypass Board Assembly (1024057) provides self-contained bypass functionality and provides external interfaces to the customer.
4.2.5
I/O Board
Refer to paragraph 4.2.5 1.X PW9355 I/O Board. The IO Board Assembly (1024053) handles IO. It controls the rectifier and inverter contactors as well as tripping the circuit breakers. The I/O Board also provides interconnect to the Control Board.
4.2.6
EMI / Surge Board
Refer to paragraph 4.2.6 EMI Board. The Electro-Magnetic Interference (EMI) Board provides input filtering and surge protection for the UPS.
© 2006 - Eaton Corporation
4-3
Functional Descriptions
4.2.7
9355 20 – 30 kVA
Contactors
The Rectifier Input Contactor K1 provides: •
Input protection to the rectifier.
Inverter Output Contactor K3 provides: •
inverter isolation when open.
Bypass Back-feed Contactor K5 provides: •
Back-feed protection when open.
The control for each contactor is: •
K1 (24VDC signal from a connection to the I/O board at X27-1 and X27-3)
•
K3 (24VDC signal from a connection to the I/O board at X21-1 and X21-3)
•
K5 (24VDC signal from a connection to the Bypass board at X51-1 and X51-3)
4.2.8
Internal Battery
The system can be configured with up to six (6) strings of batteries. Each string is eighteen (18) 12V batteries connected in series. The strings are then connected in parallel on a connection board located behind the battery breaker.
4.2.9
External Battery
The external battery has the positive connection to the circuit breaker line side along with the internal batteries. The negative connection is to the load side of the breaker. This ensures that all wiring is protected by circuit breakers and that accessible terminals are disconnected when the breakers are tripped.
4.2.10
Battery Circuit Breaker
The battery circuit breaker is a magnetic type with a DCV rating of 300V including a trip coil (24V) and an auxiliary contact, both on the same circuit. The coil voltage must be removed after tripping the breaker or it is possible to damage the trip coil. The I/O board provides the signal for tripping the circuit breaker from the X50 connector. Embedded software determines when the breaker shall be tripped; otherwise, when the current through the breaker exceeds the breaker rating the breaker will trip.
4.2.11
Ferrite Toroids
PW9355 Ferrite Toroids There are several Ferrite Toroids throughout the 9355 UPS system. Used as transformers in main power supplies, toroidal coils reduce resistance, due to the larger diameter and smaller number of windings. The magnetic flux in the toroids is confined to the core, preventing its energy from being absorbed by nearby objects. 4-4
© 2006 - Eaton Corporation
9355 20 – 30 kVA
4.2.12
Functional Descriptions
Chokes
The following is a list of PW9355 Chokes:
4.2.13
•
Battery Chokes: L2, L5, L8
•
Inverter Chokes: L3, L6, L9
•
Rectifier Chokes: L1, L4, L7
Fans
The PW9355 UPS has six (6) vane axial fans rated at 120VAC/110CFM. The fans are housed in the fan assembly. Table 2. Fan Assembly Iteration with Associated Serial Numbers 9355 20-30 kVA Fan Assembly Evolution
Associated Serial Numbers
old fan assemblies and old switchgear
EY213KXX07 and lower last digit
"new fan assembly" and "new switchgear"
EY213KXX08 and higher last digit
4.3 LCD Display Panel
Figure 22.
4.3.1
Display Panel
Overview
This section describes the functionality of the PW9355 display firmware and the basic principles of operation. The PW9355 display module has four push buttons, four light-emitting diodes (LEDs), a buzzer and a graphical Liquid Crystal Display (LCD). These are controlled by a micro-controller (PIC) which communicates with the main processor (DSP) using the Controller Area Network (CAN) bus. Refer to © 2006 - Eaton Corporation
4-5
Functional Descriptions
9355 20 – 30 kVA
paragraph paragraph 6.1.9 CAN Bridge Card and Figure 53 for more information about the Controller Area Network. Character images are stored to the PIC flash memory. The PIC provides the time-bases for LED flashing and buzzer control. The PIC also takes care of low-level LCD handling.
4.3.2
Detailed Description of Settings
Refer to the details of the user settings that are listed in the 9355 UPS User’s Guide. CSEs have access to these settings as well as the CSE Service Settings.
4.3.3
User Settings
For details of the User Settings, refer to the user setting information that is listed in the 9355 UPS User’s Guide. Table 3. Disable control commands via communication user settings Front Panel LCD User Setting
Setting Definition
To disable all control commands from a communication channel. The setting is done independently per channel.
The control commands are all XCP commands that change/modify any parameters, variables, UPS operation, and so on in the UPS; or hardware commands that are multiplexed to communication receive lines, thus simulating a long break.
Display Contrast Adjustment
The user can adjust the best LCD display contrast for the environment.
Change Language
The language selection is between English and other languages.
Start Screen in the Display
The default screen: Eaton Powerware logo or the mimic screen. This screen is displayed at reset, when ESC is pushed until the system menu returns to the top, or when the display has been untouched for a specific time period.
User Settings Password
Sets if the password is required for user settings.
Lock Communication to D-Sub
Disables the automatic multiplexing of communication channel 2 between the X-Slot 2 and the D-sub, and directs the communication to D-sub permanently.
Table 4. Disable control commands via communication user settings Front Panel LCD User Setting (or XCP command)
Setting Definition
Set Date & Time
The date and time is used for time-stamping the history log items.
Serial Port Configuration
The available speeds are 1200bps, 2400bps, 9600bps, and 19200bps, which are set independently per communication channel.
Go to Bypass
The transfer is done only if bypass is available.
4-6
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 4. Disable control commands via communication user settings Front Panel LCD User Setting (or XCP command)
Setting Definition
Battery Test Command
When the test is launched with the XCP command, the test duration is given in the command. The test selected from the LCD has fixed time. The following is a sample of a Battery Commissioning Test using command B.: BATTERY COMMISSIONING TEST BATTERY TEST # 1 TIME: 12:31:30 DATE: 11/14/2004 TEST 1 NOT COMPLETED VOLTAGE 0.00 POWER (W/CELL) 0.00 TEST 2 NOT COMPLETED VOLTAGE 0.00 POWER (W/CELL) 0.00 OPEN CIRCUIT VOLTAGE 0.00 CALCULATED RESISTANCE 0.0000 BATTERY HEALTH 0.0000
Audible Alarms
The settings are: Disable audible alarms and normal sound.
Set Nominal Output Voltage
With XCP, the value can be set with 0.1V steps. The front panel setting has larger steps. Changing this value will automatically change the voltage window defined by Bypass Voltage High Limit and Bypass Voltage Low Limit.
Bypass Voltage High Limit
The value is a positive percentage added to Nominal Output Voltage, and it follows changes automatically in the Nominal Output Voltage setting. It can be set with 1% steps, for example: +10%.
Bypass Voltage Low Limit
The value is a negative percentage subtracted from Nominal Output Voltage, and it automatically follows changes in the Nominal Output Voltage setting. It can be set with 1% steps. Example: -15%.
Synchronization Window
The value can be set with ±0.1Hz steps. This sets the frequency window used for synchronization around the Nominal Output Frequency, and it automatically follows changes in the Nominal Output Frequency setting.
Number of Battery Strings
Zero (0) means that no batteries are connected. Total battery size is number_of_strings × W/cells × cells/strings. (W/cell, 15 min rate to 1.67 VPC at 25° C)
Battery Size Setting
The size is given as Watts per battery cell, in 1W steps. Total battery size is number_of_strings × W/cells × cells/strings. (W/cell, 15 min rate to 1.67 VPC at 25° C)
Battery Low Alarm Level
The maximum current used for charging the batteries is set with this setting, in 0.1A steps.
Automatic On Delay
Values 0 ... 32767 define the extra delay in seconds, which is counted down every time the UPS is about to © 2006 - Eaton Corporation
4-7
Functional Descriptions
9355 20 – 30 kVA
Table 4. Disable control commands via communication user settings Front Panel LCD User Setting (or XCP command)
Setting Definition turn on its output. With value -1, the automatic restarts are disabled; the UPS will not turn on automatically (uncommanded) after low battery shutdown.
Nominal Output Frequency
With an XCP command, the nominal output frequency can be set with 0.001Hz steps (the front panel has larger steps). Changing this value will move the Synchronization window in accord with it.
ABM Charging Cycling Disable
Disables the cyclic ABM charging and uses the continuous mode.
Output Frequency Slew Rate
The maximum speed of changing the output frequency that the UPS uses while synchronizing or maintaining synchronization; set with 0.1Hz/sec steps.
Operation Priority While Rectifier Input Break
This selects if the UPS will prefer bypass operation to battery operation when rectifier input fails, and bypass is available.
Rectifier Current Limit
The maximum current drawn from utility by the rectifier is set here, in 0.1A steps.
Alarm Relay Configuration
For each alarm, the user selects the relay to activate.
Signal Inputs Function
For each alarm input, the user selects the function.
Input Signal Delayed Shutdown Delay
This is the delay for hardware Remote off with automatic restart command. Factory setting is 120 sec, but the user may modify it.
X-Slot Shutdown Signal Input Activation Delay
This is the delay duration the X-Slot hardware shutdown signal (connector pin 8) must be below before the associated function is activated. Factory setting is 5 sec.
Unsynchronized Transfer to Bypass
This selects if synchronization is required for making transfers to bypass.
Synchronization to Bypass
This selects if the synchronization to bypass is done.
Usage of Bypass
This selects if the bypass is used (enabled) when needed / required, or if it is never used (disabled).
Site Wiring Fault (NOTICE)
The user can enable or disable this alarm. When set as ”Disabled”, no alarm nor notice is given on the front panel. Nothing is logged into the history log. When set as ”Enabled”, the factory setting is used, alarm activation and inactivation are logged. Note: With Nodebits (service setting) it is possible to make a more detailed setting. The user setting (front panel) shows as ”Disabled” when set as event and not logged. Otherwise, the user setting shows as ”Enabled”.
4-8
© 2006 - Eaton Corporation
9355 20 – 30 kVA
4.3.4
Functional Descriptions
Service Settings
The following Service Settings are available to the CSEs for troubleshooting. In addition, CSEs have access to the User Settings that are listed in paragraph 4.3.3. For details of the User Settings, refer to the user setting information that is listed in the 9355 UPS User’s Guide. The default access to Service Settings on the LCD Display in PW9355 for the U.S. and Canada will be disabled. In other overseas markets the Service access will be enabled. Table 5. Service Settings Front Panel LCD User Setting (or XCP command)
Setting Definition
Service Control
This is an implementation defined parameter, which allows service to do special hardware controlling
Rectifier Synchronization Window
This setting defines the rectifier input frequency window that is used for synchronization when the bypass voltage has failed.
Auto Frequency Detection Back-feed Enable Battery Charging Temperature Compensation
This setting defines the number of battery cells in a battery string.
On Battery Alarm Delay
This setting defines the number of seconds the UPS is on battery operation before ”UPS on battery” alarm is given.
Battery Test Schedule EPO Disable
This setting disables/enables the Emergency Power Off signal and functions.
Modem Communication
Define the communication channel where the modem is connected. A value of zero (0) means that no modem is connected.
Modem Call Number Setting
This string is sent to the modem when a call is initiated. It holds the call command and the phone number to dial.
Modem Initialization String
This string is used when the modem is to be initialized.
Modem Communication Password
This string defines the password that is required when someone tries to change the UPS configuration or control the UPS through a modem line.
Modem Hang Up String
This string is used to hang up (disconnect) the modem/phone line.
Set Modem Call Command Set Modem Call Events Adjust Events Reset Custom Event Settings Adjust Parameters Reset Configuration to Factory Setting
With this setting it is possible to reset most of the UPS configuration to the factory settings.
© 2006 - Eaton Corporation
4-9
Functional Descriptions
9355 20 – 30 kVA
Table 5. Service Settings Front Panel LCD User Setting (or XCP command)
Setting Definition
Clear History Log
With this setting it is possible to reset the UPS event history log.
Constant Float Voltage
This setting defines the battery charging voltage (volts per cell) when ABM charging cycles are disabled.
Nodebits
Service setting. Each event can be configured several different ways. An alarm, notice, or non-alarming event Logged into the event log or not Cause a modem call Cause an audible alarm
4-10
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.4 CONTROL BOARD (PCB) Reference Documents: 1021280 Control Board Schematic
Figure 23.
4.4.1
9355 Control Board
Firmware Description and Operation
Refer to Figure 24 Control Board Machine States The 9355 has the following operation states: Shutdown - Shutdown commanded from the display or the rails can’t be powered. The load is powered-up after the UPS is commanded from the display, or the load is on bypass and the UPS is waiting until conditions accomodate transfer to normal mode. The X-Slots are not powered. Startup - The unit performs startup-steps to power up rails. The X-Slots are not powered. Standby - The inverter is ready to feed the load. The X-Slots are powered. The XCP tool can be used to power-up the load. On Inverter - The load is fed by the inverter. Energy is taken from the utility and/or from the batteries. The X-Slots are powered. On Bypass - The load is fed through the bypass line. Energy for the load is taken from the bypass/utility, but battery energy may be used for UPS testing and for other internal purposes. The X-Slots are powered, the ABF relay is closed, and the rails cannot be bled down. Bleeding – UPS performs full shutdown. The DC bus is drained. Bleeding cannot be called if the unit is on bypass. The X-Slots are disabled. Bypass-Locked - The load is on bypass. The UPS is internally shut down and will automatically restart when utility power returns. This is done during flash recovery. © 2006 - Eaton Corporation
4-11
Functional Descriptions
9355 20 – 30 kVA
Failure Shutdown – There is an active alarm that prevents UPS startup. It is possible to clear this alarm by starting the UPS from the display. The X-Slots are powered during this state.
Shutdown Bypass-
locked
Failure shutdown
Startup Bleeding
On bypass
Standby
On inverter
Figure 24.
4.4.2
9355 Control Board Machine States
Shutdown State
The load is down. The X-Slots are not powered. The only way to restart the UPS is to use the front panel “UPS On” function. If auxiliary power goes active while startup is not possible, the unit stays in the shutdown state. If auxiliary power goes active while the load is on bypass and startup is not possible, the unit waits until startup is possible and transfers the load to the inverter.
4.4.2.1
4-12
User Interface & XCP
•
XCP status = UPS OFF
•
XCP status = ON BYPASS
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.4.2.2
Initialization
4.4.2.3
Hardware
•
Bypass off
•
Inverter thyristors off
•
X-Slots are off
4.4.2.4 •
Other
None
4.4.2.5
4.4.3
Operation 1.
Wait for front panel UPS on command.
2.
Wait for good startup conditions and change the state to start-up state if the load was on bypass when start-up state was called.
Startup State
The UPS is performing its start-up sequence and automatically progressing toward standby operation or “load on inverter” operation. The load can be on bypass if commanded. The X-Slots are not powered up. The UPS powers up the DC bus. Rectifier, inverter and battery operations start.
4.4.3.1
User Interface & XCP
•
XCP status = UPS OFF
•
XCP status = ON BYPASS
4.4.3.2
Operation
4.4.3.3
Initializing State
This state is always called before shutdown state. Some startup procedures are executed here. The next state is utility startup, battery startup or shutdown depending on the conditions. 1.
Disable EPO, disregard all measurements as X-Slot and other measurements are taken from the Control Board signals, with the exception of 24V measurement.
2.
Check that the unit is 9355, that the Control Board is supported and the PLD version is known. If not, set the software incompatibility detected alarm and jump to failure shutdown state.
3.
Wait until the 24V measurement is higher than 17V; if not registering higher than 17V after 6 seconds, set the auxiliary power startup failure alarm, and jump to failure shutdown state.
4.
Wait for correct bypass status information. © 2006 - Eaton Corporation
4-13
Functional Descriptions
9355 20 – 30 kVA
5.
Initialize bypass signals.
6.
Activate I/O_GOOD (Control board logic good).
7.
Set bypass to Idle state if fire state is not detected.
8.
Turn on PWRCLK0 (Gate power clock).
9.
Turn on PWRCLK1 (Aux. power clock).
10. Turn on 12V_1 (Main circuit +12V). 11. Wait 500ms. 12. Reset the auxiliary voltage monitoring alarms in PLD. 13. Wait 400ms. 14. Enable the meters. 15. Wait 100ms. 16. Initialize slow utility measurements to fast measurement values. 17. Reset CLK_FAIL and EPO alarms. 18. Wait 1 second. 19. Enable auxiliary voltage alarm monitoring. 20. Wait 1 second to settle filtered measurements. 21. Check 12V, continue monitoring. If ok, all measurements and monitoring signals are functioning now. 22. Clear auxiliary power startup failure, the back-feed failure, the abnormal output voltage alarm, the bypass SCR failure, the DC charger failure, the balancer relay failure, the rectifier failure, the inverter startup failure, the fuse failure, and the DCOV and DCUV alarms. 23. Initialize rectifier control values. 24. Start monitoring temperature alarms, building alarms, voltages, and so on. 25. Auto zero Hall Sensor offsets. Inverter and rectifier sensors are zeroed. 26. If utility startup is possible, perform utility startup. 27. If battery startup is possible, perform battery startup, otherwise shutdown.
4.4.3.4
Shutdown State 1.
Wait for the front panel UPS ON command. OR
1.
4-14
Wait for the proper startup conditions when the load is on bypass.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
2.
4.4.4
Prepare to lose auxiliary power and jump back to the initializing state if the utility fails.
Battery Starting State 1.
Clear the old EPO alarm.
2.
Activate the EPO.
3.
Close the balancer relay.
4.
Wait 60ms.
5.
Activate GATE_ENABLE and the PLD gate outputs.
6.
Use the input phase 1 lower IGBT to transfer energy from negative rail to positive rail in order to keep auxiliary power up and running.
7.
Wait for the front panel ON command or utility voltage before continuing. If nothing happens in 3 minutes, open the battery breaker. Jump to utility startup if utility voltage is good.
8.
Wait 500ms.
9.
If not in parallel mode, bypass is not active and the output voltage is > 50V, then set the abnormal output voltage alarm, open the battery breaker and jump to the bleeding state.
10. If bypass is not active and the bypass voltage is > 50V, then set the bypass breaker failure alarm, open the battery breaker and jump to the bleeding state. 11. Wait 100ms and initialize slow bypass voltage measurements to fast measurements. 12. If the unit is not in parallel mode and bypass is not active and the output voltage is > 50V, then set the abnormal output voltage and bypass SCR failure alarms, open the battery breaker and jump to the bleeding state. 13. If bypass is available and not active, then request bypass idle mode. 14. Wait 20ms. 15. Activate the DC_CHARGE to charge the positive rail. 16. Check positive rail voltage after 10 seconds: if it is below 20V, then set DC charge failure alarm, open the battery breaker and jump to the bleeding state. 17. Wait until positive rail voltage is above battery voltage by 45V. If unresponsive after 2 minutes, then set the DC charge failure alarm, open the battery breaker and jump to the bleeding state. 18. Stop charging the positive rail. 19. Wait 10ms. © 2006 - Eaton Corporation
4-15
Functional Descriptions
9355 20 – 30 kVA
20. Use the input phase 1 upper IGBT to transfer energy from positive to negative rail. 21. Request battery relay balancing. 22. If negative DC voltage goes over 233V, then set the balancer relay failure alarm, open the battery breaker and jump to the bleeding state. 23. Check the negative voltage after 20s, if below 50V, then set the balancer relay failure alarm, open the battery breaker and jump to the bleeding state. 24. Wait until the battery relay is balanced. Maintain minimum positive rail voltage (120V). If not ready after 2 minutes, then set the balancer relay failure alarm, open the battery breaker and jump to the bleeding state. 25. Stop the charging negative rail. 26. Wait 1 second. 27. Deactivate the DC_CHARGE. 28. Ramp boost the voltage starting from lower rail voltage 240V / 1 second. 29. Wait until final rail reference is reached (188V). 30. Startup the balancer. 31. Ramp boost voltage again starting from lower rail voltage 40V / 1 second, now with the balancer active. 32. Wait 1 second. 33. Turn on 12V_2 (X-Slots), accept X-Slot communication.
4.4.5
4-16
Utility Starting State 1.
Clear the old EPO alarm.
2.
Activate EPO.
3.
Start monitoring utility voltages, jump to shutdown if not good.
4.
Check the site wiring fault and shutdown if the chassis voltage measurement is > 50V.
5.
Wait 500ms.
6.
If not in parallel mode, bypass is not active and output voltage > 50V, then set the abnormal output voltage alarm and jump to the bleeding state.
7.
If bypass is enabled and not active and bypass voltage > 50V, then set the bypass breaker failure alarm and jump to the bleeding state.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
8.
Wait 100ms and initialize slow bypass voltage measurements to fast measurements.
9.
Enable gate power and PLDs.
10. If rail is already up, exit the Utility starting state sequence and go to the “turn inverter on” state. Otherwise, continue the sequence and turn rectifier L1 on, in a mode which bleeds the balancer capacitor down. 11. Request bypass idle mode. 12. Wait 100ms. 13. If capacitor voltage is < 25V, close the balancer relay. 14. Wait 40ms. 15. Activate the DC_CHARGE to charge the positive rail. 16. Check positive rail voltage after 10s; if below 20V, then set DC charge failure alarm and jump to the bleeding state. 17. Wait until (+) rail voltage is above L1 positive peak by 45V. If it is not ready after 2 minutes, then set DC charge failure alarm and jump to the bleeding state. 18. Use input phase 1 upper IGBT to transfer energy from (+) to (-) rail. 19. Check negative voltage after 20 seconds. If below 50V, then set the balancer relay failure alarm and jump to the bleeding state. 20. Wait until negative DC is higher than L1 maximum peak + 55V or 233V. If not ready after 2 minutes, then set balancer relay failure alarm and jump to the bleeding state. 21. Stop charging the negative rail. 22. Wait until the positive rail voltage is above L1 positive peak by 45V. If not ready after 1 minute, then set the balancer relay failure alarm and jump to the bleeding state. 23. Wait 5 seconds. 24. Deactivate the DC_CHARGE. 25. Use the input phase 1 lower IGBT to transfer energy from the (-) rail to the (+) rail. 26. Wait until positive and negative rails are equal (+/-5V). If not ready after 20 seconds, then set the balancer relay failure alarm and jump to the bleeding state. 27. Wait 5 seconds. 28. Open the balancer relay, K1-K4, and wait 20ms. 29. Close the K1 contactor. The contactor is too slow to operate at zero crossing. Wait 100ms. © 2006 - Eaton Corporation
4-17
Functional Descriptions
9355 20 – 30 kVA
30. Set the initial rectifier reference to higher rail voltage + 15V or 188V. 31. L1 Rectifier on. 32. Ramp up rectifier reference voltage (10V / 1s). 33. Wait until the final rail reference is reached (188V). If not ready after 10 seconds, then set rectifier failed alarm and jump to the bleeding state. 34. L1 Rectifier off. 35. L1, L2 and L3 Rectifier ON. 36. Wait 100ms while the rectifier is running normally. If not ready after 10 seconds, then set the rectifier failed alarm and jump to the bleeding state. 37. Set the flag which communicates that the rail is high enough to commutate the battery SCR if it was turned on. 38. Turn on the 12V_2 (X-Slots), accept x-slot communication.
4.4.6
Inverter Starting State 1.
If the unit is on bypass, configure the inverter (this is for flash recovery), enable the battery, close the battery contactor, transfer the unit to bypass and exit the inverter starting state.
2.
Configure the inverter.
3.
Inverter ON.
4.
Wait 40ms.
5.
Check the inverter fuses. If inverter voltage is under 50V, then set the fuse failure and inverter startup failure alarms and jump to the bleeding state.
6.
Check that the inverter is within its operational window. If not, then set the inverter startup failure and jump to the bleeding state.
7.
If not in parallel mode, bypass is not active and UPS output voltage is > 50V, then set the abnormal output voltage and inverter startup failure alarms and jump to the bleeding state.
8.
Enable battery operations and close the battery contactor.
9.
Wait 5 seconds.
10. Jump to the standby state.
4-18
© 2006 - Eaton Corporation
9355 20 – 30 kVA
4.4.7
Functional Descriptions
Standby State
The UPS is brought to this state on the first startup after auxiliary power comes up, load is not on bypass and startup is possible. During standby state the load is down and the X-Slots are powered; the inverter, rectifier and battery operations are active; and the output SCRs are open. The batteries are charged if utility is good. Auxiliary power is drawn from utility or from the battery if utility isn’t available. During standby the UPS output has been turned off. The UPS is ready to turn the output on when commanded to do so, or when the utility is OK, depending on the standby precursory condition resolution. Standby stays active as long as all of the following conditions are met and the load is not commanded on. Table 6. Active Standby Conditions Conditions Required to Maintain DC Bus Voltages
Timeout Before Action
Inverter hardware over current limit
0ms
Rectifier hardware over current limit
0ms
Overload >100% and shutdown timeout reached
0ms
Auxiliary power failure
0ms
DC bus over voltage (>250 V)
0ms
DC bus very low voltage (<100 V)
0ms
Inverter output fuse failure
0ms
Any phase of utility > 144V
0ms
Utility not available and boost/charger hardware over current limit 0ms Utility not available and boost/charger over temperature shutdown 0ms Utility not available and low battery shutdown *
0ms *
Inverter output out of window
300ms
Temperature sensor failure
300ms
Rectifier over temperature shutdown
300ms
Inverter over temperature shutdown
300ms
Balancer over temperature
300ms
Boost/charger hardware over current limit
300ms
* Low battery shutdown timeout is 60 minutes on standby state.
When utility power fails and auxiliary power is taken from the battery, a 60minute countdown starts. When the countdown expires or the battery voltage reaches 1.67 volts/cell, the unit goes to the bleeding state and auxiliary power is shut down. If utility returns, the counter counts backwards until the 60-minute limit is reached. If standby was caused by a low battery shutdown, there is a © 2006 - Eaton Corporation
4-19
Functional Descriptions
9355 20 – 30 kVA
60-minute countdown mentioned above, but load will be powered when utility returns.
4.4.8 •
User Interface & XCP XCP status = UPS OFF
4.4.8.1
Hardware
•
Bypass off
•
Inverter thyristors off
•
X-Slots are on
4.4.8.2
Other
Restarts automatically if the “automatic on function” is enabled and when the turn-off reason is: •
Automatic off delay OR
•
Binary input delayed shutdown function OR
•
4.4.8.3
XCP delayed load power off and restart command.
Operation
The restart flag indicates if the UPS output is automatically turned back on when the utility is OK. The minimum time to remain in standby after turn-off is 10 seconds. This feature prevents inadequate breaks on the UPS output voltage. While the UPS is in this state UPS communications is working (this means the D-sub, X-Slots, binary inputs, signal relay, and so on). Battery power is used, when necessary. The UPS must be ready to restart when commanded to do so. While remaining in this state, the battery voltage is constantly monitored. If battery voltage decreases to the shut down level, battery draining ceases and the UPS is turned off; if a one-hour-long utility break occurs, the same shut down sequence occurs. The utility break counter is decreased when utility is good. If the UPS is turned off, the restart flag state is stored. When the utility returns, the state of the flag is checked, and the UPS output is automatically restarted.
4.4.9
On Inverter State
The load is fed by the inverter. Energy is taken from the utility and/or from the batteries. The X-Slots are powered.
4-20
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.4.9.1
User Interface & XCP
The XCP status is given in the following prioritized order: •
XCP status = ON BATTERY, when discharging batteries
•
XCP status = OUTPUT OVERLOAD, when the UPS is overloaded
•
XCP status = SYSTEM NORMAL, when there are no alarms
•
XCP status = UPS SUPPORTING LOAD, when alarms are active
4.4.9.2
Hardware
•
Bypass off
•
Inverter thyristors on
•
X-Slots are on
4.4.9.3 •
Other
None
4.4.9.4
Operation
During the program loop, the firmware checks for any conditions that would invoke a transfer on bypass, output shutdown, or conditions preventing a transfer on bypass. When a transfer on bypass is possible, the state of the UPS changes to a ”transfer on bypass” state. The firmware checks the conditions that caused inverter output shutdown and transfer to bypass, and the output is remedied accordingly. The XCP load off commands will then change the state of the UPS to standby. Other conditions may require rail discharge in addition to securing the output. Depending on the condition, shutdown may also be delayed. A “Delayed Pending Shutdown” is aborted if conditions become inactive before the delay has expired.
4.4.10
On Bypass State
The table below shows the conditions that normally will cause the transfer to bypass. If the transfer cannot be made, the table shows whether a condition causes an output shutdown. Table 7. Conditions Prompting an Output Shutdown Conditions Requesting Transfer to ON Bypass
Transfer Disabled if...
If Transfer is Disabled, Shutdown After...
User command to use bypass operation
ABC
-
Overload level 1 ≥102%
ABC
10 minutes
Overload level 2 ≥111%
ABC
60 seconds
© 2006 - Eaton Corporation
4-21
Functional Descriptions
9355 20 – 30 kVA
Table 7. Conditions Prompting an Output Shutdown Conditions Requesting Transfer to ON Bypass
Transfer Disabled if...
If Transfer is Disabled, Shutdown After...
Overload level 3 ≥126%
ABC
5 seconds
Overload level 4 ≥151%
AB
300ms
Inverter output out of window
AB
300ms
Temperature sensor failure
AB
300ms
Rectifier over temperature shutdown
AB
300ms
Inverter over temperature shutdown
AB
300ms
Balancer over temperature
AB
300ms
Battery low limit counter expired and load on battery
AB
0ms
Battery usage prevented and load on battery
AB
0ms
Hardware over current limit
AB
0ms
Auxiliary power failure
AB
0ms
DC bus very low voltage (<100 V)
AB
0ms
DC bus over voltage (>250 V)
AB
0ms
A
-
Service command to use forced bypass operation
A. Disable bypass mode or bypass not installed. B. Bypass voltage/frequency is unacceptable, bypass has been disabled by signal input, minimum time (3 seconds) on the inverter hasn’t expired, neutral fault, bypass failure, bypass processor not ready or unsynchronized transfers are disabled and the inverter is not synchronized to bypass. C. Bypass temporarily inhibited or the minimum time on battery before bypass counter hasn’t expired (4 seconds). This table lists other conditions to shutdown the output. Table 8. Other Condtions Prompting Output Shutdown Conditions to Shutdown the Output
Transfer Disabled if...
If Transfer is Disabled, Shutdown After...
Battery connected, Battery low limit counter expired
-
0ms
Emergency power off (EPO)
-
0ms
Turn UPS off command from front panel
-
0ms
Automatic off delay function
-
0ms
XCP ”UPS off” command
-
0ms
XCP ”delayed off” command
-
0ms
Output transformer over temperature
-
Configurable
4-22
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
The following table shows the conditions that prevent the transfer to inverter from bypass. The transfer is done 5 seconds after the last active condition becomes inactive. The following table also shows the conditions that don’t prevent transfers when bypass fails. Table 9. Condition Preventing Bypass to Inverter Transfer Conditions Preventing Transfer From Bypass to Inverter User command to use bypass operation
Doesn’t Prevent Transfer if Bypass is Bad S
Service command to use forced bypass operation Overload >100%
* Prevents Soft transfers
Hardware over current limit Inverter output fuse failure Rectifier failure Rectifier over temperature alarm
* Prevents Soft transfers
Rectifier over temperature shutdown Inverter over temperature alarm
* Prevents Soft transfers
Inverter over temperature shutdown DC bus over voltage (>250 V) DC bus very low voltage (<100 V) Auxiliary power failure Balancer over temperature Temperature sensor failure Battery under voltage
* Prevents Soft transfers
Inverter inhibit
* Prevents Soft transfers
Inverter not synchronized to bypass
* Prevents Soft transfers
Inverter output out of window CAN bus transfer command (used in paralleling) Redundant transfer command (used in paralleling) * The condition prevents ”soft” transfers only. ”Hard” transfers (bypass failures) are allowed
It is possible that the load is on bypass, on shutdown, startup, the bleeding and bypass-locked states. Transfer to inverter is never possible in these states.
© 2006 - Eaton Corporation
4-23
Functional Descriptions
9355 20 – 30 kVA
The following table shows conditions that prevent using bypass. Any of these will cause immediate transfer to the inverter, if possible. Table 10. Conditions Forcing Hard Transfer From Bypass to Inverter Bypass voltage < U out – 15% (fast ”one cycle” meter) Bypass voltage > U out + 10% Bypass frequency < 47Hz Bypass frequency > 53Hz Bypass processor in unknown state Neutral failure
The following table shows the conditions, which cause output shutdown. Table 11. Conditions that Shutdown the Output From Bypass Neutral failure and inverter not available Emergency power off (EPO) Turn UPS off command from front panel XCP ”UPS off” command XCP ”delayed off” command
4.4.10.1 User Interface & XCP The XCP status is given in the following prioritized order: •
XCP status = OUTPUT OVERLOAD, when the UPS is overloaded
•
XCP status = ON BYPASS
4.4.10.2 Initialization 4.4.10.3 Hardware •
Bypass on
•
Inverter thyristors off
•
X-Slots are on
4.4.10.4 Other •
None
4.4.10.5 Operation During the program loop, the firmware checks the conditions to transfer on inverter or to require output shutdown. The firmware checks for a condition that warrants turning the inverter off or the rectifier off. If such a condition exists, the rails stay peak charged and the converters are turned off. 4-24
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
If the rectifier or inverter is off, and all failures are clear, then the rectifier and inverter should be restarted. Let the inverter run at least 5 seconds prior to transferring online. The firmware checks conditions that prevent transfer on inverter. The firmware checks if the bypass condition forces the transfer on inverter. The firmware checks the conditions that cause output shutdown (these conditions include a neutral fault while the inverter is unavailable and the UPS off command). The output is turned off accordingly.
4.4.11
The Bleeding State
In the bleeding state the DC bus is drained. The rectifier, inverter and battery operations are shut down. All measurements are disabled for 50 seconds at the end of bleeding. Bleeding is not allowed if the unit was on bypass, because the ABF relay is feeding both the rectifier and bypass. If bleeding is justified and the unit is on bypass, the bypass state takes priority and bleeding does not occur. If utility is good after bleeding and there are no active alarms, the UPS will continue to the shutdown state; or, if the load is on bypass, to the startup state. If the utility is bad after bleeding, the auxiliary power shuts down. Bleeding can be interrupted by a front panel UPS ON command.
4.4.11.1 User Interface & XCP •
XCP status = UPS OFF
4.4.11.2 Initialization 4.4.11.3 Hardware •
X-Slots are off
4.4.11.4 Other •
None
4.4.11.5 Operation The X-Slots are off. The DC bus is drained. Measurements are disabled at the end of this state. The following steps are done at UPS DC bus discharge: 1.
Open the inverter output contactor.
2.
Turn off the inverter.
3.
Wait 30ms.
4.
Stop monitoring rail voltages, disable battery operations, open the battery relay, shut down the rectifier, turn off X-Slot power.
5.
Wait 2ms. © 2006 - Eaton Corporation
4-25
Functional Descriptions
9355 20 – 30 kVA
6.
Open the ABF relay.
7.
Wait 40ms.
8.
Disable EPO.
9.
Wait 100ms for ABF to open.
10. Bleed the balancer capacitor down with rectifier L1. 11. Wait 100ms. 12. If voltage cannot be bled less than 25V, set the balancer relay failed flag and interrupt the bleed routine. 13. If bleed down was okay, close the balancer relay. 14. Wait 60ms. 15. Use the input phase 1 lower IGBT to transfer energy from negative rail to positive rail. 16. Make sure that the positive rail stays between 188V and 178V. 17. Wait 40 seconds, or until the negative rail is lower than -20V before continuing. 18. Check for UPS on command; if TRUE, turn back on; if FALSE, disable GATE_ENABLE and PLD rectifier gate outputs. 19. Wait 10 seconds or until the positive rail is lower than 150V before continuing. 20. Wait 40ms. 21. Open the balancer relay. 22. Wait 40ms. 23. Disable all meters and meter based alarms. 24. Shut down the main 12V. 25. Request an EEPROM restart bit write. 26. Wait for EEPROM write completion. 27. Wait 40 seconds. 28. Jump to the initialization state or failure shutdown state.
4.4.12
Bypass-Locked State
The load is on bypass. The UPS auxiliary power is off. The unit restarts and transfers the load on inverter as soon as utility returns and startup is possible.
4-26
© 2006 - Eaton Corporation
9355 20 – 30 kVA
4.4.13
Functional Descriptions
Failure Shutdown State
If bleeding was caused by an alarm listed below, the unit goes to the failure shutdown state. This state ensures that the X-Slots are powered and the modem can be used to communicate the failure. •
Auxiliary power startup failure
•
Back-feed failure
•
Abnormal output voltage at startup
•
Bypass SCR failure
•
DC charger failure
•
Balancer relay failure
•
Rectifier failure
•
Inverter startup failure
•
Fuse failure
4.4.13.1 User Interface & XCP •
XCP status = UPS OFF
•
XCP status = ON BYPASS
4.4.13.2 Initialization 4.4.13.3 Hardware •
Bypass off
•
Inverter thyristors off
•
X-Slots are on
•
All analog measurements are disabled
4.4.13.4 Other •
None
4.4.13.5 Operation The purpose of this state is to maintain communication, possibly alarming a shut down cause. The only way to turn the output back on is to use the front panel UPS ON function. While the UPS is in this state the X-Slot communication is working. However, all measurements are disabled because auxiliary power is reserved for the XSlots. The DC bus isn’t maintained in this state. It means that auxiliary power shuts down and all communication is lost during a utility break. © 2006 - Eaton Corporation
4-27
Functional Descriptions
4.4.14
9355 20 – 30 kVA
Methods of Turning the UPS Off
This section describes user signals or settings that can be used to shut down the UPS output.
4.4.14.1 Front Panel UPS Off The normal means to shut down the UPS. The UPS will restart only from the front panel.
4.4.14.2 Emergency Power Off (EPO) The signal acceptance is configurable. When accepted, it shuts down the UPS. The UPS will restart only from the front panel.
4.4.14.3 Automatic Off Function This is a user settable parameter for automatically turning the output off in case of utility failure (actually, any time when operating on battery). 1.
AutoOffDelay = -1 = 65535, no automatic off function. This is the factory setting (default value).
2.
AutoOffDelay = 0…65534, the number of seconds before the output is automatically turned off if the UPS has been discharging batteries. If the UPS transfers to some other state, the automatic off countdown is aborted.
Note The automatic off countdown is not active when a service command or a battery test (or similar reason) has caused the transfer on battery. After shutdown, the output off follows the functionality of the XCP Delayed Power off and Restart command. The UPS restarts automatically when the utility returns, but only after a minimum 10 second down time.
4.4.15
XCP Command Codes
XCP command codes are issued remotely, or from a local laptop computer, by the XCP software tool.
4.4.15.1 Delayed Power Off & Restart A command code: turn UPS output off after a delay, restart automatically when utility is OK. The command is disabled when communication control commands are disabled from the front panel.
4.4.15.2 UPS Off Command A command code: turn UPS output off immediately. Restarts when commanded with XCP, or from the front panel. The command is disabled when communication control commands are disabled from the front panel. 4-28
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.4.15.3 Scheduled Off A command code: turn UPS output off after a delay. Restarts when commanded with XCP, or from the front panel. The command is disabled when communication control commands are disabled from the front panel.
4.4.16
Hardware Signals
4.4.16.1 X-Slot Signal The X-Slot shutdown signal uses a serial communication receive data line. Both X-Slots (serial channels) implement this shutdown function similarly, but independently. The X-Slot shutdown signals are disabled when communication control commands are disabled from the front panel. This shutdown works also from the service port D-sub, as it is multiplexed with X-Slot 2. This function is independent from normal serial communication. Normal communication is functional, while receive lines are monitored for the shutdown signal. When a logic 0 is received continuously for 5 seconds (as the same value for both channels), the shutdown flag is activated. When a logic 1 is received, the flag becomes inactive without the delay after slight filtering. The shutdown flag may be mapped to one of three shutdown functions: •
The UPS output is shut down after delay, automatic restart.
•
The UPS output is controlled off and on with the signal. Note that there is always the delay (default 5 seconds) before the flag activates.
•
The UPS output is turned off. Note: The shut down signal from X-Slot 2 does not work while the service port D-sub is used for communication. This is because the D-sub communication disables X-Slot 2 communication and receive input.
4.4.16.2 Building Input Either building input can be mapped to function as a shutdown flag. The shutdown flag may be mapped to one of three shutdown functions: •
The UPS output is shut down after delay, automatic restart.
•
The UPS output is controlled off and on with the signal.
•
The UPS output is turned off.
© 2006 - Eaton Corporation
4-29
Functional Descriptions
9355 20 – 30 kVA
4.4.16.3 Remote Off with Automatic Restart This function has a user selectable control source. When the signal is active: •
The UPS output is shut down after 120 seconds (EEPROM setting).
•
After shut down, the output is off at least 10 seconds.
•
When utility voltage is OK, the UPS restarts automatically if allowed by the user settable “Automatic ON Delay”. Note: The utility condition doesn’t affect shutdown signal acceptance, the signal is always accepted.
4.4.16.4 Remote On - Off This function has a user selectable control source. When the signal is active, the UPS output is off. When the signal is inactive, the output is on.
4.4.16.5 Remote Off This function has a user selectable control source. The UPS is shut down and requires the user to turn it back on via the front panel. This is the same as if the front panel UPS OFF function were used.
4-30
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.5 POWER MODULE BOARD (PCB) Reference Documents: PW 9355 1024051 Power Board Schematic, see the Prints chapter at the end of this document.
Figure 25.
4.5.1
9355 Power Board
Introduction & Overview
The description contained in this section pertains only to the hardware found on the Power Module Board. The Power Module Board provides interconnections to the I/O Board. It contains the system power train. Each Power Board is the location of the 3 main power converters: one phase of the Boost Rectifier—1/3 of the Battery Boost/Buck Charger, one phase of the Buck Inverter—their respective gate drives, and one IGBT thermal sensor. This board along with chokes and heat sink comprise a power module capable of handling 1/3 of the output power. DC voltage sensing is provided on this board. It is the home of the positive and negative rail bulk storage caps. There is also a heat sink thermostat sensor. Each interfaces with the I/O board through a 20-pin ribbon cable.
© 2006 - Eaton Corporation
4-31
Functional Descriptions
4.5.2
9355 20 – 30 kVA
Description and Operation
4.5.2.1
X11 Connector Description
X11 connector is a 20-pin ribbon connector that connects the I/O board to the Power Board. Table 12.
X11 Pinout
Pin
Signal
Description
1
Logic ground
Ground
2
PWRCLK0
Gate clock
3
Logic ground
Ground
4
Temperature1
IGBT module temp sensor (middle)
5
Spare
NC
6
INVDC_L2
Inverter choke hot end sense
7
INVDC_L1
Battery choke hot end sense
8
IO1
Thermostat (heatsink)
9
POWMOD_GOOD
Power Module good signal (detects blown gate drive fuse)
10
Logic ground
Ground
11
GATE 14
Battery gate drive signal
12
GATE 13
Battery gate mode select (boost or charger)
13
GATE 8,10,12
Lower Inverter gate drive signal
14
GATE 7,9,11
Upper Inverter gate drive signal
15
GATE 6,4,2
Lower Rectifier gate drive signal
16
GATE 1,3,5
Upper Rectifier gate drive signal
17
Logic ground
Ground
18
+12V
+12V to power gate drives
19
Logic ground
Ground
20
+12V
+12V to power gate drives
4.5.3
Other Connector Descriptions
Reference Designator
4-32
Description
X1
Negative rail busbar
X2
Positive rail busbar
X3
Neutral busbar
X5, X6
Rectifier Choke connections
X7, X8
Inverter Choke connections
X9, X10
Battery Choke connections
X12
Heatsink Thermostat connector
X13
Heatsink Neutral tie connector © 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.6 Power Board Functional Blocks The following paragraphs describe the functional blocks of the Power Board.
4.6.1
Voltage Sensing
The Power Board provides DC voltage sense resistors for voltage sense measurements done on the Control Board. Voltage sense resistors are two 1Meg ohm resistors in series. The measurements are differential measurements with respect to neutral. Redundant battery and inverter DC are sensed.
4.6.2
Rectifier
The three-phase 20khz rectifier circuit consists of an IGBT half bridge converter located in position (V3) of the IGBT module, on the heatsink closest to the busbars of each power module (that is, Power Modules L1, L2, L3). During startup one rectifier half bridge (PM L1) is first used in balancer mode (~50% duty cycle), together with rectifier chokes (L7A/B) and balancer relay (K1-3 on the I/O board), to pre-charge the negative rail capacitors from the pre-charge energy stored in the positive rail capacitors. This rail pre-charge takes place in order for the input contactor to close without causing a high inrush current from the utility to the rail caps. After this precharge period ends the balancer relays are opened and the input contactor is closed. The 3 phase rectifier half bridges (PM L1, L2, L3) midpoints are then connected to utility through parallel input chokes (L1A/B, L4A/B, L7A/B) and begin operating in boost PFC mode, boosting the rail caps to +/-195VDC wrt neutral for the inverter to use. While maintaining the boosted rail voltage it also draws a sine wave of current from utility. After the input contactor is opened during battery operation, if utility fails the rectifier relays return to the above balancer mode, in order to balance the voltage on the rail caps wrt neutral coming from the Battery Boost converter (see the next section).
4.6.3
Battery Converter
4.6.3.1
Battery Boost
The 20khz Battery Boost circuit consists of parts of three IGBT half bridge converters located in middle (V1) IGBT module position on the main heatsink of each power module. In this mode it only involves the lower IGBT and the upper diodes operating in boost mode. The negative side of the battery is connected to the negative rail. The positive side of the battery is connected through two parallel chokes (L2A/B, L5A/B and L8A/B) to the midpoint of each half bridge. The lower IGBT of each half bridge is turned on storing energy in the respective battery chokes. When the lower IGBTs are turned off the stored energy in the chokes is dumped through the upper half bridge diodes into the positive rail. This 216VDC nominal battery voltage is then boosted to 380VDC rail-to-rail. The L1 rectifier balances the rail voltages to +/-195VDC. Each power module gate drive is staggered 120 degrees to draw an effective 60khz ripple from the battery and its filter cap. © 2006 - Eaton Corporation
4-33
Functional Descriptions
4.6.3.2
9355 20 – 30 kVA
Battery Charger
The 20khz battery charger circuit consists of remaining parts of three IGBT half bridge converters located in the middle (V1) IGBT module on the main heatsink of each power module. In this case the upper IGBTs and the lower diode operate in buck mode. The upper IGBT of each half bridge is turned on storing energy in the battery chokes while charging the battery. Then, when the upper IGBTs are turned off, the stored energy in the chokes are dumped through the lower half bridge diodes into the battery as well. This then bucks the ~390VDC rail-to-rail voltage online down to the battery voltage required for floating the battery, charging it in the process. The power module gate drives are also staggered 120 degrees to supply an effective 60khz ripple to the battery and its filter cap. This charger is capable of quickly charging many parallel battery strings and is only limited by maximum input current.
4.6.4
Inverter
The 3 phase 20khz inverter circuit consists of an IGBT half bridge converter located in the (V2) IGBT module on the main heatsink furthest from the busbars in each power module (Power Modules L1, L2, L3). Its sine wave PWM bucks the +/-195VDC rail down in order to create a 120VAC nominal sine wave output voltage wrt neutral. The half bridge midpoints are connected through parallel inverter chokes (L3A/B, L6A/B, L9A/B), through fuses (F1-F3), and the inverter contactor located on the I/O board assembly, out to the load.
4.6.5
IGBT Gate Drives
The above converter gate drive circuits are located on this board. The gate waveforms are +17V/-8V, 20khz PWM signals. These signals are derived from the control board (see connector table X11) and feed optically isolated drivers to each individual gate: •
(V4, V22 for each rectifier),
•
(V44, V66 for each inverter),
•
(V41 for each battery boost),
•
and (V14 for each charger).
With signals from the DSP, Logic IC-U3 selects whether it is in charger or boost mode.
4.6.5.1
IGBT Gate Drives Power Supplies
There are three independently fused-isolated-forward converter supplies for the above gate drives located on this board. They get their clock signal from PWRCLK0. The supplies get their power from +12V and put out +18V/-9V to the above gate driver ICs.
4-34
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
The battery boost/charger gate supply consists of : •
FETs V31,
•
XFMR T1,
•
and fuse F1.
The inverter gate supply consists of: •
FETs V121,
•
XFMR T11,
•
and fuse F2.
The rectifier gate supply consists of: •
FETs V18,
•
XFMR T12,
•
and fuse F3.
U1 provides a POWMOD_GOOD signal if all the fuses are ok.
4.6.5.2
IGBT Module Thermal Sensor
The thermal sensor of the central IGBT module on each heatsink is the only one that is being monitored by the DSP. If the temperature gets too high, the IGBTs are turned off and the unit is put on bypass.
4.7 Advanced Battery Management 4.7.1
Introduction
The purpose of this section is to describe common (platform) ABM operation with common terminology. For details about Power Share, refer to paragraph 1.2.3.
4.7.2
Purpose
The purpose of ABM is to extend the life of valve regulated, absorbed electrolyte lead-acid (VRLA) batteries employed in standby service of an Uninterruptible Power Supply (UPS).
© 2006 - Eaton Corporation
4-35
Functional Descriptions
9355 20 – 30 kVA
Studies on the “end of life” mechanisms of batteries in stand-by service reveal that the cause of battery failure is positive grid corrosion due to constant float charging. A key feature of ABM is that the batteries be held at rest rather than on float for most of their service life. This is accomplished by giving them a periodic freshening charge and allowing them to rest. The length of time for the freshening and the timing of the initiating event can mitigate the benefit of rest. Care must be taken in limiting the initiating events for freshening so that the excess charging does not occur.
4.7.3
General Terms
battery rest – a battery state where it is neither charging nor discharging. This is done by disconnecting the battery from its charger. charge mode - begins a charging cycle; the battery voltage is being recharged after discharging, after an extended inactive period, and when open cell voltage decreases below batOpChrgV in rest mode. The mode ends when the battery voltage reaches batChargeV, or if the mode has lasted batChargeTMax time. charging cycle - consists of charge, float and rest modes. Battery voltage is charged in charge mode, then the voltage is kept steady in float mode, and finally batteries are inactive. continuous-float charging - batteries are held at constant voltage, batConstFloatV, instead of using a charging cycle scheme: user selectable. float charging - during ABM cycling: charging at a higher voltage level than in continuous-float charging; used to bring all cells in a battery string to their full charge state. This is done for a limited duration. float mode - after charge mode the battery voltage is kept constant at batEqualizeV during (batFloatTExt + batFloatT) time OCV - open cell voltage rest mode - batteries are inactive after float mode, without discharging nor charging. VPC - volts per cell
4.7.3.1
Values and Limits
batChargeT - charge time: how long the charge mode lasted. batChargeTMax – maximum charge time—default is 100 hours; the time-out for charge mode after which the float mode is started, even if the battery voltage has not yet reached batChargeV level. batChargeV - charge voltage—default 2.335VPC / 25ºC; the level where charge mode changes to float mode. batChrgI - charging current in charge mode. batChrgRefV - charger voltage reference in charge mode—default 2.385VPC / 25ºC. 4-36
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
batConstFloatV - continuous-float voltage—default 2.30VPC / 25ºC: used to constantly charge batteries when ABM charging cycles are disabled by the user. batDischT - cumulative discharge time—calculated internally by the UPS. batEqualizeV - ABM cycling float mode voltage—default 2.30VPC / 25ºC. batFloatT - ABM cycling float time—default 48 hours. batFloatTExt - ABM cycling float time extension: batFloatTExt = 1.5 y batChargeT. batMaxRestT - maximum rest mode time—default is 28 days: duration of rest mode, if neither discharging nor batOpChrgV have initiated a new charging cycle. batMinDischT - minimum discharge time—default 20 seconds: limit for cumulative discharge times after charge mode to initiate a new charging cycle. batOpChrgV - opportunity charge voltage—default 2.10VPC; if battery voltage decreases below this limit in rest mode, a new charging cycle is initiated immediately. batRestFailT - battery OCV failure time—default 10 days in rest mode. batSuppTestT - battery support test time moment—default 24 hours from the beginning of float mode. batSuppTestV - low voltage limit for battery support test—default 1.75VPC.
4.7.3.2
Discharging
XCP Battery data block reports ABM status: discharging. Discharging of batteries interrupts any charging mode. Cumulative discharging time is being calculated in batDischT. If after a discharge period, the value of batDischT exceeds batMinDischT, then a new charging cycle is initiated; otherwise the previous charging mode is continued.
© 2006 - Eaton Corporation
4-37
Functional Descriptions
4.7.4
9355 20 – 30 kVA
Charging Cycles Charge Mode
Rest Mode
ABM Float Mode Battery Test 1 8% of expected runtime (varies based on batteries installed)
batChrgRefV 2.39V batChargeV 2.34V batEqualizeV 2.30V batConstFloatV 2. 2.30V
Battery Test 2 30 seconds initial commissioning test; 50 seconds thereafter.
batOpChrgV 2.10V <10days batRestFailT batStartChrgV 2.00V batTestMinV 1.90V batDCUVLogicPwrV 1.80V batDCUV 1.75V
24Hrs batSupTestT
batAbsDCUV 1.56V
100Hrs max
48Hrs +
28 days
batFloatT + batFloatTExt batChargeT batMaxRestT batChrgRefV 2.39V Shoot for target when starting charge mode. BTR = Battery Time Remaining batChargeV 2.34V Stop at voltage to begin ABM float charge. ABM Float charge level. batEqualizeV 2.30V batConstFloatV 2.30V ABM is DISABLED - Constant Float charge level. batOpChrgV 2.10V Starts charger if volt level is reached in <10days of rest mode. batOCV 2.07V For BTR, only used prior to a commissioning test. batStartChrgV 2.00V For BTR, to determine the state of charge on battery. batTestMinV 1.83V If reached during battery test - cancels the test. batDCUVLogicPwrV 1.80V ACTIVE only after load loss when on battery, shuts logic power off & opens battery breaker. batDCUV 1.75V DCUV level during battery mode, ”low battery shutdown alarm, logic power on only, starts 2 min. timer. batAbsDCUV 1.67V Absolute DCUV if reached prior to end of 2 min. timer.
Figure 26.
4.7.4.1
Typical Battery Charging Cycle
Charge Mode
XCP Battery data block reports ABM status: charging. When a battery is being charged, it is charged at the batChrgI constant current rate until it reaches a set voltage (batChargeV). The charging cycle is then changed to float mode. While charging the battery voltage, the charger voltage reference is set to batChrgRefV, which prevents excessive battery voltage in the event of faulty battery voltage measurement. The charge mode duration is measured and stored in UPS internal variable batChargeT. This data is used to determine the value of batFloatTExt.
4-38
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.7.4.2
Float Mode
XCP Battery data block reports ABM status: floating. At initialization of float mode the value for batFloatTExt is calculated: •
batFloatTExt = 1.5 × batChargeT
The battery voltage is kept at constant voltage batEqualizeV for time (batFloatTExt + batFloatT). Automatic Battery Support test (batSuppTestV) is done 24 hours after float mode begins.
4.7.4.3
Rest Mode
XCP Battery data block reports ABM status: resting. The battery is effectively disconnected from the UPS. The rest mode lasts until: •
time defined by batMaxRestT has expired.
•
the value of batDischT exceeds batMinDischT.
•
the battery voltage has dropped below level batOpChrgV.
4.7.5
Temperature Compensation
4.7.5.1
Introduction
Battery temperature variation is compensated for by modifying battery-charging voltage. In ABM charge and float modes, and when ABM charging cycles are disabled, the charger voltage reference is adjusted according to the highest battery temperature measurement. The adjusted values are: •
BattChargeV—the level where charge mode changes to float mode.
•
BattEqualizeV—ABM cycling float mode voltage.
•
BattConstFloatV—used ABM charging cycles are disabled by user setting.
BattChrgRefV is adjusted. This is the voltage reference value for the charger while in charge mode. If an ABM charging scheme is working properly this reference limit is never reached, but has changed to float mode at BattChargeV. The values are adjusted in temperature ranges from 0ºC to 50ºC. Outside of these limits, the values stay the same.
© 2006 - Eaton Corporation
4-39
Functional Descriptions
4.7.5.2
9355 20 – 30 kVA
Algorithm
The compensation temperature range is from 0ºC to 50ºC, the voltage per cell is decreased 3 mV for each ºC. The EEPROM values mean the voltage levels at 25ºC. The charger values uses the following algorithm:
value (T ) = eeprom _ value − 3mV × (T − 25°C ) T = battery temperature Under 0ºC, value (0ºC) is used. Above 50ºC, value (50ºC) is used.
NOTICE IEEE optimum temperature for battery life is 25ºC (77ºF). Example Using default values for the settings, the voltage values at some temperatures are: Charging Voltage – Volts Per Cell Parameter
ºC
10ºC
25ºC
40ºC
50ºC
BattEqualizeV
2.380
2.350
2.305
2.260
2.230
BattChargeV
2.410
2.380
2.335
2.290
2.260
BattChrgRefV
2.460
2.430
2.385
2.340
2.310
BattConstFloatV
2.345
2.315
2.270
2.225
2.195
•
BattChargeV = BattEqualizeV + 0.03 VPC
•
BattChrgRefV = BattEqualizeV + 0.08 VPC
4.7.5.3
Disabled or Impossible Compensation
The temperature compensation can be disabled using a user setting. In this case, the EEPROM values (compensation values at 25ºC) are used directly. Also, when the battery temperature measurement is not available, 25ºC is assumed.
4.7.6
Forcing on Rest Mode
There is an internal flag, ForceRestMode, which disables battery charging. For example, one of the building inputs in the unit can be directed to this flag. When active, batteries are discharged when needed, but otherwise the flag forces the ABM rest mode. The original mode is resumed when the ForceRestMode flag becomes inactive. While forced on rest mode, battery failure testing/monitoring is not done. While the ForceRestMode flag is active, discharging time (batDischT) is monitored normally. If it exceeds batMinDischT, then a new charging cycle is initiated when the ForceRestMode flag becomes inactive. 4-40
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
This flag also works when the ABM charging cycles are disabled by the user. When active, the charging is disabled (rest mode is forced). When the flag becomes inactive, continuous-float charging is resumed.
4.7.7
User Disabling of ABM Charging Cycles
The user has the option of disabling the charging cycles and to select a continuous charging scheme. Cycling enabled is the factory default setting. When batteries are not discharging, the charger functions to keep batteries at a constant voltage, defined by batConstFloatV. Although batteries are charged constantly, the UPS keeps the normal ABM timer running. The operation is very similar to normal ABM cycling: 1.
Charge mode begins when - the cumulative discharging time (batDischT) exceeds batMinDischT OR - when time batFloatTExt + batFloatT + batMaxRestT has gone since the last charge mode.
2.
Charge mode changes to float mode at batChargeV.
3.
The external battery charger is controlled just as with normal ABM cycling: during charge mode and during float time extension, batFloatTExt.
4.
Battery support tests are done normally, at a point defined by batSuppTestT, just as though cycling was enabled.
5.
While in float mode, the battery voltage is kept at constant voltage, defined by batEqualizeV.
6.
Rest mode is never entered, but float mode is continued over the batMaxRestT time at the batConstFloatV, except when ABM forced rest mode is initiated.
The differences to ABM cycling are: •
Float voltage is lower, batConstFloatV.
•
There is no rest mode; float mode continues until cumulative discharging time (batDischT) exceeds batMinDischT, or batMaxRestT time has gone.
•
Battery testing/monitoring is reduced: open cell voltage monitoring test is not done.
•
The charge failure test measures charge mode time. This test is done normally, the only difference being a lower float mode voltage level.
•
As the ABM cycling timing is internally running, the battery support test is done normally, just as when cycling was enabled.
•
The ABM status is reported normally, charge or float. (including rest mode when in forced rest mode). © 2006 - Eaton Corporation
4-41
Functional Descriptions
•
4.7.8
9355 20 – 30 kVA
The external battery charger is controlled just as with normal ABM cycling: during charge mode and during float time extension, batFloatTExt.
Battery Failure Testing
Several battery tests are performed to try and determine the overall usability of the attached batteries, and to try and detect when the attached batteries will no longer provide adequate discharge time. Specific tests are performed to detect failed batteries and to detect battery end-of-life. The tests that are covered in this section are: •
Battery test / Commissioning test (user initiated)
•
Detection of failed (shorted) cell(s) caused by failure to reach float voltage
•
Detection of failed (shorted) cell(s) caused by a rapid drop of open cell voltage in rest mode
•
Detection of loss of capacity caused by failing to maintain cell voltage under load.
4.7.8.1
Battery test / Commissioning test
The battery test and battery commissioning test are almost identical, but the commissioning test is performed: •
the first time the unit batteries are initially charged for 24 hours,
•
whenever the batteries are replaced,
•
and whenever batteries are added or removed.
The results of this test are stored in EEPROM and are the baseline for subsequent battery tests. The test consists of taking data when the UPS is at 2 levels, typically at 25% load and at 100% load. This topology is accomplished by running the rectifier and battery converter at the same time (Power Share mode). For more details on Power Share, refer to paragraph 1.2.3. The Power Share control sets the rectifier sine reference magnitude to regulate battery power at the desired level. The rectifier is running in a constant current mode while the battery converter operates normally to regulate the rails. Experiments have shown that running the second part of the test at or near full load yields the best results. If full load is not available at the output of the UPS, full load on the battery can still be achieved by allowing the rectifier to backfeed power to the utility. Back-feeding the rectifier is the preferred method of running the test, but the user can disable back-feeding from the front panel. If the user disables back-feeding, the second part of the test will be run with the available load, which must be at least 50% of the UPS rating. When the test starts, battery power is set to 25% of load. Unfortunately, when the load is first put on the battery, the voltage will drop, and then recover (termed “crack of the whip”). In order to get past this phenomenon, the test runs for 8% of the expected runtime at load level 1 before taking the measurement. After test 1, 4-42
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
the power is set to test level 2 and run for 30 seconds on the initial commissioning test, and for 50 seconds thereafter. The battery voltage and power level are recorded. When the test executes, it will be transparent to the user. Unless the battery test detects a bad battery, there will be no beeping alarms and the front panel will not change state because the test is being performed. The XCP status will not change to “On Battery”. The battery test section of the LCD control menu will give an indication of test progress.
4.7.8.2
Battery Impedance / Open Cell Voltage Measurement
The battery impedance and open cell voltage will be determined by performing the following steps: Run test level 1 at 25% of the full UPS watt rating on the battery. The test duration is 8% of the expected runtime at this power level. The battery voltage and power are recorded at the end of test level 1. Current is also recorded for XCP battery data block only and does not impact runtime calculations. Run test level 2 at the full available load for 50 seconds. After 50 seconds, battery voltage and power are recorded. Current is also recorded for XCP battery data block only and does not impact runtime calculations. Calculate Open Cell Voltage: Open Cell Voltage = ((Test 1 Voltage × Test 2 Power ) − (Test 2 Voltage × Test 1 Power )) ÷ (Test 2 Power − Test 1 Power )
If this is a commissioning test, this voltage is stored as is; otherwise it is filtered with previous test results. Calculate Battery Resistance: Battery impedance = (Open Cell Voltage − Test 1 Voltage ) ÷ Test 1 Power
If this is a commissioning test, then calculated battery impedance is stored as both commissioning impedance and test impedance, otherwise: ⎛3 ⎞ Battery test impedance = (3 × Battery test impedance + calculated battery impedance ) ÷ 4 ⎜ filter ⎟ ⎝4 ⎠
If this is a commissioning test the battery health is set to 1, otherwise: Battery health = Commissioning impedance ÷ Battery test impedance
4.7.8.3
Cell Voltage Failure Under Load
When the unit drops on battery, the battery cell voltage is monitored during the first 25% of the discharge as determined by the battery runtime prediction. If the battery cell voltage drops below a certain level during the first 25% of discharge, “Battery Test Failed” is set. Failure of this test represents a loss of battery capacity and is not considered a potentially hazardous condition. This alarm is not stored in EEPROM and charging is not disabled as a result of test failure. This alarm is cleared when power is cycled, the batteries are replaced, or the battery test successfully completes. This test is active during the battery test/commissioning test. © 2006 - Eaton Corporation
4-43
Functional Descriptions
9355 20 – 30 kVA
The failure limit for this test is 1.833V/cell if expected runtime is greater than 15 minutes, or 1.81V/cell if expected runtime is less than or equal to 15 minutes.
4.8 Battery Lifetime 4.8.1
Introduction
The 9355 battery lifetime algorithm is executed every second. It accounts for run-time, chronological (wall clock) time, battery temperature, and battery discharges when calculating the expected battery lifetime available.
4.8.1.1
User Interface
Battery lifetime, in hours, is maintained in nonvolatile memory and is displayed as a percentage of nominal.
4.8.1.2
4.8.2
User Selectable Values 1.
Battery Lifetime can be reset to whatever value the user wants, as long as it is equal to or less than the nominal battery lifetime. The default value is 43830 hours or five years.
2.
Nominal Battery Lifetime can be set by the user to any value less than 4,294,967,296 (2^32) hours. The default value is 43830 hours or 5 years.
3.
Battery Discharge Coefficient is the amount of time that is subtracted from Battery Lifetime every time the unit runs from battery. The default value is one hour.
Operational Sequence
When the PW9355 first powers up, 2 hours are subtracted from the battery life as UPS down time is not monitored. If it is known that the unit has been powered down for longer than 2 hours, it is recommended that the Battery Lifetime be updated accordingly. Based on the calculated Battery Lifetime, the percentage of remaining battery lifetime is calculated for display on the battery meter screen. The battery lifetime routine is called every second. After the initial call of the battery lifetime routine, only battery discharge and run-time effects are calculated, until a temperature sensor for the batteries is available.
4.8.3
Battery Discharge
If the unit goes to battery, the amount of time specified by the Battery Discharge Coefficient is subtracted from the Battery Lifetime. This value can be changed with the XCP Service Tool. If the battery discharge is short (less than 1 second), the discharge may occur between a call to the battery lifetime routine, in which case the routine may not detect the discharge and the Battery Lifetime will not be updated.
4-44
© 2006 - Eaton Corporation
9355 20 – 30 kVA
4.8.4
Functional Descriptions
Run-Time and Temperature
A run-time and temperature algorithm currently does not compensate for the temperature degradation of the battery, due to a lack of battery temperature sensors. Once an hour, an hour is subtracted from the battery lifetime. This number is stored to nonvolatile memory every 3 hours. The counter does not run when the unit is off, since there is no real time clock. The counter algorithm does not account for the depth of battery discharge.
4.9 Battery Test 4.9.1
Introduction
This section describes the operation of ABM and battery test in PW9355.
4.9.1.1
Battery Test Run Time
The run time calculation uses voltage load and battery information to give a prediction of battery run time.
4.9.1.2
Battery Test Operation
Battery testing occurs periodically and each time that the unit performs an ABM charging cycle. The test starts at a fixed time after ABM begins. The time relative to the start of the ABM float charge cycle is programmable, but it is typically set to half of the float time.
4.9.2
Battery Test 1
The Battery Test begins with test 1. During this test, the battery is discharged at the specified load for a specified duration. At the end of the test, the voltage and power level are recorded. If the required discharge load is less than the output load, the rectifier will backfeed the line with the excess power. The test will abort if the utility is lost, if battery voltage falls below a preset level, or if a charger malfunction occurs.
4.9.3
Battery Test 2
The Battery Test ends with test 2. During this test, the battery is discharged at a specified load for a specified duration. At the end of the test, the voltage and power level are recorded. If the required discharge load is less than the output load, the rectifier will backfeed the line with the excess power. The test will abort if the utility is lost, if battery voltage falls below a preset level, or if a charger malfunction occurs.
4.9.3.1
Battery Test Levels and Times
Test 1 is typically set for 25% of load for an 8% discharge of the battery (6 minutes). Test 2 is set for 100% of load for 30 seconds.
© 2006 - Eaton Corporation
4-45
Functional Descriptions
4.9.4
9355 20 – 30 kVA
Battery Test Calculations
The following parameters are recorded during the battery test. •
Date and Time
•
Status
•
Test 1 - End voltage
•
Test 1 - Power level
•
Test 2 - End voltage
•
Test 2 - Power level
From the above data, the Battery Open Circuit voltage, Battery resistance and Battery health are calculated. The data is then used to alter the battery time remaining algorithm. Table 13. Battery Setup Data Name
Effects
Battery setup
Charger ABM
Num cells
String Calcs
Number of cells in a single battery string
Num Strings
String Calcs
Number of battery Strings
Battery DCOV
Alarm
Battery Equalize
Charger ABM
The level that is used to charge the batteries for the Battery Float Time, typically 48 hours
Battery Charge
Charger ABM
The target voltage level at the beginning of an ABM charge cycle. This voltage is higher than Battery Equalize.
Battery is Charged Level
Description Setup Bitword for the battery
Battery DCOV level
Charger ABM Lower than Battery Charge, the level that ends regulation to Battery Charge.
Battery Float Level
Charger Float
Level to regulate to, if ABM is disabled.
Battery Not Charged
ABM ALARM
If the battery voltage falls below this level within the rest fail time, a “Check Battery” alarm is annunciated, otherwise an ABM cycle is started.
Battery DCUV
ABM BTR ALARM OPER.
This is the level that triggers the low Battery shutdown alarm. The system will shutdown in the programmed Battery DCUV Time
BATTERY DCUV Shutdown Time
BTR OPER
Time in seconds before shutdown if the Battery voltage falls below Battery DCUV.
Absolute Battery DCUV
OPER
If the Battery Voltage falls below this level, the system is shutdown within a few seconds.
Battery DCUV for Logic Power Off
OPER
The power supply is disabled if the battery is sully the power and the battery voltage falls below this
4-46
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 13. Battery Setup Data Name
Effects
Description level.
Battery temperature compensation
Nothing
Place holder for future applications
Battery Charge Current Limit
Charger
Level at which the battery charge current is limited.
Battery Charge Current Limit On Generator
Nothing
Place holder for future applications
Support Test Time
Batt Test
Hours, When ABM enters float, the Battery test runs after float charging the Battery for this time.
Battery Charge Time Max
ABM
Hours, ABM must reach equalize voltage before this time or a “Check Battery” alarm is annunciated
Battery Float Time
ABM
Hours, ABM float charges the battery for this time during each ABM Charge cycle.
Battery rest fail Time
ABM
Hours, If the battery voltage falls below a preset level before this time, a “Check Battery” alarm is annunciated.
Max Rest Time
ABM
Hours, the time before an ABM charge cycle is initiated.
Maximum Battery Discharge Time before Charge
ABM
Seconds, if the unit drops on battery for greater than this time an ABM charge cycle is initiated.
Battery Run Time at Battery Watts
BTR
Tenth minutes, Run Time at Battery Watts, typically full load run time
Battery Watts
BTR
Watts/cell, Battery watts at Battery run Time
Battery open Cell Voltage
Batt test BTR
Volts/cell, used only until commission test occurs
Battery Start charge
BTR
Volts/cell, Used by BTR to determine the state of charge on the battery while resting or charging.
Battery resistance
BTR
Q15, milliohms, used by BTR until the commissioning test runs
Battery Test 1 voltage
BTR
Volts/cell, Used by BTR until the commissioning test runs.
Lin Pred
BTR
Not used
Lin PUV
BTR
Not Used
On Battery delay
ALARM
Battery Current Meter zero
Meter
Battery Discharge Coef.
Battery Lifetime
Number of hours to subtract off of battery life when we drop on battery
Expected Battery Lifetime
Battery Lifetime
Number of hours before replacement of battery is recommended.
Battery Lifetime left
Battery Life Time
Battery Test 1 Power
Batt Test BTR
Delay time before queuing “ON Battery” Number of tenth amps below which the battery current meter is zeroed
Number of hours the battery currently has left before replacement is needed Tenth KW, Total KW for Battery Test 1
© 2006 - Eaton Corporation
4-47
Functional Descriptions
9355 20 – 30 kVA
Table 13. Battery Setup Data Name
Effects
Description
Battery test 1 Time
Batt test
Seconds, Time Battery test 1 runs at Battery Test 1 Power
Battery Test 2 Power
Batt Test
Tenth KW, Total KW for Battery Test 2
Battery test 2 Time
Batt Test
Seconds, Time Battery test 2 runs at Battery Test 2 Power
Battery Test Min Voltage
Batt Test
If the battery voltage falls below this level during battery test, the test is aborted and a “Check Battery” alarm is annunciated.
4.9.4.1
User Interface to Battery Test Information
4.9.4.2
Battery Test Queue Printing
The battery test queue can be viewed in TERMINAL mode by entering “ESC B” at any serial port. The commissioning test and the contents of the battery test log are printed. The information provided by the printout is shown below: •
Battery Test Number
•
Date and Time of the battery test
•
If the test failed, the reason Battery Test Status
•
Test 1 results, voltage per cell and power
•
Test 2 results, voltage per cell and power
•
Calculated open circuit voltage
•
Calculated Battery Resistance in Milliohms V/P not V^2/P
•
Calculated Battery Health (percentage health)
4.9.4.3
Battery Test Information via XCP
The Battery Test information is transmitted in the XCP Battery Test data block.
4-48
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.10 I/O BOARD (PCB) Reference Documents: PW9355 1024055 I/O Board Schematic, see the Prints chapter at the end of this document. For detailed descriptions of board components, refer the Chapter 8, Removal and Replacement.
Figure 27.
4.10.1
PW 9355 I/O Board
Overview
The IO Board has many functions within the Electronics module. It provides input and output filtering (including EMI) for the system. AC and Battery Voltage sensing is provided in many locations. Current sensing for the inverter, rectifier, and battery converter and load are contained here - along with level shifting for the control board. Fusing is provided for the inverter path only. In this topology the inverter is connected to the output by a contactor - which is contained on the IO Assembly. The IO Board feeds input mains to the Power Board and provides battery start capability. Single or dual feed mains input with a separate Rectifier contactor is contained here. Also, the balancer and battery relays are contained on this board. Battery start circuitry and AC Fan power to 3 of the fans is provided here. © 2006 - Eaton Corporation
4-49
Functional Descriptions
9355 20 – 30 kVA
It also contains an Auxiliary Power supply that is derived from mains (or battery) during startup and then runs from the positive rail. This A-aux supply powers the relays, control board, and the X-Slot, and it powers the IGBT gate drives and alarms circuitry. The control board interface is located on this board, a battery circuit breaker trip circuit/sensor, a manual bypass switch position sensor, and an input output circuit breaker trip. Finally it contains the rail cap pre-charge circuitry.
4.10.2
I/O Connector Descriptions
4.10.2.1 Control Board Interconnect Description Table 14. Control Board Interconnect Description Pin
Signal
Description
X8-1
Logic ground
Ground
X8-2
XSLOT2_K4
X8-3
XSLOT2_K3
X8-4
XSLOT2_K2
X8-5
XSLOT2_K1
X8-6
XSLOT1_K4
X8-7
XSLOT1_K3
X8-8
XSLOT1_K2
X8-9
XSLOT1_K1
X8-10
Logic ground
X8-11
XSLOT2_TX
X8-12
XSLOT1_RX
X8-13
XSLOT2_RX
X8-14
XSLOT1_TX
X8-15
Logic ground
X8-16
CAN_HI
X8-17
CAN_LO
X8-18
ID
X8-19
Not Used
X8-20
Logic ground
X8-21
XSLOT1_DTR
X8-22
XSLOT2_DTR
X8-23
PAR_RED1
X8-24
PAR_RED2
X8-25
POWMOD_GOOD
Gate drive fuses OK
X8-26
Logic ground
Ground
4-50
Ground
Ground
connected to logic ground Ground
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 14. Control Board Interconnect Description Pin
Signal
Description
X8-27
IO1
Thermostat
X8-28
Not Used
DC Fan (unused)
X8-29
+12_2ON
X8-30
Not Used
DC Fan (unused)
X8-31
Not Used
DC Fan (unused)
X8-32
Logic ground
Ground
X8-33
Not Used
DC Fan (unused)
X8-34
EPO_ ENABLE
X8-35
V114 gate
X8-36
Not Used
X8-37
Not Used
X8-38
Not Used
X8-39
IO_GOOD
X8-40
Logic ground
X8-41
SER_RX
X8-42
SER_TX
X8-43
ALARM_RELAY
X8-44
BLD_ALARM2
X8-45
BLD_ALARM1
X8-46
EPO_ ENABLE
X8-47
Logic ground
X8-48
Not Used
X8-49
Not Used
X8-50
Not Used
X8-51
Not Used
X8-52
Not Used
X8-53
Not Used
X8-54
DALLAS_IN
X8-55
DALLAS_OUT
X8-56
Logic ground
Ground
X8-57
Logic ground
Ground
X8-58
+5V
X8-59
Logic ground
Ground
X8-60
Logic ground
Ground
X8-61
+5V
Reserved for display
Enables IGBT gate drive (unused) Ground
Ground
© 2006 - Eaton Corporation
4-51
Functional Descriptions
9355 20 – 30 kVA
Table 14. Control Board Interconnect Description Pin
Signal
X8-62
+12_ON
X8-63
DC_CHARGE
X8-64
Not Used
X8-65
Not Used
X8-66
Logic ground
X8-67
+12V /control
X8-68
Logic ground
Ground
X8-69
+24V
AAUX
X8-70
+12V/control
X8-71
Logic ground
Ground
X8-72
+24V
AAUX
X8-73
Logic ground
Ground
X8-74
Logic ground
Ground
X8-75
GATE13
Battery L1 gate
X8-76
GATE14
Battery Boost/Charger Mode Select
X8-77
GATE5
Upper Rectifier L3 gate
X8-78
GATE6
Lower Rectifier L3 gate
X8-79
Logic ground
Ground
X8-80
GATE3
Upper Rectifier L2 gate
X8-81
GATE4
Lower Rectifier L2 gate
X8-82
GATE1
Upper Rectifier L1 gate
X8-83
GATE2
Lower Rectifier L1 gate
X8-84
Logic ground
Ground
X8-85
GATE15
Battery L3 gate
X8-86
GATE16
Battery L2 gate
X8-87
GATE11
Upper Inverter L3 gate
X8-88
GATE12
Lower Inverter L3 gate
X8-89
Logic ground
Ground
X8-90
GATE9
Upper Inverter L2 gate
X8-91
GATE10
Lower Inverter L2 gate
X8-92
GATE7
Upper Inverter L1 gate
X8-93
GATE8
Lower Inverter L1 gate
X8-94
POWERCLOCK0
unused
X8-95
POWERCLOCK1
Gate supply, EPO supply, BLD ALMS supply , and rail precharge clock
X8-96
Logic ground
Ground
4-52
Description
Ground
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 14. Control Board Interconnect Description Pin
Signal
Description
X9-1
Logic ground
Ground
X9-2
CHASSIS_VOLT
Chassis Voltage measurement referenced to Neutral
X9-3
OUTP_DCVOLT_L1
Inverter L1 DC sense
X9-4
DCN1
Inverter L1 DC sense
X9-5
Logic ground
Ground
X9-6
DCN2
Inverter L2 DC sense
X9-7
OUTP_DCVOLT_L2
Inverter L2 DC sense
X9-8
DCN3
Inverter L3 DC sense
X9-9
OUTP_DCVOLT_L3
Inverter L3 DC sense
X9-10
Logic ground
Ground
X9-11
RAIL_VOLTS_PLUS
Rail sense
X9-12
RAIL_VOLTS_MINUS
Rail sense
X9-13
BATT_VOLT1
Measures L1 input cap voltage
X9-14
BATT_VOLT2
Battery + Voltage (before Battery relay) measurement referenced to Neutral
X9-15
Logic ground
Ground
X9-16
BATT_VOLT1_BACKUP
Negative battery sense
X9-17
BATT_VOLT2_BACKUP
Positive battery sense after the chokes on L1 power module
X9-18
Unused
X9-19
+5V_REF
Unused
X9-20
Logic ground
Ground
X9-21
N1
Neutral reference for rail (and battery) voltage sense
X9-22
N1_BACKUP
Neutral reference for rail (and battery) voltage sense
X9-23
Logic ground
Ground
X9-24
UTI_CURR_L1
Line 1 Rectifier Choke current measurement
X9-25
UTI_CURR_L2
Line 2 Rectifier Choke current measurement
X9-26
UTI_CURR_L3
Line 3 Rectifier Choke current measurement
X9-27
Logic ground
Ground
X9-28
OUT_CURR_L1
Line 1 Output Current measurement
X9-29
OUT_CURR_L2
Line 2 Output Current measurement
X9-30
OUT_CURR_L3
Line 3 Output Current measurement
X9-31
Logic ground
Ground
X9-32
INV_CURR_L1
Line 1 Inverter Choke current measurement
X9-33
INV_CURR_L2
Line 2 Inverter Choke current measurement
X9-34
INV_CURR_L3
Line 3 Inverter Choke current measurement
© 2006 - Eaton Corporation
4-53
Functional Descriptions
9355 20 – 30 kVA
Table 14. Control Board Interconnect Description Pin
Signal
Description
X9-35
Logic ground
Ground
X9-36
BATT_CURR1
Battery Choke current measurement
X9-37
CASE_TEMPERATURE
Ambient Temp measurement
X9-38
Logic ground
Ground
X9-39
TEMPERATURE1
Battery Boost IGBT module temperature sensor L1 power module
X9-40
TEMPERATURE2
Battery Boost IGBT module temperature sensor L2 power module
X9-41
TEMPERATURE3
Battery Boost IGBT module temperature sensor L3 power module
X9-42
Logic ground
Ground
X9-43
UTIL_VOLT_L1N
Line 1 Utility Voltage Measurement L-N before contactor
X9-44
UTIL_VOLT_L2N
Line 2 Utility Voltage Measurement L-N before contactor
X9-45
UTIL_VOLT_L3N
Line 3 Utility Voltage Measurement L-N before contactor
X9-46
Logic ground
Ground
X9-47
INV_VOLT_L1N
Line 1 Inverter Voltage Measurement L-N
X9-48
INV_VOLT_L2N
Line 2 Inverter Voltage Measurement L-N
X9-49
INV_VOLT_L3N
Line 3 Inverter Voltage Measurement L-N
X9-50
Logic ground
Ground
X9-51
BUPASS_VOLT_L1N
Line 1 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
X9-52
BUPASS_VOLT_L2N
Line 2 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
X9-53
BUPASS_VOLT_L3N
Line 3 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
X9-54
Logic ground
Ground
X9-55
OUTP_VOLT_L1N
Line 1 Output Voltage Measurement L-N
X9-56
OUTP_VOLT_L2N
Line 2 Output Voltage Measurement L-N
X9-57
OUTP_VOLT_L3N
Line 3 Output Voltage Measurement L-N
X9-58
Logic ground
Ground
X9-59
Logic ground
Ground
X9-60
SPI_SI
Signals to backup EPROM
X9-61
SPI_CS
Signals to backup EPROM
X9-62
SPI_SD
Signals to backup EPROM
X9-63
SPI_CLOCK
Signals to backup EPROM
X9-64
Logic ground
Ground
X9-65
ID0
Connected to logic ground
4-54
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 14. Control Board Interconnect Description Pin
Signal
Description
X9-66
ID1
NC
X9-67
ID2
Connected to logic ground
X9-68
ID3
Connected to logic ground
X9-69
INV_SCR/CONTACTOR
Enable signal for Inverter Contactor – active low
X9-70
Logic ground
Ground
X9-71
Not Used
X9-72
INVONLINE
Output signal used to control D1 state machine for Bypass
X9-73
MBS
MBS switch position
X9-74
REL_BAL
Balancer relay drive – active low
X9-75
BATT_CB_TRIP
BATT CB trip signal
X9-76
REL_L2-3
Redundant Input Rectifier Contactor Drive – active low
X9-77
Logic ground
Ground
X9-78
Not Used
X9-79
REL_L1
Input Rectifier Contactor Drive – active low
X9-80
BYP_RDY
Output from D1 used by control to determine state of D1
X9-81
BACK-FEED
Bypass Contactor Drive
X9-82
EPOCBTRIP
EPO CB Trip (if needed)
X9-83
B_UP_OK
Not used
X9-84
Logic ground
Ground
X9-85
BYP_AVAIL
Output signal from control board used to control D1 state machine
X9-86
BATT_CB_STATE
BATT CB switch state sense
X9-87
SPARE_IN1
Not used
X9-88
SPARE_IN2
Not used
X9-89
Logic ground
Ground
X9-90
Not Used
X9-91
RES_ON
Signal for turning on contactor cap reservoir
X9-92
Logic ground
Ground
X9-93
Not Used
X9-94
REL_BAT
X9-95
Not Used
X9-96
Logic ground
Battery Relay Drive – active low Ground
© 2006 - Eaton Corporation
4-55
Functional Descriptions
9355 20 – 30 kVA
Table 15. Interconnect Descriptions Reference Designator X50
4-56
Description To Battery CB Trip
X48, X49
Batt + from CB
X34, X51
Batt - from CB
X26
From Rect Contactor to L1 Rect input
X24
From Rect Contactor to L2 Rect input
X22
From Rect Contactor to L3 Rect input
X13
L3 input, also to rectifier contactor
X23
L2 input, also to rectifier contactor
X25
L1 input, also to rectifier contactor
X54
N input
X78
To Output CB Trip
X2
To Input CB Trip
X37
Inv L1 Out to Inv Contactor
X36
Inv L2 Out to Inv Contactor
X35
Inv L3 Out to Inv Contactor
X38
N output (unused)
X40
From Inv Contactor to L1 output
X41
From Inv Contactor to L2 output
X42
From Inv Contactor to L3 output
X3, X20
Neutral connection to Power Board Neutral Bursar
X34, X51
Battery Neg connection to Power Board Ned Rail Busbar
X30
Pos Rail connection to Power Board Pos Rail Busbar
X67
AC Fan connection (inverter L1-N)
X66
AC Fan connection (inverter L2-N)
X65
AC Fan connection (inverter L3-N)
X21
Inverter Contactor Control
X27
Rectifier Contactor Control
X17
Display jack
X44
AAUX 24V
X5
L1 Rectifier choke connection
X70
L1 Rectifier choke current sense connection
X10
L2 Rectifier choke connection
X69
L2 Rectifier choke current sense connection
X14
L3 Rectifier choke connection
X68
L3 Rectifier choke current sense connection © 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 15. Interconnect Descriptions Reference Designator
Description
X74
L1 Battery Choke current sense connection
X4
L1 Battery Choke connection
X75
L2 Battery Choke current sense connection
X29
L2 Battery Choke connection
X76
L3 Battery Choke current sense connection
X28
L3 Battery Choke connection
X19
L1 Inverter choke connection
X73
L1 Inverter choke current sense connection
X18
L2 Inverter choke connection
X72
L2 Inverter choke current sense connection
X15
L3 Inverter choke connection
X71
L3 Inverter choke current sense connection
X58, X59
Marine ground connection
X79
Battery start pushbutton connector
X43, X45, X46, X47, X52 X55, X56
Table 16. 4.10.3
Hipot/test connectors X-Slot connectors
X6, X7, X11 Connector Pinout
Pin
Signal
Description
1
Logic ground
2
PWRCLK1
3
Logic ground
4
TEMPERATURE1,2,3
5
SPARE
6
OUTP_DCVOLT_L1N,L2N,L3N
7
BATT_VOLTS2_BACKUP
8
THERMAL SWITCH
9
POWMOD_GOOD
10
Logic ground
11
GATE14
Battery Boost/Charger Mode Select
12
GATE13
Battery gate
13
GATE8, 10, 12
Lower Inverter L1, L2, L3 gate
14
GATE7, 9, 11
Upper Inverter L1, L2, L3 gate
15
GATE2, 4, 6
Lower Rectifier L1, L2, L3 gate
16
GATE1, 3, 5
Upper Rectifier L1, L2, L3 gate
Ground Gate Clock Ground IGBT module Temp sensor from power board Unused Inverter DC feedback Batt Choke hot end Heatsink Thermostat Closes on Temperature Gate drive fuses OK Ground
© 2006 - Eaton Corporation
4-57
Functional Descriptions
Table 16. 4.10.3
9355 20 – 30 kVA
X6, X7, X11 Connector Pinout
Pin
Signal
Description
17
Logic ground
18
+12V
19
Logic ground
20
+12V
Ground +12V for gate drive supply Ground +12V for gate drive supply
Table 17. X12 Connector Pinout
4-58
Pin
Signal
Description
1
Logic ground
2
BUPASS_VOLT_L1N
Line 1 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
3
BUPASS_VOLT_L2N
Line 2 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
4
BUPASS_VOLT_L3N
Line 3 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
5
Logic ground
6
AAUX
7
ALARM_RELAY
8
MBS
9
BAUX
10
Unused
11
SER_RX
12
SER_TX
13
Logic ground
14
EPO_ ENABLE
15
BLD_ALARM1
16
BLD_ALARM2
17
Logic ground
Ground
18
INVONLINE
Output signal used to control D1 state machine for Bypass
19
BYP_RDY
Output from D1 used by control to determine state of D1
20
BACK-FEED
Bypass Contactor Drive
21
Logic ground
Ground
22
B_UP_OK
23
BYP_AVAIL
24
IO_GOOD
Ground
Ground +24V supply on IO board
+24V supply on BYP board
Ground
Not used Output signal from control board used to control D1 state machine
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 17. X12 Connector Pinout Pin
Signal
Description
25
LED_OVERRIDE
Display
26
Logic ground
Ground
4.11 I / O Board Functional Sections 4.11.1
Auxiliary Power Supply
This circuit (N8, V62, T1) is an 80W-isolated flyback switching power supply. It receives input power from rectified 120VAC during an AC start or 216VDC nominal battery during a DC start. Once the Rails are charged it runs from nominal 195VDC positive rail. This input is then converted to 24VDC (AAUX). This 24V output supplies input power for the RS-232 supply and alarms on the bypass board. It is also powers the Battery and Balancer relays. It is used for operating the rectifier, inverter contactors, and momentarily to power the battery circuit breaker shunt trip from the cap reservoir. The Aux Power Supply is stepped down by two buck converters to 12VDC. The first buck converter circuit (N10) outputs (+12V) capable of ~3A, powers the rail precharge circuit, contactor relays, input/output CB trip relays, and IGBT gate drives on the Power Board. The second circuit (N12) output (+12V_2), capable of ~1A, only powers the two X-Slots. There is a linear voltage regulator (N1) that reduces it to (+12V) for use by the Control Board.
4.11.2
Rail Precharge
The Rail Precharge circuit (V70, V68, V69, T3, N9, L2) function is to precharge the positive rail capacitors located on the power boards during startup. It receives its input from rectified 120VAC during an AC start or from 216VDC nominal battery during a DC start. This constant current converter takes several seconds to charge all these caps to near input voltage. (T_ON) is the signal that is used to power this converter (N9). This circuit continues to precharge the positive rail until precharge of both rail caps are done (see next section).
4.11.3
Voltage Sensing
The IO Board provides Voltage Sense Resistors for most of the AC and DC voltage sense measurements (including chassis) done by the Control Board. There are also some additional sense resistors located on the power board and the bypass board. Voltage sense resistors are made up of two 1Meg ohm resistors in series for safety reasons. The measurements are differential measurements with respect to Neutral. Op Amps are referenced to signal +5V_REF created on the control board. Outputs of the Op Amps are divided down to a 1.5V reference to the DSP with an anti-aliasing filter. © 2006 - Eaton Corporation
4-59
Functional Descriptions
9355 20 – 30 kVA
4.12 Current Measurements and Hardware Current limits Inverter, Rectifier, and Battery Current Measurements are made on the IO board. The measurements are made by the LEM-LAS100 closed loop hall sensor. All measurements made are choke current measurements. There are two chokes in parallel in each phase of the Inverter and Rectifier, but only 1 choke is measured. The battery converter has 6 chokes in staggered parallel; however, only 3 chokes are measured, one from each power module. See paragraph 4.5.3 for respective choke connections. Table 18. Phase and Battery Chokes Sensor
Converter
Choke
Split
B1
Rectifier Line 1
L7A
2
B2
Rectifier Line 2
L4A
2
B3
Rectifier Line 3
L1A
2
B7
Inverter Line 1
L9A
2
B6
Inverter Line 2
L6A
2
B4
Inverter Line 3
L3A
2
B8
Battery
L2A L5A L8A
2
LEM sensors are powered by +5V which is derived from the control board. They output a nominal 2.5V with no current. The +5V is buffered and divided to 3.3V and used as the reference voltage for N3-A, N3-B, N3-C, N5-D, N5-C, N5B and N5-A. Each Op amp will now put out a nominal +3.3V with no current running through its respective LEM sensor. Measurements are scaled so that control board hardware current limit is set at approximately 240Apk @ 20kHz. This allows for overload conditions and system non-linear loads with high crest factors. Calibration takes care of any slop caused by current splitting scheme used to measure current. Software current limits are also in place.
4.12.1
Output Current Measurement
Line 1, 2, 3 phase currents are monitored by B5, B9, B10 CTs respectively. These measurements (currents) are not split. R54 and R55 adjusts gain for Line 1 measurement, R146 and R147 adjusts Line 2 measurement gain, and R148 and R149 adjusts Line 3 measurement gain. This measurement is sized to handle 110% overload on the inverter with 1% low tolerance and a 3:1 crest factor. Measurement will also handle the 150% overload at low line at a 2.2:1 crest factor per the PDR (reference 1).
4.12.2
Input and Output Filtering Scheme
High Frequency Y-Caps are provided on Input, Output, Neutral, and Battery Connections to Chassis: High Frequency X-Caps are provided on Input, Output Connections to Neutral and across the Battery: • 4-60
Ferrite cores are also placed strategically to form a common mode choke pi filter on the input for emi. © 2006 - Eaton Corporation
9355 20 – 30 kVA
•
Functional Descriptions
Input and output filter capacitors for the rectifier and inverter carrier rejection are provided on the I/O board: - C115-117, C129-134, C210-212
These caps along with the system inductor provide a 2nd order filter with the following corner frequency: fr = 1/ (2π√L⋅C) = 1960Hz where L = 50µH and C = 132µF
4.12.3
Inverter/Rectifier Fault Methodology
An input breaker feeds the rectifier path, which may trip if there is a bus fault with the rectifier or inverter. If the fault is due to a inverter IGBT module failure, fuses (F1, 2, 3) may clear also. The inverter and rectifier have hardware and software current limit protection. The inverter output path is fused with 160A LET semiconductor fuses (F1, 2, 3). The inverter path is connected through a contactor to the bypass SCR output. These paths are OR’d, which leads to fast transfer times in the unit. This connection is then run through the load CTs. In an output short circuit condition, the inverter will current limit, transfer to bypass, and then open the inverter contactor if the load short circuit does not clear. Software keeps the inverter from going back online after bypass until the load short circuit has cleared. The bypass feed is protected by fuses (not on this board), and an upstream (customer) circuit breaker.
4.12.4
Single Feed/Dual Feed Input Contactors
The Low Voltage UPS module uses either a single feed or dual feed by adding or removing a jumper. There are separate contactors for the Bypass and Rectifier paths. The redundant drive for the rectifier contactor (circuit consisting of K12, K14, X27) is located on this board. The drive for the inverter contactor (circuit consisting of K11, X21) is located on this board. Both drives are powered from the 24V reservoir capacitors. It takes approximately 4A for about 100ms (100W) to pull in the contactors.
4.12.5
Battery Relay, Battery Start and Current Measurement
The Low voltage UPS module contains a system battery breaker; Battery + and Battery – connections come to the IO board. Battery capacitors C15, 81, 14 are provided and work with the two parallel battery chokes to form a carrier ripple filter. The Battery Relay (K5-10—six 40 Amp relays in parallel), is driven by way of V7D and V7C and clamped with V1. The battery relay connects the battery-tobattery chokes once the rails are charged, so there is no inrush. Battery current is then measured by LEM sensor B8. Choke currents from each power module are each split by two (see paragraph 4.5.3) so that half of battery current is sensed by the LEM.
© 2006 - Eaton Corporation
4-61
Functional Descriptions
9355 20 – 30 kVA
During a battery start SCR V6 provides battery start capability in absence of utility. This SCR is triggered by a battery start pushbutton connected to X79 once the battery breaker is closed. This circuit then provides power to the AAUX supply. Once the battery start circuit latches, control board power comes up and the control board comes alive. A precharge circuit then pumps up the positive rail to hold up the AAUX power supply. The balancer relay (K19-21) closes and the L1 rectifier converter, acting as a balancer, transfers charge to the negative rail. Software waits for a “UPS on” command from the front display. If the unit is not started, software properly shuts down the unit.
4.12.6
Balancer Relays and Drive
A Line 1 Rectifier converter is used to balance the rails to neutral when on battery and during startup. Balancer Relay (K1-4) is used to connect Line 1 after the contactor is opened to Neutral. The coils are powered with +24V from AAUX and are driven by V8-C, V8-G and are clamped by V11. Firmware is in place to keep the Balancer relay and the rectifier contactor from being closed at the same time avoiding a short on the utility and welded relays.
4.12.7
Battery CB Trip
This circuit shunt trips the battery CB. It gets its power from +24V reservoir capacitors through FET V105 out connector X50. It takes approx 4A for ~100ms (100W) to trip the breaker.
4.12.8
Input/Output CB Trip
The circuit (K4,14, X2, 78) shunt trips the input/output CB. It gets its power for the input trip coil from the L1 input and for the output trip coil from the L1 output.
4.12.9
Other Sensing
There are three buffers dedicated for sensing. The state of the Battery CB is reported back to the control board through buffer V91-G from connector X50. The state of the SPARE_IN1 is reported back to the control board through buffer V91-D from connector X61. The state of the SPARE_IN2 is reported back to the control board through buffer V91-C from connector X60. Ambient temperature is sensed by U1.
4.12.10 X-Slots Connectors X55 and X56 go out to the two X-Slots. The X-Slots each get +12V_2 through a 5 ohm 1A PTC thermistor R285, R286 plus signals to and from the control board.
4-62
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.12.11 AC Fans There are three AC fans powered from this board. Fan 1 (X65) is connected phase L3- N across the inverter. Fan 2 (X66) is connected phase L2-N across the inverter. Fan 3 (X67) is connected phase L1-N across the inverter. All are located after the inverter fuse. They can also be powered by the output when the inverter is off by closing the inverter contactor.
4.12.12 Chassis GND Chassis screws E14, E15, normally ground logic common. The emi Y-caps are connected via screws E13, E16.
4.12.13 Troubleshooting 4.12.13.1 Fuses The IO Board contains the inverter (F1-3) fuses that disconnect any failed converters on the power modules.
4.12.13.2 Circuits If the display is not working check the F4 fuse going to the AAUX supply. Look for the presence of +24V on X44.
4.12.13.3 Relays Check for welded balancer relays (K1-3) if the rectifier CB is tripped open or a rectifier converter has failed. Check for welded battery relays (K5-10) after a battery converter failure.
© 2006 - Eaton Corporation
4-63
Functional Descriptions
9355 20 – 30 kVA
4.13 Bypass Board System Overview Reference Documents: PW9355 1024059: Bypass Board Schematic and 1024062: silkscreen, see the “Prints” chapter at the end of this document.
Figure 28.
Bypass Control Board
Each Power Board is the location for the 3 main power converters: •
one phase of the Boost Rectifier, 1/3 of the Battery Boost/Buck Charger,
•
one phase of the Buck Inverter, and their respective gate drives,
•
and one IGBT thermal sensor.
This board, along with chokes and heatsink, comprise a power module capable of handling 1/3 of the output power. DC voltage sensing is provided on this board. It is the home of the positive and negative rail bulk storage caps. There is also a heatsink thermostat sensor. Each interfaces with the I/O board containing a 20 pin ribbon cable Table 19. Interconnect Description Reference Designator
4-64
Description
X24
Bypass L3 input to SCRs after contactor
X8
Bypass L2 input to SCRs after contactor
X9
Bypass L1 input to SCRs after contactor
X10
N input © 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
Table 19. Interconnect Description Reference Designator
Description
X25
From MBS switch status
X51
To Bypass Back-feed contactor
X53
RS-232 9 pin DSUB
X5
L1 output after SCRs
X11
L2 output after SCRs
X13
L3 output after SCRs
X1
PIC flash phone jack
X17
AC Fan connection Bypass L1-N load side
X18
AC Fan connection Bypass L2-N load side
X1
AC Fan connection Bypass L3-N load side
X27
Pull Chain connection
X2-4, X14-16
Bypass SCR gate connectors
Table 20. X6 Connector Pinout Pin
Signal
Description
1
Logic ground
2
BUPASS_VOLT_L1N
Line 1 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
3
BUPASS_VOLT_L2N
Line 2 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
4
BUPASS_VOLT_L3N
Line 3 Bypass Voltage Measurement L-N after Bypass Relay and Fuse
5
Logic ground
6
AAUX
7
ALARM_RELAY
8
MBS
9
BAUX
10
Unused
11
SER_RX
12
SER_TX
13
Logic ground
14
EPO_ ENABLE
15
BLD_ALARM1
16
BLD_ALARM2
17
Logic ground
Ground
18
INVONLINE
Output signal used to control D1 state machine
Ground
Ground +24V supply on IO board
+24V supply on BYP board
Ground
© 2006 - Eaton Corporation
4-65
Functional Descriptions
9355 20 – 30 kVA
Table 20. X6 Connector Pinout Pin
Signal
Description for Bypass
19
BYP_RDY
Output from D1 used by control to determine state of D1
20
BACK-FEED
Bypass Contactor Drive
21
Logic ground
Ground
22
B_UP_OK
23
BYP_AVAIL
24
IO_GOOD
25
LED_OVERRIDE
Display
26
Logic ground
Ground
Not used Output signal from control board used to control D1 state machine
4.14 Bypass Board Functional Blocks 4.14.1
BAUX Power Supply
This circuit (N1, Q1, T2) is an 80W isolated flyback switching power supply. It receives input power from rectified 120VAC during an AC start. This input is then converted to 24VDC (BAUX). It is used for operating the bypass contactor from the cap reservoir circuit of N8, C34, and C35. The BAUX Power Supply is stepped down by a buck converter to 12VDC (+12V_2). The buck converter circuit (N11) output (+12V) capable of ~3A, powers the bypass SCR gate drives. It is then stepped down by linear regulator (N2) to +5V (+5V_2), capable of ~1A to power the bypass PIC (D1). The +5V is stepped down by linear regulator (N10) to serve as a +2.5V reference. This circuit is protected by fuse F4.
4.14.2
Voltage Sensing
The Bypass Board provides Voltage Sense Resistors for bypass voltage sense measurements done on the Control Board. The measurements are made after the bypass contactor and fuses. Voltage sense resistors are two 1Meg ohm resistors in series. Reference sense resistors to Neutral are provided on the Power Board. The measurements are differential measurements with respect to Neutral. Op Amps are referenced to signal +5V_REF created on the control board. Outputs of the Op Amps are divided down to a 1.5V reference to the DSP with an antialiasing filter. Voltage measurement signals are described in paragraph 4.5.2.1.
4-66
© 2006 - Eaton Corporation
9355 20 – 30 kVA
4.14.3
Functional Descriptions
Input Contactor
The system uses an “input all pole break” input bypass contactor. The drive for the contactor (a circuit consisting of K1, X51) is located on this board. It is powered from the 24V reservoir capacitors. It takes approx 4A for ~100ms (100W) to pull in the contactor.
4.14.4
Alarm Supply
There is a separate un-fused forward converter for supplying EPO and Building Alarms. Alarm Supply gets its power from +24V (AAUX on I/O) and is reduced to +12V by (N5) and uses a gate signal from N3. The circuit consists of FET V87 and XFMRs T4, 5, 6. This results in three isolated ~12VDC outputs for use by the alarms.
4.14.5
EPO Alarm
There is a normally open EPO input on X12 and a normally closed input on X52. Opto isolator V110 sends this alarm to the control board.
4.14.6
Building Alarms
There are two building alarms on X44 and X45 that can be programmed to be used in a number ways by the customer (via the display board) just by adding a jumper. OPTO isolators V108 and V84 send these alarms to the control board.
4.14.7
RS-232
There is another separate un-fused forward converter for supplying isolated RS-232 power. The circuit consists of N13, N14, V113, and T7. It runs from the 24V (AAUX on I/O) input and outputs +/-6V for use by the transmit and receive circuits of isolators V102 and V103. This appears on DB9 RS-232 connector X53 as RxD, TxD, and GND.
4.14.8
NO/NC Relay Contacts
There is a set of isolated NO/NC relay contacts K7 ouput on connector X57.
4.15 Bypass SCR Gate Drive and SCRs Bypass SCRs are mounted on the back of the lower power module heatsink. The gate drives operate at approximately 22kHz with a 25% duty cycle. The drive is controlled by N4, which is a UC3845A Current Mode controller that gets its power from +24V (BAUX). Transformers T18, T19, T21, T22, T23, and T24 provide gating pulses. These transformers provide SELV isolation from the line to the gate drive, which operates from system logic ground. _2 is regulated with a linear regulator N2. This voltage is used for the logic power for bypass PIC D1.
© 2006 - Eaton Corporation
4-67
Functional Descriptions
4.15.1
9355 20 – 30 kVA
Standalone Bypass Functionality
Bypass function is controlled by PIC processor D1. The processor is a microcontroller and operates at 5MIPS. Pins 6, 9, and 10 control the processors state transition. Pin 8 tells the main processor what state it is in with a clocked output. Pin 5 feeds a window comparator with a clock. This comparator disables the bypass gate drive with a brownout condition, clock failure, or watchdog failure. Pin 7 locks the LED on the unit display when the unit goes to bypass. Pin 11 drives Darlington drivers V6-C, V8-B, and V43-H. These drivers turn on the Static Switch gate drive, latch on the contactor drive relay. LED V4 shows what state the processor is in and is driven via a Darlington driver with pin 12. Connector X1 is used to program the processor.
4.15.2
Bypass State Machine
Operation of the Bypass Control Board is described below using machine states. Bypass machine states can be viewed as modes of operation. Each table below describes a machine state. The last group of tables describes all possible machine state transitions
Fire
Ready Armed
Ready
Idle
Init
Figure 29.
4-68
State Diagram
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
The following tables describe the Bypass Control states show in Figure 29: Table 21. Fire State [FIRE STATIC SWITCH]
= ON
[CLOSE BYPASS]
= ON
[CLOCK OUT]
= 50% duty cycle 10KHz
[BYPASS READY]
= 50% duty cycle square wave (1020 Hz)
[BYPASS RELAY]
= ON
[GREEN LED]
= ON
Table 22. Ready State [FIRE STATIC SWITCH]
= OFF
[CLOSE BYPASS]
= OFF
[CLOCK OUT]
= OFF
[BYPASS READY]
= 50% duty cycle square wave (510 Hz)
[BYPASS RELAY]
= OFF
[GREEN LED]
= 1 Hz 10% duty cycle BLINKING
Table 23. Ready Armed State [FIRE STATIC SWITCH]
= OFF
[CLOSE BYPASS]
= OFF
[CLOCK OUT]
= OFF
[BYPASS READY]
= 50% duty cycle square wave (715 Hz)
[BYPASS RELAY]
= OFF
[GREEN LED]
= TOGGLE EVERY .5 SEC
Table 24. Idle State [FIRE STATIC SWITCH]
= OFF
[CLOSE BYPASS]
= OFF
[CLOCK OUT]
= OFF
[BYPASS READY]
= 20 millisecond square wave (50Hz)
[BYPASS RELAY]
= OFF
[GREEN LED]
= OFF
© 2006 - Eaton Corporation
4-69
Functional Descriptions
9355 20 – 30 kVA
During the Intialization state the Microcontroller is initialized and tested. All Microcontroller outputs will be disabled. Table 25. Initialization State [FIRE STATIC SWITCH]
= OFF
[CLOSE BYPASS]
= OFF
[CLOCK OUT]
= OFF
[BYPASS READY]
= OFF
[BYPASS RELAY]
= OFF
[GREEN LED]
= OFF
Machine State Transitions Table 26. From Initialization to Idle State For 100 milliseconds: {INVERTER ON LINE}
= TRUE AND
{BYPASS AVAILABLE}
= FALSE AND
{POWER FAIL}
= FALSE AND
{IO GOOD}
= TRUE
Table 27. From Idle State to Ready State For 100 milliseconds: {INVERTER ON LINE}
= FALSE AND
{BYPASS AVAILABLE}
= TRUE AND
{POWER FAIL}
= FALSE AND
{IO GOOD}
= TRUE
Table 28. From Ready State to Ready Armed State For 100 milliseconds: {INVERTER ON LINE}
= FALSE AND
{BYPASS AVAILABLE}
= FALSE AND
{POWER FAIL}
= FALSE AND
{IO GOOD}
= TRUE
Table 29. From Ready State to Fire State For 750 microseconds:
4-70
{INVERTER ON LINE}
= TRUE AND
{BYPASS AVAILABLE}
= TRUE AND
{POWER FAIL}
= FALSE AND
{IO GOOD}
= TRUE
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
This state transfer should only be executed when the system is configured as parallel for redundancy. Table 30. From Ready Armed State to Fire State For 750 microseconds: {INVERTER ON LINE}
= TRUE AND
{BYPASS AVAILABLE}
= TRUE AND
{POWER FAIL}
= FALSE OR
{IO GOOD}
= FALSE AND
{POWER FAIL}
= FALSE
Table 31. From Fire State to Ready Armed State For 750 microseconds: {INVERTER ON LINE}
= FALSE AND
{BYPASS AVAILABLE}
= FALSE AND
{IO GOOD
= TRUE
I/O GOOD insures we don’t come off of bypass and drop load if the Control Board Logic Voltage fails. Make sure that bypass “available true” in hardware is not “naturally pulled-up state.” That way if in logic there is “Failure on Interface Board” we stay on bypass. Table 32. From Armed State to Ready State For 5 milliseconds: {INVERTER ON LINE}
= FALSE AND
{BYPASS AVAILABLE}
= TRUE AND
{POWER FAIL}
= FALSE AND
{IO GOOD}
= TRUE
Table 33. From Ready State to Idle State For 50 millisecond: {INVERTER ON LINE}
= TRUE AND
{BYPASS AVAILABLE}
= FALSE AND
{POWER FAIL}
= FALSE AND
{IO GOOD}
= TRUE
© 2006 - Eaton Corporation
4-71
Functional Descriptions
9355 20 – 30 kVA
4.15.2.1 Control Interface The Control Interface is comprised of three dedicated control signals: •
Inverter on line (input)
•
Bypass Available (input)
•
O GOOD (input) and Bypass Ready (output).
The Inverter uses the first two control signals to tell the Bypass Control Board what the "State" the whole system is in. The Bypass Control uses these signals (Inverter on Line and Bypass Ready) to transition from state to state. The Bypass Control uses IO GOOD (input) to insure that the system does not drop load if there is a logic failure on the control board. The Bypass Control uses the third control signal to tell the Inverter Control what state the Bypass Control is in.
4.15.2.2 Clock signals All clock signals generated by the bypass board should vary in frequency by no more than 5%. Since CLK_OUT and FIRE_STSW are generated directly by an ISR they should not vary. BYP_READY is generated by the state machine and could vary, but no more than +/- 5%. This state is entered when a Microcontroller reset occurs. Reset could occur because of any of the following reasons: Table 34. From All Machine States to Initialization States LOGIC POWER RESET FROM THE LOGIC POWER FAIL STATE WATCHDOG TIMEOUT S/W MALFUNCTION. {RESET IN}
= TRUE
{INVERTER ON LINE}
= DON'T CARE
{BYPASS AVAILABLE}
= DON'T CARE
{POWER FAIL}
= DON'T CARE
{FIRE BYPASS}
= DONT CARE
4.15.3
AC Fans
There are three AC fan connectors X17, X18, and X19. X17 is connected phase L1- N across the output. X18 is connected phase L2- N across the output. X19 is connected phase L3- N across the output.
4-72
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Functional Descriptions
4.16 ELECTRO-MAGNETIC INTERFERENCE (EMI) BOARD (PCB) Reference Documents: EMI Board Schematic (110720620) in the “Prints” chapter at the end of this document.
4.16.1
Introduction
The EMI Board handles surge protection and EMI filtering.
4.16.1.1 EMI Connector Descriptions 4.16.2
EMI Board Functional Sections
4.16.2.1 Surge (PW 9355) 4.16.2.2 EMI Filter (PW 9355) 4.16.2.3 Paralleling Inductors (PW 9355) TBD
4.16.2.4 Miscellaneous The connection to the logic power supply on the I/O Board comes from the connections J1 and J2 on the EMI board. This connection bypasses the ABF contactor.
© 2006 - Eaton Corporation
4-73
Functional Descriptions
9355 20 – 30 kVA
This page was left blank intentionally. .
4-74
© 2006 - Eaton Corporation
5 Connectivity and Communication 5.1 9355 GENERAL CONNECTIVITY DEVICES 5.1.1
Basic Serial Communication
Two serial ports are available with the standard unit. One of the serial ports is dedicated to an X-Slot. The other port is exclusively an X-Slot or it can be shared with a local DB9 RS-232 port. The second X-Slot can be used at the customer’s discretion.
5.1.2
Relay Signaling
One general-purpose relay, with SELV compliant contacts, is available for output signaling. The default set-up for this relay is “Alarm.”
5.1.3
Building Alarm Inputs
The unit will have two configurable, galvanic isolated (SELV) “building alarm” inputs.
5.1.4
Additional Connectivity & Software
The UPS will support the XCP protocol. The units will support the following: •
LanSafe-power management software for system data integrity
•
PowerVision-UPS performance analysis, monitoring software
•
Foreseer
•
Modem-based Remote Notify
•
Power Strategy Command
•
XCP-based service tools
UPS Firmware “flashing” at all levels will be accommodated through any serial channel. Flashing of controls and communications code segments will be handled separately.
© 2006 - Eaton Corporation
5-1
Connectivity and Communication
9355 20 – 30 kVA
5.2 9355 X-SLOT CONNECTIVITY DEVICES The Powerware® 9355 supports a variety of connectivity devices from additional RS-232 and RS-485 serial ports to SNMP (Simple Network Management Protocol) network and web adapters. To accommodate these devices, the Powerware® 9355 product supports two (2) X-Slots which house these devices. Slots 1 and 2 can be used for any of the available cards. An optional X-Slot driver board (Mini-CSB) may add three (3) additional external XSlots. All X-Slot cards are “Hot-Swappable,” meaning that the UPS does not have to be powered down or transferred to BYPASS for the card to be installed or removed. For additional information and specific details pertaining to the setup and configuration of each connectivity device, refer to www.powerware.com for sales brochures and product manuals. Table 35. X-Slot Connectivity Device Options PART NUMBER
DESCRIPTION
05146533-5501
X-Slot, Single Port RS-232 / Serial / AS400 (Field Kit)
05146447-5501
X-Slot, Multi-Port / Multi-Server Serial / AS400 Signals (Field Kit)
05146508-551
X-Slot, USB Module
05146288-5501
X-Slot, ConnectUPS-M SNMP (Field Kit)
IPK-0330
X-Slot, ConnectUPS-X SNMP / Web Adapter 10 (Field Kit)
103002974-5501
X-Slot, ConnectUPS-S SNMP / Web / Hub 10/100 (Field Kit)
1018460
X-Slot, Low Voltage (LV) Relay Interface (Field Kit)
103003055
X-Slot, High Voltage (HV) Industrial Relay / RMP Interface (Field Kit)
103002510-5501
X-Slot, MODBUS (Field Kit)
1019017
X-Slot, Modem (Generic) (Field Kit)
1019018
X-Slot, Modem (New Zealand, Australia) (Field Kit)
103002687-001
Remote Monitoring Display Field Kit (Powerware®)
103004336
X-Slot CAN Bridge Card
*Field Kits include Board, Cable, Screws, Manual, and Software
For more details on X-Slot cards, refer to the 9355 UPS User’s Guide, Communication Options.
5.2.1
Modem Handling
A modem can be connected so that the UPS can receive calls and the UPS can make out-going calls when a programmed event occurs (Remote Notify and P-record Phone Home). When connected, the modem is pinged periodically.
5-2
© 2006 - Eaton Corporation
9355 20 – 30 kVA
5.2.1.1
Connectivity and Communication
Modem Pinging
The Modem is pinged not only to ensure that is connected, but also for modem hang-up, initialization and also prior to making any out-call to assure that the modem is functional. A transfer to the pinging state occurs for the following reasons. •
The modem is pinged whenever the serial port has not received data for 15 minutes
•
Communication Server Board (CSB) Logic Power On
•
Remote Notify or P-record Phone Home Request
5.2.1.2
Modem Connected (Incoming Call)
When the Modem Connected Response is received from a serial port connected to a Modem, the status “Modem Connected” is queued in the event history queue.
5.2.1.3
Remote Notify State or XCP Modem Call Request
Any event in the system can cause a XCP Phone Home or Remote Notify call when the event transitions to its active state. The modem is always pinged prior to the call to ensure that the modem is functional and initialized. To do this, a transfer to the Ping Modem State occurs when a call is requested. All of the following items must be true for an out-call to be initiated: •
A request is made for a Remote Notify or XCP call. (See requesting calls, below.)
•
One minute has expired since an out-call to any Phone # has been made.
•
This serial port is set up to make the corresponding Remote Notify call.
•
Input as not be received for 15 Minutes. Note: Only one modem can be connected.
After the Outcall, the modem is hung up if inactivity occurs for 1 minute.
5.2.1.4
Requesting Calls
As shown below, any event can trigger an out-call. When the event goes active, the request activates if enabled for the corresponding serial port.
© 2006 - Eaton Corporation
5-3
Connectivity and Communication
9355 20 – 30 kVA
P-
The Call requests are made periodically until the Call request is cleared. Up to three calls are made hourly. The modem must be disconnected for fifteen minutes before a call is initiated.
5.2.2
Modem Operation
5.2.2.1
Modem Communication Terminology
AT command set – fairly standardized command set used by modems. Most commands to the modem start with ”AT” and end to a carriage-return. Carriage-return – the ASCII code 0x0D, that is commonly used as string/line termination. D-sub – the 9-pin communication connector in PW9355. FORS – software running in a service center host computer. Whenever there is some active alarm requiring service attention, the UPS calls to FORS. Also, FORS may periodically call to the UPS to request the state and history log from the unit. Modem – a communication device that allows using serial communication over public telephone lines. XCP – the communication protocol used with PW9355. X-Slot – an extension card slot. PW9355 has two X-Slots, 1 and 2.
5-4
© 2006 - Eaton Corporation
9355 20 – 30 kVA
5.2.2.2
Connectivity and Communication
Introduction
This document describes the modem support in PW9355. The modem handling is designed to work with FORS service system and any modem that uses the industry standard ”AT” command set. When the UPS requires service attention, it automatically calls to the service center. Then, using the normal XCP, the service center host computer requests data from the UPS. The service center may initiate the call to the UPS. This makes modem handling in the UPS simple. The UPS is only responsible for: •
Detecting the condition that requires service attention: this is done by correctly selecting and setting the alarms, which cause the UPS to make the call.
•
Making the call: this is done by periodically sending a correctly set command string to the modem. This is repeated until the connection is created, or predefined number of tries has been made.
•
Responding: while the connection is active, the UPS responds normally to any XCP monitoring commands. All control commands are disabled, until the required password is given.
•
Disconnecting the line: this is done by periodically sending a correctly set hang-up string to the modem, until the modem responds expectedly.
The 9355 modem support uses binary XCP. The ASCII Computer Mode (ACM), which is mentioned in the XCP Protocol Specification, is not used.
5.2.2.3
Communication Speed
The communication speed for the modem communication channel (between the UPS and the modem) must be set correctly. Modems may be able to detect this speed automatically, but the recommendation is to use a fixed speed in the modem. •
The factory setting for both communication channels is 19200bps.
5.2.2.4
Lock Communication to D-Sub
Normally the serial communication of channel 2 is done via the X-Slot 2. When the D-sub is used for communication, then channel 2 is automatically switched there from the slot. When the D-sub isn’t used anymore, the channel 2 is switched back to the X-Slot 2. The setting disables the automatic switching between the two, and locks the communication to the D-sub. This removes the possibility of losing the first command/message when a communication session is started with the UPS. This setting is recommended if channel 2 communication is used only by the Dsub. For example, this is the case when the modem is installed to the D-sub while the serial communication in the X-Slot 2 is unused. This setting has no effect on communication channel 1. The factory setting is FALSE, ”not locked to D-sub”. © 2006 - Eaton Corporation
5-5
Connectivity and Communication
5.2.2.5
9355 20 – 30 kVA
Control Commands Inhibition
This setting is for security: it disables all control and configuration commands coming from the communication channel. There is an independent setting for each channel. This is settable using the front panel LCD menu only. When this setting is ”not allowed” for the modem communication channel, all UPS control and configuration commands via the modem are disabled. To allow any control of the UPS via the modem, this setting must be set to ”allowed” for the communication channel, and the correct modem communication password must be given during the modem session. Note: The factory setting for both channels is ”not allowed”.
5.2.2.6
Modem Communication
This setting tells the UPS if a modem is connected to the UPS. Zero value means that no modem is installed. Other values define the communication channel where the modem is installed. All modem handling and communication restrictions (”AT” commands and password requirements, for example) are directed to this channel. The other communication channel operates normally. When the modem is installed and this parameter is correctly set, the UPS will automatically make a call when an event requires it. The call is made to the number defined by the modem call number string. •
The factory setting is zero, ”modem not installed”.
5.2.2.7
Modem Call Number
This is a string that holds the call command and the cal number. The maximum string length is 39 characters. To initialize a modem call, the UPS simply sends this string to the modem; it must include all (commands/numbers) the modem needs to make the call. For example, the phone number of the service center computer is 123-4567: Modem call number = ”ATDT1234567”. The string may also include other modem control commands. •
The factory setting is an empty string, only the automatically added carriage-return is sent to the modem.
5.2.2.8
Modem Initialization String
This string is used to initialize the modem. Normally, the correct configuration is stored into the modem non-volatile memory, and this string only directs the modem to reset itself and use the stored configuration. The maximum string length is 47 characters. While the modem handling is in the modem idle state, the UPS firmware automatically sends the initialization string to the modem every 15 minutes. The modem initialization can be commanded using a XCP parameter or with the
5-6
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Connectivity and Communication
front panel. Using this command causes the modem to be initialized immediately. If there is an open modem call, it will be hung up. •
The factory setting is ”ATZ0.”
5.2.2.9
Modem Communication Password
When a new modem call begins, only UPS monitoring is allowed; this means commands that retrieve normal ”user” data from the UPS, meters, status, alarms, history log, and so on. To make any UPS control or configuration via the modem, a password must be given. The given password is valid only during the present modem session, and it must be given again when a new modem call is made. The password is given using the XCP Configuration Field command. The password is a write-only string for the user. Service may change the password. The maximum string length is 9 characters. In addition to giving the correct password, the control commands must be allowed for the communication channel. •
The factory setting is an empty string - the user must use the XCP Configuration Fields command to fill the empty string.
5.2.2.10 Modem Hang-up String This string is used for “escaping” the modem to command mode and hangingup the line. The maximum string length is 31 characters. All other characters except comma ’,’ (ASCII 0x2C) are sent to the modem. The comma character causes a 2 second pause before continuing. •
The factory setting is ”,+++,ATH0”.
5.2.2.11 Modem Message String When this string is set, (its length > 0) then the operation changes when the UPS makes the call. About 5 seconds after the connection is made (”CONNECT”), the UPS sends this string to the line, then sends the internal alarm message string and number (in ASCII format) that requested the call, then the UPS disconnects the line and returns to Modem Idle state. The maximum string length is 31 characters, or preferably 63 bytes if there is room in the EEPROM. The factory setting is an empty string.
© 2006 - Eaton Corporation
5-7
Connectivity and Communication
5.2.3
9355 20 – 30 kVA
Modem Call Handling States
No Modem
Modem Idle Modem Initializing
Modem Hanging Up Modem Dialing
Modem Session
Figure 30.
Modem Call Handling States
Modem handling has six states:
5-8
1.
No Modem: the parameter “modem communication” has the value zero. The serial communication works normally without extra modem handling.
2.
Modem Idle: no active communication is occurring through the modem. The firmware is waiting on an incoming call, or an alarm causing the UPS to make a call.
3.
Modem Initializing: the modem is being initialized.
4.
Modem Dialing: the modem is dialing, trying to make the connection with the remote host computer.
5.
Modem Session: communication with the remote host computer is active.
6.
Modem Hanging Up: the modem is disconnecting the line.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
5.2.3.1
Connectivity and Communication
No Modem
Refer to Figure 31 No Modem State As long as the parameter “modem communication” is zero, the modem handling firmware stays in this state. The serial communication operates normally to both communication channels without additional modem handling. When the parameter value is changed to 1 or 2, the modem handling is directed to that channel, and the firmware changes to modem idle state.
NO modem
NO
Modem The parameter < > 0
YES Modem idle
Figure 31.
No Modem State
© 2006 - Eaton Corporation
5-9
Connectivity and Communication
5.2.3.2
9355 20 – 30 kVA
Modem Idle
Refer to Figure 32 Modem Idle State In this state, the modem is disconnected from the phone line. On entering to this state, the modem handling is initialized and all active call requests from currently active alarms are cleared. Only a new alarm will cause the modem call. The internal flag “modem communication password given” is cleared. If the service needs to use control commands in the next modem session, the password must be given again. A new alarm that requests a modem call will cause the firmware to start the dialing sequence. First, a simple test is made that the modem really is off-hook. This is achieved by sending the “AT” command, which the modem should respond to with “OK”. If this is not responded to correctly after two attempts, the hang up state will be executed before dialing. The state then changes to modem dialing. If a command, or a string starting with CONNECT, is received from the modem, then a call to the UPS has been received. The state changes to modem session. While looping in this state, the UPS periodically initializes the modem by sending the modem initialization string to the modem.
5-10
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Connectivity and Communication
Modem idle
Clear call requests of currently active alarms. (A modem call is initialized only by a new alarm.) Clear internal flag Modem Communication Password Given.)
Time to initialize the modem?
YES Send the initialization string to the modem.
NO
Connect or a command from the modem?
YES Modem session
NO
YES
An alarm a call?
Modem dialing
NO
YES Modem installed?
The parameter < > 0
NO NO
Figure 32.
Modem Idle State
© 2006 - Eaton Corporation
5-11
Connectivity and Communication
5.2.3.3
9355 20 – 30 kVA
Modem Initializing
In this state, the initialization string is sent to the modem. The response “OK” is expected as an indication of successful initialization. Depending on the situation, after initialization the modem either returns to idle state or continues dialing.
5.2.3.4
Modem Dialing
Refer to Figure 33 Modem Dialing State To initialize the call, UPS sends the modem call number string to the modem. When the connection is opened, the UPS receives a string that starts with CONNECT, or any command from the line. If the connection is not made in the dialing time of 50 seconds, dialing is interrupted by sending a carriage-return (0x0D) to the modem. The dialing time (factory setting 50 seconds) is an EEPROM value, and changeable by service. The UPS makes call attempts (up to 9 times) until the connection made. The sequence consists of three groups of three attempts. A new attempt in a group is done about one minute after the previous one. The groups have 10 minutes in between them. When starting a new re-attempt group, an additional initialization of the modem is performed. The dialing is stopped if the connection cannot be opened during nine call attempts. The call requests are cleared and the firmware jumps to “modem idle” state to wait the next new alarm to request a call.
5-12
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Connectivity and Communication
Modem dialing
Initialize dialing sequence
Send the call number string to the modem
YES Connect or a command received from the modem?
Modem session
NO NO 50 seconds gone?
YES Interrupt the dialing by sending a carriage return to the modem
NO Wait a while.
Dialing sequence done? YES Modem idle
Figure 33.
5.2.3.5
Modem Dialing State
Modem Session
Refer to Figure 34 Modem Session State The monitoring commands (status, meters, history log, and so on) work normally during a modem session. The control commands require that they be allowed for the communication channel, and that the modem communication password is correctly given during the session. The password is valid only during the current session; it must be given again for the new session.
© 2006 - Eaton Corporation
5-13
Connectivity and Communication
9355 20 – 30 kVA
When the UPS receives a hang-up command, 5 minutes (EEPROM setting) has elapsed since the last command was received, string OK+carriage return, or a string starting as “NO CARRIER” is received, then the firmware state changes to “hanging up.” Modem session
Execute any monitoring commands. If the control commands are allowed via the channel and the internal flag Modem Comm. Password Given is set, execute control commands.
Correct "Modem communication password" given?
YES
Set the internal flag "Modem communication password given".
NO
YES Hang up command?
NO
"OK"+carriage-return or "NO CARRIER" received?
YES
NO
NO
5 minutes gone since the last command received?
YES
Modem hanging up
Figure 34.
5-14
Modem Session State
© 2006 - Eaton Corporation
9355 20 – 30 kVA
5.2.3.6
Connectivity and Communication
Hanging Up
Refer to Figure 35 Hanging Up State The “modem hang up” string is sent to the modem every 10 seconds until the modem responds with “OK”+ a carriage return, meaning the modem is hanging up. The firmware jumps to the modem idle state. Note that the comma ’,’ in the “modem hang-up” string has a special meaning: it is not sent to the modem, but a 2-second pause is observed before continuing with the next character in the string.
Modem hanging up
Send the hang up string to the modem. Initialize 10 sec timer.
"OK"+carriage-return
Modem idle
received?
NO
NO 10 seconds gone?
YES
Figure 35.
Hanging Up State
© 2006 - Eaton Corporation
5-15
Connectivity and Communication
5.2.3.7
9355 20 – 30 kVA
Modem Failure
After sending a command (except the off-hook test in Idle Mode) when the “OK” response is expected but is not received, sending the same command is repeated up to 10 times. After each try, the anticipated response duration is 10 seconds. If the modem still fails to respond correctly after the retries, the “modem failed” notice will become active. Modem failure does not affect the behavior of modem handling, but it causes an additional initialization if a new modem call is requested. Modem failure will be deactivated (“modem OK” in history log) when the modem is working properly again, that is, either the periodic initialization is carried out successfully or an incoming call is answered.
5.2.4
Communication During a Modem Session
5.2.4.1
XCP Monitoring Commands
All XCP monitoring commands work normally. These commands are the ones that read information from the UPS, but do not write or change anything.
5.2.4.2
XCP Control Commands
To be able to use the control commands during a modem session, the control commands must be enabled for the modem communication line, and the modem communication password must already be given during that session. The control commands must be preceded by an appropriate authorization code.
5.2.4.3
Requesting the History Log
An ASCII dump of the history log in PW9355 can be requested with a special command L (= 0x1B, 0x4C). There is no XCP command for this. The history log dump can easily be requested using simple terminal software. The following is a sample of a 9355 History Log using L command. [2J01/24/2005 16:30:07.590 Event #173: UPS Off Command 01/24/2005 16:30:07.660 Event #139: Inverter Off 01/24/2005 16:30:12.860 Event #140: Charger Off 01/24/2005 16:30:16.260 Alarm #199: Batteries Disconnected 01/24/2005 16:30:21.605 Notice #059: Utility Not Present 01/24/2005 16:30:21.960 Notice #008: Input Under or Over Frequency 01/24/2005 16:30:21.960 Notice #057: Utility Fail 01/24/2005 16:30:24.960 Notice #105: Bypass Not Available 01/01/0001 00:00:00.000 Event #138: Control Power On 01/24/2005 16:30:22.260 Alarm #199: Batteries Disconnected 01/24/2005 16:30:23.460 Alarm #199: Batteries Connected 01/24/2005 16:30:59.355 Event #172: UPS On Command 01/24/2005 16:31:12.960 Notice #105: Bypass Not Available 01/24/2005 16:31:13.160 Notice #105: Bypass Not Available ok 01/24/2005 16:31:21.560 Event #139: Inverter On 01/24/2005 16:31:36.660 Event #140: Charger On 5-16
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Connectivity and Communication
5.2.4.4
Hang-Up Command
At the end of a session, the host can, and should, command the UPS to hang up. This ensures that the UPS knows that the session has ended and is immediately ready for the next call. The hang up command is the Exit XCP to Unspecified Mode (0xFF). The host sends first the standard authorization code, and then: SFD AB
LEN 01
CMD FF
CSUM XX
Note: PW9355 “exit XCP to unspecified mode (0xFF)” command in one of the control commands that is always resident, as the service center host computer uses it as the hang-up command.
5.2.4.5
Giving the Modem Communication Password
The modem communication password is given with the XCP configuration field command (0x96) using field number 0xFFFE, “enter access password.” The modem user initially has a lower access level than a normal user with direct connection: he can use only monitoring commands. By giving the correct modem password, the user is raised to the “normal user” level. This affects not only 0x96 commands, but all control commands. The PW9355 checks the given password immediately. If the password is accepted, then XCP response is executed (0x31). If the password is incorrect, then the response is “parameter out of range” (0x35). Example 1: To give the factory default password (empty string), the host sends first the standard authorization code, and then: SFD
LEN
CMD
AB
05
96
Field # FE
FF
format
length
CSUM
01
00
XX
Example 2: To give the password ”WHATISTHIS”, the host first sends the standard authorization code, and then: SFD LEN CMD AB
0F
96
Field # FE
FF
format length 01
0A
string W
H
A
© 2006 - Eaton Corporation
T
I
S
CSUM T
H
I
S
XX
5-17
Connectivity and Communication
5.2.4.6
9355 20 – 30 kVA
Setting the Modem Communication Password
To set the modem communication password, the XCP configuration field command (0x96) field number 0x0017, “modem communication password” must be used. Prior to issuing this command, the user must have used the configuration field command field 0xFFFE “enter access password” to get the correct access level for setting this string. Example 1: To set the password of ”WHATISTHIS”, the host first sends the standard authorization code, and then: SFD LEN CMD Field # format length AB
5-18
0F
96
17 00
01
0A
string W
H
A
T
© 2006 - Eaton Corporation
I
S
CSUM T
H
I
S
XX
9355 20 – 30 kVA
Connectivity and Communication
5.3 9355 COMMUNICATION 5.3.1
5.3.2
Default Communication Access Passwords Access
Password
User
-
Service
SERV
Signal Inputs & Programmable Functions
This section describes the signal inputs used in the Powerware 9355 UPS. The signal inputs are control inputs that can be used to trigger a programmable function. This section also discusses both how to use the signal inputs and what programmable functions are available.
5.3.2.1
Signal Inputs 1 & 2
The UPS incorporates two programmable inputs: X44 and X45. The connectors X44 and X45 can be found on the front of the UPS. Shorting the pins with a maximum resistance of 10 ohms activates the input signal. The function programmed to the input is triggered after the input has been in the active state for at least 1ms (±0.2ms) continuously. The same timing applies for inactivation. The inputs can also be programmed to use reverse logic. In that case, the input would be shorted by default, then opened to activate the programmable function. The logic direction is selectable from the front panel display.
5.3.2.2
X-Slot Inputs 1 & 2
Pulling the X-SLOT serial port RX-signal to a voltage between +3V and +15V for more than 5 seconds activates the input signal. The time for activating the signal is user configurable and can be selected between 0 and 65 seconds from the front panel display. The same parameter can be found in the service menu. The input signal related to X-SLOT 2 can also be activated from the service (Dsub) connector since the signals are multiplexed. The programmed function goes inactive after the activating condition has been absent for 1 second.
5.3.3
Programmable Functions
The signal inputs can be used to trigger a programmable function. By default, each signal input is linked to a building alarm, which is active while the corresponding input signal is active. The only exceptions are if the signal input is configured to the “empty” setting or to trigger another building alarm.
© 2006 - Eaton Corporation
5-19
Connectivity and Communication
9355 20 – 30 kVA
The corresponding building alarms are listed below. •
INPUT 1
Building Alarm 1
•
INPUT 2
Building Alarm 2
•
X-SLOT 1
Building Alarm 3
•
X-SLOT 2 / SERVICE
Building Alarm 4
5.3.3.1
Disable Bypass
This command disables the usage of bypass. While the signal is active, the unit will not change to bypass, neither in normal operation nor as a response to the bypass command. While active, it prefers dropping the load to changing to bypass. This function is only overridden using the “Force Bypass” setting.
5.3.3.2
Shutdown
Causes the unit to shut down immediately when activated. This function does not initiate the automatic restart itself, but if the automatic restart is already pending, it will not cancel it either. This function is edge activated. Shutting the unit down using this function will not prevent starting it up again using the front panel display or XCP. Note: The LV unit bleeds the DC rails down and does a full shut down, whereas the HV unit goes to Standby Mode.
5.3.3.3
Remote On / Off
Activating the function causes the unit to shut down. Inactivation causes the unit to start up again. If two or more input signals configured to this function are active, the start-up will be triggered when the last of the inputs inactivate. Shutting the unit down using this function will not prevent starting it up again using the front panel display or XCP.
5.3.3.4
Delayed Shutdown
Activating this function causes the unit to shut down after a user-defined delay. The default shutdown delay is 120 seconds. It can be changed on the front panel display. After shutting down, the automatic restart is initialized which will start the unit up after a delay. The pending automatic restart has higher priority than starting the unit up by XCP or by other signal input function.
5-20
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Connectivity and Communication
Both the pending shutdown and automatic restart can be cancelled by pressing the front panel display on/off button (TURN UPS OFF). While the automatic restart is pending, the front panel display can be used to turn the unit ON immediately.
5.3.3.5
Force Bypass
Forces the unit to bypass operation immediately when the signal activates. The transfer is unconditional and causes load loss if bypass operation is not possible (bypass not available, etc.). Note: Force Bypass does not have any effect if the usage of bypass is disabled with the user parameter.
5.3.3.6
Request Bypass
The unit tries to transfer to bypass operation for two seconds each time when the function activates. This function is edge-triggered and only responds to the activation. The unit will not transfer to bypass if bypass is disabled with an active “disable bypass” signal input function The unit will not transfer to bypass if bypass is disabled with the user parameter.
5.3.3.7
Request Normal
This function clears an active bypass request. When the unit is in requested bypass operation, this function will cause the unit to return to normal operation. This function is edge-triggered and only responds to the activation.
5.3.3.8
Normal / Bypass
The unit tries to transfer to bypass operation for two seconds each time this function is activated. If bypass operation was achieved, the inactivation of this function causes the bypass request to be cleared and the unit to return to normal operation. If two or more input signals configured to this function are active, the normal command is given when the last one is inactivated.
5.3.3.9
External Battery Breaker
This is the external battery breaker status. While this status is active, it causes the “Battery Breaker Open” alarm to be active. The alarm remains active while one or more signal inputs configured to this function are in the active state. During the active state the batteries will not be charged (ABM: battery not connected). When the function is inactivated, the ABM will start a new charging cycle. This function also causes the active “Battery Test Failed” notices to be cleared.
© 2006 - Eaton Corporation
5-21
Connectivity and Communication
9355 20 – 30 kVA
5.3.3.10 Charger Off Turns off the charger and forces the ABM cycling to the resting status. The “battery charging disabled” notice is active while the function is active. It stays active while one or more signal inputs configured to this function are in active state. The ABM returns to normal operation when the function is deactivated.
5.3.3.11 Building Alarms Causes the selected building alarm to be active while the input signal is active. The building alarm stays active while one or more signal inputs causing the same alarm are in the active state.
5.3.3.12 External Transformer Overtemperature Starts the ”Transformer Overtemperature” alarm. If the signal is constantly active during the user settable delay, the UPS output is shut down.
5.3.3.13 On Generator While active, the UPS detects that the input is fed from a generator.
5.3.3.14 Empty This is an empty function that does not do anything. It does not cause the default building alarm to activate.
5.3.4
Signal Inputs on Front Panel Display
The input signal configuration menu on front panel display can be found under “Settings? / User Settings? / Signal Inputs”.
5.3.4.1
Selecting the Input Signal
In the first phase, the desired input signal is selected using the up/down arrow buttons. While selecting, the current settings can be seen on the display. Pressing enter (↵) selects the desired signal input for reconfiguring.
5.3.4.2
Selecting the Function
In this phase, the desired function can be selected using the up/down arrow buttons. Pressing the bent arrow (the leftmost button) cancels the selection and returns to selecting the signal. On input signals 1 and 2, pressing enter (↵) moves on to selecting the logic setting. If the selected signal is either of the X-SLOT input signals, pressing the enter button confirms the selection and it will be taken into use. 5-22
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Connectivity and Communication
Note: If the selected input signal is active when confirming the selection, the function will activate immediately. There is a danger of load loss if the selected function is, for example, ‘shutdown’ and the unit is online.
5.3.4.3
Selecting the Logic Setting
In this phase, the desired logic setting can be selected using the up/down arrow buttons. Logic 1 means that the function is active when the input is shorted (normally open). Logic 0 means that the function is active when the input is opened (normally closed). Pressing the bent arrow (the leftmost button) cancels the selection and returns to selecting the signal. Pressing the enter (↵) button confirms the selection and activates the new function. Note: If the selected input signal is active when confirming the selection, the function will activate immediately. There is a danger of load loss if the selected function is, for example, ‘shutdown’ and the unit is online.
5.3.5
Configuration Fields
This command is used to set or modify the UPS configuration (parameters, variables). This is an XCP command that allows various types of configuration settings. Table 36. Configuration Settings NAME
DESCRIPTION
UNITS
TYPE
Audible Alarms
0 = disable horn, 1 = normal, 2 = mute current alarms
Nominal Output Voltage
Changing this value will also adjust the window set by Bypass Voltage Maximum and Bypass Voltage Minimum
0.1V
U16_T 16-bit, range -32768 … +32767.
Bypass Voltage Maximum
Max accepted bypass deviation from Nominal Output Voltage. Follows changes in Nominal Output Voltage setting
1%
S8_T 8-bit, range -128 … +127.
Bypass Voltage Minimum
Min. accepted bypass deviation from Nominal Output Voltage. Follows changes in Nominal Output
1%
S8_T 8-bit, range -128 …
© 2006 - Eaton Corporation
U8_T 8-bit, range 0 … 255.
5-23
Connectivity and Communication
9355 20 – 30 kVA
Table 36. Configuration Settings NAME
DESCRIPTION
UNITS
Voltage setting Nominal Output Frequency
Changing this value will also adjust the Synchronization Window accordingly
Synchronization Window
Accepted bypass frequency deviation from Nominal Output Frequency. Follows changes in Nominal Output Frequency setting
Output Frequency Max Slew Rate
The maximum speed for UPS to change the output frequency
Number Of Battery Strings
Battery Watts Per Cell
15 min. rate to 1.67 VPC at 25 C
Battery Cells Per String
TYPE +127.
0.001 Hz
U16_T 16-bit, range 32768…+32767
0.1 Hz
U8_T 8-bit, range 0 … 255.
0.1 Hz/s
U16_T 16-bit, range -32768 … +32767.
1
U16_T 16-bit, range -32768 … +32767.
1 W/cell
U16_T 16-bit, range -32768 … +32767.
1
U16_T 16-bit, range -32768 … +32767.
Constant Float Voltage
Sets the battery charging voltage when ABM cycling is disabled
0.001 V/cell
U16_T 16-bit, range -32768 … +32767.
Low Battery Warning Level
Voltage level at which the low battery alarm is given
0.001 V/cell
U16_T 16-bit, range -32768 … +32767.
On Battery Alarm Delay
The number of seconds on battery after which ”UPS on Battery” alarm is given
1s
U16_T 16-bit, range -32768 … +32767.
Maximum Charge Current
The maximum current for battery charging
0.1 A
U16_T 16-bit, range -32768 … +32767.
Automatic On Delay
Values 0...32767 = extra turn-on delay in seconds; value -1 = no automatic restarts
1s
U16_T 16-bit, range -32768 … +32767.
Automatic Off Delay
Values 0...32767 = seconds on battery after which output is automatically turned off; value -1 = no timed turn-off
1s
U16_T 16-bit, range -32768 … +32767.
Hardware Remote Off Delay
The delay before the shutdown, when hardware Remote off with restart command is activated.
1s
U16_T 16-bit, range -32768 … +32767.
X-Slot shutdown signal activation delay
The filtering delay, before the input signal is considered active.
1s
U16_T 16-bit, range -32768
5-24
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Connectivity and Communication
Table 36. Configuration Settings NAME
DESCRIPTION
UNITS
TYPE … +32767.
Rectifier Current Limit
Maximum current the rectifier draws from utility
0.1 A
U16_T 16-bit, range -32768 … +32767.
Modem Communication Password
Which communication channel the modem is installed to; value 0 = no modem
1
U8_T 8-bit, range 0 … 255.
Modem Call Number
The call command and number for the modem to make the call
SSTRING_T String. Maximum 128 bytes.
Modem Initialization String This string is used to initialize the modem
SSTRING_T String. Maximum 128 bytes.
Modem Communication Password
SSTRING_T String. Maximum 128 bytes.
Giving this password is required to control the UPS via modem
Unit Telephone Number
SSTRING_T String. Maximum 128 bytes.
CTO Number
SSTRING_T String. Maximum 128 bytes.
Serial Number
SSTRING_T String. Maximum 128 bytes.
Part Number
SSTRING_T String. Maximum 128 bytes.
UPS Family Name
For XCP ID block, front panel display, etc
SSTRING_T String. Maximum 128 bytes.
Reset
Changes automatically back to zero after execution Bit 0: Reset most configuration fields to factory setting Bit 1: Reset the history log Bit 2: Reset & initialize the modem
BMASK16_T
Battery Handling
Bit 0: Automatic battery support test: 0=enable/1=disable Bit 1: ABM charging cycling: 0=enable/1=disable Bit 2: Charging temperature compensation: 0=enable/1=disable
BMASK16_T
© 2006 - Eaton Corporation
5-25
Connectivity and Communication
9355 20 – 30 kVA
Table 36. Configuration Settings NAME
DESCRIPTION
UNITS
TYPE
Operation Settings
Bit 0: Preferred operation mode during rectifier input fail: 0=on battery/1=on bypass Bit 1: In case of overload, transfer on bypass 0=immediately/1=after a delay Bit 2: To transfer on bypass, the synchronization is 0=not required/1=required (never transfers unsynchronized) Bit 3: Synchronization is 0=enabled/1=disabled Bit 4: Usage of bypass is 0=enabled/1=disabled Bit 5: Site wiring fault alarm is 0=enabled/1=disabled
BMASK16_T 8-bit bit field + 8-bit mask defining the implemented bits.
Service Control
This is UPS specific control, read service manual for details
U16_T 16-bit, range -32768 … +32767.
5.3.5.1
CAN Traffic
The bridge will monitor the internal CAN bus for messages that have 0xD in the Source field of the routing identifier. The bridge will then modify the source solely to identify which bridge card the message is being transferred from, and transmit the message on the external CAN bus. The bridge will also monitor the external CAN bus for messages with a destination field that matches its identifier, all units identifier (0xE), or the “everyone” identifier (0xF). The bridge will then strip the destination and replace it with 0xD and transmit the message on the internal CAN bus.
5.3.5.2
CAN IDs
5.3.5.3
Baud Rates
The internal CAN bus is 1 Mbit and the external CAN bus is 250 Kbit.
5.3.5.4
Serial Port
The RS-232 serial port on the bridge card has two modes of operation. If the Serial Function (Command 0x04) is set to 0, the RS-232 will be a pass-through to the X-Slot interface. If the Serial Function is set to 1, the RS-232 will be a serial over CAN interface. The RS-232 serial port on the bridge card will be controlled by a serial to CAN routine to pass the information to the serial processing on the Control Board (or Mini-CSB).
5-26
© 2006 - Eaton Corporation
9355 20 – 30 kVA
5.3.6
Connectivity and Communication
HyperTerminal
5.3.6.1
HyperTerminal Emulation Configuration for the Powerware® 9355 UPS 1.
Click on the Start Button, go to Programs, go to Accessories, go to Communications, Click on HyperTerminal, Figure 36.
Figure 36.
2.
Path to HyperTerminal Application
Click on HyperTerminal.exe Enter a name for the emulation and select an icon, when complete Select OK, Figure 37.
Figure 37.
HyperTerminal Opening Screen Selections © 2006 - Eaton Corporation
5-27
Connectivity and Communication
3.
The Connect To window appears, Connect using: COM1 or COM2 – Select OK after selecting the active serial port from the drop-down menu, Figure 38.
Figure 38.
4.
9355 20 – 30 kVA
Select COM1 or COM2 from the drop-down menu
When the COM1 or COM2 Properties window appears, make the following selections on the screen, Figure 39: -
Bits per second: 19200 Data Bits: 8 Parity: None Stop Bits: 1 Flow Control: None when complete select OK
Figure 39.
5-28
Port Parameter Setup
© 2006 - Eaton Corporation
9355 20 – 30 kVA
5.
Connectivity and Communication
Go to the File menu on the Menu bar, click on Properties, Figure 40.
Figure 40.
File, Properties menu options, Settings tab, Emulation drop-down
6.
The Properties window comes up, click on the Tab labeled Settings, Figure 40.
7.
In the window click on the Emulation drop-down menu and select ANSI - Go to the View menu on the Menu bar, click on Font, ensure that the Font selected is Terminal
Figure 41.
Font Settings menu
When you have completed the previous instructions – don’t forget to save your new emulation. Go to File and select Save. The following functions are available in the Terminal Emulation: •
ESC B – Battery Test Queue
•
ESC L – Set to Print out the History Log, see para 5.2.4.3.
These buttons should be pressed sequentially, not simultaneously. Failure to follow this procedure may cause communications to lock-up. Example: Press and release the ESC key, wait 2 seconds and press the L (log history) key. © 2006 - Eaton Corporation
5-29
Connectivity and Communication
9355 20 – 30 kVA
This page was intentionally left blank.
5-30
© 2006 - Eaton Corporation
6 Options Chapter 6 Options 6.1 Communications and Connectivity Options 6.1.1 Single Port RS-232 Serial or AS/400 Signal Card 6.1.2 Multi-Port/Multi-Server Card 6.1.3 Low Voltage (LV) Relay Interface Card 6.1.4 High Voltage (HV) Industrial Relay / RMP Interface Card 6.1.5 ConnectUPS Network Adapters 6.1.6 MODBUS Communications Card 6.1.7 Modem Card 6.1.8 USB Module 6.1.9 CAN Bridge Card 6.1.10 Remote Monitor 6.2 Options Cabinet 6.3 Power Distribution Unit (PDU) 6.4 Remote Power Panel (RPP) 6.4.1 IQ 100 Series RPP 6.4.2 IQ 200 Series RPP
© 2006 - Eaton Corporation
6-2 6-2 6-3 6-5 6-7 6-8 6-9 6-10 6-13 6-14 6-14 6-15 6-18 6-19 6-19 6-19
6-1
Options
9355 20 – 30 kVA
6.1 Communications and Connectivity Options 6.1.1
Single Port RS-232 Serial or AS/400 Signal Card
Figure 42.
Single Port Serial Card
This card makes an additional RS-232 communications port available, and AS/400 interface signals via open collector outputs, containing the following signals: •
PS Available/On Bypass
•
Utility Failure
•
Low Battery
Connection to the card is accomplished with a single DB9 female connector:
6-2
Pin 1 = (OUT)
“Low Battery” signal (Open Collector (O.C.)
Pin 2 = (OUT)
TXD Transmit to external device
Pin 3 = (IN)
RXD Receive from external device
Pin 4 = (IN)
DTR PnP from external device
Pin 5 = (GND)
Signal common
Pin 6 = (OUT)
DSR Module Ready to external device
Pin 7 = (IN/OUT)
RTS PnP from external device (default) or “On Bypass” signal (O.C.) (jumper-selectable)
Pin 8 = (OUT)
“AC Fail” signal (O.C.)
Pin 9 = (OUT)
Power Source +V (8 to 24 volts DC power)
© 2006 - Eaton Corporation
9355 20 – 30 kVA
6.1.2
Options
Multi-Port/Multi-Server Card
Figure 43.
Multi-Port Serial Card
This card provides multiple RS-232 ports for communications between several UPS modules or multiple computer servers and is available for use on any of the provided X-Slots. Six (6) DB-9 female connectors (COM1 – COM6) are provided. COM1 (configuration port) supports both RS-232 and AS/400 signals. AS/400 signals are all open collector type outputs: •
UPS Available/On Bypass
•
Utility Failure
•
Low Battery
Pin 1 = (OUT)
“Low Battery” signal (Open Collector (O.C.))
Pin 2 = (OUT)
TXD Transmit to external device
Pin 3 = (IN)
RXD Receive from external device
Pin 4 = (IN)
DTR PnP from external device
Pin 5 = (GND)
Signal common
Pin 6 = (OUT)
DSR Module Ready to external device
Pin 7 = (IN/OUT)
RTS PnP from external device (default) or “On Bypass” signal (O.C.) (jumper-selectable)
Pin 8 = (OUT)
“AC Fail” signal (O.C.)
Pin 9 = (OUT)
Power Source +V (8 to 24 volts DC power)
© 2006 - Eaton Corporation
6-3
Options
9355 20 – 30 kVA
COM2 – COM6 are RS-232, but only configurable for the following modes:
6-4
•
Terminal
•
Computer (XCP)
•
Modem
Pin 1 = (IN)
DCD input
Pin 2 = (OUT)
TXD Transmit to external device
Pin 3 = (IN)
RXD Receive from external device
Pin 4 = (IN)
DTR PnP from external device
Pin 5 = (GND)
Signal common
Pin 6 = (OUT)
DSR .Module Ready” to external device
Pin 7 = (IN)
RTS From external device
Pin 8 = (OUT)
CTS To external device
Pin 9 = (OUT)
Power Source +V (8 to 24 VDC power) Out
© 2006 - Eaton Corporation
9355 20 – 30 kVA
6.1.3
Options
Low Voltage (LV) Relay Interface Card
Figure 44.
Low Voltage Relay Interface Card
This card provides true FORM C relay contacts (NC and NO) through two methods which are: 1) a single 15 point terminal block, and 2) a single two row DB-15 male connector. Table 37. Low Voltage Relay Interface Contacts RELAY #
SYSTEM STATE
K1: Utility Fail
D15 / TB1
CONTACT *
1
C
Utility OK
2
NC
Utility Failure
3
NO
4
C
Normal Battery
5
NC
Low Battery
6
NO
7
C
UPS Alarm
8
NC
UPS OK
9
NO
10
C
On Bypass
12
NC
On Inverter
11
NO
LV Supply **
13
+12 VDC
14
C
15
(IN)
K2: Battery
K3: UPS Alarm
K4: Bypass
UPS Shutdown **
* - Normally Closed (NC) and Normally Open (NO) are indicated when the card / relay is de-energized. ** - To activate a UPS shutdown via an external contact closure, the UPS shutdown input (Pin 15) must be held high (+12VDC) for a minimum of 5 seconds. Relay contacts are rated for a maximum 1A at 30VAC or 200 ma at 60 VDC. All relay outputs are galvanically isolated from other circuits in the UPS (IEC 950, EN 50091-1). © 2006 - Eaton Corporation
6-5
Options
9355 20 – 30 kVA
NOTES: The shut down function is only supported by single-phase products. The relay contacts must not be galvanically connected to any mains connected circuits. Do not use Pin 13 (+12 VDC) as a power supply source to support external devices. Reinforced insulation to the mains is required for equipment and cables connected to these devices.
6-6
© 2006 - Eaton Corporation
9355 20 – 30 kVA
6.1.4
Options
High Voltage (HV) Industrial Relay / RMP Interface Card
Figure 45.
High Voltage Industrial Relay Card
This card provides both an RMP signal interface and four sets of Form C relay contacts serving as both an RMP driver and a Relay Interface Module (RIM). The RMP signals and relay status contacts can be used simultaneously but cannot be programmed separately. RMP Signal Interface:
J1 (6 total positions, 2 plugs, 3 positions each)
Relay Contact Interface: J2 (12 total positions, 4 plugs, 3 positions each) The Industrial Relay Card (IRC) can provide the following signals as shown in the following table: Table 38. High Voltage Relay Interface Contacts RELAY # K1: Utility Fail
K2: Bypass
K3: Battery
K4: UPS Alarm
SYSTEM STATE
J2
CONTACT *
1
NC
2
C
Utility Failure
3
NO
On Bypass
4
NC
5
C
On Inverter
6
NO
Normal Battery
7
NC
8
C
Low Battery
9
NO
UPS Alarm
10
NC
11
C
12
NO
Utility OK
UPS OK
* Normally Closed (NC) and Normally Open (NO) are indicated when the card / relay is de-energized.. Relay contacts are rated for a maximum 5A at 250 VAC or 1A at 60 VDC. All relay outputs are galvanically isolated from other circuits in the UPS (IEC 950, EN 50091-1).
© 2006 - Eaton Corporation
6-7
Options
9355 20 – 30 kVA
6.1.5
ConnectUPS Network Adapters
These devices provide UPS data to one or more computers over an Ethernet network. Board connections include: •
RJ-45 network connector
•
DB-9, RS-232 configuration port
There are several different vintages of these adapters: •
Classic (external enclosures, non-X-Slot)
•
Models M, MX, X
•
10 MB SNMP/Web Card Adapter
•
10/100 MB SNMP/Web/Hub Card Adapter
Figure 46.
10 Megabyte SNMP/Web
Figure 47. 6-8
10/100 Megabyte SNMP/Web/Hub
SNMP / Web / Hub Card Components © 2006 - Eaton Corporation
9355 20 – 30 kVA
6.1.6
Options
MODBUS Communications Card
Figure 48.
MODBUS Communications Card
The MODBUS card provides both RS-232 and RS-485 serial data to a customer’s Building Management System (BMS). Board connections include: •
Both a 2 wire and 4 wire topology
•
RS-232 and RS-485 Communications
•
RS-485 Hard Wire Terminal Block
•
RS-485 DB-9 MOD Bus Port
•
RS-232 DB-9 MOD Bus Port
•
RS-232 DB-9 Configuration Port
Figure 49.
MODBUS Communications Card Components
© 2006 - Eaton Corporation
6-9
Options
9355 20 – 30 kVA
Table 39. MODBUS Communications Card Connector Pins SIGNAL
RS-232 (DB-9F) RS-485 (DB-9F)
RS-485 (TB)
TxD (+)
2
2
1
RxD (+)
3
1
2
TxD (-)
-
7
3
RxD (-)
-
6
4
Signal Ground
5
5
5
6.1.7
Modem Card
Figure 50.
Modem Card
The X-SLOT Modem is made for UPS remote monitoring purpose. The modem card allows the unit to be connected to remote computers via a standard phone line connection. It is installed to UPS X-SLOT extension place and it offers one RJ-11 phone-jack connector for telephone network connection and four LEDs to indicate its status on its faceplate. There are also an on-board RS-232 port and DC-socket for the purpose of configuration which are not available when the Modem is installed in the UPS. The X-SLOT Modem is based on Conexant SocketModem or Multitech ModemModule chip. SocketModem is a fully functional modem that needs only +5 VDC and some external components for the interfaces to operate. The following will explain the functional parts of the modem board.
6-10
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Options
Figure 51.
6.1.7.1
X-Slot Modem Functional Parts
Functional Parts 1.
SocketModem chip (C9, M1, R2, R5) Fully functional modem chip. There are two alternative manufacturers: Conexant and Multitech.
2.
Jumpers (J1 - J3) These jumpers set modem behavior in terms of hardware signals. The assembly picture explains how to assemble these jumpers. By default, hardware signals are not used.
3.
Telephone network interface (F1, V9, X7) The telephone network interface consists of RJ-11 connectors and overvoltage-(V9) and overcurrent (F1) surge arresters.
4.
Indicator LEDs (R13 - R16, V1 - V4) Indicator LEDs shows modem status. There are four LEDs: Receiving (RX), Sending (TX), Data Carrier Detect (off-hook) (DCD) and Data Terminal Ready (that is, modem is ready (DTR)), which will nearly always be lit.
© 2006 - Eaton Corporation
6-11
Options
6-12
9355 20 – 30 kVA
5.
RS-232 interface (C4 - C8, D1, R17, X3) RS-232 interface consists of a 9-pin RS-232 port and MAX3232 voltage level conversion IC (D1). This port is for configuration purposes. Modem should be configured before it is assembled in the UPS.
6.
+5V DC-DC converter (C1 - C3, C10, L1, N1, R1, V5, V8) This circuit will make the operating voltage for the modem board. It will convert 8 - 25 VDC input from the X-SLOT +V to +5 VDC. This DC-DC converter is based on National Simple Switcher® IC (N1).
7.
Current limiter (C11, R3, R4, R7 - R11, V6, V7) The current limiter is situated between the X-SLOT +V (8-25 VDC) output and +5V DC-DC converter input. It protects UPS power supplies from overloading. Current is limited to under 550mA with transistor circuitry. Short-circuit protection is implemented with fusible resistors R3 and R4.
8.
DC-socket (X4) This DC-socket is for configuration purposes. 9 - 25 VDC is supplied via this connector when the modem board is configured.
9.
Faceplate screw terminals (X5, X6) The faceplate of the modem board is attached through these terminals. There is not any electrical connection between modem circuitry and faceplate terminals.
10.
X-SLOT connector (X1) The modem draws its power and communicates with the UPS through the X-SLOT connector when the modem is assembled into the UPS.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
6.1.8
Options
USB Module
The X-Slot Universal Serial Bus (USB) Module Card is an X-Slot connectivity device that allows your UPS system to communicate with a USB - compliant computer using LanSafe power management software.
Figure 52.
USB Module
The following requirements must be met to install the USB Module: •
A computer with a USB port
•
LanSafe III power management software (v4.15 or higher)
•
Microsoft Windows 98 or higher
© 2006 - Eaton Corporation
6-13
Options
9355 20 – 30 kVA
6.1.9
CAN Bridge Card
Figure 53.
CAN Bridge Card
A CAN Bridge Card is connected between two different CAN networks denoted the ICAN and ECAN. The CAN Bridge receives messages that are addressed to it and re-transmits these messages on the other network. Refer to Figure 53 of the CAN Bridge Card. The function of the CAN Bridge Card is to provide a translation interface between the internal CAN bus and the external CAN. One CAN Bridge Card per module is required for a 9355 parallel system. The bridge card also controls one relay, one building alarm, and an RS-232 serial port.
6.1.10
Remote Monitor
The Remote Monitor panel has a two-wire connection. The breakdown of the connections is shown below in Figure 54 CAN Bridge Card J3 Terminals.
J3
Building Alarm 2 replacement, or can be used for Pull-Chain wiring if Building Alarm 2 on TB1 is already in use.
Connections for Parallel System Control
Connections for Bypass Status
Figure 54. 6-14
Connections for RMP, RIM, or SCM
CAN Bridge Card J3 Terminals
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Options
6.2 Options Cabinet
NOTICE For more in-depth information about the Options Cabinet, including setup and installation, download the 9355 UPS 20/30kVA User’s Guide from www.Powerware.com.
The Options Cabinet is available in four models: 1.
Options Cabinet with a maintenance bypass switch that provides wrap-around bypass for UPS maintenance or service without shutting down the load, see Figure 55.
Options Cabinet with MBS Only L1 L2 L3 Input N N L1 L2 L3
Output
N N
Maintenance Bypass Auxiliary Contacts
Options Cabinet with MBS and Input Isolation Transformer L1 L2 Input L3
L1 L2 L3
Output
N N
Figure 55.
2.
Options Cabinet with MBS Wiring
Options Cabinet with both MBS and input isolation transformer that allows operation from a 208V, 480V, or 600V 60-Hz source (input transformer in single-feed systems or bypass transformer in dual-feed systems). © 2006 - Eaton Corporation
6-15
Options
9355 20 – 30 kVA
3.
Options Cabinet for dual-feed systems, see Figure 56, provides the second input from a 208V, 480V, or 600V 60-Hz source.
Second Options Cabinet with Rectifier Transformer
Second Options Cabinet with MBS Only
L1
L1
L2 Input
L2
L3
L3 Input N N L1 L2 L3
Output
N N
Maintenance Bypass Auxiliary Contacts
Figure 56.
6-16
Options Cabinet with Dual-Feed Wiring
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Options
4.
Options Cabinet with an output isolation transformer for 480V loads, see Figure 57.
Second Options Cabinet with Output Transformer
First Options Cabinet with MBS Only L1 L2 L3 Input N N
L1
L1
L2
L2
L3
Output
L3
N
N
N
N
Output
Maintenance Bypass Auxiliary Contacts
Figure 57.
Options Cabinet with Output Transformer Wiring
© 2006 - Eaton Corporation
6-17
Options
9355 20 – 30 kVA
6.3 Power Distribution Unit (PDU) The 9355 20-30kVA UPS module(s) may be connected to an optional Power Distribution Unit, see publication 164201641, Powerware PDU 30-300kVA. A three phase power input is wired to the input of the Power Distribution Unit (PDU) and distributed to numerous output panels (one to ten). Each of these output panels contains a main circuit breaker that feeds up to 42 smaller branch circuit breakers and / or sub-feed breakers. The branch circuit breakers can be single or multi-phase and are wired to the customers load. The PDU may also contain a transformer for isolation and/or voltage conversion.
6-18
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Options
6.4 Remote Power Panel (RPP) 6.4.1
IQ 100 Series RPP
Eaton’s Cutler-Hammer IQ 100 is designed for basic feeder applications where minimal data is required by the end user, see Figure 58. This simple-to-use meter provides accurate measurement and displays up to 12 electrical parameters including average voltage and current for the system, plus line-to-line and line-to-neutral measurements. As an option, frequency can also be monitored. The IQ 100 has programmable voltage and current transformer ratios and true RMS indication for accurate measurement of distorted waveforms, which can be viewed through four screens via a high visibility LED display. The IQ 100 is an invaluable tool for all power monitoring applications. There are two models in the IQ 100 series of meters: •
The IQ 110 models provide voltage and current measurement only.
•
The IQ 115 models provide frequency monitoring in addition to voltage and current measurement.
All other characteristics are identical in all meters in the IQ 100 series.
6.4.2
IQ 200 Series RPP
Eaton’s Cutler-Hammer IQ 200 compact size and flexible mounting capabilities make it perfectly suited for machine control panels such as panel board and switchboard mains and feeders, low voltage metal-enclosed switchgear feeders, motor control centers, and especially for individual load monitoring, see Figure 58. The base module can be display mounted, panel-mounted, DIN-rail mounted or side mounted. The display fits into a standard 1/4 DIN cutout, and for retrofit applications a 100mm ANSI collar is available. One IQ 200 provides an alternative to an assortment of individually wired and mounted ammeters, voltmeters, ammeter and voltmeter switches, watt-meters, var-meters, power factor meters, frequency meters, watt hour and demand meters. ANSI C12 Class 10 revenue metering accuracy make the IQ 200 an ideal choice for sub-metering and sub-billing applications. The IQ 200 can be easily programmed and monitored from the faceplate keypad which features a 4 line x 20 character LED back-lit LCD display. Opting for the compatible Eaton Cutler-Hammer Power Net system allows the user to program and monitor the meter remotely from a PC. Retrofit Opportunities: •
Retrofit of existing electrical distribution systems with the IQ 200 for load and energy monitoring
•
Five mounting options makes installation easier
© 2006 - Eaton Corporation
6-19
Options
9355 20 – 30 kVA
IQ 100 series Figure 58.
6-20
IQ 200 series
Remote Power Panels Series 100 and 200
© 2006 - Eaton Corporation
7 Troubleshooting and Maintenance 7.1 Troubleshooting Charts 7.1.1
Action Levels
The following table explains the various action levels and actions taken for the Powerware® 9355. This table is to be used when determining a course of action to respond to a system event generated by the UPS Events or Web Card. See paragraph 7.1.2 and paragraph 7.1.4 for Failure Analysis. Table 40. 9355 Action Levels Name of Action Level
Description of Action to be Taken
Examples
Mon. SW Alert Level
Advisory
User should be aware that a condition exists which does not threaten the protected equipment, but that might need to be checked.
Building Alarm, Shutdown Scheduled, Some Events
Inform
Alarm Level 1 (User Alarm - User action required)
The User should note the condition and may need to take immediate action. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Alarm Lamp will light when the associated bit is active.
Check Modem, Battery Voltage Low, and so on.
Major
Alarm Level 2
Not defined.
Alarm Level 3 (Shutdown is Imminent)
This alarm condition indicates that shutdown of the UPS could occur. The Shutdown could result in a load loss. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Alarm Lamp will light when the associated bit is active.
Load Over 100%, OverTemperature, and so on.
Critical
Alarm Level 4 (Schedule Service)
A condition in the UPS has been detected that requires servicing but could be scheduled and does not require immediate service. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Alarm Lamp
Check Battery, Redundant Fan Failure, and so on.
Minor
© 2006 - Eaton Corporation
7-1
Troubleshooting and Maintenance
9355 20 – 30 kVA
Table 40. 9355 Action Levels Name of Action Level
Description of Action to be Taken
Examples
Mon. SW Alert Level
will light when the associated bit is active. Alarm Level 5 A technically oriented alarm condition. The (Service Information) user should call for service to evaluate the condition. These conditions may clear but may indicate a pending problem. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Alarm Lamp will light when the associated bit is active.
7-2
Inverter Current Limit, Inverter Overload, Rectifier Overvoltage, DC Link Overvoltage
Minor
Alarm Level 6 (Service Required)
Service of the UPS is required. In some Inverter Failure, UPS products, the message is displayed on Fan Failure, and the Active Alarm/Notice Screen and the so on. Alarm Lamp will light when the associated bit is active.
Major
Command
UPS Control Commands
UPS ON, UPS OFF, and so on.
Inform
Immediate Service
A condition exists which can threaten the protected equipment; it must be addressed today.
On Bypass, Fan Failure
Major
Load Power Off
The UPS is not providing power to the protected equipment at this time.
UPS Off by Command, DCUV
Critical
Non-Critical Shutdown
A condition exists in which the UPS may not be able to continue protecting all loads; non-critical equipment should be shutdown at this time.
Normal
None
(Normal)
Notice Level 1 (Information Only)
Notice conditions that are for Information only. These Notices require no action. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Notice Lamp will light when the associated bit is active.
Input AC Under Voltage, Equalizing Battery, and so on.
Inform
Notice Level 2 (User Interaction)
Notice conditions that tell the User to do something. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Notice Lamp will light when the associated bit is active.
User is being told to close the Input Breaker.
Minor
Notice Level 3 (Protection Level)
Notice conditions that inform the User that the level of load protection has increased or decreased. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Notice Lamp will light when the associated bit is active.
Bypass is Not Available, System Not Redundant, System Redundant, and so on.
Minor
Notice Level 4 (Investigate UPS)
The user should investigate the UPS. In some UPS products, the message is displayed on the Active Alarm/Notice Screen and the Notice Lamp will light when
Building Alarms, Emergency Transfer to Bypass
Minor
© 2006 - Eaton Corporation
Major
9355 20 – 30 kVA
Troubleshooting and Maintenance
Table 40. 9355 Action Levels Name of Action Level
Description of Action to be Taken
Examples
Mon. SW Alert Level
the associated bit is active. Notice Level 5
Not Defined.
Notice Level 6
Not Defined
Notification
Simple Event Notification; no action required
Some Events
Inform
OFF
An Indicator, LED, or Switch is OFF; no action required.
Front Panel LED
Inform
ON
An Indicator, LED, or Switch is ON; no action required.
Front Panel LED
Inform
Safety Hazard
A condition exists which may imperil personnel near the UPS.
Door Ajar with Voltage Present
Major
Schedule PM
A condition exists which must be addressed Battery Health by scheduling service for the UPS. Low
Minor
Service Status (Information Only)
Status conditions that are service oriented
Inverter On, Input Filter closed
Inform
Shutdown Required
The UPS can only provide power to the protected equipment for less than the configured Low Battery Warning Time; all protected equipment should commence shutdown procedures immediately.
Low Battery Shutdown Pending, Shutdown Imminent
Critical
User Status (Information Only)
Status conditions that are User oriented.
On Battery, Unit Normal, Input Breaker Closed
Inform
Warning
User should be aware that a condition exists which does not currently threaten the protected equipment but that it indicates an underlying problem and may lead to a situation that will.
On Battery Battery not charged, Output Overload
Minor
7.1.2
Alarm, Notice, Status & Flag Definitions
The following are lists of all the various notices and alarms that can be annunciated or acted on by the Powerware® 9355 UPS. Use these charts with the charts in paragraph 7.1.2, Action Levels and paragraph 7.1.4, Failure Analysis to determine the course of action. The functional descriptions are also an excellent source for determining the expected machine states during start up and shut down. This can help narrow down which board is generating the problem error.
© 2006 - Eaton Corporation
7-3
Troubleshooting and Maintenance
9355 20 – 30 kVA
Definitions (Alarm # = Node Bit #)(Listed in alphabetical order of LCD Description) for PW9355 Alarm #
7-4
LCD Description
Web card description
Comments
Notes After replacing SCRs, using the XCP Tool, Options Tab, enable auto freq detect. Shut the unit down completely (no logic power) and restart. Unit will autoconfig and auto freq will disable.
222
Abnormal output voltage at startup
The output condition (other than Output Overload) is out of tolerance
Voltage detected on the output when there shouldn't be any (bypass SCRs assumed bad)
203
Ambient over temperature
UPS Temperature Alarm condition exists
Ambient temperature sensor reads higher than limit (45ºC)
202
Ambient under temperature
UPS Temperature Alarm condition exists
This alarm is listed in the alarm block, but is never set in DSP firmware
219
Autocalibration Failed
UPS General System Test failed
An attempt to automatically (re-) calibrate the UPS has failed.
206
Automatic shutdown pending
UPS turn off countdown underway
Unit has received scheduled off command from XCP
199
Batteries disconnected
Replace Battery Warning condition exists
Battery circuit breaker open, or voltage less than disconnected limit
107
Battery contactor open
UPS Circuit Breaker Alarm condition exists
Signal input, disables charger
47
Battery current limit
UPS hardware fault detected
Hardware current limit trip, Unit saw boost or charger current reached the hardware limit for 20 consecutive line cycles
68
Battery DC over-voltage
UPS hardware fault detected
Battery voltage higher than 50mV/cell above charger float voltage, shunt trips battery breaker
56
Battery low
Low Battery Alarm present
Battery voltage is below configured level (1.88V/cell). Only active if unit is on battery
© 2006 - Eaton Corporation
9355 20 – 30 kVA Alarm #
LCD Description
Troubleshooting and Maintenance Web card description
Comments
149
Battery needs service
Replace Battery Warning condition exists
Detected reversed battery polarity
191
Battery test failed
Replace Battery Warning condition exists
1 or more of the ABM battery tests failed, see ABM documentation
256
Battery Test in Progress
A UPS Notice condition exists
A Battery Test has begun.
19
Building alarm 1
One of the defined building alarms has occurred
Signal input, user configurable
18
Building alarm 2
One of the defined building alarms has occurred
Signal input, user configurable
17
Building alarm 3
One of the defined building alarms has occurred
Signal input, user configurable
16
Building alarm 4
One of the defined building alarms has occurred
Signal input, user configurable
15
Building alarm 5
One of the defined building alarms has occurred
Signal input, user configurable
14
Building alarm 6
One of the defined building alarms has occurred
Signal input, user configurable
3
Bypass ac over voltage
UPS bypass unavailable
Bypass voltage is > user configured over voltage level.
4
Bypass ac under voltage
UPS bypass unavailable
Bypass voltage is < user configured over voltage level.
33
Bypass breaker fail
A Relay, Contactor, or Breaker has failed
Bypass voltage is detected at startup (should be mapped to alarm #195, "Back-feed contactor failure")
188
Bypass failure
A Relay, Contactor, or Breaker has failed
DSP cannot read status of bypass pic, or bypass pic is not changing states when commanded to
105
Bypass not available
UPS bypass unavailable
Bypass voltage and/or frequency is out of configured limits, bypass transfer is not allowed
© 2006 - Eaton Corporation
Notes
7-5
Troubleshooting and Maintenance Alarm #
7-6
LCD Description
9355 20 – 30 kVA Web card description
UPS bypass unavailable
Comments
119
Bypass phase rotation
Indicates bypass phase displacement is different from inverter phase displacement, bypass transfer is not allowed
109
Bypass Switchgear Open
38
Bypass Uncalibrated
A UPS Notice condition exists
This is a warning that the autocalibration has failed, while calibrating Bypass sensor.
5
Bypass under/over frequency
UPS bypass unavailable
Bypass frequency is outside of user configured window
21
Charger over temperature
An internal temperature is out of tolerance
Battery converter / Charger IGBT module temperature exceeds its limit
249
Charger over temperature shutdown
An internal temperature is out of tolerance
Boost IGBT temperature exceeded shutdown level (90ºC)
140
Charger Status
Not Applicable
The charger is on.
121
Check Parallel Board
UPS hardware fault detected
The board used for paralleling control appears to have failed.
36
Check Static Switch
A Relay, Contactor, or Breaker has failed
Static switch fault: The static switch appears to have failed.
224
Configuration error
UPS hardware fault detected
EEROM error. Eeprom section does not match mirror, eeprom section needed to be rebooted, or eeprom version is higher than code supports (back rev)
241
Contact Service (battery test failed)
UPS hardware fault detected
Battery failed to reach float voltage in time allowed
244
Contact service (illegal instruction)
UPS hardware fault detected
Internal CPU error
The bypass breaker is open.
© 2006 - Eaton Corporation
Notes Using the XCP Tool, Options Tab, enable auto freq detect. Shut the unit down completely (no logic power) and restart. Unit will autoconfig and auto freq will disable.
9355 20 – 30 kVA Alarm #
Troubleshooting and Maintenance
LCD Description
Web card description
Comments
138
Control Power Status
N.A.
Control power has been applied. This status is set when the controls first power up. It is used to record the date and time of return of power after a power fail.
146
CPU ISR error
UPS hardware fault detected
This alarm is listed in the alarm block, but is never set in DSP firmware
28
dc link over voltage
UPS hardware fault detected
Either positive rail was greater than 250V, or negative rail was less than 250V
29
dc link under voltage
UPS hardware fault detected
Either positive rail was less than 100V, or negative rail was greater than -100V
178
DC Start Occurred
N.A.
The UPS has been started on battery when AC input power is not present. This alarm is used to record the date and time of this event.
42
DC Voltage Uncalibrated
A UPS Notice condition exists
This is a warning that unit is not calibrated.
193
Fan failure
The failure of one or more fans in the UPS has been detected
Fan tach pulses are too slow
95
From Bypass Command
191
Fuse failure
The UPS batteries need to be replaced (IETF).
If no separate bypass input, is set if bypass voltage is not equal to utility voltage. Also set if no inverter voltage when the inverter is turned on.
73
Heatsink Over Temperature
An internal temperature is out of tolerance
Heat sink fault: the heat sink temperature at an unspecified module exceeds the upper temperature limit for normal operation
Notes
A command has been received to transfer the load from bypass to the inverter. This command may come from a local control panel or from a remote source.
© 2006 - Eaton Corporation
7-7
Troubleshooting and Maintenance Alarm #
7-8
LCD Description
9355 20 – 30 kVA Web card description
Comments
74
Heatsink temperature sensor fail
UPS hardware fault detected
Rectifier/inverter IGBT sensor or ambient temp sensor read either unreasonably high or low, indicating open/shorted sensor
212
Incoming Modem Call Started
N.A.
A modem connected to the UPS has received an incoming call and has begun to negotiate a connection.
6
Input ac over voltage
Utility power has failed
Input voltage is greater then eeprom limit (144VAC), unit can't run utility, is on battery
8
Input under/over frequency
Utility power has failed
Input frequency is outside of limits (45-65Hz for normal unit, 55-65Hz for transformer unit) Unit is on battery
1
Inverter ac under voltage
UPS Inverter fault detected
Set if phase-to-phase or phase-to-neutral voltage is < 90% of set point.
221
Inverter output failed
UPS Inverter fault detected
Fast inverter UV, inverter voltage outside window limit
27
Inverter output over current
UPS Output overloaded
Hardware current limit trip, Unit saw inverter current reached the hardware limit for 20 consecutive line cycles
24
Inverter over temperature
An internal temperature is out of tolerance
Inverter IGBT temperature sensor is reading higher than eeprom limit (80ºC). Has 2 levels 80ºC is warning level, 90ºC is transfer to bypass if available, dump load if not.
111
Inverter Over Temperature Trip
An internal temperature is out of tolerance
The inverter temperature has exceeded it s rating operating temperature.
48
Inverter startup failure
UPS Inverter fault detected
Startup alarm, inverter alarm present when inverter is started, inverter voltage below limit, output voltage present when inverter started (SCR failure)
139
Inverter Status
N.A.
The inverter is on. © 2006 - Eaton Corporation
Notes
9355 20 – 30 kVA Alarm #
Troubleshooting and Maintenance
LCD Description
Web card description
Comments
41
Inverter Uncalibrated
A UPS Notice condition exists
This is a warning that the autocalibration has failed, while calibrating inverter.
159
L1 Overload
UPS Output overloaded
PHA VA or watts greater than 111% UPS rating
165
L1 Overload (Extreme Level)
UPS Output overloaded
PHA VA or watts greater than 149% UPS rating
162
L1 Overload (High Level)
UPS Output overloaded
PHA VA or watts greater than 126% UPS rating
160
L2 Overload
UPS Output overloaded
PHB VA or watts greater than 111% UPS rating
166
L2 Overload (Extreme Level)
UPS Output overloaded
PHB VA or watts greater than 149% UPS rating
163
L2 Overload (High Level)
UPS Output overloaded
PHB VA or watts greater than 126% UPS rating
161
L3 Overload
UPS Output overloaded
PHC VA or watts greater than 111% UPS rating
167
L3 Overload (Extreme Level)
UPS Output overloaded
PHC VA or watts greater than 149% UPS rating
164
L3 Overload (High Level)
UPS Output overloaded
PHC VA or watts greater than 126% UPS rating
170
Load Dumped (Load Power Off)
UPS output has been turned off
No power is being provided to the load (load dump). This alarm is used to record the date and time of a power-off event.
173
Load Off Command Received
N.A.
A load control command to turn OFF the/an output has been issued to the UPS (may be with a delay). This alarm is used to record the date and time of this event.
172
Load Power On Command Received
N.A.
A load control command to turn ON the/an output has been issued to the UPS (may be with a delay). This alarm is used to record the date and time of this event.
174
Low battery shutdown
UPS Battery completely discharged
Battery voltage is less than 1.75V/cell, 1 minute shutdown timer is started
143
Maintenance Bypass Mode
The UPS has been placed on Maintenance / Manual Bypass by an
The load is being supplied power by a wrap-around maintenance bypass switch.
© 2006 - Eaton Corporation
Notes
7-9
Troubleshooting and Maintenance Alarm #
LCD Description
9355 20 – 30 kVA Web card description
Comments
operator
216
Modem call completion failed
N.A.
A modem connected to the UPS has failed to successfully complete a transaction sequence as expected.
214
Modem Connection Established
N.A.
A modem connected to the UPS has established a connection with a remote modem or paging service.
211
Modem failed
N.A.
Can’t communicate with modem
53
Non-volatile RAM failure
UPS General System Test failed
EEPROM has failed
213
Outgoing Modem Call Started
N.A.
A modem connected to the UPS has gone off hook and has begun to either dial a number or negotiate a connection.
10
Output ac under voltage
The output condition (other than Output Overload) is out of tolerance
This alarm is listed in the alarm block, but is never set in DSP firmware
25
Output overload
UPS Output overloaded
Greater than 102% load on any output phase
58
Output Short Circuit
The output condition (other than Output Overload) is out of tolerance
Output short circuit detected
72
Power supply 12 volt fault
UPS hardware fault detected
Digital input from control board power supply monitoring chip
71
Power supply 5 volt fault
UPS hardware fault detected
Digital input from control board power supply monitoring chip
70
Power supply failure
UPS hardware fault detected
One of the internal power supplies is failed
30
Rectifier failed
An uncorrected problem has been detected within the UPS charger subsystem
Startup failure, either rectifier didn't report "normal" status or was unable to maintain dc link voltage after rail precharge.
7-10
© 2006 - Eaton Corporation
Notes
9355 20 – 30 kVA Alarm #
LCD Description
Troubleshooting and Maintenance Web card description
Comments
26
Rectifier input over current
UPS hardware fault detected
Hardware current limit trip, Unit saw rectifier current reached the hardware limit for 20 consecutive line cycles
223
Rectifier over temperature
An internal temperature is out of tolerance
Rectifier IGBT temperature sensor is reading higher than eeprom limit (80ºC). Has 2 levels 80ºC is warning level, 90ºC is transfer to bypass if available, dump load if not.
225
Redundancy Loss Due To Overload
In a parallel UPS system, one of the power modules has failed or the specified power rating has been exceeded
The specified power rating of an "n+1" parallel system has been exceeded. The load is supported, but the system lacks redundant protection while this overload persists.
12
Remote emergency power off
UPS output has been turned off
Signal input, output is deenergized and battery breaker is tripped. Output can't be energized while active
220
Selective Trip Of Module
One module in a parallel or multiple component system has failed
A UPS module has been automatically removed from a parallel system, usually due to improper load sharing or other fault.
55
Shutdown imminent
UPS Shutdown Imminent Alarm condition exists
UPS will shut the load down, either from low battery or delay UPS off command pending
194
Site fault
UPS hardware fault detected
Measure chassis voltage too high measured against neutral
176
Software incompatibility detected
UPS General System Test failed
Wrong PLD version, wrong DSP rev, wrong unit
229
System Alarm Active
A System / Subsystem Alarm is active
Critical Alert (Summary Alarm): If non-zero, there is at least one severe alarm active at the system level at this time.
© 2006 - Eaton Corporation
Notes
7-11
Troubleshooting and Maintenance Alarm #
LCD Description
9355 20 – 30 kVA Web card description
Comments
132
System Not Redundant
In a parallel UPS system, one of the power modules has failed or the specified power rating has been exceeded
For an "n+1" parallel system, the load is supported, but the system is no longer has redundant protection.
257
System Test in Progress
A UPS Notice condition exists
One of the Systems Tests has begun.
258
Test Aborted
A UPS Notice condition exists
A Battery or Systems Test has been aborted while running due to conditions or operator command, or was inhibited from starting.
94
To bypass command
UPS internally bypassed
Signal input used to send unit to bypass
201
Transformer over temperature
An internal temperature is out of tolerance
Signal input
237
UPS Normal
N.A.
The UPS is in its normal operating mode of operation.
168
UPS on battery
UPS switched to battery power
UPS is on battery
169
UPS on bypass
UPS internally bypassed
UPS is on bypass
248
UPS on generator
The system is being powered by its Alternate Power Source
Signal input
57
Utility fail
Utility power has failed
Utility voltage or frequency outside limits. Does not necessarily mean unit is on battery.
59
Utility not present
Utility power has failed
Utility voltage is outside limits, unit is on battery
192
Alarm # 1
7-12
Notes
The failure of one or more fuses has been detected
LCD Description Inverter AC under voltage
Web card description
Comments
UPS Inverter fault detected
Set if Phase to phase or phase to neutral voltage is < 90% of setpoint.
© 2006 - Eaton Corporation
Notes
9355 20 – 30 kVA Alarm #
LCD Description
Troubleshooting and Maintenance Web card description
Comments
3
Bypass ac over voltage
UPS bypass unavailable
Bypass voltage is > user configured over voltage level.
4
Bypass ac under voltage
UPS bypass unavailable
Bypass voltage is < user configured over voltage level.
5
Bypass under/over frequency
UPS bypass unavailable
Bypass frequency is outside of user configured window
6
Input ac over voltage
Utility power has failed
Input voltage is greater then eeprom limit (144Vac), unit can't run utility, is on battery
8
Input under/over frequency
Utility power has failed
Input frequency is outside of limits (45-65Hz for normal unit, 55-65Hz for transformer unit) Unit is on battery
10
Output ac under voltage
The output condition (other than Output Overload) is out of tolerance
This alarm is listed in the alarm block, but is never set in DSP firmware
12
Remote emergency power off
UPS output has been turned off
Signal input, output is deenergized and battery breaker is tripped. Output can't be energized while active
14
Building alarm 6
One of the defined building alarms has occurred
Signal input, user configurable
15
Building alarm 5
One of the defined building alarms has occurred
Signal input, user configurable
16
Building alarm 4
One of the defined building alarms has occurred
Signal input, user configurable
17
Building alarm 3
One of the defined building alarms has occurred
Signal input, user configurable
18
Building alarm 2
One of the defined building alarms has occurred
Signal input, user configurable
19
Building alarm 1
One of the defined building alarms has occurred
Signal input, user configurable
© 2006 - Eaton Corporation
Notes
7-13
Troubleshooting and Maintenance Alarm #
LCD Description
9355 20 – 30 kVA Web card description
Comments
21
Charger over temperature
An internal temperature is out of tolerance
Battery converter / Charger IGBT module temperature exceeds it's limit
24
Inverter over temperature
An internal temperature is out of tolerance
Inverter IGBT temperature sensor is reading higher than eeprom limit (80ºC). Has 2 levels 80ºC is warning level, 90ºC is transfer to bypass if available, dump load if not.
25
Output overload
UPS Output overloaded
Greater than 102% load on any output phase
26
Rectifier input over current
UPS hardware fault detected
Hardware current limit trip, Unit saw rectifier current reached the hardware limit for 20 consecutive line cycles
27
Inverter output over current
UPS Output overloaded
Hardware current limit trip, Unit saw inverter current reached the hardware limit for 20 consecutive line cycles
28
dc link over voltage
UPS hardware fault detected
Either positive rail was greater than 250V, or negative rail was less than -250V
29
dc link under voltage
UPS hardware fault detected
Either positive rail was less than 100V, or negative rail was greater than -100V
30
Rectifier failed
An uncorrected problem has been detected within the UPS charger subsystem
Startup failure, either rectifier didn't report "normal" status or was unable to maintain dc link voltage after rail precharge.
33
Bypass breaker fail
A Relay, Contactor, or Breaker has failed
Bypass voltage is detected at startup (should be mapped to alarm #195, "Back-feed contactor failure")
36
Check Static Switch
A Relay, Contactor, or Breaker has failed
Static switch fault: The static switch appears to have failed.
38
Bypass Uncalibrated
A UPS Notice condition exists
This is a warning that the auto calibration has failed, while calibrating Bypass sensor.
7-14
© 2006 - Eaton Corporation
Notes
9355 20 – 30 kVA
Troubleshooting and Maintenance
Alarm #
LCD Description
Web card description
Comments
41
Inverter Uncalibrated
A UPS Notice condition exists
This is a warning that the auto calibration has failed, while calibrating inverter.
42
DC Voltage Uncalibrated
A UPS Notice condition exists
This is a warning that unit is not calibrated.
47
Battery current limit
UPS hardware fault detected
Hardware current limit trip, Unit saw boost or charger current reached the hardware limit for 20 consecutive line cycles
48
Inverter startup failure
UPS Inverter fault detected
Startup alarm, inverter alarm present when inverter is started, inverter voltage below limit, output voltage present when inverter started (SCR failure)
53
Non-volatile RAM failure
UPS General System Test failed
EEPROM has failed
55
Shutdown imminent
UPS Shutdown Imminent Alarm condition exists
UPS will shut the load down, either from low battery or delay UPS off command pending
56
Battery low
Low Battery Alarm present
Battery voltage is below configured level (1.88V/cell). Only active if unit is on battery
57
Utility fail
Utility power has failed
Utility voltage or frequency outside limits. Does not necessarily mean unit is on battery.
58
Output Short Circuit
The output condition (other than Output Overload) is out of tolerance
Output short circuit detected
59
Utility not present
Utility power has failed
Utility voltage is outside limits, unit is on battery
68
Battery dc overvoltage
UPS hardware fault detected
Battery voltage higher than 50mV/cell above charger float voltage, shunt trips battery breaker
70
Power supply failure
UPS hardware fault detected
One of the internal power supplies is failed
71
Power supply 5 volt fault
UPS hardware fault detected
Digital input from control board power supply monitoring chip
© 2006 - Eaton Corporation
Notes
7-15
Troubleshooting and Maintenance
9355 20 – 30 kVA
Alarm #
LCD Description
72
Power supply 12 volt fault
UPS hardware fault detected
Digital input from control board power supply monitoring chip
73
Heatsink Over Temperature
An internal temperature is out of tolerance
Heat sink fault: the heat sink temperature at an unspecified module exceeds the upper temperature limit for normal operation
74
Heatsink temperature sensor fail
UPS hardware fault detected
Rectifier/inverter IGBT sensor or ambient temp sensor read either unreasonably high or low, indicating open/shorted sensor
94
To bypass command
UPS internally bypassed
Signal input used to send unit to bypass
95
From Bypass Command
105
Bypass not available
UPS bypass unavailable
Bypass voltage and/or frequency is out of configured limits, bypass transfer is not allowed
107
Battery contactor open
UPS Circuit Breaker Alarm condition exists
Signal input, disables charger
109
Bypass Switchgear Open
111
Inverter Over Temperature Trip
An internal temperature is out of tolerance
The inverter temperature has exceeded it s rating operating temperature.
119
Bypass phase rotation
UPS bypass unavailable
Indicates bypass phase displacement is different from inverter phase displacement, bypass transfer is not allowed
121
Check Parallel Board
UPS hardware fault detected
The board used for paralleling control appears to have failed.
7-16
Web card description
Comments
A command has been received to transfer the load from bypass to the inverter. This command may come from a local control panel or from a remote source.
The bypass breaker is open.
© 2006 - Eaton Corporation
Notes
9355 20 – 30 kVA Alarm #
LCD Description
Troubleshooting and Maintenance Web card description
Comments
132
System Not Redundant
In a parallel UPS system, one of the power modules has failed or the specified power rating has been exceeded
For an "n+1" parallel system, the load is supported, but the system is no longer has redundant protection.
138
Control Power Status
N.A.
Control power has been applied. This status is set when the controls first power up. It is used to record the date and time of return of power after a power fail.
139
Inverter Status
N.A.
The inverter is on.
140
Charger Status
N.A.
The charger is on.
143
Maintenance Bypass Mode
The UPS has been placed on Maintenance / Manual Bypass by an operator
The load is being supplied power by a wrap-around maintenance bypass switch.
146
CPU ISR error
UPS hardware fault detected
This alarm is listed in the alarm block, but is never set in DSP firmware
149
Battery needs service
Replace Battery Warning condition exists
Detected reversed battery polarity
159
L1 Overload
UPS Output overloaded
PHA VA or watts greater than 111% UPS rating
160
L2 Overload
UPS Output overloaded
PHB VA or watts greater than 111% UPS rating
161
L3 Overload
UPS Output overloaded
PHC VA or watts greater than 111% UPS rating
162
L1 Overload (High Level)
UPS Output overloaded
PHA VA or watts greater than 126% UPS rating
163
L2 Overload (High Level)
UPS Output overloaded
PHB VA or watts greater than 126% UPS rating
164
L3 Overload (High Level)
UPS Output overloaded
PHC VA or watts greater than 126% UPS rating
165
L1 Overload (Extreme Level)
UPS Output overloaded
PHA VA or watts greater than 149% UPS rating
166
L2 Overload (Extreme Level)
UPS Output overloaded
PHB VA or watts greater than 149% UPS rating
167
L3 Overload (Extreme Level)
UPS Output overloaded
PHC VA or watts greater than 149% UPS rating
© 2006 - Eaton Corporation
Notes
7-17
Troubleshooting and Maintenance Alarm #
LCD Description
9355 20 – 30 kVA Web card description
Comments
168
UPS on battery
UPS switched to battery power
UPS is on battery
169
UPS on bypass
UPS internally bypassed
UPS is on bypass
170
Load Dumped (Load Power Off)
UPS output has been turned off
No power is being provided to the load (load dump). This alarm is used to record the date and time of a power off event.
172
Load Power On Command Received
N.A.
A load control command to turn ON the/an output has been issued to the UPS (may be with a delay). This alarm is used to record the date and time of this event.
173
Load Off Command Received
N.A.
A load control command to turn OFF the/an output has been issued to the UPS (may be with a delay). This alarm is used to record the date and time of this event.
174
Low battery shutdown
UPS Battery completely discharged
Battery voltage is less than 1.75V/cell, 1 minute shutdown timer is started
176
Software incompatibility detected
UPS General System Test failed
Wrong PLD version, wrong DSP rev, wrong unit
178
DC Start Occurred
N.A.
The UPS has been started on battery when AC input power is not present. This alarm is used to record the date and time of this event.
188
Bypass failure
A Relay, Contactor, or Breaker has failed
DSP cannot read status of bypass pic, or bypass pic is not changing states when commanded to
191
Battery test failed
Replace Battery Warning condition exists
1 or more of the ABM battery tests failed, see ABM documentation
191
Fuse failure
The UPS batteries need to be replaced (IETF).
If no separate bypass input, is set if bypass voltage != utility voltage. Also set if no inverter voltage when inverter is turned on.
7-18
© 2006 - Eaton Corporation
Notes
9355 20 – 30 kVA Alarm #
LCD Description
192
Troubleshooting and Maintenance Web card description
Comments
Notes
The failure of one or more fuses has been detected
193
Fan failure
The failure of one or more fans in the UPS has been detected
Fan tach pulses are too slow
194
Site fault
UPS hardware fault detected
Measure chassis voltage too high measured against neutral
199
Batteries disconnected
Replace Battery Warning condition exists
Battery circuit breaker open, or voltage less than disconnected limit
201
Transformer overtemperature
An internal temperature is out of tolerance
Signal input
202
Ambient under temperature
UPS Temperature Alarm condition exists
This alarm is listed in the alarm block, but is never set in DSP firmware
203
Ambient over temperature
UPS Temperature Alarm condition exists
Ambient temperature sensor reads higher than limit (45ºC)
206
Automatic shutdown pending
UPS turn off countdown underway
Unit has received scheduled off command from XCP
211
Modem failed
N.A.
Can’t communicate with modem
212
Incoming Modem Call Started
N.A.
A modem connected to the UPS has received an incoming call and has begun to negotiate a connection.
213
Outgoing Modem Call Started
N.A.
A modem connected to the UPS has gone off hook and has begun to either dial a number or negotiate a connection.
214
Modem Connection Established
N.A.
A modem connected to the UPS has established a connection with a remote modem or paging service.
216
Modem call completion failed
N.A.
A modem connected to the UPS has failed to successfully complete a transaction sequence as expected.
219
Autocalibration Failed
UPS General System Test failed
An attempt to automatically (re-)
© 2006 - Eaton Corporation
7-19
Troubleshooting and Maintenance Alarm #
LCD Description
9355 20 – 30 kVA Web card description
Comments calibrate the UPS has failed.
220
Selective Trip Of Module
One module in a parallel or multiple component system has failed
A UPS module has been automatically removed from a parallel system, usually due to improper load sharing or other fault.
221
Inverter output failed
UPS Inverter fault detected
Fast inverter UV, inverter voltage outside window limit
222
Abnormal output voltage at startup
The output condition (other than OutputOverload) is out of tolerance
Voltage detected on the output when there shouldn't be any (bypass SCRs assumed bad)
223
Rectifier over temperature
An internal temperature is out of tolerance
Rectifier IGBT temperature sensor is reading higher than eeprom limit (80ºC). Has 2 levels 80ºC is warning level, 90ºC is transfer to bypass if available, dump load if not.
224
Configuration error
UPS hardware fault detected
EEROM error. Eeprom section does not match mirror, eeprom section needed to be rebooted, or eeprom version is higher than code supports (back rev)
225
Redundancy Loss Due To Overload
In a parallel UPS system, one of the power modules has failed or the specified power rating has been exceeded
The specified power rating of an "n+1" parallel system has been exceeded. The load is supported, but the system lacks redundant protection while this overload persists.
229
System Alarm Active
A System / Subsystem Alarm is active
Critical Alert (Summary Alarm): If non-zero, there is at least one severe alarm active at the system level at this time.
237
UPS Normal
N.A.
The UPS is in its normal operating mode of operation.
241
Contact Service (battery test failed)
UPS hardware fault detected
Battery failed to reach float voltage in time allowed
244
Contact service (illegal instruction)
UPS hardware fault detected
Internal CPU error
7-20
© 2006 - Eaton Corporation
Notes
9355 20 – 30 kVA Alarm #
LCD Description
Troubleshooting and Maintenance Web card description
Comments
248
UPS on generator
The system is being powered by its Alternate Power Source
Signal input
249
Charger over temperature shutdown
An internal temperature is out of tolerance
Boost IGBT temperature exceeded shutdown level (90C)
256
Battery Test in Progress
A UPS Notice condition exists
A Battery Test has begun.
257
System Test in Progress
A UPS Notice condition exists
One of the Systems Tests has begun.
258
Test Aborted
A UPS Notice condition exists
A Battery or Systems Test has been aborted while running due to conditions or operator command, or was inhibited from starting.
© 2006 - Eaton Corporation
Notes
7-21
Troubleshooting and Maintenance
7.1.3
9355 20 – 30 kVA
Detailed Definitions
7.1.3.1
Automatic Off Delay
This is user settable parameter for automatically turning the output off in case of utility failure (any time when operating on battery). 1.
AutoOffDelay = -1 = 65535, no automatic off function. This is factory setting (default value).
2.
AutoOffDelay = 0…65534, the number of seconds preceding output turn-off if the UPS has been discharging batteries. If the UPS transfers to some other state, the automatic-off countdown is aborted.
Note that the automatic-off countdown is not active when a service command or battery test is issued (or for some other operator initiated reason) causing the transfer on battery.
7.1.3.2
Automatic On Delay
This is user settable parameter for adding extra delay before turning UPS output on. This parameter can also be used for disabling the automatic restarts. 1.
AutoOnDelay = 0, no extra delay. This is factory setting (default value).
2.
AutoOnDelay = 1…65534—the number of seconds that is counted down when the output is about to be turned on (at startup, at automatic restart, and so on)
3.
AutoOnDelay = -1 = 65535—the number of seconds automatic restarts (any non-commanded) are disabled after low battery shutdown.
7.1.3.3
Batteries Disconnected
The battery relay can be closed only when the battery circuit breaker is closed. On start-up, and after closing the battery breaker, the UPS performs the following steps: 1.
2.
7-22
During startup and if battery circuit breaker is closed, then a.
Check that battery voltage isn’t negative.
b.
Trip battery breaker and give “Battery Needs Service” alarm if test fails
Equalize battery relay voltages using boost and charger IGBTs a.
Close the battery relay
b.
Wait 2 seconds
c.
Check that battery voltage and battery backup voltage measurements are about equal (±10V)
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Troubleshooting and Maintenance
3.
7.1.3.4
d.
Trip battery breaker and give “Battery Contactor Fail” alarm if test fails
e.
Make sure that “Battery Over Temperature” shutdown and battery hardware current limit alarms aren’t active.
If battery circuit breaker is open, then: a.
Open battery relay
b.
Give “Battery Contactor Open” alarm
c.
Disable battery operation until the battery circuit breaker has been closed
Battery DC Overvoltage
Battery voltage has been too high for a constant period. The factory setting of the time limit is 60 seconds. The voltage level follows the temperature compensated battery charging scheme (if the temperature compensation is disabled, then the voltage level stays the same): •
Battery over voltage level = batChargeV + 0.05VPC
where batChargeV is the battery voltage, where charge mode changes to float mode (see ABM document), and 0.05VPC is taken from EEPROM. Causes “Battery DC Overvoltage” alarm and the battery circuit breaker to be opened; this will disable battery operation.
7.1.3.5
Battery Low
This is the alarm level of battery voltage (about 1.88VPC). Battery low alarm is enabled when the charger has been running for 100ms, after opening the battery relay, or when boost is active. The alarm stays active until boost is deactivated and Low Battery Shutdown is inactive.
7.1.3.6
Battery Needs Service
Battery Needs Service is activated when the UPS senses negative voltage on battery measurement. Negative battery voltage is checked during UPS startup. The alarm is triggered when battery voltage is below 100 volts.
7.1.3.7
Binary Input - Delayed Shutdown Function
A binary input can be set to use this function. When the input signal is active, the UPS output is turned off after a configurable delay (factory setting is 120 seconds). The output is turned on when the utility is OK.
7.1.3.8
Binary Input - On / Off Function
A binary input can be set to use this function. When the input signal is active, the UPS output is turned off. When the signal becomes inactive, the UPS output is turned back on. © 2006 - Eaton Corporation
7-23
Troubleshooting and Maintenance
7.1.3.9
9355 20 – 30 kVA
Binary Input - Shutdown Function
A binary input can be set to use this function. When the input signal is active, the UPS output is turned off, as when the front panel menu function is used to shut down the unit.
7.1.3.10 Bypass Disable Timer Bypass is disabled for 3 seconds when transferring from bypass because of bypass power failure.
7.1.3.11 Bypass Disabled Flag This is a service settable mode, useful with emergency lighting for example. In this mode, the bypass operation is always disabled.
7.1.3.12 Bypass Down Flag A small bypass processor controls the bypass hardware. This processor signals when bypass is ”up” and bypass control is possible. When the signal is inactive, bypass is ”down”: it is not controllable and bypass voltage measurement is not possible. When the bypass is “down”, the back-feed contactor is controlled-open. •
When the bypass becomes “up”, the back-feed contactor is controlledclosed, and after few seconds, bypass voltage measurement is usable and use of bypass is possible.
7.1.3.13 Bypass Operation Preferred to Discharging Batteries This is user setting. When the UPS On Battery alarm is active, the load will transfer to bypass, if bypass is acceptable. Load stays on battery for 4 seconds before transferring on bypass.
7.1.3.14 DC Bus Low Voltage Low DC voltage, on either or both sides, causes the battery converter to begin discharging the batteries. •
Voltage limit is 29V below rail setpoint.
7.1.3.15 EPO - Emergency Power Off Shuts down the inverter and the batteries are disconnected (CB opened). The load becomes unpowered. Usually, if the load is on bypass, the bypass is also shut down; but when DSP is unable to communicate with the bypass processor (PIC), the bypass stays on. EPO input is disabled during shutdown, startup, failure shutdown, bleeding and bypass-locked states. The user can also set a disable EPO parameter.
7-24
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Troubleshooting and Maintenance
7.1.3.16 Input Transformer Overtemperature Input Transformer Overtemperature will drop the load after a configurable delay and the UPS remains in standby mode. The default delay is 120 seconds.
7.1.3.17 Inverter Temporary Inhibit There is a mechanism to prevent the UPS from constantly transferring from inverter to bypass and vice versa. It is possible that the UPS doesn’t detect a reason to transfer to bypass, but the inverter cannot support the load. If the UPS transfers load from inverter to bypass 3 - 5 times within ten minutes, transfers to the inverter are temporarily inhibited. A variable ForcedFromInverterCounter is initialized to the value of three (3) once in ten minutes. Every time the UPS transfers load from inverter to bypass the variable is decremented. If the variable becomes zero, then flag InvTmpInhibit is set. The transfers are automatically enabled once in an hour, the flag InvTmpInhibit is cleared, and the variable ForcedFromInverterCounter is reset to value three (3). The user can enable transfers by pressing any front panel button, which does the same initialization.
7.1.3.18 Low Battery Shutdown If on-battery status is active and the battery voltage has dropped below the minimum limit (typically 1.75VPC), the timer counts down (typically for 60 seconds), after which discharging of batteries must be stopped. The counter is initialized when the Low Battery Shutdown alarm is inactive. If battery voltage drops to absolute minimum limit (typically 1.67VPC), the timer duration is reduced to 1 sec. •
Low battery shutdown alarm stays active until the rectifier is running or the system is not on bypass.
7.1.3.19 Neutral Fault Detection Neutral fault is triggered when chassis voltage is over 15V and voltage on either DC bus is over 250V. Neutral fault can be disabled by a user parameter. A neutral fault causes transfer on the battery. The neutral fault is reset every minute so that the UPS can attempt to use the utility again. When the neutral fault is detected, the “Neutral fault” alarm is activated and the utility voltage and bypass voltage alarms are disabled. The “Utility Fail” and “Bypass not Available” alarms are activated. The neutral fault alarm is cleared only after neutral fault flag has been cleared for one minute. If the neutral fault is detected again after transfer online, the same alarm persists and a new alarm is not generated.
© 2006 - Eaton Corporation
7-25
Troubleshooting and Maintenance
9355 20 – 30 kVA
7.1.3.20 On Battery Status This status is given when batteries are discharging. Status is not given if a battery test is in progress and the low battery alarm is not active. This is not an alarm, but only shows that the UPS is discharging batteries. See “UPS On Battery Alarm” for battery alarm status.
7.1.3.21 Output Shutdown When bypass is not available, then: •
UPS load level 4 ≥151% will shut down the output after 300ms
•
UPS load level 3 ≥126% will shut down the output after 5 sec.
•
UPS load level 2 ≥111% will shut down the output after 60 sec.
•
UPS load level 1 ≥102% will shut down the output after 10 min.
7.1.3.22 Overload Loading condition is detected from output wattage and output current ,compared to nominal (100%) level, to determine the load level for each. For units with multi-phase outputs, the loading condition for each individual phase is detected. The quantity, which has highest load level, determines the UPS load level. When the UPS load level is above 100%, the UPS is overloaded.
7.1.3.23 Site Wiring Fault Site wiring fault is checked during startup. If chassis voltage measurement is over 50V, the “Site Wiring Fault” alarm becomes active and startup is aborted.
7.1.3.24 Transfer to Bypass When bypass is available and the UPS load level is above 102%, the UPS transfers to bypass. The following delays are used when delayed transfer to bypass on overload is set in EEPROM: •
UPS load level 4 ≥151% will transfer to bypass after 0 seconds
•
UPS load level 3 ≥126% will transfer to bypass after 0 seconds
•
UPS load level 2 ≥111% will transfer to bypass after 5 seconds
•
UPS load level 1 ≥102% will transfer to bypass after 5 seconds
As long as the bypass is OK and the UPS load level is above 100%, the UPS will stay on bypass.
7-26
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Troubleshooting and Maintenance
7.1.3.25 UPS on Battery Alarm Normally, when the UPS has been continuously discharging batteries for 5 seconds, this alarm is given. This alarm is not given during battery testing, nor when service command is forcing batteries to be discharged, if battery low alarm is not active. This alarm is the signal for the software to start the shutdown countdown.
7.1.3.26 Utility Overvoltage To prevent very high voltage on the rectifier and/or DC bus, >144V (EEPROM value) at the rectifier input on any phase causes a transfer to battery operation.
7.1.3.27 XCP Delayed Load Power Off & Restart Command When this command is given, the UPS output is shut down after the delay duration defined with the command. After the shutdown, the UPS waits until the utility is OK and restarts. The output shutdown has a minimum 10 second duration.
7.1.3.28 XCP Scheduled Load Power Off Command When this command is given, the UPS output is shut down after the delay duration defined with the command. The UPS output is kept off until an ON command is received.
7.1.3.29 XCP Scheduled Load Power On Command When this command is given, and the UPS output was turned off with an XCP command, the UPS will turn on the output after the delay duration defined with the command. If the utility is down, then turning on the output is delayed until the utility is OK.
7.1.3.30 XCP UPS Off Command When this command is given, the UPS output is turned off immediately. The UPS output is kept off, until an ON command is received.
7.1.3.31 XCP UPS On Command The UPS output has been turned off with an XCP command when this command is given. The UPS will turn on the output as soon as the utility is OK.
7.1.4
Failure Analysis
The following are lists of all the various notices and alarms that can be annunciated or acted upon by the Powerware® 9355 UPS. Use these charts with the charts in paragraph 7.1.1 Action Levels and paragraph 7.1.2, Alarm, Notice, Status, and Flag Definitions to determine course of action.
© 2006 - Eaton Corporation
7-27
Troubleshooting and Maintenance
7.1.4.1 FAILURE MODE
9355 20 – 30 kVA
Definitions of Table Headings FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
FAILURE MODE - These are the ways in which the activities / processes associated with Equipment could ”fail, or go wrong” FAILURE EFFECT - How would the customer feel this failure? What impact would it have? There may be more than 1 effect for each failure. POTENTIAL CAUSE - Why might this failure happen? What could lead to its occurrence? •
USE THE 5 WHYs - Follow these steps to get to the root cause:
d.
First, identify what you believe to be the cause
e.
Then ask yourself ”why” would this problem occur and what would cause it
f.
Then, starting with the answer to this question, repeat steps a. and b. five times until you arrive at the real cause for this failure
OCCURRENCE - Rate the failure (1-10). How likely is the failure to occur? •
1 is unlikely
•
10 is very likely (inevitable)
CONTROLS - What exists that might detect the failure or the impact of the failure? RECOMMENDED CORRECTIVE ACTION - possible ways to correct this failure.
Table 41. Power Board Failures FAILURE MODE Battery Charger Circuit - No Charge
7-28
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
Batteries do not get charged, Unit alarms within 24 hours.
Component failure
3
FW measurement detection
Verify if any other alarms are active. If the system appears to be operating normally, with the exception of the battery charger, verify the batteries and the battery fuse are not bad. If the batteries and fuse are good, change the IGBTs on the Power Board. Inspect the Power Board, if any
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Troubleshooting and Maintenance
RECOMMENDED CORRECTIVE ACTION - possible ways to correct this failure.
Table 41. Power Board Failures FAILURE MODE
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
Battery Charger Circuit - Over Charge Battery
Batteries will get hot, swell
Component failure
3
Battery breaker will shunt trip, Measure battery voltage, LED red blinking, alarm
Verify if any other alarms are active. If the system appears to be operating normal with the exception of the battery charger verify the batteries and the battery fuse are not bad. If batteries and fuse are good, change the IGBTs on the Power Board. Inspect Power Board, if any damage is present replace the Power Board also.
Battery Converter
On battery - load dropped
Electrical over stress, IGBT devices possible spring failure, gate drives.
3
Sufficient electrical margin.
Check correct torque values. Replace Power Board and IGBTs
On battery - load dropped
Thermal Overstress
2
Sufficient thermal margins verified, calculated and measured
Verify ambient temperature in the room. If the room temperature is too hot, the fans cannot create enough cool airflow over the heat sink.
If online - switch to Bypass
Customer Overloads and abnormal conditions, thermal overstress
3
Online - go to bypass
Electrical over stress, IGBT devices possible spring failure, gate drives
4
Rectifier
© 2006 - Eaton Corporation
CONTROLS
RECOMMENDED CORRECTIVE ACTION damage is present replace the Power Board also.
Verify Customers load, room temperature, or any other abnormal conditions. Current limiting and sensing, MOVs on input
Verify input current and if within specifications replace IGBTs. Inspect the Power Board for damage if IGBTs are destroyed then 7-29
Troubleshooting and Maintenance
9355 20 – 30 kVA
RECOMMENDED CORRECTIVE ACTION - possible ways to correct this failure.
Table 41. Power Board Failures FAILURE MODE
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION replace the Power Board also if needed.
Thermal overstress
4
Concerned with overload conditions.
Verify customers load is not in a overload condition. Check ambient room temperature.
On battery - load dropped
Electrical over stress, IGBT devices possible spring failure, gate drives
3
Sufficient electrical margin.
Check correct torque values. Replace Power Board and IGBTs
On battery - load dropped
Thermal overstress
3
Sufficient thermal margins verified, calculated and measured.
Verify ambient temperature in the room. If the room temperature is too hot the fans cannot create enough cool airflow over the heat sink.
Online go to bypass
Electrical over stress, IGBT devices possible spring failure , gate drives
3
Current limiting and sensing.
Verify input current and if within specifications replace IGBTs. Inspect Power Board for damage if IGBTs are destroyed, then replace the Power Board also if needed.
Online go to bypass
Thermal overstress
3
Thermal margin verified calculated and measured
Verify ambient temperature in the room. If the room temperature is to hot the fans cannot create enough cool airflow over the heat sink.
on battery - load dropped
Electrical over stress, IGBT devices possible spring failure, gate drives
3
Sufficient electrical margin.
Replace Power Board and IGBTs
on battery - load
Thermal
3
Thermal
Verify ambient
Online - go to bypass
Inverter Circuit
7-30
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Troubleshooting and Maintenance
RECOMMENDED CORRECTIVE ACTION - possible ways to correct this failure.
Table 41. Power Board Failures FAILURE MODE
FAILURE EFFECT dropped
POTENTIAL CAUSE
OCC.
overstress
CONTROLS
RECOMMENDED CORRECTIVE ACTION margin temperature in the verified room. If the room calculated and temperature is to hot measured. the fans cannot create enough cool airflow over the heat sink.
Communications - X-Slot Short circuit
No Communications
X-Slot failure
2
Separate supply from critical circuits.
If the X-Slot card is not working swap positions and verify it’s not he position. If the problem is still present try a new card. If the problem is still present replace the Power Board.
User Interface (LCD)
No display and or front panel user controls
LCD, cable, component failure
1
Proven Design and circuit used in HV by HPO
Replace Display Assembly
Internal Voltage Sensing
Online - Goes to Bypass
Component failure
2
Component not overstressed.
Using the calibration procedure to identify voltage checks, verify all voltages are present and no fuses are open. After verifying all correct verify the LED on the Control board is flashing if not replace the Control Board. Test sensing voltages from I/O Board to X6 and verify sensing voltages are going to the Control Board.
On battery drops load
Component failure
2
Component not overstressed, mature design
Verify Battery Breaker has not failed or open. Verify Batteries are good.
Over voltage on PS, Failed component
2
FW and auxiliary set of contacts, FW monitors PS voltage
Replace Power Board or I/O Board. Check Power Supply voltage on each board.
Battery disconnect control trips breaker
On battery Dropped load
© 2006 - Eaton Corporation
7-31
Troubleshooting and Maintenance
9355 20 – 30 kVA
RECOMMENDED CORRECTIVE ACTION - possible ways to correct this failure.
Table 41. Power Board Failures FAILURE MODE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
Online - Transfer Over voltage to Bypass, once on PS, Failed DSP reset, component transfer to online, alarm
2
FW and auxiliary set of contacts, FW monitors PS voltage
Replace Power Board or I/O Board. Check Power Supply voltage on each board.
Battery disconnect control cannot trip breaker
Back-feeding on an EPO event
Failed Component, loss of A_AUX supply
2
All-pole break, and FW
IGBT Gate Drive Circuits
Online go to bypass
Component failure
2
Proven design Replace Power Circuit used in Board and IGBTs HV by HPO
On battery drop load
Component failure
2
Proven design Replace Power Circuit used in Board and IGBTs HV by HPO
Control board failure during Hypot
Component failure
1
Calculations and measurement
Engineering Test Failure N/A to field personnel.
On battery drops load
Component failure
1
Sufficient Electrical Margin
Replace IGBTs and maybe Power Board.
EPO Circuit Failure
Safety, battery still connected
Component failure
2
Proven design Replace I/O Board. Circuit used in HV by HPO
Alarms
Loss of customer customization
Component failure
2
Proven design Replace Control Circuit used in Board. HV by HPO
Ambient Temp Sensor
No overtemp warning
Component failure
2
Alternate temp sensing (heatsink)
Heatsink temp sensor
Online - Goes to Bypass
Component failure - part indicates overtemp
4
FW detection
FW and DVT
Online - Goes to Bypass
Component failure - part does not indicate overtemp
2
FW detection
FW and DVT
On Battery drops load
Component failure - part does not indicate overtemp
2
FW detection
Bridging Resistors
7-32
FAILURE EFFECT
POTENTIAL CAUSE
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Troubleshooting and Maintenance
RECOMMENDED CORRECTIVE ACTION - possible ways to correct this failure.
Table 41. Power Board Failures FAILURE MODE LPS
FAILURE EFFECT Goes to Bypass, yellow LED, Alarm
POTENTIAL CAUSE
OCC.
Component failure
1
CONTROLS
RECOMMENDED CORRECTIVE ACTION None
Table 42. Control Board Failures FAILURE MODE Control board disengaged
FAILURE EFFECT Online - Goes to Bypass
POTENTIAL CAUSE Shipping
OCC.
9
CONTROLS
RECOMMENDED CORRECTIVE ACTION
Mechanical / Reseat card DVT
Table 43. I/O Board Failures FAILURE MODE Voltage Sensing
Current Sensing Battery
Current Sensing Input
Current Sensing Output
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
On output goes to bypass
Component failure
2
Proven design Circuit used in HV by HPO
Replace I/O Board
On battery, drops load
Component failure
2
Proven design Circuit used in HV by HPO
Replace I/O Board
If on battery trip battery breaker and drop load
Component failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
If online alarms, no effect
Component failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
If online - switch Component to Bypass failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
If on-battery no effect
Component failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
If online - switch Component to Bypass failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
If on-battery Drops Load
3
Proven design Circuit used in HV by HPO
Replace I/O Board
Component failure
© 2006 - Eaton Corporation
7-33
Troubleshooting and Maintenance
9355 20 – 30 kVA
Table 43. I/O Board Failures FAILURE MODE Current Sensing Bypass
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
If online Alarms, no effect
Component failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
If on-Battery Alarms, no effect
Component failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
If on-bypass Alarms, no effect
Component failure
3
Proven design Circuit used in HV by HPO
Replace I/O Board
Bypass SCR
Bypass in parallel with UPS
Over current, breakdown voltage is exceeded, DVDT
1
MOV front end and Snubber
Replace I/O Board
Inverter Fuse
On-battery drops load
Component failure
2
HW Current limit
FW Current limit, verify settings. Replace fuse.
On-battery drops load
Unusual load conditions
4
HW Current limit
FW Current limit, check fuse, Replace I/O Board
On utility - and bypass not available lose load
Unusual load conditions
4
HW Current limit
FW Current limit, Replace I/O Board
On utility - and bypass is not available
Unusual load conditions
4
HW Current limit
FW Current limit, Replace I/O Board
On Battery and Bypass is not available Drop load
Defective Component
1
Fused
FW Controls , Check fuses, Replace I/O Board
Online - go to bypass
Defective Component
1
Fused
Check fuses
On Battery and Bypass is not available Drop load
Defective Component
1
Proven design Circuit used in HV by HPO
Replace I/O Board
Online - go to bypass
Defective Component
1
Proven design Circuit used in HV by HPO
Replace I/O Board
Bypass in parallel with UPS
Component failure
2
Proven design Circuit used in HV by HPO
Replace I/O Board
On Bypass Drops Load
Component failure
2
Proven design Circuit used in HV by HPO
Replace I/O Board
Inverter SCR
Inverter SCR Gate Drive Circuits
Bypass SCR Gate Drive Circuits
7-34
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Troubleshooting and Maintenance
Table 43. I/O Board Failures FAILURE MODE
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
LPS
Goes to Bypass, yellow LED, Alarm
Component failure
1
Mature proven design
Replace I/O Board
Battery Start Circuit
Will not battery start
Component failure
6
DVT
Replace I/O Board
Battery life Component reduction in rest failure mode
6
DVT
Complete calculations for battery life reduction. Add to user’s manual to open battery breaker if unit is powered down for an extended period
Bypass Fuse open due to high in-rush
Drop load
Load characteristics
3
Return to inverter
Replace Fuses
Rectifier fuse open
If on battery no effect
Electrical overstress
3
Current limit, and FW
Replace Fuses
If online go to bypass
Electrical overstress
3
Current limit, and FW
Replace Fuses
Table 44. Relay Failures FAILURE MODE
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
Battery Relays Sticks Closed
Relay sticks battery drain after unit shutoff
Breaking or making current, not sharing, rating exceeded
3
3 relays Check relays on I/O sharing, equal board and if need trace lengths replace I/O Board.
Battery Relays Never closes
Alarm sounds
Component failure
2
FW Controls, current sensing, and voltage sensing
Replace I/O Board.
Balancer Relay stuck on Battery
UPS will not start
Defective Component
1
None
Replace I/O Board.
Contactor Driver relay Open, cannot close
Drop on Over-voltage, Battery, Battery Relay that alarm, drives coil fails schedules shutdown
1
Detected through power-up, cannot start
Replace I/O Board.
Contactor Driver relay Closed when should be open
Safety
3
FW detection
Replace I/O Board.
Relay failure
© 2006 - Eaton Corporation
7-35
Troubleshooting and Maintenance
9355 20 – 30 kVA
Table 45. Fan Failures FAILURE MODE
FAILURE EFFECT
POTENTIAL CAUSE
OCC.
CONTROLS
RECOMMENDED CORRECTIVE ACTION
Fan Failure
Alarm sounds
Fan component failure
4
Tach and F/W
Replace Fan
Tach Fails
Alarm sounds
Fan or Tach Circuit
2
none
Replace I/O Board.
7.1.5
Electronics Module and Other Failures
FAILURE MODE
POTENTIAL CAUSE
OCC.
Converter failure
Windings shorted to core
7
None
Replace Inductor Assembly.
Lack of current sharing
Bad connection either at PCB or internal
7
EM test limits, current scalers
Individual component testing on current sensors. See Calibration procedure.
DC Coil Contactor Fails to close or opens unexpectedly
Goes on battery, alarm, write to log, scheduled shut down
Over-voltage, Relay that drives coil fails
1
No controls in place, scheduled shutdown
Replace I/O Board.
DC Coil Contactor Fails to open (back-feed)
Possible back-feed after EPO
Contactor welded
1
FW controls
Replace Contactor.
EMI / Surge Assembly
Loss of surge withstand capability
Electrical overstress
2
Mature Design within Powerware
Replace EMI Board
One Battery String not connected
Latent failure mode on battery, short runtime
Battery open
5
Should be detected by Service at start-up during battery test
Inductors
7-36
FAILURE EFFECT
CONTROLS
© 2006 - Eaton Corporation
RECOMMENDED CORRECTIVE ACTION
8 Removal / Replacement 8.1.1
Removal Preparation 1.
Remove the UPS front door panel.
2.
Remove the top fan dead front, see Figure 60.
3.
Bleed the DC Bus or check for <20VDC.
4.
Remove the fan wires directly from fans 4, 5 and 6
5.
Unplug the fan wires to remove the fan assembly.
6.
•
(If this is an older unit, remove the right front cover if it is not integrated with the fan assembly).
•
Remove the inverter fan plugs from the I/O board and push the wires through, and away from, the I/O board (X65, X66, and X67, see Figure 61).
•
Remove the fan plugs on the bypass fan assembly, see Figure 62.
Unplug the battery start (cold start) wires, see Figure 61 for location.
Note : If there is an External Battery Cabinet (EBC), ensure that the EBC breaker is open.
7.
With a DVM, ascertain an absence of voltage on the front Input and output terminals, X1 and X2, power connections.
Note : CB-1 and CB-2 need to be open. If this is a dual feed unit, check for an absence of voltage at CB-1.
8.1.2
Removing the L3 Power Module
WARNING THE MBS NEEDS TO BE IN BYPASS WITH CB-1 AND CB-2 OPEN. WAIT UNTIL THE DC LINK VOLTAGE HAS BLED DOWN BEFORE PROCEEDING.
© 2006 - Eaton Corporation
8-1
Removal and Replacement
9355 20 – 30 kVA
CAUTION Be careful to avoid scraping or cutting any wiring during the removal and replacement of the L3 Power Module, see Figure 59.
Figure 59.
Damage Sustained by the IGBTs Due to Severed Wiring
Figure 60.
1.
8-2
Top Fan Dead Front and Bracket Plates
Remove the DC link screws from the I/O board, see Figure 61.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Removal and Replacement X11 Ribbon Cable
X61 X60
DC+
BATT CD TRIP X50
X55
DC Link Screws L3
X6
X12
X7
X11
INV
AAUX
INV L3
X71, X15
X21 X27
INV L2 FANS
INV L1
Fan Plugs
K3
RECT L3
X68, X14
X45
BAT
DC-
X25
Figure 61.
X78 X2 IN/OUT CB TRIP
BAT COLD START
X79
K1
BATT BKUP X46
X82 L3 L2 L1 X28 X29 X4
BATTERY CHOKES
X28
L3 X76
X76
X23 X13
X54
X42 X41 X40
L3 and Fan Removal Points on the I/O Board
Figure 62.
Bypass Board Silk Screen
© 2006 - Eaton Corporation
8-3
Removal and Replacement
9355 20 – 30 kVA
2.
Remove the right front bracket plate, see Figure 60.
3.
Cut the tie wraps from the ribbon cable and other wiring.
4.
Remove the bus bar screws.
5.
Remove wires at X71, X15, X68, X14, X28 and X76 from the I/O board, see Figure 61.
6.
Remove ribbon cable X11 from the I/O board, see Figure 61.
7.
Slide the L3 Power Module out of the UPS by grasping the lower module lip.
CAUTION Do not grasp the middle aluminum bar to remove the Power Module. Be aware of the proximity of wiring so that wires near the top and sides are not severed by the UPS frame during removal.
8.1.3
Replacing the L3 Power Module
The following procedure reverses the preceding removal procedure.
CAUTION Be careful to avoid scraping or cutting any wiring during the removal and replacement of the L3 Power Module
1.
Perform Removal Preparation, see paragraph 8.1.1.
2.
Slide the L3 Power Module into the top front shelf of the UPS being careful to avoid cutting any loose wiring on the UPS shelf lip, see Figure 63.
Figure 63.
3. 8-4
L3 PM Shelf Insertion
Replace the bus bar screws. © 2006 - Eaton Corporation
9355 20 – 30 kVA
Removal and Replacement
4.
Attach ribbon cable X11 to the I/O Board, see Figure 61.
5.
Re-attach wires at X71, X15, X68, X14, X28 and X76 to the I/O board, see Figure 61, and secure the wiring with tie-wraps.
6.
Insert and tighten the I/O board DC link screws, see Figure 61.
7.
Plug the battery cold start wiring into the I/O board.
8.
Placing the fan assembly in place on the UPS:
9.
•
thread the fan wiring through the UPS assembly to the I/O board, reattaching the inverter fan plugs (X65, X66, and X67, see Figure 59).
•
Re-attach the fan plugs to the bypass fan assembly, see Figure 60. (If this is an older unit, replace the right cover if it is not integrated with the fan assembly)
Re-attach the top fan dead front, Figure 60.
© 2006 - Eaton Corporation
8-5
Removal and Replacement
8.1.4
9355 20 – 30 kVA
Removing the L2 Power Module
CAUTION Be careful to avoid scraping or cutting any wiring during the removal and replacement of the L2 Power Module
WARNING 1.
Perform removal preparation, see section 8.1.1.
2.
The MBS needs to be in bypass with CB-1 and CB-2 open.
Note : If this is a dual feed unit, check for an absence of voltage at CB-1.
3.
Remove the DC Link screws from the I/O board, see Figure 61. X7 Ribbon Cable
X61 X60 BATT CD TRIP X50
X55
DC+ X12
X7
X6
X11
INV
AAUX
INV L3
X21 X27
INV L2
X72, X18
FANS
INV L1
DC Link Screws L2
K3
RECT L3
X69, X10
X45
BAT
DC-
X25
Figure 64.
8-6
X78 X2 IN/OUT CB TRIP
BAT COLD START
K1
BATT BKUP X46
X82 L3 L2 L1 X28 X29 X4
BATTERY CHOKES
X29
L3 X76
X75
X79
X23 X13
X54
X42 X41 X40
L2 Removal Points on the I/O Board
4.
Cut the tie wraps from the ribbon cable and other wiring.
5.
Remove wires at X18, X72, X10, X69, X75 and X29, see Figure 64. © 2006 - Eaton Corporation
9355 20 – 30 kVA
Removal and Replacement
6.
Remove ribbon cable X7 from the I/O board, see Figure 64.
7.
Slide the L2 Power Module out of the UPS by grasping the shelf lower module lip.
CAUTION Do not grasp the middle aluminum bar to remove the Power Module. Be aware of the proximity of wiring so that wires near the top and sides are not severed by the UPS frame during removal.
8.1.5
Replacing the L2 Power Module
CAUTION Be careful to avoid scraping or cutting any wiring during the removal and replacement of the L2 Power Module
The following procedure reverses the preceding removal procedure. 1.
Slide the L2 Power Module into the UPS.
2.
Re-attach the ribbon cable to X7, see Figure 64.
3.
Re-attach wires at X18, X72, X10, X69, X75 and X29, see Figure 64.
4.
Replace the bus bar screws.
5.
Consolidate and secure the wiring with tie-wrap.
6.
Insert and tighten the DC link screws on the I/O board, see Figure 61.
7.
Plug the battery cold start wiring into the I/O board.
8.
Placing the fan assembly in place on the UPS:
9.
•
thread the fan wiring through the UPS assembly to the I/O board, reattaching the inverter fan plugs (X65, X66, and X67, see Figure 59).
•
Re-attach the fan plugs to the bypass fan assembly, see Figure 60. (If this is an older unit, replace the right cover if it is not integrated with the fan assembly)
Re-attach the top fan dead front, Figure 60.
© 2006 - Eaton Corporation
8-7
Removal and Replacement
8.1.6
9355 20 – 30 kVA
Removing the L1 Power Module and Bypass Board
CAUTION Be careful to avoid scraping or cutting any wiring during the removal and replacement of the L1 Power Module Use needle nose pliers to disconnect the plugs from the Bypass Board, do not pull the plugs by the plug wires.
WARNING BEFORE PERFORMING THIS PROCEDURE ENSURE THAT THE UPS IS IN EXTERNAL MAINTENANCE BYPASS, THAT ALL MAIN BREAKERS ARE OPEN, AND THAT THE POWER TO THE UPS IS OFF. IF USING SIDE ACCESS, THIS PROCEDURE MAY BE PERFORMED USING INTERNAL MAINTENANCE BYPASS.
8.1.6.1
Removing the Power Module L1 / Static Switch Assembly from the UPS. 1.
Perform Removal Preparation, see section 8.1.1.
2.
Unplug the battery start (cold start) wires.
3.
Remove the battery dead front and disconnect the positive red wires (6) from the each battery string: T1, T3, T5, T7, T9 and T11, see Figure 65.
Figure 65.
8-8
Positive Battery String Wires
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Removal and Replacement
Note : If there is an External Battery Cabinet (EBC), ensure that the EBC breaker is open. If this is a dual feed unit, check for an absence of voltage at CB-1.
4.
With a DVM, ascertain an absence of voltage on the front X1 and X2 power connections.
5.
Unplug the static switch ribbon cable and remove the front, side panel.
6.
Disconnect the X25 plug and push it through the assembly.
7.
Unplug the X10 neutral wire from the bypass board in the Static Switch module, see Figure 66. X10 X23,X26,X22
X51
Figure 66.
Bypass Static Switch Connections
8.
Disconnect the gate drive plug, X51, and the plugs at X23, X26 and X22 (from front to back) on the Bypass Board in the Static Switch Assembly, see Figure 66.
9.
Remove the bus bar screws.
© 2006 - Eaton Corporation
8-9
Removal and Replacement
9355 20 – 30 kVA
Note : Tilt the screws slightly downward once they extend beyond the I/O Board to prevent the washers from falling into the UPS cabinet.
10. Remove the ribbon cables from I/O board X6 and pull to the front of the UPS. 11. Using a 3/16” wrench, disconnect Power Cables 1, 2, and 3 from TB5, see Figure 73. 12. Remove the side panel. •
Using an 5/16” wrench remove the K5 wiring.
13. Let the removed wires hang from the front of the UPS. 14. Using an 5/16” wrench disconnect the wires X73, X19, X70, X5, X74, and X4 from the I/O board, see Figure 67.
X61 X60 BATT CD TRIP X50
X55
DC+ X6
X12
X7
X11
INV
AAUX
INV L3
X21 X27
INV L2 FANS
INV L1
X73,X19
K3
RECT L3 BAT COLD START
L3 X76
X79
K1
BATT BKUP X46
X45
BAT
DC-
X82 L3 L2 L1 X28 X29 X4
X4
BATTERY CHOKES
X74
X25
Figure 67.
X78 X2 IN/OUT CB TRIP
X70,X5
X23 X13
X54
X42 X41 X40
I/O Board Wiring Connections to Static Switch
15. Slide the L1 Power Module forward, removing it from the UPS.
8-10
© 2006 - Eaton Corporation
9355 20 – 40 kVA
Removal and Replacement
CAUTION Do not grasp the middle aluminum bar. Verify the correct placement of all plugs on their plug pins during removal and installation of the Bypass Board
8.1.6.2
Removing the Bypass Board from the Static Switch Housing 1.
Turn the Static Switch module on its side.
CAUTION Do not damage the Static Switch assembly connector during handling, see Figure 68.
2.
Remove the two (2) Bypass Board assembly screws to remove the board assembly from the power module housing.
3.
Remove the power wires connecting the Static Switch to the SCRs.
Note: If you are replacing the SCRs, remove the SCRs from the heat sink. If you have the initial release of the UPS (serial number digit 7 = “X”), your SCR wiring harness sequence is 3, 1, 2. The subsequent UPS release (serial number digit 7 = “A”), has an SCR wiring harness sequence of 1, 2, 3, see Figure 68 . 4.
Remove the front terminal block connections.
5.
Remove the seven (7) screws securing the Bypass Board to replace the Static Board. Handle side of assembly with care, board protrusion and connector susceptible to damage during handling
3 1 1 or 2 2 3
Figure 68.
Static Switch Housing and SCRs
© 2006 - Eaton Corporation
8-11
Removal and Replacement
8.1.6.3
9355 20 – 30 kVA
Replacing the Bypass Board
The following procedure reverses the preceding removal procedure.
8.1.7
1.
Attach and secure the Bypass Board to the L1 assembly with the seven (7) screws.
2.
Replace the front terminal block connections.
3.
Attach the power wires connecting the SCRs to the Static Switch.
4.
Attach the board assembly to the power module housing using the two (2) Bypass Board assembly screws.
Replacing the L1 Power Module / Static Switch Assembly
The following procedure reverses the preceding removal procedure. 1.
Slide the L1 module into the the UPS.
2.
Plug the X10 neutral wire from the Static Switch module to the bypass board, and reconnect the gate drive plug, X51, and the plugs at X23, X26 and X22, see Figure 66.
3.
Connect the wires X73, X19, X70, X5, X74, and X4, see Figure 67.
4.
Routing the wiring through the front of the UPS, connect the ribbon cables to I/O board X6.
5.
Replace the bus bar screws.
6.
Attach the K5 wiring.
7.
Connect the X25 plug bringing it through the UPS assembly.
8.
Connect the Power Cables 1, 2, and 3 going to TB5, see Figure 73.
9.
Plug in the static switch ribbon cable.
10. Connect the positive red wires (6) to each battery string (T1, T3, T5, T7, T9 and T11), see Figure 65. 11. Plug-in the battery cold start wires. 12. Place the top fan dead front in position on the UPS and re-attach the fan plugs to the I/O board. 13. Secure the top fan dead front and UPS front door panel if appropriate.
8-12
© 2006 - Eaton Corporation
9355 20 – 30 kVA
8.1.8
Removal and Replacement
Removing the I/O Board Assembly 1.
Perform removal preparation, see section 8.1.1.
2.
Remove the UPS front side metal panel between the I/O board and the Power Module (the panel is slotted at the bottom).
3.
Remove the UPS side metal panel.
4.
Using a DVM, check the DC link for voltage (you can use the DC+ connector at the top of the I/O board and the DC– connector at the bottom of the I/O board as testing points).
Figure 69.
DC Link Check Points
WARNING WAIT UNTIL THE DC LINK VOLTAGE HAS BLED DOWN BEFORE PROCEEDING.
5.
Remove the tie wraps from the inductor and power module wires.
© 2006 - Eaton Corporation
8-13
Removal/Replacement
9355 20 – 30 kVA
6.
Grasp the Control Board that is sitting on top of the I/O Board and gently move it from side to side to lift it off of the I/O Board, see Figure 70.
Figure 70.
Removing the control board from the I/O board
CAUTION When removing wiring from the I/O board ensure that all washers are accounted for and correctly placed.
7.
8-14
Place the Control Board in a static-free area.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Removal and Replacement
8.
9.
Using an 8mm (5/16”) socket, remove the inverter wiring from the I/O board connectors, see Figure 71: •
Inverter L3 wires X71, X15
•
Inverter L2 wires X72, X18
•
Inverter L1 wires X73, X19
Remove the rectifier wiring from the I/O board connectors, see Figure 71: •
Rectifier L3 wires X68, X14
•
Rectifier L2 wires X69, X10
•
Rectifier L1 wires X70, X5
10. Remove battery choke wires, see Figure 71: •
Remove L3 battery choke wires at X76, X28.
•
Remove L2 battery choke wires at X75, X29.
•
Figure 71.
Wiring Locations
Remove L1 battery choke wires at X74, X4
© 2006 - Eaton Corporation
8-15
Removal/Replacement
9355 20 – 30 kVAt
11. Remove fan power plugs from X65, X66, X67, see Figure 72. 12. Remove the cold-start ribbon cable at X79. 13. Remove the ribbon cables at X11, X7, X6 and X12. 14. Unplug the XSlot cables and keyed ribbon cables X-55 and X-56, see Figure 72. 15. Unplug the display (CAT-5) cable connector, see Figure 72. 16. Remove the TB1 output ( X25, X23, X13 and X54) and K1 wires (X13 and X54), and the K3 output wires (X42, X41, X40). Note: If removing the I/O board from the assembly I/O board assembly, remove the K3 and K1 disconnect wires, see Figure 72, and remove the second set of wires attached to the TB1 output connectors and K3 output connectors.. X55, X56, X11, X7, X6, X12 ribbon cables 5
T CA
X61 X60 BATT CD TRIP X50
X55
DC+
X21, X27
X12
X7
X6
X11
INV
AAUX
INV L3
X21 X27
INV L2
INPUTS TO K3 DISCONNECT
FANS
INV L1
K3
RECT L3
INPUTS TO K1 DISCONNECT
X45
BAT
DC-
X25
Figure 72. 8-16
X78 X2 IN/OUT CB TRIP
K1
BATT BKUP X46
L3 L2 L1 X28 X29 X4
BATTERY CHOKES
L3 X76
BAT COLD START
X79
X23 X13
X54
X42 X41 X40
Wiring Removal Diagram
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Removal/Replacement
17. Remove the 3 sets of wires (should be thread through the CTs) from the I/O Board side of TB5 using a 4.5mm Allen wrench, see Figure 73.
Figure 73.
TB5
18. Remove negative battery bus bar bolts at X51, X34, and at X82, see Figure 74. 19. Remove DC bus bar bolt X30, X81, X80 and Inverter neutral bolts X20 and X3 (behind the blue current sensor B3), see Figure 74. X61 X60 BATT CD TRIP X50
X55
DC+ X6
X12
X7
X11
INV
AAUX
INV L3
X21 X27
INV L2 FANS
INV L1
K3
RECT L3 X78 X2 IN/OUT CB TRIP
K1
BATT BKUP X46
X45
BAT
DC-
X82 L3 L2 L1 X28 X29 X4
BATTERY CHOKES
L3 X76
BAT COLD START
X79
X25
Figure 74.
X23 X13
X54
X42 X41 X40
Bus bar and neutral bolts
© 2006 - Eaton Corporation
8-17
Removal and Replacement
9355 20 – 30 kVA
CHASSIS SCREWS
X61 X60 BATT CD TRIP X50
X55
DC+ X12
X7
X6
X11
INV
AAUX
INV L3
X21 X27
INV L2 FANS
INV L1
K3
RECT L3 X78 X2 IN/OUT CB TRIP
K1
BATT BKUP X46
X45
BAT
DC-
L3 L2 L1 X28 X29 X4
BATTERY CHOKES
L3 X76
BAT COLD START
X79
X25
Figure 75.
X23 X13
X54
X42 X41 X40
Chassis Screws
Note: If you are removing the I/O Board from the assembly mounting, skip items 20 and 21 and perform step 22.
20. Remove the Philips head retaining bracket screws and chassis screws on the I/O assembly mounting plate to remove the I/O assembly from the UPS.
CAUTION The I/O board assembly is slot-mounted, so lift the board from its slotted position when removing.
21. Tilt the I/O assembly forward to disconnect the assembly from the side slots. Then lift the board assembly off the bottom slots and set it down in a static-free open area. 22. Remove the ten (10) plastic stand-offs around the board perimeter and from the center of the I/O board, and the chassis screws, see Figure 75, to remove the I/O board. 8-18
© 2006 - Eaton Corporation
9355 20 – 30 kVA
8.1.9
Removal/Replacement
Replacing the I/O Board
The following procedure reverses the preceding removal procedure. Note: If you removed the I/O Board from the assembly skip steps 2 and 3.
1.
Attach the I/O board to the I/O board assembly using the ten (10) plastic stand-offs around the board perimeter and the center of the I/O board and reattach the chassis screws (see Figure 75).
2.
Attach the I/O assembly to the UPS by aligning it with the side and bottom slots.
3.
Secure the I/O assembly to the UPS by inserting the bracket screws and chassis screws with a Philips head screwdriver.
4.
Attach the DC bus bar bolts X30, X81, X80 and Inverter neutral bolts X20 and X3 (behind the blue current sensor B3), see Figure 74.
5.
Attach the negative battery bus bar bolts at X51, X34, and at X82, see Figure 74.
6.
Thread the 3 sets of wires going to the I/O Board through the CTs.
7.
Attach the 3 sets of wires to the I/O Board side of TB5 using a 4.5mm Allen wrench, see Figure 73.
8.
Attach the TB1 output ( X25, X23, X13 and X54) and K1 wires (X13 and X54), and the K3 output wires (X42, X41, X40).
Note: If the I/O board was removed from the I/O board assembly, attach the K3 and K1 disconnect wires and the second set of wires attached to the TB1 output connectors and K3 output connectors.
9.
Attach the 3 sets of wires from the I/O Board side of TB5 using a 4.5mm Allen wrench, see Figure 73.
10. Plug-in the display (CAT-5) cable connector, see Figure 72. 11. Plug-in the XSlot cables and all ribbon cables observing the orientation of the red pin 1 wire, see Figure 72. 12. Attach the ribbon cables at X11, X7, X6 and X12, see Figure 72. 13. Attach the cold-start ribbon cable at X79. 14. Attach the fan power plugs from X65, X66, X67, see Figure 72. 15. Attach the battery choke wires, see Figure 71: •
L3 battery choke wires at X76, X28.
•
L2 battery choke wires at X75, X29.
•
L1 battery choke wires at X74, X4
© 2006 - Eaton Corporation
8-19
Removal and Replacement
9355 20 – 30 kVA
16. Attach the rectifier wiring from the I/O board connectors, see Figure 71: •
Rectifier L3 wires X68, X14
•
Rectifier L2 wires X69, X10
•
Rectifier L1 wires X70, X5
17. Using an 8mm (5/16”) socket, attach the inverter wiring to the I/O board connectors, see Figure 71: •
Inverter L3 wires X71, X15
•
Inverter L2 wires X72, X18
•
Inverter L1 wires X73, X19
18. Attach the control board to the I/O board, see Figure 70. 19. Secure the inductor wiring and power module wiring with tie wraps. 20. Re-attach the UPS side metal panel, if appropriate. 21. Attach the front metal panel between the Power Module and the I/O board, if appropriate.
8-20
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Removal/Replacement
8.2 TECHNICAL SUPPORT KNOWLEDGE BASE CSEs should regularly search the Knowledge Base, updated by Technical Support personnel, for 9355 UPS information, such as: •
Troubleshooting and maintenance
•
Connectivity and communication issues
•
Software and monitoring
•
Back up times
•
Technical and non-technical questions
Eaton CSEs can find the Knowledge Base by going to Powerware Intranet at: http://poweratwork/usa/ Go to USA Groups, then click on Global Services Intranet On Powerware Global Services page, go to Technical Support Centers, and click on: Technical Support Knowledge Base Click on “View Top Solutions,’ and ’Find More Solutions.’ Click the Search in ’ALL Topics’ pulldown. 9355 information will be available under Three Phase, 9355. Here CSEs will see detailed information on issues, causes, and resolutions for each product. Authorized Distributors can find other Knowledge Base information on the Powerware Internet at: http://www.powerware.com/USA/default.asp Click on Powerware 9355 Click on Powerware UPS Product Page Click on Services for 9355 UPS Click on Technical Support Knowledge Base Here Distributors will see Customers’ Frequently Asked Questions and responses for each product. Additionally, Eaton CSEs and Authorized Distributors can find Bulletin Board information on the Powerware Intranet for documentation, technical support and training. Go to the Powerware Global Services Bulletin Board and login with your User Name and Password. CSEs: Go to the Intranet, click on USA Groups/CSE/Quicklinks/Technical Support Distributors: Enter this URL into your Browser address: http://gstechsup.powerware.com/.
© 2006 - Eaton Corporation
8-21
Removal and Replacement
9355 20 – 30 kVA
This page was left blank intentionally.
8-22
© 2006 - Eaton Corporation
9 Calibration Calibration is the adjustment of a given parameter based on known or proven data to make that parameter truer or more consistent. Refer to Figure 76, Analog Potentiometer Diagram. In an analog control system, a potentiometer (or variable resistor) has often been used to alter a DC voltage on a given test point. The adjusted voltage could be an alarm threshold or trigger point for many different types of analog circuits. When the voltage at the input of the circuit reaches or exceeds the value set by the variable resistor, the circuit becomes active or inactive depending on the design of the circuit. Vi
12vdc TP
TP
Vi
Figure 76.
Vo
Vi < TP, Vo = Inactive Vi > TP, Vo = Active
Analog Potentiometer Diagram
Refer to Figure 77, Analog to Digital Circuit. Like the analog circuit, a digital circuit can be altered in a similar manner. In place of the analog potentiometer, a digital circuit will use an analog to digital (A/D) converter to process the analog signal into a numeric representation for use by a digital processor. A voltage of 6VDC may be represented in the A/D converter by the hexadecimal number 2315. Although 2315 has no significant meaning to us, this number represents 6VDC to the processor. This number is often called a “RAW” value, meaning that the digital number is assigned by the A/D converter to represent the 6VDC analog signal. The manner in which an A/D Converter represents the analog data it detects is dependant on the type of converter and its parameters. Analog (6vdc) Vi
Digital (0010 0011 0001 0101)
A/D Figure 77.
6vdc
CPU
Laptop
Analog to Digital Circuit
© 2006 - Eaton Corporation
9-1
Calibration
9355 20 – 30 kVA
Refer to Figure 78, Digital Potentiometer Diagram. Calibration in a computer environment can be looked at as a digital potentiometer, variable resistor, or trim pot having a minimum and maximum limit. Like analog adjustment devices, digital pots also have minimum and maximum limits. Since values found in EEP are 16 bits in length, the range of an individual EEP address is 0000 to FFFF in HEX or 0 to 65535 in decimal. This becomes the minimum and maximum limits for the digital pot. 32,768
(+)
(-)
(+)
(-)
10,000
(Calibration)
0
Digital Potentiometer Range: 0 - 65535
Figure 78.
Digital Potentiometer Diagram
In a digital circuit (like those found in the Powerware® 9355), the raw value can be altered or scaled so that the value seen by the user has more meaning. A formula (created by a firmware engineer) is used by the CPU firmware to make this transition. This value now becomes known as a “Metered Value.” An element of that formula is called a “Meter Calibration Factor” and serves to provide a means to adjust the value used by the CPU firmware. The calibration factor is stored in an EEPROM (EEP) location as a percentage of the computed value from the A/D converter. These metered values and their associated calibration factors are stored in the EEPs of the DSP processor and are accessible by the XCP Service Tool. All calibration factors are stored as a percentage: 10,000 represents 100.00% of scale Values are usually linear which means: •
If the Calibration Factor is increased, the reading increases
•
If the Calibration Factor is decreased, the reading decreases
The formula typically used to adjust any 10000 based calibration factor is as follows: Actual × Cal . Factor = New Cal . Factor Unit
9-2
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Calibration
Actual = a reading taken from a calibrated DVM: •
On a single feed unit from X1-1, X1-2, and X1-3.
•
On a dual feed unit at CB-1 (2, 4, 6).
Unit = the metered value (on display) from the unit or METERS tab on XCP Service Tool. (Preferred method is XCP Service Tool.) Cal. Factor = value found in the associated EEP location New Cal. Factor = the resulting cal. factor entered into EEP Example #1, (Meter Calibration) DSP EEPROM 3040 – UTILITY VOLTAGE PHASE A CALIBRATION FACTOR Value found in this location is 10000 Meter value as seen by the XCP Service Tool (and DSP) shows 208VAC. Meter value as seen by a calibrated DVM shows 215VAC. There is a calibration error of 7VAC. To calibrate this metering input, the formula presented above is used: 215 ⎞ Example: ⎛⎜ ⎟ × 10000 = 10336 ⎝ 208 ⎠
This means that this meter calibration factor must be increased by 3.36% to a new EEP value of 10336 (103.36%). 10000 in DSP EEP 3013 is replaced with a value of 10336. The metered value now read by the UPS should be 215VAC, a true representation of the actual voltage measurement. Note: Exact EEP values for meter calibration factors may have to be altered slightly from the calculated result in order to be able to achieve the exact meter values desired.
The same techniques just illustrated above are used for calibrating meter values and display values as they relate to current and power values.
CAUTION It is good practice to map the system EEPROMS prior to performing Calibration to circumvent potential problems.
© 2006 - Eaton Corporation
9-3
Calibration
9.1.1
9355 20 – 30 kVA
Calibrate Bypass AC Input Voltage
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation.
9-4
1.
UPS / Customer load should be on maintenance bypass wraparound or off (down stream breakers open).
2.
Begin with the UPS in Standby mode.
3.
Connect the XCP Service Tool and go to the Meters Tab.
4.
Calibrate the Bypass AC Input Voltage (see Figure 79 for 208V test points: •
Measure Bypass AC Input: (208V) X1-1 (Phase A) to X-4 (N).
•
Double-click on the Bypass AC Phase A input meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Bypass AC Input: (208V) X1-2 (Phase B) to X-4 (N).
•
Double-click on the Bypass AC Phase B input meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Bypass AC Input: (208V) X1-3 (Phase C) to X-4 (N).
•
Double-click on the Bypass AC Phase C input meter on the XCP Service Tool and enter the measured value from the DVM.
5.
Verify meters on the Front Display, XCP Service Tool and DVM and match them to within 2%. If they are not within 2%, then repeat Step 4.
6.
Calibration complete.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
9.1.2
Calibration
Calibrate Utility AC Input Voltage
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. 1.
UPS / Customer load should be on maintenance bypass wraparound or off (down stream breakers open).
2.
Begin with the UPS in Standby mode.
L1, L2, L3 CB1 contacts
Input L1, L2, L3 X1-1, X1-2, X1-3 X4 - Neutral
X4 - Neutral
Output L1, L2, L3 X2-1, X2-2, X2-3
Figure 79.
9355 Front Calibration Points
© 2006 - Eaton Corporation
9-5
Calibration
9355 20 – 30 kVA
3.
Connect the XCP Service Tool and go to the Meters Tab.
4.
Calibrate the Utility AC Input Voltage, see Figure 79 for 208V test points. •
Measure Utility AC Input (208V) X1-1 (Phase A) to X-4 (Neutral).
Note: For a dual feed UPS use the L1 contact point at the CB-1 input. •
Double-click on the Utility AC Phase A input meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Utility AC Input: (208V) X1-2 (Phase B) to X-4 (Neutral).
Note: For a dual feed UPS use the L2 contact point at the CB-1 input. •
Double-click on the Utility AC Phase B input meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Utility AC Input: (208V) X1-3 (Phase C) to X-4 (Neutral).
Note: For a dual feed UPS use the L3 relay point at the CB-1 input. •
9-6
Double-click on the Utility AC Phase C input meter on the XCP Service Tool and enter the measured value from the DVM.
5.
Verify meters on the Front Display, XCP Service Tool and DVM and match them to within 2%. If they are not within 2%, then repeat Step 4.
6.
Calibration complete
© 2006 - Eaton Corporation
9355 20 – 30 kVA
9.1.3
Calibration
Calibrate Battery Voltage
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. The battery breaker must be closed to calibrate battery voltage. The UPS must be off with logic power only. Once the battery breaker is closed, the system can be returned to bypass mode. 1.
UPS / Customer load should be on maintenance bypass wraparound or off (down stream breakers open).
2.
Begin with battery breaker closed and the UPS off with logic power only.
3.
Connect your laptop to the UPS and run the XCP Service Tool:
4.
•
Select the Meters tab
•
Verify DC is less than 25 Volts
•
Verify that Battery voltage is greater than 216 Volts
Calibrate the Battery Voltage: •
Measure Battery Voltage from the positive connection X49 to the negative connections X34. ⎛ DVM Re ading ⎞ ⎟⎟ × 10000 = EEPROM entry ⎝ Meters Re ading ⎠
Using the calibration equation ⎜⎜ •
Double click on the Battey meter on the XCP Service Tool and enter the measured value from the DVM. The service tool will ask you to enter it a second time, enter the same reading you entered the first time.
5.
Verify meters on the Front Display, XCP Service Tool and DVM and match them to within 2%. If they are not within 2%, then repeat Step 4.
6.
Calibration complete.
© 2006 - Eaton Corporation
9-7
Calibration
9.1.4
9355 20 – 30 kVA
Calibrate DC Link Voltage
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM) Table 46. DC Link Voltage Calibrations Output Voltage
DC Link:
208
(+) or (-) 194.5
400
(+) or (-)
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. Note: Write down EEPROMs before beginning this procedure.
1.
UPS / Customer load should be on maintenance bypass wraparound or off (down stream breakers open.
2.
Begin with UPS on NORMAL and Battery Charger off.
3.
Connect the XCP Service Tool and go to the Meters Tab.
4.
Calibrate the DC Link Rail Voltages: (see Figure 81 for 208V test points). •
Measure the Positive DC Link Voltage: (208V) from connector X47 (DC+) to X52 (Neutral); or you may test from the bus bar.
•
Double-click on the +DC meter on the XCP Service Tool and enter the target voltage from Table 46 and the measured value from the DVM.
Note: The DC Link Voltage is not shown on the UPS LCD.
9-8
5.
Wait until the battery charger is on and confirm voltage with a DVM.
6.
Verify XCP Service Tool meters and DVM match within 2%. If they are not within 2%, then repeat Step 4.
7.
Calibration complete.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
9.1.5
Calibration
Calibrate UPS AC Output Voltage
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. 1.
UPS / Customer load should be on maintenance bypass wraparound or off (down stream breakers open).
2.
Begin with UPS on BYPASS.
3.
Connect to the XCP Service Tool and go to the Meters Tab.
4.
Calibrate the UPS AC Output Voltage: (see Figure 79 for 208V test points). •
Measure UPS AC Output: X2-1 (Phase A) to X-4 (Neutral)
•
Double-click on the Output AC Phase A output meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure UPS AC Output: X2-2 (Phase B) to X-4 (Neutral)
•
Double-click on the Output AC Phase B output meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure UPS AC Output: X2-3 (Phase C) to X-4 (Neutral)
•
Double-click on the Output AC Phase C output meter on the XCP Service Tool and enter the measured value from the DVM.
5.
Verify XCP Service Tool meters and DVM match within 2%. If they are not within 2%, then repeat Step 4.
6.
Calibration complete.
© 2006 - Eaton Corporation
9-9
Calibration
9.1.6
9355 20 – 30 kVA
Calibrate Inverter AC Output Voltage
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation.
NOTICE When performing a whole system calibration, the inverter voltage must be done last. When calibrating the Inverter AC Output, the calibration adjustment is not to match the measured voltage, but to adjust the measured voltage as seen in Table 47, Inverter Voltage Calibrations. The output meters on the display were adjusted with the bypass calibration while the unit was in bypass.
Table 47. Inverter Voltage Calibrations Output Voltage
Calibrate To:
208
120.1
400
230.9
1.
UPS / Customer load should be on maintenance bypass wraparound or off (down stream breakers open).
2.
Begin with UPS on NORMAL.
3.
Connect the XCP Service Tool and go to the Meters Tab.
NOTICE Once the Inverter has reached its target voltage, the XCP Service Tool meters stabilize and do not change during normal operation. The objective with Inverter AC Output calibration is to adjust the inverter output until the DVM meter is at the target voltage listed in Table 47. The output meters should indicate the change but the inverter meters will not. 9-10
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Calibration
4.
9.1.7
Calibrate the Inverter AC Output Voltage: (see Figure 79 for 208V test points): •
Double click on the Inverter AC Phase A output meter on the XCP Service Tool and enter the target voltage from Table 47.
•
Enter the measured value from the DVM for each phase. After entering phase “A” the tool will ask for phase “B” and then for phase “C”.
•
Measure Inverter AC Output: (208V) X2-1 (Phase A) to X-4 (Neutral).
•
Measure Inverter AC Output: (208V) X2-2 (Phase B) to X-4 (Neutral).
•
Measure Inverter AC Output: (208V) X2-3 (Phase C) to X-4 (Neutral).
5.
Verify that the XCP Service Tool output target voltage and the DVM match within 2%. If they are not within 2% then repeat step 4.
6.
Calibration complete.
Calibrate Inverter DC Output Voltage
Due to the special metering required to accurately measure the DC on the inverter output, this calibration cannot be performed at this time and is not required; however, this calibration is performed at the factory after manufacturing. If the Control Board must be changed, every effort must be made to set EEPROM 3070 & 3072 on the new Control Board to the same setting as the old Control Board. Otherwise, EEPROM 3070 & 3072 should be set to the default of 10000.
© 2006 - Eaton Corporation
9-11
Calibration
9.1.8
9355 20 – 30 kVA
Calibrate Bypass Current (Output)
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
•
AMP Clamp
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. This calibration procedure requires a minimum of 80% load to be accurate. If this procedure is not conducted with the minimum load requirement (80%), metering results may be skewed as much as 5% or more at 100% load. Default of 10000 is better than mis-calibration. 1.
UPS / Customer load should be on or a load bank attached to the output of the UPS.
2.
Begin with UPS on BYPASS.
3.
Connect the XCP Service Tool and go to the Meters Tab.
4.
Calibrate Bypass Current: •
Measure Bypass Phase A current: (208V) at X40 on the I/O Board. (see Figure 80)
Figure 80.
9-12
I/O Board Bypass Phase A, B and C
•
Double click on the Bypass Phase A current meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Bypass Phase B current: at X41 on the I/O Board. (see Figure 80).
•
Double click on the Bypass Phase B current meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Bypass Phase C current: at X42 on the I/O Board. (see Figure 80) © 2006 - Eaton Corporation
9355 20 – 30 kVA
Calibration
•
Double click on the Bypass Phase C current meter on the XCP Service Tool and enter the measured value from the DVM.
5.
Verify that the XCP Service Tool meters and DVM match within 2%. If they are not within 2% repeat step 4.
6.
Calibration complete.
X61 X60
DC+
BATT CD TRIP X50
X55
DC+ X47
X12
X6
X7
X11
INV
AAUX
INV L3
X21 X27
INV L2 FANS
INV L1
K3
DC neut RECT L3 X78 X2 IN/OUT CB TRIP
BAT COLD START
L3 X76
K1
BATT BKUP X46
X45
BAT
DC-
X82 L3 L2 L1 X28 X29 X4
DCX43
BATTERY CHOKES
Batt Bkup X46
X79
X25
Figure 81.
X23 X13
X54
X42 X41 X40
Batt Plus X49 208V DC Link Voltage Calibration test points
© 2006 - Eaton Corporation
9-13
Calibration
9.1.9
9355 20 – 30 kVA
Calibrate Utility Current
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
•
AMP Clamp
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. This calibration procedure requires a minimum of 80% load to be accurate. If this procedure is not conducted with the minimum load requirement (80%), metering results may be skewed as much as 5% or more at 100% load. Default of 10000 is better than mis-calibration.
9-14
1.
UPS / Customer load should be on or a load bank attached to the output of the UPS.
2.
Begin with UPS on NORMAL.
3.
Connect the XCP Service Tool and go to the Meters Tab.
4.
Calibrate Utility Input Current , (see Figure 81 for 208V test points): •
Measure Utility Phase A current: (208V) X1-1 (Phase A) to X-4 (Neutral)
•
Double click on the Utility Phase A current meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Utility Phase B current: (208V) X1-2 (Phase B) to X-4 (Neutral)
•
Double click on the Utility Phase B current meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Utility Phase C current: (208V) X1-3 (Phase C) to X-4 (Neutral)
•
Double click on the Utility Phase C current meter on the XCP Service Tool and enter the measured value from the DVM.
5.
Verify that the XCP Service Tool meters and DVM match within 2%. If they are not within 2% repeat step 4.
6.
Calibration complete.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
9.1.10
Calibration
Calibrate Battery Current
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
•
Clamp-on DCCT
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. This procedure requires that the battery be discharging for a short period of time so the discharge current can be measured and calibrated. This calibration procedure also requires a minimum of 80% load to be accurate. If this procedure is not conducted with the minimum load requirement (80%), metering results may be skewed as much as 5% or more at 100% load. Default of 10000 is better than mis-calibration. At the beginning of the procedure, the system must be in NORMAL mode with the battery breaker closed. 1.
Connect the XCP Service Tool and go to the Meters Tab.
2.
Put the system in battery mode by opening the Utility Input breaker, simulating a utility outage.
3.
Calibrate Battery Current (with 80% load while discharging) : a.
Measure Battery Current on the battery wire connected to: (208V) X49, see Figure 81
b.
Double click on the Battery current meter on the XCP Service Tool and enter the measured value from the DVM.
4.
Restore utility input to the system. (System should automatically return to NORMAL mode.)
5.
Verify that the XCP Service Tool meters and the DVM match within 2%. If they are not within 2% repeat step 4.
6.
Calibration complete.
© 2006 - Eaton Corporation
9-15
Calibration
9.1.11
9355 20 – 30 kVA
Calibrate Inverter Current
Tools Required: •
XCP Service Software Tool
•
Computer with software tool authorization
•
Calibrated, True RMS Digital Volt Meter (DVM)
•
AMP Clamp
If at any time during this procedure an alarm condition prevents the continued execution of the following steps, consult paragraph 7.1.2, Alarm, Notice, Status & Flag Definitions to determine and correct the cause of the event annunciation. This calibration procedure requires a minimum of 80% load to be accurate. If this procedure is not conducted with the minimum load requirement (80%), metering results may be skewed as much as 5% or more at 100% load. Default of 10000 is better than mis-calibration.
9-16
1.
UPS / Customer load should be on or a load bank attached to the output of the UPS.
2.
Begin with UPS on NORMAL.
3.
Connect the XCP Service Tool and go to the Meters Tab.
4.
Calibrate Inverter Output Current: •
Measure Inverter Phase A current (for 208V see Figure 79 for Phase A test points X2-1 and X-4).
•
Double click on the Inverter Phase A current meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Inverter Phase B current (for 208V see Figure 79 for Phase B test points X2-2 and X-4).
•
Double click on the Inverter Phase B current meter on the XCP Service Tool and enter the measured value from the DVM.
•
Measure Inverter Phase C current (for 208V see Figure 79 for Phase C test points X2-2 and X-4).
•
Double click on the Inverter Phase C current meter on the XCP Service Tool and enter the measured value from the DVM.
5.
Verify that the XCP Service Tool meters and the DVM match within 2%. If they are not within 2% repeat step 4.
6.
Calibration complete.
© 2006 - Eaton Corporation
10 Parts Chapter 10 Parts 10.1 PW 9355 30kVA SPARE PARTS LISTINGS 10.1.1 Low Voltage PW 9355 30kVA Spare Parts Kit “A” P/ N 106711170 10.1.2 High Voltage PW 9355 30kVA Spare Parts Kit “A” P/ N 10.2 PW 9355 30kVA UPS Subassemblies 10.2.1 LV Electronic Module 10.2.2 HV Electronic Module 10.3 Parts Break-down / Look-up Procedure 10.3.1 Requirements: 10.3.2 Procedure
10-1 10-1 10-2 10-2 10-2 10-3 10-4 10-4 10-4
10.1 PW 9355 30kVA SPARE PARTS LISTINGS
NOTICE Part numbers are subject to change. CSE’s should always check the latest assembly and part numbers on PRMS ACCESS to verify part numbers before ordering.
10.1.1 Low Voltage PW 9355 30kVA Spare Parts Kit “A” P/ N 106711170 Component
Description
UM
Qty
1021278
PCBAS CONTROL BOARD
EA
1
1024053
PCBAS K30 LV 3PH I/O BOARD
EA
1
1024049
PCBAS K30 LV 3PH PWR BOARD
EA
1
1021994
IGBT 3X94A 600V HB SKIIP2
EA
3
103004890
SUBAS K15 DISPLAY PANEL
EA
1
101073763
EMI BOARD
EA
1
128308001-012
FUSE, 200 A, 500 VAC
EA
1
1024057
BYPASS BOARD
EA
1
129400054-002
THERMAL INTERFACE PAD
EA
6
143319005-001
SCR, DUAL, MODULE, 160A, 1600V
EA
3
© 2006 - Eaton Corporation
10-1
Parts
9355 20 – 30 kVA Component
Description
UM
Qty
8052457
160A 240V 160LET Fuse
EA
3
1024046
FAN 119x119x39 51l/s 115VAC UL
EA
2
129400066-001
THERMAL INTERFACE PAD, IGBT
EA
6
10.1.2
High Voltage PW 9355 30kVA Spare Parts Kit “A” P/ N Component
UM
Qty
PCBAS CONTROL BOARD
EA
1
PCBAS K30 LV 3PH I/O BOARD
EA
1
PCBAS K30 LV 3PH PWR BOARD
EA
1
IGBT 3X94A 600V HB SKIIP2
EA
3
SUBAS K15 DISPLAY PANEL
EA
1
EMI BOARD
EA
1
FUSE, 200 A, 500 VAC
EA
1
BYPASS BOARD
EA
1
THERMAL INTERFACE PAD
EA
6
SCR, DUAL, MODULE, 160A, 1600V
EA
3
8052457
160A 240V 160LET Fuse
EA
3
1024046
FAN 119x119x39 51l/s 115VAC UL
EA
2
129400066-001
THERMAL INTERFACE PAD, IGBT
EA
6
1021278
103004890 128308001-012 129400054-002
Description
10.2 PW 9355 30kVA UPS Subassemblies 10.2.1
LV Electronic Module P/N
10-2
DESC
QTY
1021278
PCBAS CONTROL BOARD
1
103004890
SUBAS K30 DISPLAY PANEL
1
1021994
IGBT 3X94A 600V HB SKIIP2
9
1024046
FAN 119X119X39 51L/S 115VACUL
6
157809032
TRAY, BATTERY
24
101073763-001
9355 30kVA EMI / MOV PCB
1
1024049
PCBAS, POWER BOARD 3K30LV
3
1024053
PCBAS, IO BOARD 3K30LV
1
1024057
PCBAS, BYPASS BOARD 3K30LV
1
122129008-001
CIRCUIT BREAKER, 2 POLE, 200 A
1
122161004-001
CIRCUIT BREAKER, 3 POLE, 125 A
1
123118002-001
CONT, 115A, 480VAC,3 POLE, NO
1
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Parts
P/N
DESC
QTY
123118002-002
CONT, 130A, 480VAC,3 POLE, NO
2
128308001-012
FUSE, 200 A, 500 VAC
3
129400054-002
THERMAL INTERFACE PAD
3
129400066-001
THERMAL PAD, SKIIP2 PACKAGE
9
143319005-001
SCR, DUAL, MODULE, 160A, 1600V
3
145205027-001
SWITCH, SELECTOR, 100 A, 600 V
1
145301073-001
SWITCH, PUSHBUTTON, SPST, N.O.
1
151201040-004
AIR FILTER, STRATADENSITY
1
151501017-001
FAN GUARD, 4.125" MOUNT
6
58700036-001
BATTERY, 12V, 9 AH
10.2.2
108
HV Electronic Module P/N
1021278
DESC
QTY
PCBAS CONTROL BOARD
1
SUBAS K30 DISPLAY PANEL
1
IGBT 3X94A 600V HB SKIIP2
9
FAN 119X119X39 51L/S 115VACUL
6
TRAY, BATTERY
24
9355 30kVA EMI / MOV PCB
1
PCBAS, POWER BOARD 3K30LV
3
PCBAS, IO BOARD 3K30LV
1
PCBAS, BYPASS BOARD 3K30LV
1
CIRCUIT BREAKER, 2 POLE, 200 A
1
CIRCUIT BREAKER, 3 POLE, 125 A
1
CONT, 115A, 480VAC,3 POLE, NO
1
CONT, 130A, 480VAC,3 POLE, NO
2
FUSE, 200 A, 500 VAC
3
THERMAL INTERFACE PAD
3
THERMAL PAD, SKIIP2 PACKAGE
9
SCR, DUAL, MODULE, 160A, 1600V
3
SWITCH, SELECTOR, 100 A, 600 V
1
SWITCH, PUSHBUTTON, SPST, N.O.
1
AIR FILTER, STRATADENSITY
1
FAN GUARD, 4.125" MOUNT
6
BATTERY, 12V, 9 AH
© 2006 - Eaton Corporation
108
10-3
Parts
9355 20 – 30 kVA
10.3 Parts Break-down / Look-up Procedure This procedure is designed to ensure that Customer Service Engineers have the flexibility to look up the most current part number and/or research a previously listed part number on any Powerware® product.
10.3.1
10.3.2
Requirements: a.
Access to Eaton’s Powerware Division Intranet: http://poweratwork/usa/
b.
An assembly number where the parts are located. A CTO Number
Procedure
Once you have the assembly or CTO number, you can break it down and retrieve the part number using the following steps:
NOTICE The PRMS system may be slow, depending on the number of Logins and time of day. If at any time during this process you receive a web page message stating that it is not available, your session has timed out and you will have to start over.
10-4
1.
Go to http://poweratwork/usa/
2.
Under “Applications” on the right hand side, select “PRMS ACCESS.”
3.
For “User” enter “LSGINQ” (upper or lower case)
4.
For “Password” enter “ky9ag” (upper or lower case)
5.
Leave all other entries blank.
6.
At top left of the next page select “ENTER” (at top left).
7.
Select “ENTER” two more times (to bypass the Sign On and Display Messages pages.)
8.
In the “Option” block, enter “1” and press “ENTER” for “Production Utility”.
9.
In the “Option” block, enter “1” and press “ENTER” for “Product Structure Inquiry”.
© 2006 - Eaton Corporation
9355 20 – 30 kVA
Parts
At this point you have some options: a.
Option One: - To simply break down an assembly to its various components (part numbers), go to step 10.
b.
Option Two - To break down the assembly to its various component parts from a previous date, (an earlier product release) go to step 11.
c.
Option Three: - If you have a part number to a part, other than the one you want, but it is in the same assembly, you can look up a “where used”. You can then look for the part number of the component you’re looking for. Go to step 12.
d.
Option Four: - To look up assembly and component (part) numbers using the Configuration to Order (CTO) number, go to step 13.
10. In the assembly block enter the assembly number and press ”ENTER”. (Use the buttons at the bottom of the web page to navigate to the next pages containing additional components for that assembly. If ’More...’ is shown on bottom of right column, click the ’Next Page’ button to see the remaining parts. The last page of parts will show ’Bottom.’) 11. In the assembly block enter the assembly number and in the effective date block enter a previous date (format mmddyy) and press ”ENTER”. 12. Select “F2” at the bottom of the web page. In the “Component” block enter the part number and press ”ENTER”. The system will provide you with the assembly numbers on every unit where that part is used. If it is a common part across platforms you will have several pages of information. 13. In the assembly block enter the CTO number and press ”ENTER”. (You must use the buttons at the bottom of the web page to navigate to the subsequent pages containing additional components for that assembly.)
NOTICE If you need to look up another assembly number, or a sub-assembly of the assembly you just looked up, you must use the “F” buttons near the bottom of the web page, not the “F” keys on your keyboard.
© 2006 - Eaton Corporation
10-5
Parts
9355 20 – 30 kVA
This page was left blank intentionally.
10-6
© 2006 - Eaton Corporation
11 Prints PW 9355 20 - 30 kVA Prints Table Of Contents PAGE
DRAWING
SHT
CATEGORY
DESCRIPTION
REV
1
1024051
1
Schematic
Power Board 30kVA LV
2
2
1024055
1
Schematic
I/O Board 30kVA
B
3
2
4
3
5
1024056
1
Silkscreen
I/O Board
B
6
1024059
1
Schematic
Bypass Board 30kVA LV
3
7
1024062
1
Silkscreen
Bypass Board
3
8
110720620
1
Drawing
9355 EMI Filter
A00
9
110720639
1
Schematic
Top Level 30kVA 9355 LV
1
10
110720676
1
Schematic
9355 Options Cabinet
C00
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
110720683
1
Drawing
9355 30kVA EMI Filter
B00
19
110720684
1
Drawing
9355 30kVA EMI Filter
A00
20
110720687
1
Drawing
9355 30kVA Input EMI Filter
A00
21
121102093
1
Drawing
Rectifier/Inverter Choke
A00
22
121102094
1
Drawing
Battery Choke
A00
23
CTO Chart
1
Table
110577093
C00
24
2
© 2006 - Eaton Corporation
11-1
Prints
9355 20 – 30 kVA
This page was left blank intentionally
11-2
© 2006 - Eaton Corporation
1024055B.sch-1 - Wed Dec 28 10:01:09 2005
1024055B.sch-2 - Wed Dec 28 10:01:14 2005
1024055B.sch-3 - Wed Dec 28 10:01:23 2005
Page 5
10240593.sch-1 - Mon Nov 21 08:40:23 2005
Page 7
1
1
9355 30kVA Option Cabinet
120V
120V 120V
9355-30 Options cabinet - 208/208, 480/208, 600/208 Bypass Transformer
1
8
9355 30kVA Option Cabinet
9355-30 Options Cabinet - MBS only
2
8
9355 30kVA Option Cabinet
120V
120V 120V
9355-30 Options cabinet - 208/208, 480/208, 600/208 Mains Input transformer
3
8
9355 30kVA Option Cabinet
T1 277V 208V
277V
208V
277V
208V
9355-30 Options Cabinet - 208/480 Output Transformer
4
8
9355 30kVA Option Cabinet 9355 30kVA UPS Cabinet
120V
120V 120V
9355-30 Options Cabinet - System - Single feed 208/208, 480/208, or 600/208
5
8
9355 30kVA Option Cabinet 9355 30kVA UPS Cabinet
9355-30 Options Cabinet - System - Single feed, MBS only
6
8
9355 30kVA Option Cabinet
9355 30kVA Option Cabinet 9355 30kVA UPS Cabinet
120V
120V 120V
T1 277V 208V
277V
208V
277V
208V
9355-30 Options Cabinet - System - Single feed 480/480
7
8
9355 30kVA Option Cabinet
9355 30kVA Option Cabinet 9355 30kVA UPS Cabinet
120V
120V 120V
120V
120V 120V
9355-30 Options Cabinet - System - Dual feed 208/208, 480/208, or 600/208
8
8
NOTES: 1. Materials/com ponents shall meet RoHS regulations per Eaton Power Quality RoHS specification 164080496. 2. Bulk packaging shall indicate contents are RoHS com pliant. 3. Docum entation indicating m aterials/components are RoHS com pliant (Certificate of Compliance and M aterial Analysis) shall be available upon request.
NOTES: 1. M aterials/com ponents shall meet RoHS regulations per Eaton Power Quality RoHS specification 164080496. 2. Bulk packaging shall indicate contents are RoHS com pliant. 3. Docum entation indicating m aterials/components are RoHS com pliant (Certificate of Compliance and M aterial Analysis) shall be available upon request.
1 Model Type
K
PW9355
2 Product Family
A
9355-15 (See 110577092)
B
9355-30
3-4 UPS KVA Rating
5 Application
20
20 KVA
1
30
30 KVA
2
6 Battery Configuration
R/T
Note: Selections in this column can't be 0-4, 6, 7,D, S, L.
(no output breaker) (Factory default)
Parallel (no output breaker)
3
3x battery shelves 9Ah (108 batteries)
7 UPS Configuration
8 Comm Option (Slot 1)
9 Future Option
10 Future Option
11 Future Option
12 Future Option
13 Future Option
14 OEM
0
0
0
0
0
1
1
120/208V in/out 50/60 Hz Autodetect
0
None
2
127/220V in/out 50/60 Hz Autodetect
3
Connect UPSX Web/SNMP
3
R/T with output breaker
4
Modbus Card
4
Parallel with output breaker
5
Relay Card
6
Industrial Relay Card
7
Modem Card
None
None
None
None
None
15 Future Option
Eaton
0
None
Only Slot 1 populated from factory
Notes: 1
Supporting Documents: Schematic - 30kVA UPS Schematic - 30kVA EBC Option Cabinet CTO
110720639 110720675 110577094
Description: CTO Created By:
CHART, 9355 30KVA UPS HARDY_J
Modified By:
Date: 05-JAN-06 Date:
OBJECT ID:
110577093
Checked By:
WALLACE_T
Date: 21-MAR-06
ECN 9355-0164
Revision: C00
Approved By:
HARDY_J
Date: 21-MAR-06
Status: RELEASED
Sheet 1 of 2
These Drawings and Specifications Are the Property Of Eaton / Powerware and Shall Not be Reproduced or Copied or Used as the Basis for Manufacture of Sale of Apparatus Without Permission
Position
1 Model Type
2
3-4
Product UPS KVA Rating Family
5
6
7
8
Application
Battery Configuration
UPS Configuration
Comm Option
Base unit K
B
20 or 30
BOM 1
103004897
R/T (no output breaker)
103005372
BOM 3 3 battery shelves
103004887 (12x)
BOM 1
0 None
3 Connect UPS-X 2 Parallel (no output breaker)
103005372 + 101073663-001
2
3 R/T with output breaker
4 Parallel with output breaker
103005373
103005373 + 101073663-001
9-12
4
13
14
15
Future Option
OEM
Future Option
BOM
BOM
NA
1
103004888
103002974-5501
4 Modbus Card
103002511-551 + 103002818 + 164201376
5 Relay Card
1018460
6 Industrial Relay Card
103002686 + 164201433
7 Modem Card
1019017
5
6
Only Slot 1 populated from factory
Options REPO Remote Monitor Wall mount MBS Parallel Tie Cabinet External battery (4 strings) External battery (2 strings) kVA Upgrade 20 to 30 Parallel Upgrade Kit Seismic Kit
103002939 103002687-001 + 103003055 124100026-001 124100026-001 103004868 103005183 103004901 103005160 103004896
X-slot Communication Options (Order separate, field install) Parallel (CAN Bridge) 103004336 Connect UPS-X Web/SNMP 103002974-5501 Modbus Card 103002510-5501 Relay Card 1018460 Industrial Relay Card 103003055 Modem Card 1019017
Description: CTO
CHART, 9355 30KVA UPS OBJECT ID:
Created By:
HARDY_J
Date: 05-JAN-06
Modified By:
X
Date:
Checked By:
WALLACE_T
Date: 21-MAR-06
ECN 9355-0164
Revision: C00
Approved By:
HARDY_J
Date: 21-MAR-06
Status: RELEASED
Sheet 2 of 2
110577093
These Drawings and Specifications Are the Property Of Eaton / Powerware and Shall Not be Reproduced or Copied or Used as the Basis for Manufacture of Sale of Apparatus Without Permission