MMBS Installation Guide < Sprint >
2011 3 2011. 3. 25 H/W Infra Lab.
Annotation) This data could be revised while designing in detail.
1. System Description Confidential Items System Type Frequency Sector Channel BW (MHz)
Weight
Network Interface
Specification MMBS Outdoor 800MHz, 1.9GHz, 2.5GHz, 2.5GHz @ RRU Max. 4 RRU/ sector (Total 12 RRU max) 7MHz (800M), (800M) 65MHz(1 65MHz(1.9G), 9G) 20MHz(2 20MHz(2.5G) 5G) BBU Cabinet : - (kg) w/o DU shelf - (kg) with 4 DU shelf Battery Cabinet : - (kg) w/o battery - (kg) with battery T1 or M/W or optic
Physical Dimensions 1800x700x1018(820) 800 00 0 8(8 0) mm / 70.8in 0 8 x 29.5in 9 5 x 40.1(37.0)in 0 (3 0) (H W D) (HxWxD) 220VAC (22A,max) @ w/o battery,Only CDMA 220VAC (36A,max) @ w/o battery,CDMA/LTE/WiMAX Power Consumption 220VAC (40A,max) @ with battery, Only CDMA 220VAC (80A (80A,max) ma ) @ with ith batter battery, CDMA/LTE/WiMAX DU-RU Interface
CPRI 4.0 specification (Optic)
Note Recommended NFB Capacit Note. Capacity 100A,max. 100A ma 1EA
1
Confidential
Rectifier module Specification Items
Specification
Voltage Range
185~275VAC
Frequency
45~66 Hz(50/60 Hz)
O t t Voltage Output V lt
-53.5 53 5 VDC
Output Voltage Range
-43.5~-57.6VDC
y Efficienty
96% % @ 2kW Output,module p ,
Maximum Output Power
2,000W x 7 @ 25 ℃
Weight
1.950 kg (4.3lbs)
2
Battery
Confidential
3
1.1 System configuration Confidential BBU cabinet
Battery cabinet
PDP Rectifier Battery
WiMAX
Old version
TD-LTE/FDD LTE CDMA CDMA/FDD LTE
User space
Battery
User Space Battery
Cabling Space
Cabling Space
[BBU Cabinet]
Battery
[Battery Cabinet]
4
Confidential <66Block> - Maker : - P/N :
Mudroom
GPS port
- Maker : Roxtec - P/N : ComSeal 16/16
2” Conduit 2 5
4
3
2
1
0
- Maker : Symmetricom - P/N : 58536A
[Mudroom] [Back side of the BBU cabinet] Note. This data could be revised while designing in detail.
5
1.2 System Dimension Confidential
700 0 700.0
[Front View]
433.0
300.0
1,80 00.0
BBU Cabinet
1 018 0 1,018.0
[Left View]
[Rear View] 6
Confidential
Old version
Old version
1,800.0
Battery Cabinet
742.5 700 0 700.0
[Front View]
1 022 3 1,022.3
[Left View] 7
1.3 Floor Layout Confidential
959.8
1225.5
min. distance for no colision opening cabinets
60
1,460min
8
959.8
2,209 9.5
Confidential
60
1,460 min 1,739.8 min
9
670.0 0
Confidential
630.0
[Power/Battery / Cabinet C Anchor Location] 10
1.4 Service Area 60 0 60.0
Confidential
700 0 700.0
762.0
700 0 700.0
Battery
60 2,209.5
System
1,447.5
136 61.0
743.0
Mudroom
1,123.4
760.0
11
1.5 Environment Control Module & Sensor Confidential
Fire Sensor
Fire Sensor
Door Switch
Door Switch
Lamp
Lamp
User Space
Cabling Space Flood sensor
[BBU Cabinet]
Flood sensor
[Batery Cabinet]
12
1.6 External I/F Cable(BBU cabinet) Confidential Item
Cable
Connector
Terminal name
Q’t
Provider
Power (AC)
1P3W, L1/L2 /N : AWG 2 Black/Red/White
NFB terminal
L1,L2,N
Conduit #1
1
STA
Battery Power #0a (Battery)
AWG 1/0 Black/Blue
Compression terminal,1H, M8
Battery switch
Conduit #0
2
Eltek
CAN bus #0(Battery)
SFTP,4p
RJ-45
Conduit #0
1
Eltek
Ferrule
Conduit #0
1
Eltek
Conduit #5
2
Eltek
DC Power #0b(Battery) AWG 12 Battery Power #1a ((Battery) y)
AWG 1/0 Black/Blue
Compression terminal,1H, , , M8
CAN bus #1(Battery)
SFTP,4p
RJ-45
Conduit #5
1
Eltek
DC Power #1b(Battery) AWG 12
Ferrule
Conduit #5
1
Eltek
RRU cable
Power,bare wire
-
Conduit # 2,3,4
3
HQ
Mudroom, C Comseal l
16max
STA
1
STA
1
STA
1
STA
Hybrid, Option
Battery switch
Optic,LC Backhaul(T1)
Shield type
RJ-45, wire
Surge protector
User Define Alarm
Shield type
Bare wire
66 block
GPS
LMR-400
N-Male or N-Female
GPS arrestor
Ground
AWG 2
Compression terminal 2H M6 terminal,2H, M6, L5/8” L5/8
Ground bus bar
Conduit #1
13
1.7 I/F Port Position Confidential
Battery Power terminal AC terminal
Battery operating power terminal
RRU DC P Power RRU Optic
User Space
CAN BUS
CAN BUS Cabling Space
Ground
[BBU Cabinet]
[Batery Cabinet]
14
Confidential
UDA,Backhaul
Mudroom
GPS port
< Comseal > - Maker : Roxtec - P/N : ComSeal 16/16
2” Conduit 2 5
4
3
2
1
0
UDA or Link cable GPS cable
[Mudroom] [Back side of the BBU cabinet] Note. This data could be revised while designing in detail.
15
1.8 Power Blockdiagram Confidential
System Power Blockdiagram
PE
16
Battery Cabinet Power Blockdiagram
Check power supply TN-C in USA 1P3,can it use 2 SPD(L to N) ?
Confidential
17
Confidential
Load Breaker
N o
F 1
F 2
F 3
F 4
F 5
F 6
F 7
F 8
F 9
F 1 0
F 1 1
F 1 2
F 1 3
F 1 4
F 1 5
F 1 6
F 1 7
F 1 8
F 1 9
F 2 0
F 2 1
F 2 2
F 2 3
C a p ac ity
1 6 A
1 6 A
1 6 A
1 6 A
1 6 A
1 6 A
1 6 A
1 6 A
1 6 A
2 0 A
1 6 A
1 6 A
1 6 A
2 0 A
1 6 A
1 6 A
1 6 A
2 0 A
4 A
4 A
2 A
2 A
2 A
RRU#7
RRU#8
RRU#9
RRU#10
RRU#11
FAN #1
FAN#2
Smoke
Light
EAIU
AUX
UADU
F 2 4
RRU RRU#6
RRU#5
RRU#4
RRU#3
RRU#2
RRU#1
RRU#0
DU#3
DU#2
DU#1
DU#0
AUX1
AUX0
Label
1.9 9GHz
1.9 9GHz
1.9 9GHz LVLD LVBD
Coldstart contactor
18
Ref. Power distribution system at US Confidential
19
2.1 SOW Confidential
GPS Antenna Lightning rod BBU Cabinet RRU
Aux. Equip.
AC Power Distribution Panel
Backhaul UDA
Mudroom
AC220V
Ground
Tower Battery Cabinet
Ground
20
2.2 Material List Confidential
To be defined.
21
3. Installation Process Confidential
Material Check
Ground Cable
DU Installation
Backhaul Cable
Ground Buss Installation
AC Power Cable
EAIU Installation
UDA Cable (Option)
Backup Battery Cable
GPS Arrestor& Splitter
GPS Cable
BBU Cabinet Anchoring
Battery Cabinet Anchoring
AUX Installation (Option)
RRU Cable
Check RRU Installation
22
Confidential Antenna
RRU RF Antenna Cable Frame Ground Cable
Power DC Cable GPS Antenna Cable
Optic Cable
User Space Cablin g Space
Power Cable (FR-8 25 mm2 × 3C, 1ea) AC Distribution Panel
Main Ground Bar
Ground Cable(GV 25 mm2 ×1C)
23
Confidential
PDP Rectifier WiMAX TD-LTE/FDD LTE CDMA CDMA/FDD LTE
User Space
Cabling Space Battery cable AC cable hybrid cable
[Front View]
24
Confidential
5
4
3
2
1
To RRU
[Rear View]
0
Conduit No.
Usage
0
Battery #0
1
AC/Ground
2
RRU Alpha
UDA or Link cable
3
RRU Beta
GPS cable
4
RRU Gamma
5
Battery #1
[Mudroom]
25
3.1 Anchoring
670.0
Confidential
630.0
[Power/Battery Cabinet Anchor Location] 26
Confidential
Anchor Bolt
Nut Spring Washer Plane Washer
Floor
2.76”
(M10 Anchor-Bolt)
C Completion off Anchoring
Each equipment requires specific bolting pattern. pattern Verify that you have the right bolt pattern. pattern
27
3.2 Ground Cable Confidential
(Front view)
User Space
25 mm2 Pressure Terminal (ST, M6,2hole, Dist: 5/8”)
Cabling C bli Space
28
3.3 AC Power Cable Confidential
AC (Front view)
100A, 1P3W L1/L2/N
User Space
Cabling C bli Space
Power Cable P C bl AC : L1/L2/N (BLACK/RED/WHITE)
1) Through the conduit #1 2) Connect Ferrule to wire and Fix the cable with switch screw .
29
3.4 Backup Battery Cable Confidential Battery power switch
Routing path : Left,rear edge Batter Battery
Battery
Battery operating power terminal
(Front view)
CAN BUS
User Space
User Space Battery
CAN BUS
Cabling Space Battery
Cabling C bli Space
[Battery Cabinet]
[BBU Cabinet]
30
Confidential
(Front view)
User Space
Cabling C bli Space
31
3.5 UADU installation Confidential 1) Install DU shelf support bracket at 20U with cage nut(M6) 2) Install DU shelf upper side of bracket stackable 3) Tag the DU shelf label 4) Connect DU shelf cable (power GPS Backhaul Alarm) (power,GPS,Backhaul,Alarm)
Power switch
UADU
(Front view)
Bracket
DU shelf bracket
User Space
User Space
Cabling Space
Cabling Space
[BBU Cabinet]
32
Confidential Step.1 DU Blank bracket Install
Example .
1) Fix the bracket at 20U from bottom Mounting frame with M6 Cage nuts
33
Confidential Step.2 UADU Install Step 2-1 UADU Ground cable connection Step.2-1 Detail ‘A’ M6 SEMS
DU Unit backside
4 mm2 Pressure Terminal (d2: 16 mm, 2Hole)
Heat Shrink Tube (Green)
Ground Cable (AWG10, GV 4 mm2 × 1C) Detail ‘B’
※ first connect the Ground cable before install DU unit
1)) Connect ground g cable backside of UADU 2) Fix the UADU upper DU blank bracket with M6 floating nuts 3) Connect the other ends of ground cable at ground bar of the cabinet left bottom . 34
Confidential Step.2-2 UADU install
M6 SEMS
Cage nut
Step.2-3 Ground cable - frame
Ground Cable(AWG10, GV 4 mm2 × 1C)
Heat Shrink Tube(Green) 4 mm2 Pressure Terminal (LUg Type, 2Hole) M6 Hex. Nut Ground Bar
35
Confidential
Power Cable SPEC. from Rectifier to UADU
A2: RTN
D-Sub Plastic hood
Cable
Connector
A1: -48 VDC
SPEC
Wire Color
Power Cable Color ( (CV 2.5 mm2 × 1C-2))
A1(-48VDC: blue) A2(RTN: ( red))
D-Sub Connector(2W2C)302W2CPXX42A10X & Hood
-
Maker
CONEC
36
3.6 EAIU4-U Installation Confidential UDA
Ethernet
(Front view) Switch
User Space
Cabling Space
UDE
Power
1) Re-assemble the wing brackets of EAIU as picture. 2) Fix EAIU at the right frame with M6 M6,SEMS SEMS 2ea as picture
37
Confidential
Cable SPEC. from Rectifier to EAIU
SPEC
Wire Color
Maker
Cable
UL2464 AWG20 UL2464, AWG20, 2C BLK
Black
Korea Maker
Connector
51067-0300
-
MOLEX
SEC CODE : EP39-01736A
38
3.7 Surge protector Installation Confidential
GPS splitter
GPS arrestor
(Rear view)
Roxtec Comseal
Mudroom
[Mudroom]
Note. It will add the surge protector for T1 .
39
3.8 Auxillary Unit Installation Confidential * To be defined.
Power switch
UADU
(Front view)
Bracket
DU shelf bracket
User Space
User Space
Cabling Space
Cabling Space
[BBU Cabinet]
40
3.9 Backhaul – When T1 Confidential
66 Block
GPS splitter
GPS arrestor
(Rear view)
Mudroom
Roxtec Comseal
UDA or Link cable
[Mudroom]
Note. It will add the surge protector for T1 .
41
Confidential
Note. BH did not Final Confirmed
BH (Front view)
User Space
Cabling Space
T1 (from Cell Site Router. Install at User space )
1) Link the cable from UDE port of UADU to CSR. 2) Link T1 cable from CSR to surge protector at mudroom mudroom.
42
Confidential
T1 cable SPEC. from DU to CSR
* Pin MAP RJ45 PLUG Shield type
Pin No.
Pair
Description
COLOR MAP
S-FTP 1
Tip
Rx+
WHITE /ORANGE
2
Ring
Rx-
ORANGE WHITE /GREEN
3 4
Ti Tip
T Tx+
BLUE
5
Rimg
Tx-
WHITE /BLUE
6
GREEN
7
WHITE /BROWN
8
BROWN
SPEC
Wire Color
Maker
Cable
S-FTP, CAT5e
-
-
C Connector t
RJ45 PLUG (Shi (Shield) ld)
-
-
SEC CODE : EP39-
43
3.10 UDA cable Confidential UDA_EAIU ALARM_CABINET 66 Block
(Rear view)
Mudroom
Roxtec Comseal UDA or Link cable
[Mudroom] 1) Pin map is not defined. 2) T1 surge protector spec. is not confirmed. 44
Confidential
SMART PACK_REC PACK REC
Mudroom
UDE (Front view)
UDE
UDE User Space
Cabling Space
2A_PDP
UDE
[EAIU4-U]
45
Confidential
66 Block Pin Map Conne Pin ctor No. 1 2 3 4 5 6 7 8 9 10 11 12 66 13 Block 14 15 16 17 18 19 20 21 22 23 24 25
Primary
Color Map
Secondary
Pin No. 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
Primary
Color Map
Secondary
To be defined.
46
Confidential
Cable SPEC. from EAIU to 66 block
SPEC
Wire Color
Maker
Cable
UL2919 AWG24 UL2919, AWG24, 20PR
-
-
②Connector
10136-3000ve
-
3M
SEC CODE : EP39-01555A
47
Confidential
Cable SPEC. from DU to EAIU/SpartPack
* Pin MAP RJ45 PLUG Shield type
S-FTP
Pin No.
Pair
Description
COLOR MAP
1
TX0+
Ethernet TX Positive signal
WHITE /ORANGE
2
TX0-
Ethernet TX Negative signal
ORANGE
3
RX0+
Ethernet RX Positive signal
WHITE /GREEN
4
TX1+
Ethernet TX Positive signal(Gigabit)
BLUE
5
TX1-
Ethernet TX Negative signal(Gigabit)
WHITE /BLUE
6
RX0-
Ethernet RX Negative signal
GREEN
7
RX1+
Ethernet RX Positive signal(Gigabit)
WHITE /BROWN
8
RX1-
Ethernet RX Negative signal(Gigabit)
BROWN
SPEC
Wire Color
Maker
Cable
S-FTP, S FTP, CAT5e
-
-
Connector
RJ45 PLUG (Shield)
-
-
SEC CODE : EP39-01342B
48
Confidential
Cable SPEC. from SpartPack to Mudroom
* Pin MAP Pin No.
Pair
Description
COLOR MAP
1 2 3 4 5
To be defined
6 7 8
SPEC
Wire Color
Maker
Cable
S-FTP, S FTP, CAT5e
-
-
Connector
-
-
-
SEC CODE : EP39-
49
3.11 GPS Cable Confidential
GPS plitter
GPS arrestor
(Rear view)
Roxtec Comseal
Mudroom
[Mudroom] 1) GPS surge protector spec. is not confirmed. 50
GPS Cable at UADU
Confidential
WiMAX Only
LTE Only
(Front view)
CDMA Only
CDMA + LTE User Space
Cabling Space
1) Cable route GPS Splitter from Mudroom 51
Confidential
Cable SPEC. from GPS Arrestor to Splitter
To be defined SPEC
Wire Color
Maker
Cable
-
-
Connector
-
-
SEC CODE : EP39-A
Cable SPEC. from Splitter to UADU
To be defined SPEC
Wire Color
Maker
Cable
-
-
Connector
-
-
SEC CODE : EP39-A
52
3.12 RRU Cable Confidential
RRU Power(Lab. Certi.)
Table. Pin map
-48V -48V V -48V
-48V -48V V -48V
RTN RTN N RTN
-48V -48V V -48V
RTN RTN N RTN
1 9GHz 1.9GHz
RTN RTN N RTN
800MHz
RTN RTN N RTN
2 5GHz 2.5GHz
-48V -48V V -48V
gam beta a ahph
(Front view)
2 5GHz 2.5GHz
-48V
Power Cable(AWG 6~10) -48V : Blue RTN : Black User Space
Cabling Space
1) Through the conduit #2, #3, #4 2) Connect Ferrule to wire and Fix the cable with switch screw.
53
Confidential
RRU Modified Power Cable (FIT&Commercial) Table. Pin map p
2.5 2.5 800 1.9 2.5 2.5 800 1.9 2.5 2.5 800 1.9 GHz GHz MHz GHz GHz GHz MHz GHz GHz GHz MHz GHz RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V RTN -48V alpha
beta
gamma
Power Cable(AWG 6~10) -48V : Blue RTN : Black
(Front view)
Move SPD position Changing Changing..
DC SPD Block DC SPD Block User Space
Cabling Space
1) Through the conduit #2, #3, #4 2) Connect Ferrule to wire and Fix the cable with switch screw 54
Optic cable
Confidential
WiMAX Only
LTE Only
(Front view)
CDMA Only
CDMA + LTE User Space
Cabling Space
1) Through the conduit #2, #3, #4 2) Connect suitable optic cable 55
Ref. Conduit finishing method Confidential [Optic cable storage box]
It can use storage box when the Optic cable is long
If Power cable is long , Cut the power cable. And Connect Ferrule to wire
2” Conduit Optic cable
Cable gland or Butyl
Power cable Hybrid cable < 1m [BBU Cabinet Right view]
Flexible pipe length can be changeable. It is why waterproof .
56
Ref. Hybrid cable type (sort by length) Confidential Table. Cable Type T Type 1
T Type 2
T Type 3
Total Length
~40m
~70m
~120m (requirement is 300feet = 91.4m)
Hybrid H b id Power P C bl Cable configuration
AWG 8 1 pair, i AWG 10 3 pair
AWG 6 1 pair, i AWG 8 3 pair
AWG 4 1 pair, i AWG 6 3 pair
Cable diameter
32mm
32mm
36mm
Bending radius
800mm
800mm
900mm
Optic cable
LC/PC-to-LC/PC Single mode
LC/PC-to-LC/PC Single mode
LC/PC-to-LC/PC Single mode
BBU cabinet (power cable terminal max size AWG 6 )
-
-
AWG 4 -> AWG 6 conversion kit need
RRU Power cable Spec
AWG 10, 4 pair
AWG 10, 4 pair
AWG 10, 4 pair
Non use Power and optic cable protection
2 pair power and optic cable With PE pipe
2 pair power and optic cable With PE pipe
2 pair power and optic cable With PE pipe
Note. SAMSUNG FIBEROPTICS. 57
[Type 1] 30m Hybrid Cable Confidential length : 2.5m
[1.9Mhz] Power cable AWG #8, 2C Optic cable LC/PC * 4ea + spare 1ea
1900MHz
AWG #8 AWG #10 5.5mm
5 core optic
To BBU Cabinet
Max : 41mm
800MHz & 2.5Ghz
AWG #10
Break out point C bl AWG #6 Cable #6, #8 converte AWG #10
800MHz & 2.5Ghz
[800Mhz & 2.5Ghz] Power cable : AWG #10 , 2C Optic cable : LC/PC * 4ea + spare 1ea
[Future Used] Water-proof C Cap
800MHz 800MH & 2.5Ghz
length : 5m [Future Used] [ Cable AWG convertor] All Power cable : AWG #10 , 2C * 4ea
[Type 2] 60m Hybrid Cable Confidential length : 2.5m
[1.9Mhz] Power cable AWG #6, 2C Optic cable LC/PC * 4ea + spare 1ea
1900MHz
AWG #6 AWG #10 5.5mm
5 core optic
To BBU Cabinet
Max : 41mm
800MHz & 2.5Ghz
AWG #8
Break out point C bl AWG #6 Cable #6, #8 converte AWG #10
800MHz & 2.5Ghz
[800Mhz & 2.5Ghz] Power cable : AWG #8 , 2C Optic cable : LC/PC * 4ea + spare 1ea
[Future Used] Water-proof C Cap
800MHz 800MH & 2.5Ghz
length : 5m [Future Used] [ Cable AWG convertor] All Power cable : AWG #10 , 2C * 4ea
[Type 3] 90m Hybrid Cable AWG #4 -> #6 ferulle * 2ea
Confidential length : 2.5m
[1.9Mhz] Power cable AWG #4, 2C Optic cable LC/PC * 4ea + spare 1ea
1900MHz
AWG #4 5.5mm
5 core optic
To BBU Cabinet
Max : 41mm
800MHz & 2.5Ghz
AWG #6
Break out point C bl AWG #4 , #6 Cable converte AWG #10
[800Mhz & 2.5Ghz] Power cable : AWG #6 , 2C Optic cable : LC/PC * 4ea + spare 1ea
800MHz & 2.5Ghz
x3
[Future Used] Water-proof C Cap
800MHz 800MH & 2.5Ghz
length : 5m [Future Used] [ Cable AWG convertor] All Power cable : AWG #10 , 2C * 4ea
Ref. Hybrid cable length Confidential
2 2sector t
1sector 5.0m
Y
Cable length is changed by the RRU location.
X2
Need the RRU height but Tower height.
2 5m 2.5m Grounding User Space
Cabling Space
3sector
X1
Cable length = X1 + X2 61
RRU cable connection (example) Unit: mm
There are 3 Type RRU .
Confidential
RU cabling window Figure differ 3RRU .
Depending RRUs Depending RRUs
D Depending di RRU RRUs
< RRU > 5~6 AWG10
20(max)
< Cable Gland > • Maker : PFLITSCH http://www.pflitsch.de/ • P/N : 22052y, 13 (M20, 13 ~ 9mm) SHOT BOOT
200(Max)
insulator
Optic core No. :5
Insulator color “-48V”→( blue ) “GND”→( red )
Bending radius =R 20
Φ12±0.5 Φ5.5±0.5
< Power Cable > Note. This picture is similar sample
< Optic Cable > 62
Ref. UADU Confidential
WiMAX Only
LTE Only
CDMA Only
CDMA + LTE
63
Confidential Power
CDMA Only
UDA BH0 BH1 UDE EDSG Power
GPS OPTIC(L0~L5) OPTIC(L0 L5)
OPTIC
LTE Only
UDA BH0 BH1 UDE0 UDE1
GPS BH2 BH1 REC EDGB
64
Confidential Power
OPTIC
WiMAX Only
UDA BH0 BH1 UDE0 UDE1 Power
GPS BH2 BH1 REC EDGB
OPTIC
CDMA + LTE
UDA BH0 BH1 UDE EDSG
GPS OPTIC(L0~L5)
65
Ref. Single Solution Cabinet Confidential
Battery Circuit Breaker PDP Rectifier WiMAX TD LTE/FDD LTE TD-LTE/FDD
12 DC Circuit Breaker
CDMA CDMA/FDD LTE AC circuit breaker
User Space
User space
Cabling Space 6 Conduits
Cabling Space
[BBU Single Cabinet] Note. This data could be revised while designing in detail.
66