OFFER FOR 1×150 KVA SUB-STATION COMPOSED OF 150KVA ONAN TYPE TRANSFORMER 250AMP LOW TENSION TENSION SWITCHGEAR 90 KVAr PFI PLANT. Project: 14/D, Borobagh , Mirpur-02,Dhaka-1216.
To Sir 14/D, Borobagh , Mirpur-02,Dhaka-1216.
NASIR ENGINEERING Plot -320,Moynarbag,North Badda, Dhaka -1212. Mobile: 01837440983,01716805046, E-mail:
[email protected]
Ref: N.E/MIR/2016/077 Date: 08/08/2016
To Sir 14/D, Borobagh , Mirpur-02,Dhaka-1216. Installation & Commissioning Commissioning of 150 KVA Substation Substation Sub. : Quotation for Supply, Installation Equipments. Dear Sir, We would like to introduce ourselves as Nasir Engineering. Our Company is high quality Substation Equipments and related accessories, that is, Distribution Transformer. Step-up Transformer, Step-Down Transformer, High Tension (HT) Switchgear, Low Tension (LT) Switchgear, Power Factor Improvement (PFI) Plant, Distribution Box (DB) etc. Manufacturer, Distributor & Suppliers.
At present, we are manufacturing & marketing: a) Sub-Station Equipments (Distribution Transformers, HT Switchgear, LT Switchgear, PFI Plant, etc.) b) Uninterruptible Power System (UPS) – Off-Line, On-Line c) Instant Power Supply (IPS) & other Electronic equipments d) Generator (Engine Origin of Deutz, Germany/ Perkins, UK) e) Solar System. We are confident about the quality of our products and believe that our products will be acceptable to you in all respects. Thanking you, Nasir Engineering
--------------------------(Md. Nurul Islam) CEO Cell: 01625491649
PRICE SCHEDULE OF 150 KVA SUB-STATION. Part-A Sl. # 01. 02. 03.
Item 150KVA Transformer 250 A L.T Switchgear 90KVAR Auto PFI Plant
Qty. 01 Set 01 Set 01 Set
Unit. Price 3,20,000.00 1,10,000.00 1,05,000.00
Total Price 3,20 ,000.00 1,10,000.00 1,05,000.00 5,35,000.00
Sub-Total = In words: Taka Five Lac & Thirty Five Thousand Only. Part –B Sl. No 01.
Qty.
Unit. Price
Total Price
11 KV Drop-out fuse Supply & fitting 11 KV Lighting Arrestor Supply & fitting Cable Stand,Angle, Channel & Nuts & Bolts Arrestor Supply & fitting
01 Set 01 Set
9,000.00 5,000.00
9,000.00 5,000.00
01 Set
6,000.00
6,000.00
04 Sets
10,000.00
40,000.00
05.
Earthing: 6 SWG Copper wire, Boring & filling complete. 11 KV Hick Shrink Kits
02 Set
3,000.00
6,000.00
06.
Transformer Caring & Installation
01 Job
5,000.00
5,000.00
07.
H.T & L.T Cable Installation Installat ion
01 Job
5,000.00
5,000.00
08.
Sub-station Installation & Wiring
01 Job
8,000.00
8,000.00
09.
Miscellaneous Miscellaneous Expenses for Electrical License( Only Ground Floor).
01 Job
40,000.00
40,000.00
Sub-Total =
1,24,000.00
02. 03. 04.
Item
Total Taka in word: Taka One Lac Thirty Two Thousand Only.
Grand Total Part (A+B) = (5,35,000.00+1,24,000.00) = 6,59,000.00 In words: Taka Six Lac Fifty Nine Thousand Thousand Only. Thanking you, Nasir Engineering
--------------------------(Md. Nurul Islam) CEO Cell: 01625491649
Terms and Conditions
Validity
:
The offer shall be remain valid for 30 days from the date of submission.
Warranty
:
24 (Twenty (Twenty Four) Months from the date of of Supply. Supply. The warranty warranty does not cover natural calamites
Delivery
:
20 ( Twenty) days after confirmed confirmed work order.
Payment
:
70% advance advance along with work order, 25% at the time of delivery & 5% after Commissioning. Commissioning.
Excluding Works
: This offer is excluding (i) Demand note deposit (ii) Metering demand note deposit (iii) H.T Line,H.T Cable, & L.T Cable (any cable & cable sockets) (iv) Load Permission (v) Road cutting ( any civil works) (vi) Solar plant (vii) VAT (viii) Fire Service & Environment NOC (ix) Others accessories.
Thanking you, Nasir Engineering
--------------------------(Md. Nurul Islam) CEO Cell: 01625491649
OPTION PRICE Part-C Sl. 01 02 03 04
Item HT Cable ( 3x50 rm)BRB. LT Cable ( 1x70 rm) PFI Cable ( 1x50 rm) Cable ( 1x10 rm BYA)
Qty. mtr. 50 mtr. 20 mtr. 100 mtr.
Unit Price 2,800.00 850.00 650.00 135.00
Sub-Total
In words: Taka
Thanking you, Nasir Engineering
--------------------------(Md. Nurul Islam) CEO Cell: 01625491649
Total Price 42,500.00 13,000.00 13,500.00
SPECIFICATION OF 150KVA, 11/0.415 KV, 3-
TRANSFORMER
Standard
:
IEC-63
Model
:
MILI/2016
Rated Capacity
:
150KVA
Rated Frequency
:
50 Hz.
Voltage ratio at no load
:
11/0.415 KV
Type
:
Core type, oil immersed, ONAN cooled.
Vector Group
:
Dyn 11
Mounting
:
Outdoor / Indoor / pad mounting.
Tap changer
:
Off load manual type.
Rated tapping
:
+1x2.5%, 0, -3x2.5% of rated KV.
Impedance
:
4.0%
No load loss
:
350 W +10%
Load loss Accessories
: :
1950 W + 10% 1) Silica gel breather. 2) Dial type type thermometer. thermometer. 3) Horn gap arrester. 4) Conservator. 5) Lifting lugs. 6) Earthing terminals. 7) Name -plate.
Dimensions & weights Length Width Height Weight
= = = =
91 cm. 83 cm. 128 cm. 830 Kg.
Country of Origin: Assembled By Silicon Steel Copper Strip Copper Wire Mineral Oil
: : : : :
Nasir Engineering Nippon, Japan/Ak steel USA BRB Bangladesh. Gazi Wires Ltd/BRB, Bangladesh. Savita, India.
SPECIFICATION OF 250A L.T SWITCHGEAR SWITCHGEAR Supply of sheet steel clad, dust and vermin proof, free standing, floor mounting type completely factory assembled 3-phase, 4-wire 415V, 50 Hz indoor type Low Tension (LT) switchgear panel having 300A hard drawn electrolytic copper busbars & comprising of followings :
Incoming : 01 -
250A, 35kA, TP MCCB with thermal overload & short circuit protection.
03 -
Current transformer having ratio 250/5A with suitable accuracy & burden.
01 -
Ammeter having scale 0-250A with selector switch.
01 -
Voltmeter having scale 0-500V with selector Switch.
03 -
Phase indicating lamps.
Outgoing: 1
-
160A, 25 KA, TP MCCB with thermal overload & short circuit protection.
Country of Origin: Assembled By
: Nasir Engineering
Circuit Breaker : ABB / Hyundi/MK,Itali,Korea.
SPECIFICATION OF 90KVAr PFI PLANT Supply of sheet steel clad, dust and vermin proof, free standing, floor mounting type completely factory assembled 3-phase, 415V, 50 Hz indoor type 60KVAr Power Factor Improvement Plant having hard drawn electrolytic copper busbars & comprising of followings : 01 -
Automatic Power Factor Correction Relay with built in digital power factor measuring meter.
01 -
25 KVAr TP, 415V, 50Hz Power capacitor bank with built in discharge resistor
01 -
20 KVAr KVAr TP, TP, 415V, 415V, 50Hz Power Power capacitor capacitor bank with built in discharge discharge resistor .
01 -
15 KVAr TP, 415V, 50Hz Power capacitor bank with built in discharge resistor
01 -
10 KVAr KVAr TP, TP, 415V, 415V, 50Hz Power Power capacitor capacitor bank with built in discharge resistor .
01 -
10 KVAr KVAr TP, TP, 415V, 415V, 50Hz Power Power capacitor capacitor bank with built in discharge discharge resistor .
01 -
5 KVAr KVAr TP, 415V, 50Hz Power capacitor bank with built in discharge resistor.
01 -
5 KVAr KVAr TP, TP, 415V, 415V, 50Hz Power Power capacitor bank with built in discharge resistor (Fixed).
06 -
TP, 220V magnetic contactor. contactor.
21 -
HRC fuses with base of adequate rating.
06 -
Indicating Lamps.
01 -
Set of control fuses.
01 -
160/5A Current Transformer Transformer
Country of Origin: Assembled By Capacitor M. Contactor PFC, Relay
: : : :
Nasir Engineering Aneer Aneer gold(EU) Hyundai(Korea) Shizuki(Japan )/ Mikro(Malaysia).
Specification of Dropout Fuse Rated Voltage (Nominal)
:
11KV
Rated Maximum Voltage
:
15 KV
Rated frequency
:
50 Hz.
BIL
:
75 KV.
Rated current RMS
:
100A
Interrupting current RMS
:
10KA
Dry, 1 Min.
:
35 KV.
Wet, 10 Sec.
:
30 KV.
Withstand test voltage
Country of Origin: Desco Approved.
Specification of Lightning Arrestor Rated Voltage (RMS)
:
9KV
Rated system voltage
:
12 KV.
Frequency
:
50 Hz.
Minimum spark over voltage (RMS)
:
14 KV.
Maximum spark over voltage (RMS)
:
40 KV.
Maximum impulse spark (crest)
:
45 KV
Dry, 1 Min.
:
28 KV
Wet, 10 Sec.
:
24 KV
Discharge 33 KV (crest)
:
5 KA
Impulse current withstand
:
55KA
Withstand Voltage
Country of Origin: Desco Approved.
Specification of Earthling & Heat Shrink Cable Kit Sub-Station Earthing The substation earthing system comprising of following items shall comply DESCO and elect. Licensing Board regulation and requirement. Earth resistance shall be maximum 1 Ohm in driest season. The work is inclusive of all materials and work required stated in item below.
Earth Electrode and Lead Supply and installation of required 4SWG HDBC copper wire each minimum 80 ft long copper electrode driven to ground. The earth lead shall be continuous up to the Earthing Block (10”x30mmx3mm) located at the substation room and having required holes for ECC connection.
Earth Continuity Conductor Supply and installation of copper cable (10 rm-BYA)/4SWG as per site R/Meter (ECC), require for the earth connection of all requirement substation equipment with the earthing block . Transformer Neutral/Transformer Earthing Installation of single core insulated stranded copper cable. As per site site R/Meter wire of required length length to earth the requirement transformer neutral with the earth electrode (arranged by customer).
Heat Shrink Cable Kit & Others Accessories Supply & Installation of 06 nos. Heat Shrinkable Kit, Cable lux/socket, Tap etc. required for installation, testing & commissioning of substation. This is item also includes for maintaining the formalities for issuing of Clearance Certificate from the Electrical Licensing Board.