FPRA & Site Star Installation Guide - PERU David Torres June, 2010
For internal use 1 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
FPRA & Site Star Installation guide PERU
For internal use 2 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / cable entry plate removal
For internal use 3 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / removing plate 1
For internal use 4 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / removing plate 2
For internal use 5 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / removing FOAM 1
For internal use 6 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / removing inner plate 1
For internal use 7 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / removing inner plate 2
For internal use 8 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / cable entry
For internal use 9 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Cable entry installation
For internal use 10 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / battery shelf kits, cable entry and support rails
Side & top rails
Battery shelf kits
Cable entry
For internal use 11 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Battery cable routing
For internal use 12 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Battery cable routing- A/C ACpower
For internal use 13 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / PDA module overview High-integrated power system Modularized design Flexible applications: load/battery configuration Variable AC power connection Control via the GUI IP54/55
For internal use 14 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
PDA description & functions AC input distribution DC output distribution Battery control function: status test, LVD System supervisor: LCD/LED display, alarm indication Network connection
For internal use 15 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Delivery contents/ preparing installation
For internal use 16 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Preparing Installation / Test Equipment_tools PC Multi-meter: FLUKE 170 or equivalent DC current clamp: FLUKE I410 or equivalent Rubber hammer Chisel Hydraulic crimping tool 13 mm torque wrench T10, 20, & 30 screwdrivers Cutting knife Protecting gloves & glasses.
For internal use 17 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Removing PDA from shelf
For internal use 18 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / General view of the PDA
For internal use 19 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / PDA front panel overview
For internal use 20 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Front panel LEDS overview
For internal use 21 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / rear cover removal
For internal use 22 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Rear internal layout PDA rear cover
OVP DIN Rail
AC terminal block E D SPD ground clamp PDA earth cable
OVP sensor connector AC ground clamp
A
C B
Rear cover Retention cable
Cable restraint F
For internal use 23 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / OVP
For internal use 24 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Configure the AC terminal block
3-Δ
Single-phase 3-Y
For internal use 25 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Prepare the AC cable
Inserting the AC cable
Stripping the wires
For internal use 26 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / One Phase AC with OVP
AC Terminal Block
OVP L1 L2
L3
PE
N
L
N
1
AC mains
For internal use 27 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
2
3
4
5
6
Installation – Single-phase AC connection with the OVP
Set up the OVP
For internal use 28 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Single-phase AC connection with the OVP
Connecting the SPD and AC terminal block For internal use 29 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – 3Y AC connection with the OVP
AC Terminal Block OVP
PE
1
L1
L2
L3
N
L1
L2
L3
N
2
AC Mains
For internal use 30 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
3
4
5
6
Installation – 3Y AC connection with the OVP
Connecting the OVP and AC terminal block For internal use 31 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – 3Y AC connection with the OVP
For internal use 32 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – 3Δ AC connection with the OVP AC Terminal Block OVP
PE
1
L1
L2
L3
L1
L2
L3
N
AC mains
For internal use 33 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
2
3
4
5
6
Installation – 3Δ AC connection with the OVP
For internal use 34 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Before routing the DC cables
For internal use 35 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Identifying the DC terminals
For internal use 36 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Configure the breakers
If connecting to separate load / battery blocks, the load / battery switch lever bar and the terminal short link have to be removed. For internal use 37 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Connecting the DC cable
Inserting the cable through front panel
For internal use 38 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Securing into the clamp
Installation – Configuration of DC cables
Typical Parallel load Parallel battery
Load & return:
35mm2
2
Battery & return:
35mm2
2
Load grounding:
25mm2
1
For internal use 39 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Finishing the DC connection
Push the front panel back and secure it For internal use 40 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Finishing the DC connection
For internal use 41 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Drawer layout
For internal use 42 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Connecting the temperature cable
Connect to J22
7 8 9
TEM_GND Red TEM SENSE_IN White TEMP_VCC Black
10
EARTH
For internal use 43 © Nokia Siemens Networks
Cable screen
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Placing the temperature probe
The temperature probe should be put where might has the highest temperature For internal use 44 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Connecting the alarm cable
Connect Alarm Out cable to J22
For internal use 45 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
3 4 5 6 7 8 9 10 11 12 13
ALARM_COM MAINS 1 ALARM_COM MAINS 2 ALARM_COM MAINS 3 ALARM_COM CRITICAL ALARM_COM MAJOR ALARM_COM
14
MINOR
Installation – Fixing the communication cable
Correctly grounding the cable shield is crucial to the electromagnetic compatibility (EMC) of the entire system.
For internal use 46 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Putting back and secure the drawer
For internal use 47 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Installing the PDA into case
For internal use 48 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Connecting the earth cable System earth cable
PDA earth cable For internal use 49 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Connecting the Ethernet cable
For internal use 50 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Installing the rectifiers into case
For internal use 51 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Connecting the rectifiers
Connecting the power cable
Connecting the RS485 cable For internal use 52 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Connecting the rectifiers
For internal use 53 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Recommended configuration of the cable through cable gland
Option 1
Option 3
Option 2
For internal use 54 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Insert the cable through cable gland
For internal use 55 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Installing the cable glands with cables
For internal use 56 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Fixing all the cables to the case
For internal use 57 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Fixing the AC cable with cable restraints
For internal use 58 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Fixing the PDA earth cable to case
Fix the PDA earth cable to the cable gland with cable tie so as not to block the LCD. For internal use 59 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Exiting the alarm cable
The alarm cable is exiting from top of the case if required For internal use 60 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Finishing the cables
For internal use 61 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Installing the front and back cover
Front cover
Back cover
The FPRA is IP55 after installing the front and back cover
For internal use 62 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – FPRA General view after the installation without conduit pipes
For internal use 63 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Fixing the two FPRA units
Stacking and fixing the two FPRA units For internal use 64 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Paralleling the two drawers - RS-422 cables
J22 #1 11 1 2 3
Parallel cable #1
4 5 6
Parallel cable #2
12
For internal use 65 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
J22 #2 12 4 5 6 1 2 3 11
Installation – Paralleling the two drawers
Parallel cable #2 Parallel cable #2
Parallel cable #1
Parallel cable #1
Drawer #1
For internal use 66 © Nokia Siemens Networks
1
Drawer #2
FPRA & Site Star Installation PERU / David Torres/ June, 2010
2
Installation – Paralleling the two drawers
For internal use 67 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / reccomended cable sizes
For internal use 68 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Installing the two FPRA units
Installing the two FPRA units separately
For internal use 69 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Installing the three drawers
J22 #1 11 1 2 3
J22 #2 12 4 5 6
Parallel cable #1
4
1 2
5 6
3 11
12
Parallel cable #2
J22 #3 For internal use 70 © Nokia Siemens Networks
11 1 2 3
Parallel cable #3
4
5
6 12
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Installing the three drawers
Parallel cable #1
Parallel cable #1
Parallel cable #2
Parallel cable #3
Parallel cable #3 Parallel cable #2
1 Drawer #1
For internal use 71 © Nokia Siemens Networks
2 Drawer #2
FPRA & Site Star Installation PERU / David Torres/ June, 2010
3 Drawer #3
Installation – Installing the three FPRA units
For internal use 72 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Interface with Site Star Cabinet
For internal use 73 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / 2” conduit PIPE (Battery Cables)
For internal use 74 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / 1” conduit Pipes (AC input & DC output to loads) Alluminium plates
For internal use 75 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Conduit fix to FPRA
For internal use 76 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Final view
For internal use 77 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Cable Routing
Parallel cable
Alarms & communications
Battery string #3, alarms & temp sensor
AC Shelf 2
DC to BTS Battery strings 1 & 2 AC Shelf 1
For internal use 78 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Cable routing
For internal use 79 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Cabinet alarm routing
For internal use 80 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation / Alarm routing
For internal use 81 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Browser and control unit setup
Configure the setup environment
For internal use 82 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Change the CU IP-address Via the LCD: change the CU IP-address into local IP range Via the GUI: Change the user PC IP-address to the CU IP range Connect to the CU via the GUI Change the CU IP to the local internet/intranet IP range Change the user PC IP-address back to the local internet/intranet IP range Connect the CU and user PC in the local internet/intranet via the GUI
For internal use 83 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – Change the CU IP-address via GUI
After changing the CU IP-address, need reconnect the CU manually For internal use 84 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Installation – GUI home page
For internal use 85 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Commissioning – DC setup
Note: the battery voltage must be over 43Vdc.
For internal use 86 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Commissioning – Check the status
Check the data via the GUI or LCD
For internal use 87 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Commissioning – Set up the parameters
Each FPRA has already been calibrated before the shipment For internal use 88 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Export/Import Conf.BIN file
For internal use 89 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Maintenance Checking the connector seal Checking the cable connectors Checking the screws Checking the rectifier fans Replacing the OVP module, when this is necessary Updating the system firmware
For internal use 90 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Alarm definition CLARO PERU MAINS 1 (Alarm 16) REC AC UVP
( POR CADA MODULO)
MAINS 2 (Alarm 15) REC GENERAL ERROR REC SENSOR FAIL REC NORM. TEMP HIGH REC NORM TEMP LOW REC EXCEP TEMP HIGH REC EXCEP TEMP LOW REC ELEMENT LOSS REC OTP REC FAN FAILURE REC AC OVP REC DC OVP
(POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO)
MAINS 3 (ALARM 14) CU/PDU BATT TEST FAIL PDA OVP
(POR CADA FPRA) (POR CADA FPRA)
CRITICAL (ALARM 13) BATT LOW VOLTAGE CU/PDUCIRCUIT BREAKER 1 CU/PDUCIRCUIT BREAKER 2 CU/PDUCIRCUIT BREAKER 3 CU/PDUCIRCUIT BREAKER 4 CU/PDUCIRCUIT BREAKER 5 CU/PDU LVD ALARM REC DC OVP
(POR CADA FPRA) (POR CADA FPRA) (POR CADA FPRA) (POR CADA FPRA) (POR CADA FPRA) (POR CADA FPRA) (POR CADA FPRA) (POR CADA MODULO)
MAJOR (ALARM 12) CU/PDU BATT TEMP. LOW CU/PDU BATT TEMP. HIGH REC POWER LIMIT
(POR CADA MODULO) (POR CADA MODULO) (POR CADA MODULO)
Alarma de puerta : Directa a la BTS (ALARM 1) voltaje flotacion por celda=2.27 @ 25°c carga 1/10 de la capacidad por 10 horas por numero de bancos Se dejan los jumpers entre los puertos de load y entre los puertos de battery.
La alarma CLU failure del gabinete Site Star se cablea en serie con la alarma 14 Alarma de Fan de Site Star en serie con alarma 12 Alarma de compresor de Site Star en serie con alarma 12
For internal use 91 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Alarm definition CLARO PERU (Cont) Alarmas asignadas al FPRA J11
N# ALARMA
RELAY 1
PIN 3 Y 4
16
RELAY 2
PIN5 Y 6
15
RELAY 3
PIN7 Y 8
14
RELAY 4
PIN 9 y 10
13
RELAY 5
PIN 11 Y 12
12
RELAY 6
PIN 13 y 14
Alarma de Sensor de Temperatura color de cable
For internal use 92 © Nokia Siemens Networks
J22
Rojo
PIN 7
Blanco
PIN 8
negro
PIN 9
tierra
PIN 10
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Best Practices While connecting the AC or DC cables into the FPRA system, make sure the power switches are at the OFF position All cables have to pass the cable glands via their indicated holes before connecting into the system While inserting the cable from the front panel, be careful not to destroy the waterproof All the screws must be tightened using proper screwdrivers with appointed torques Note the AC terminal block configuration for different AC mains types The battery/load breaker switch lever bar and the corresponding clamp short link should be removed when supporting different battery/load. After finishing the AC or DC cables connection, user is recommended to test at the cable inputs to ensure no short exists
For internal use 93 © Nokia Siemens Networks
FPRA & Site Star Installation PERU / David Torres/ June, 2010
Best Practices
While commissioning with a battery input, make sure the battery voltage is over 43Vdc before connecting to the system While removing the PDA from the case, the AC mains must be switched off, but battery could also be on to power the system Before install a OVP to the system, the AC mains must be switched off The IP rating (IP54) is no longer guaranteed while connecting the Ethernet cable
For internal use 94 © Nokia Siemens Networks