Substation Automation Products
Transformer protection RET670 Overexcitation protection
1MRG019263
Chapter 07
Contents
© ABB Group September 10, 2015 | Slide 2
Application
Operating characteristics
Logical diagram
Settings
Monitored data
Application overexcitation protection function
Chapter 07
The overexcitation is not an internal transformer fault, although it can lead to one
The peak flux density Bmax is directly proportional to induced voltage E, and inversely proportional to frequency f, turns n and area A E = 4.44 × f × n ×Bmax× A
© ABB Group September 10, 2015 | Slide 3
Overexcitation results from excessive voltage or below-normal frequency or a combination of the two, such that the volts/Hz exceed rated values
Overexcitation of a transformer can occur whenever the ratio of the pu voltage to pu frequency (V/Hz) exceeds its rating of 1.05 pu on transformer base at full load or 1.1 pu at no load
Overexcitation of power transformers Application
Overexcitation will cause
overheating
increase in magnetizing currents
increase in vibration and noise
IEC 60076-1
© ABB Group September 10, 2015 | Slide 4
Chapter 07
Continuously 10% above rated voltage at no load and rated frequency
Overexcitation protection function Application
The function is measuring the terminal voltage and current. It uses the fundamental frequency components.
Calculates the relative Volts per Hertz ratio.
Two operate characteristics (IEEE / Taylor made)
Operating range:
© ABB Group September 10, 2015 | Slide 5
Uph-ph > 70% of rated value (if below, the algorithm is not calculating the overexcitation) and
33< f <60 Hz in 50 Hz system or 42< f <75 Hz in 60 Hz system
Binary inputs to
empty heat content
block the function
Chapter 07
Overexcitation protection function Application
24
Y
Number of instances: < 2
Analog measurements must not be taken from a winding where OLTC is located
Measures input voltage
U/f>
OEX PVPH Y
SMAI
∇
Σ
SMAI
Single phase-to-phase voltage or three phase voltage (positive sequence)
Calculates the induced voltage E if the leakage reactance (and current) is known
otherwise the terminal voltage is used
SMAI
24
U/f>
Y Y
OEX PVPH
∇
SMAI Y Y
© ABB Group September 10, 2015 | Slide 6
Chapter 07
∇
SMAI
24
U/f>
OEX PVPH
The current measurement should have the same component selection as voltage (positive sequence or delta current)
Overexcitation protection function Operating characteristics
Chapter 07
Delay tMax
The relative excitation M (relative V/Hz) is expressed as:
If M < V/Hz> then the transformer is not overexcited (< 1.0)
harmful
under excitation
overexcitation
tMin 0 M=V/Hz> V/Hz>
V/Hz>: the maximum continuously allowed no-load voltage at rated frequency, set as a % of UBase/fr (default: 110 %)
Mmax - V/Hz> Overexcitation M-V/Hz> V/Hz>> Emax
Excitation M E (only if f = fr = const)
© ABB Group September 10, 2015 | Slide 7
The relative overexcitation is thus defined
Overexcitation protection function Operating characteristics – IEEE curve
Delay
Chapter 07
Operate characteristic
tMax: Maximum cut-off operate time at low degree of overexcitation
tMax
inverse delay under excitation
overexcitation
tMin 0 M=V/Hz> V/Hz>
Mmax - V/Hz> Overexcitation M-V/Hz> V/Hz>> Emax
Excitation M
tMin: Minimum cut-off operate time at high degree of overexcitation
E (only if f = fr = const)
© ABB Group September 10, 2015 | Slide 8
Beyond M = V/Hz>> the operate time will always be tMin
Overexcitation protection function Operating characteristics – Tailor made curve
Delay
The interval between M = V/Hz> and M = V/Hz>> is automatically divided into 5 equal subintervals
6 operating time points has to be defined
Straight line between the points to calculate operating time
tMax: Maximum cut-off operate time
tMin: Minimum cut-off operate time
tMax
underexcitation
overexcitation
tMin
Overexcitation M-Emaxcont 0
V/Hz>
© ABB Group September 10, 2015 | Slide 9
Mmax - Emaxcont Excitation M V/Hz>>
Chapter 07
Beyond M = V/Hz>> the operate time will always be tMin
Chapter 07
Cooling and alarm Operating characteristics Delay tMax
Overexcitation causes overheating
An exponential cooling feature is implemented
harmful
under excitation
overexcitation
tMin 0 M=V/Hz> V/Hz>
tCooling: Time constant (default setting 1200 seconds (20 minutes))
Alarm
Mmax - V/Hz> Overexcitation M-V/Hz> V/Hz>> Emax
Excitation M E (only if f = fr = const)
© ABB Group September 10, 2015 | Slide 10
i.e. shorter operating time if the transformer has been exposed for overexcitation before and not yet reached normal temperature
Per cent of operate level (heat content, THERMSTA)
Time delay
Reset input to clear heat content
Chapter 07
Overexcitation protection function Simplified logical diagram BLOCK AlarmLevel
t
RESET
Heat content
t V/Hz>
Calculation of internal induced voltage Ei
I3P
Xleak
Ei
M
© ABB Group September 10, 2015 | Slide 11
t>tMin
&
TRIP
M
IEEE
M Tailor-made M>V/Hz>>
V/Hz>>
ALARM
tMin k
M= (Ei / f) (Ur / fr)
&
tAlarm
M>V/Hz>
tCooling
U3P
t>tAlarm
t tMax
≥1
&
START
Chapter 07
Overexcitation protection function settings Overview
First instance of OEX PVPH
Advanced settings
© ABB Group September 10, 2015 | Slide 12
Overexcitation protection function settings General
Chapter 07
Voltage and current selection: ph-ph or positive sequence NB: MeasusedU and MesururedI must be set to the same value (ILxILy is calculated internally)
Operation On/Off Base values Leakage reactance of adjacent winding Trip pulse length Alarm in % of operate level (9000 s ~ 2,5 h)
© ABB Group September 10, 2015 | Slide 13
Overexcitation protection function settings Characteristic
Chapter 07
Base values Operate level: - No load and rated frequency - High level where tMin is used Trip delay: - Minimum - Maximum Core cooling time constant Characteristic IEEE/Tailor made IEEE curve
Tailor made curve
© ABB Group September 10, 2015 | Slide 14
Chapter 07
Monitored data
© ABB Group September 10, 2015 | Slide 15
Test/Functions status/Voltage protection/overexcitation (PVPH,24)
Trip
Start
Alarm
TMTOTRIP – Calculated time to trip (s)
VPERHZ – V/Hz (pu)
THERMSTA – Thermal status in % of trip level
Chapter 07
Monitored data Time
THERMSTA <100%
tMax TMTOTRIP=tMax s THERMSTA >100% (if no trip)
THERMSTA=100% and TMTOTRIP=0
THERMSTA <100% TMTOTRIP
tMin Under excitation © ABB Group September 10, 2015 | Slide 16
V/Hz> VPERHZ=1.100
Over excitation
V/Hz>>
Chapter 07
© ABB SA-TGroup Training September 10, 2015 | Slide 17
© SA-T Training