Conditions of Use Vaillant issue these diagrams on condition that the user; 1. 2. 3. 4. 5.
Ensures Ensures the installati installation on conform conforms s with the applian appliance ce installa installation tion instructio instructions ns Ensures that any external control connected to a Vaillant boiler or VANTAGE ANTAGE unvented hot water cylinder is compatible. Accepts Accepts all liability liability for verificat verification ion of the circuitry circuitry as being being corr correct ect and suitable suitable for the use intended intended.. Accepts all liability for verification of the system design being correct and suitable for the use intended. intended. Accepts the condition condition that any any wiring, wiring, pipe pipe run, sizing, or layout ect, where where shown are illustrations and not to be used other than as a guide.
Any electrical work should be in accordance with BRITISH STANDARDS and IEE Regulations. Legends to the drawings for both electrical and pipe work diagrams give basic requirements, recommendations and symbols used. Used within these diagrams and tables are trademarks and registered propriety names, Vaillant acknowledges their owners rights and thanks them for help in providing this information.
DATE 09/04/2001 DRAWING N0. CD0/0/0/0/14
TITLE:- PRELIMINARY ELECTRICALCHECKS
Before carrying out preliminary electrical checks , ENSURE there is NO VOLTAGE at the appliance using an electrical test meter .
EARTH CONTINUITY CHECK Appliance must be electrically disconnected , meter set on Ω ( ohms ) scale . Test leads from all appliance earthed metals to earth pin or plug . Resistance should be less than 1 Ω ( ohm ) . If the resistance is greater than 1 Ω ( ohm ) then check all earth wires for continuity and all contacts clean and tight . If resistance of earth is still greater than 1 Ω ( ohm ) then this should be rectified r ectified by a electrician .
SHORT CIRCUIT CHECK Appliance electrically disconnected . All switches ON ( including stats ) . Meter set on Ω (ohms ) scale . Test leads from L and N in appliance terminal strip / block , if i f meter reads “ 0 “ then there is a short circuit .
RESISTANCE TO EARTH CHECK
DATE 09/04/2001 DRAWING No. CD0/0/0/0/12
TITLE:- EARTH CONTINUITY CHECK TEST 3 PIN PLUG
THREE PIN PLUG OR SPUR CONNECTION UNIT
ELECTRIC TEST METER
VAILLANT BOILER TERMINAL STRIP
R less than 1 ohm
TEST PROBE ON BOILER CHASSIS
E
E
1/N 2/L 3
4
5
3 amp FUSE N
L VΩ + COM
EARTH CONTINUITY :If the resistance between the earth pin of the plug and the appliance case is greater than 1 ohm (Ω ) check all the earth wires for continuity and that all the contacts are clean and tight. If the resistance to earth is still greater than 1 ohm ( Ω ) then the fault must be rectified before proceeding . WARNING, Poor, or no earth continuity will cause a danger if there is a short circuit on the appliance, as supposedly earthed metal would become LIVE giving rise of an electrical shock when touched.
DATE 09/04/2001 DRAWING No. CD0/0/0/0/13
TITLE:- SHORT CIRCUIT CHECK
THREE PIN PLUG OR SPUR CONNECTION UNIT
ELECTRIC TEST METER
VAILLANT BOILER TERMINAL STRIP
R less ? 0
E
E
1/N 2/L 3
4
5
3 amp FUSE N
L VΩ + COM
SHORT CIRCUIT TEST :-
The resistance between L and N indicates the internal resistance of the appliance. Where this is zero ohms, there is a short circuit fault which must be rectified. If a fuse repeatedly fails, but no fault is indicated in this test, a detailed continuity check ( i.e. by disconnecting and checking each component ) is required to trace the faulty component. It is possible that fault could occur as a result of local burning / arcing, but no fault is found under test. However, a detailed visual inspection should reveal evidence of burning around the fault.
DATE 10/04/2001 DRAWING No. CD0/0/0/0/15
TITLE:- RESISTANCE TO EARTH CHECK
THREE PIN PLUG OR SPUR CONNECTION UNIT
ELECTRIC TEST METER
VAILLANT BOILER TERMINAL STRIP
R=8
E
E
1/N 2/L 3
4
5
3 amp FUSE N
L VΩ + COM
RESISTANCE TO EARTH CHECK :All switches, including any thermostats, should be switched on. If the resistance between L and E is other than infinity ( ∞ ), there is a fault which should be isolated. A detailed continuity check is required to trace the faulty component.
DATE 10/04/2001 DRAWING No. CD0/0/0/0/16
TITLE:- MAINS VOLTAGE AND POLARITY CHECK: PART 1
THREE PIN PLUG OR SPUR CONNECTION UNIT
ELECTRIC TEST METER
VAILLANT BOILER TERMINAL STRIP
240 Vac
E
E
1/N 2/L 3
4
5
3 amp FUSE N
L VΩ + COM
MAINS VOLTAGE AND POLARITY CHECK ( TESTS PARTS 1. 2. 3 ) :If a low Vac reading is given between terminals L and N or Land E, there is an electrical fault. Repeat the test at the appliance plug / inlet spur to check the wiring system up to the appliance and rectify any fault. If necessary, repeat the test at the supply system socket outlet / spur. If the fault also occurs at this stage, then there is a house system fault. This should be rectified by a competent electrician, such as a NICEIC registered contractor. The appliance should be left disconnected and the customer warned not to use the appliance until this work has been carried out.
DATE 10/04/2001 DRAWING No. CD0/0/0/0/17
TITLE:- MAINS VOLTAGE AND POLARITY CHECK PART: 2
THREE PIN PLUG OR SPUR CONNECTION UNIT
ELECTRIC TEST METER
VAILLANT BOILER TERMINAL STRIP
240 Vac
E
E
1/N 2/L 3
4
5
3 amp FUSE N
L VΩ + COM
MAIN VOLTAGE AND POLARITY CHECK CONTINUED :- Part two Most appliances will appear to operate normally with the live and neutral connections transposed. The exceptions are some models with spark generators or microprocessor controls. However, if there is a short to earth, the fuse would not blow and the resulting current flow could cause a fire. In addition, most switches are normally connected in the live circuit and transposition of the live and neutral would mean the appliance was still ‘on’ when apparently switched ‘off’. Transposing live and earth connections should cause the fuse to blow. It would also cause the appliance to become live if there was a fault in the earth circuit. Transposing neutral and earth would not prevent the appliance from working, but is contrary to the electricity supply regulations and must be avoided. On some installations it would cause the earth trip to fail.
DATE 10/04/2001 DRAWING No. CD0/0/0/0/18
TITLE:- MAINS VOLTAGE AND POLARITY CHECK PART: 3
THREE PIN PLUG OR SPUR CONNECTION UNIT
ELECTRIC TEST METER 0 to 15 Vac
E
E
3 amp FUSE N
VAILLANT BOILER TERMINAL STRIP
L VΩ + COM
MAIN VOLTAGE AND POLARITY CHECK CONTINUED :- Part three - conclusion
1/N 2/L 3
4
5
DATE 06/04/2001
TITLE:- LEGEND TO DRAWINGS … ELECTRICAL ALL WIRING TO COMPLY WITH BRITISH STANDARDS AND I E E REGULATIONS
DRAWING No. CD0/0/0/0/4
MAIN ELECTRICAL SUPPLY : 3 AMP FUSED - 240V, VIA FUSED 3 PIN, UNSWITCHED, SHUTTERED SOCKET TO BS 1363. ALTERNATIVELY, VIA FUSED, DOUBLE - POLE ISOLATOR WITH AT LEAST 3 mm SEPARATION IN ALL POLES APPLIANCE MUST BE EARTHED. WIRING CENTRE / JUNCTION BOX : DO NOT USE A PRE-WIRED PRINTED CIRCUIT BOARD TYPE . ALL CONTROLS & COMPONENTS ARE SHOWN AS WIRED TO THESE TERMINALS UNLESS OTHERWISE STATED. TERMINAL INDICATORS IDENTIFICATION : E : EARTH ,
. N : NEUTRAL ,
. L : LINE ,
.
EARTH TERMINAL DESIGNATION :
OR
WIRING COLOURS : BL : BLUE . BK : BLACK . BR : BROWN . GR : GREY . OR : ORANGE . WH : WHITE . RED : RED . YL : YELLOW . G/Y : GREEN / YELLOW . GN : GREEN . W-B : WHITE OR BROWN . V : VIOLET . TL: TRANSLUCENT . TP : TRANSPARENT . LIVE TO SYSTEM =
, SW LIVE TO STAT CH = HW =
LINE DRAWING : CONNECTING =
, CROSSING =
, DEMAND TO BOILER = , JOINING =
, NEUTRAL FROM SYSTEM = , SWITCH =
l
.
l
DESIGNATION : C OR COM : COMMON . D OR DEM : DEMAND . SAT : SATISFIED . SW : SWITCHED . NO : NORMALLY OPEN . NC : NORMALLY CLOSED . N/U : NOT USED . SP : SPARE . DHW : DOMESTIC HOT WATER . S/C OR SEC /C : SECONDARY CIRCUIT . DP DT : DOUBLE POLE DOUBLE THROW SP ST : SINGLE POLE SINGLE THROW . PROGRAMMER : CONNECTION DETAILS MUST BE IN ACCORDANCE WITH PROGRAMMER INSTALLATION INSTRUCTIONS , READ IN CONJUNCTION WITH BOILER INSTALLATION INSTRUCTIONS . NOTE LINKS MAY OR MAY NOT BE NEEDED . HW : HOT WATER . CH : CENTRAL HEATING . S/CH : SINGLE CHANNEL . 2/CH : TWO CHANNEL . VFC : VOLT FREE CONTACT OR CONTACTS . NOTE :- INSTALLERS MUST ENSURE THAT ANY EXTERNAL CONTROLS CONNECTED TO VAILLANT BOILERS ARE COMPATIBLE . WIRING DIAGRAMS ISSUED BY VAILLANT ARE A GUIDE ONLY, AND ISSUED STRICTLY ON CONDITION THAT THE INSTALLER ACCEPTS ALL LIABILITY FOR VERIFICATION OF THE CIRCUITRY AS BEING CORRECT AND SUITABLE FOR THE USE INTENDED .
DATE 22/03/2001
TITLE:- LEGEND TO DRAWINGS … PIPEWORK SCHEMATICS ALL PIPEWORK TO COMPLY WITH BRITISH STANDARDS AND THE RELEVE NT WATER REGULATIONS
DRAWING No. CD0/0/0/0/5
NOTE :- ALL DRAWINGS ARE DIAGRAMMATIC LAYOUTS ONLY , ISSUED AS A GUIDE . THEY ARE ISSUED STRICTLY ON CONDITION THAT THE INSTALLER ACCEPTS ALL LIABILITY FOR THE SYSTEM DESIGN BEING CORRECT AND SUITABLE FOR THE USE INTENDED . THE INSTALLER TO ENSURE THAT THE INSTALLATION CONFORMS TO THE APPLIANCE INSTALLATION REQUIREMENTS . PIPE RUNS AND SIZING ECT WHERE SHOWN ARE ILLUSTRATIONS AND NOT TO BE USED OTHER THAN AS A GUIDE. WHERE THE CIRCUIT RESISTANCE EXCEEDS 25kPa ( 2.5 metres ), A CORRECTLY SIZED ADDITIONAL PUMP WILL BE REQUIRED. ON MODULAR INSTALLATIONS ENSURE : SUFFICIENT EXPANSION CAPACITY IS PROVIDED . ADDITION SYSTEM PUMPS TO BE ON THE COMMON FLOW . A REVERSE RETURN PIPEWORK ARRANGEMENT USED WITH NON-RETURN VALVES ON FLOW PIPES FROM BOILERS . WITH VANTAGE UNVENTED HOT WATER CYLINDERS , THE SUPPLIED 3 PORT MID POSITION VALVE MAY BE REPLACED WITH A 2 PORT SPRING RETURN VALVE . SYMBOLS & CUSTOMS USED = PRIMARY FLOW .
= PRIMARY RETURN .
= SHUT OFF VALVE : SUFFIX LS = LOCK SHIELD , BV = BALANCING VALVE , DC = DRAIN COCK , = PRESSURE RELIEF VALVE
= 2 PORT SPRING RETURN VALVE , = NON - RETURN VALVE = PUMP = FILLING LOOP
= 3 PORT MID POSITION VALVE
= ADDITIONAL EXPANSION VESSEL
DATE 21/03/2001
TITLE:- VAILLANT BOILER TERMINAL DESIGNATION
DRAWING No. CD0/0/0/0/1 T3W BOILER RANGE
6 t
N/U VC, VCW RANGE THERMOcompact COMBIcompact ECOmax 200 SERIES
5
4
3
t
t
t
SW/N SW/L L/OUT
2R
1Mp
t
t
L
N
ECOmax - as part of terminal strip N
L
14243
not used UK
not ECOmax
1N
2L
t
t
N
L
3
4
5
7
t
t
t
9
8
7
5 t
144424443
not used in UK
ECOmax 800 SERIES 600 SERIES
TURBOmax Pro TURBOmax Plus THERMOcompact 600 SERIES ecoMAX 800/2 SERIES 600/2 SERIES
N
7
L
SW/N
3
4
t
t
11
12
144424443
20 VDC 200 V not used in UK
4
3
L
t
t
t
t
L
N
8
9
SW/L L/OUT
5
t
N
L
L/OUT SW/L SW/N
8
9
L
24V not used in UK
10
X3
t
144424443
9
144424443
L/OUT SW/L SW/N
X1 VU, VUW RANGE THERMOcompact TURBOmax
8
t
7
t
L
N
0 Vac
1444442444443
24V~ not used in UK
N
t
N
3 t
t
4 t
5 t
L/OUT SW/L SW/N
NOTE :- ALL BOILERS SUPPLIED WITH LINK BETWEEN TERMINALS 3 & 4. EXTERNAL CONTROLS SWITCH BETWEEN THESE TERMINALS.
DATE 29/03/2001 DRAWING N0. CD0/0/0/0/9
TITLE:- VAILLANT COMBINATION BOILER TERMINAL CONNECTIONS FOR SINGLE CHANNEL TIME SWITCHES
ACL DRAYTON Tempus 1, Tempus 2 Lifestyle LP111, LP711
s
ACL DRAYTON SWITCHMASTER SM300
N L 4
3
s s
s
s
N L 1 2 3
4
ACL DRAYTON SWITCHMASTER 980
N L 3 s
4
3
s
s
s
s
1 2 A B C 3 4 4
3 E N L
s
s
1 2
s
s
s
3 E
5
6
E N L
4 3
s
s
s
s
E N L 1
GRÄSSLIN TOWERCHRON QE1, QM1
3 4
N L
DANFOSS RANDALL 103 SERIES
DANFOSS RANDALL TS715
s
N L 1 2
N L
DANFOSS RANDALL SET 1E, TS975
4
s
N s
2 3 4
s
5 6
L 3 s
4
s
s
N L 1
2 3 4
N
L
s
s
3 4 s
s
DATE 29 . 03 . 2001 DRAWING N0. CD0/0/0/0/8
TITLE:- VAILLANT COMBINATION BOILER TERMINAL CONNECTIONS FOR PROGRAMMABLE ROOM THERMOSTATS
ACL DRAYTON Lifestyle PT271, PT371
N L s
s
3
4
s
s
N L 1 2
ACL DRAYTON Digistat 2, 3, 4,
3
4
s
s
1 ACL DRAYTON Digistat RF - SCR Receiver
s
DANFOSS RANDALL TP4, TP5, TP5E
4
s
s
2
4
3 s
2 1
N
L
3
4
s
s
s
s
N L 1 DANFOSS RANDALL TP75 A B C 1
2
3
s
3
GRÄSSLIN TOWERCHRON RTC 7
2 3
N L 3 s
N L 1
DANFOSS RANDALL TP5E RF with receiver RX1
3 4
2 3
4
3
4
s
s
3
4 5 6 3
4
s
s
DATE 21 . 03 . 2001 DRAWING N0. CD0/0/0/0/3
TITLE:- 2 CHANNEL PROGRAMMERS FOR USE WITH VAILLANT BOILERS USING 3 PORT MID-POSITION VALVES single boiler application connection details
DRAYTON LP241, LP522, LP722
N
L
HW OFF 1
Note: X indicates terminal not used
t
t
t
t
t
t
5
3
8
X
7
6
CH OFF 2
HW ON 3
CH ON 4
TEMPUS 6, TEMPUS 7
Note: X indicates terminal not used
E
N
t
t
t
t
E
5
3
8
DANFOSS RANDALL CP715, FP715 Note: X indicates terminals not used
HW OFF L 1
HW OFF L 1
CH OFF 2
t X
CH OFF 2
HW ON 3
CH ON 4
t
t
7
6
HW ON 3
CH ON 4
E
N
t
t
t
t
t
t
t
X
5
3
8
X
7
6
CH OFF 2
HW ON 3
CH ON 4
GRÄSSLIN TOWERCHRON QE2, QM2
N
L
HW OFF 1
Note: X indicates terminal not used
t
t
t
t
t
t
5
3
8
X
7
6
HW
HW
COM
HONEYWELL
CH
CH
COM
DATE 30 . 04 . 2001 DRAWING No. CD0/0/0/0/2
TITLE:- 2 CHANNEL PROGRAMMERS FOR USE WITH VAILLANT BOILERS USING 2 PORT SPRING RETURN ZONE VALVES single boiler application – use as guide only for multi boiler applications
DRAYTON LP241, LP522, LP722
N
L
HW OFF 1
Note: X indicates terminals not used
t
t
t
t
t
t
5
3
X
X
7
6
CH OFF 2
HW ON 3
CH ON 4
TEMPUS 6, TEMPUS 7
Note: X indicates terminals not used
HW OFF L 1
Note: X indicates terminals not used
CH ON 4
N
t
t
t
t
t
t
t
E
5
3
X
X
7
6
CH OFF 2
HW ON 3
CH ON 4
L
HW OFF 1
E
N
t
t
t
t
t
t
t
X
5
3
X
X
7
6
L
HW OFF 1
CH OFF 2
HW ON 3
CH ON 4
GRÄSSLIN TOWERCHRON QE2, QM2
N
Note: X indicates terminals not used
HONEYWELL
HW ON 3
E
DANFOSS RANDALL CP715, FP715
CH OFF 2
CH ON
t
t
t
t
t
t
5
3
X
X
7
6
CH OFF
COM
HW ON
HW COM OFF
DATE 02 . 04 . 2001 DRAWING N0. CD0/0/0/0/11
TITLE:- VAILLANT BOILER TERMINAL CONNECTIONS FOR PROGRAMMABLE ROOM THERMOSTATS ON HEATING SYSTEMS SINGLE BOILER APPLICATIONS = QQQ
ACL DRAYTON Lifestyle PT271, PT371
N L C s
s
SW/L
s
s
N L 1 2
ACL DRAYTON Digistat 2, 3, 4,
3 4
C
SW/L
s
s
1 ACL DRAYTON Digistat RF - SCR Receiver
2 3
N L C s
s
SW/L
s
s
N L 1 DANFOSS RANDALL TP4, TP5, TP5E
DANFOSS RANDALL TP5E RF with receiver RX1
N
L
s
s
C
s
s
3
2 1
C SW/L s
C
GRÄSSLIN TOWERCHRON RTC 7
2 3
s
2 3
4
SW/L
s
A B C 1
3
SW/L
N L 1 DANFOSS RANDALL TP75
2
s
4 5 6 C
SW/L
s
s
DATE 30/04/2001 DRAWING No. CD0/0/0/0/6
TITLE:- TERMINAL DESIGNATIONS FOR ROOM THERMOSTATS WITH VAILLANT BOILERS USING EITHER ZONE VALVES OR 3 PORT MID-POSITION VALVE SINGLE BOILER APPLICATION = QQ NOTE:- USE ONLY AS GUIDE FOR THERMOSTAT TERMINALS ON MULTI BOILER APPLICATIONS
ROOM THERMOSTAT TERMINAL DESIGNATION COMMON LINE IN
SWITCHED LINE OUT 6
NEUTRAL FOR ANTICIPATOR 9
5
VAILLANT VRT 30
3/L 4/* 5/N
DRAYTON DIGISTAT 1
1
DRAYTON RTS1, RTS2
L 3 N
HONEYWELL T6360
1
3 2
SIEMES – LANDIS & STAEFA RAD1
1
2
DANFOSS RMT 230
1
2 4
DANFOSS RET 230
L 3 N
GRÄSSLIN TOWERCHRON RS
1
3 4
SUNVIC TLX2000 series
3
1
POTTERTON PRT2
TL H N
HORSTMANN HRT2
1
E
3
3
E
4 E
4
EARTH
DATE 30/04/2001
TITLE:- TERMINAL DESIGNATIONS FOR CYLINDER THERMOSTATS WITH VAILLANT BOILERS USING EITHER 3 PORT MID-POSITION VALVE OR ZONE VALVES = Q NOTE:- USE ONLY AS A GUIDE FOR CYLINDER STAT TERMINALS ON MULTI BOILER APPLICATIONS
DRAWING No. CD0/0/0/0/7
CYLINDER THERMOSTAT TERMINAL DESIGNATION 3 PORT MID-POSITION VALVE SYSTEM 2 x 2 PORT ZONE VALVE SYSTEM 1 - COMMON LINE IN
2 - SWITCHED BRAKE ON RISE
3 - SWITCHED MAKE ON RISE
1 - COMMON LINE IN
2 - SWITCHED BRAKE ON RISE
3 - SWITCHED MAKE ON RISE
7
4
DRAYTON HTS3
C
1 2
C 1
2
DANFOSS ATC
1
2 3 E
1 2
3 E
GRÄSSLIN TOWER CS1
8 E
EARTH
RED BK YL
7 10 N/U E
RED BK YL
HONEYWELL L641
C
1 2
C
1 2
HORSTMANN HTC1
1
2 3
1
2 3
SIEMENS – LANDIS & STAEFA RAM1 1
2
1
2
SUNVIC SA 2452
1 2
3
1 2
3
3 E
3 E
EARTH
DATE 02/04/2001
TITLE:- SCHEMATIC OF WIRING A VAILLANT BOILER TO A TIMER AND ROOM THERMOSTAT
DRAWING No. CD0/0/0/0/10 FOR BOILER TERMINAL LAYOUT SEE SPECIFIC BOILER INSTALLATION INSTRUCTIONS
20 VDC N
L
3
4
6447448
5
7
8
9
DO NOT USE IN UK MAINS SUPPLY 230 V 50 Hz ~
N L 3 amp FUSE
SWITCH CONTACTS
ROOM THERMOSTAT
t l
t
s
l
N CLOCK
s