TP48200T-D20A1 & D20A2 & D14A1 & D14A2 V300R001
User Manual
Issue
01
Date
2012-06-01
HUAWEI TECHNOLOGIES CO., LTD.
Copyright © Huawei Technologies Co., Ltd. 2012. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders.
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd. Address:
Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China
Website:
http://www.huawei.com
Email:
[email protected]
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
i
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
About This Document
About This Document Purpose This document describes the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 in terms of its features, structure, components, installation, commissioning, and maintenance.
Intended Audience This document is intended for:
Sales engineers
Technical support personnel
Maintenance personnel
Symbol Conventions The symbols that may be found in this document are defined as follows. Symbol
Description Alerts you to a high risk hazard that could, if not avoided, result in serious injury or death. Alerts you to a medium or low risk hazard that could, if not avoided, result in moderate or minor injury. Alerts you to a potentially hazardous situation that could, if not avoided, result in equipment damage, data loss, performance deterioration, or unanticipated results. Provides a tip that may help you solve a problem or save time. Provides additional information to emphasize or supplement important points in the main text.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
ii
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
About This Document
Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues.
Issue 01 (2012-06-01) This issue is the first official release.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
iii
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Contents
Contents About This Document .................................................................................................................... ii 1 Overview......................................................................................................................................... 1 1.1 Designation Explanation .................................................................................................................................. 1 1.2 Typical Networking .......................................................................................................................................... 1 1.3 Configuration ................................................................................................................................................... 2 1.4 Features ............................................................................................................................................................ 8
2 Component Description............................................................................................................... 9 2.1 Cabinet ............................................................................................................................................................. 9 2.2 Temperature Control Unit .............................................................................................................................. 11 2.2.1 Direct-Cooling Unit .............................................................................................................................. 11 2.2.2 TEC ....................................................................................................................................................... 15 2.3 Rectifier .......................................................................................................................................................... 21 2.3.1 Appearance ............................................................................................................................................ 21 2.3.2 Panel...................................................................................................................................................... 22 2.4 Monitoring Unit ............................................................................................................................................. 23 2.4.1 Appearance ............................................................................................................................................ 23 2.4.2 Main Control Module............................................................................................................................ 24 2.4.3 Basic I/O module .................................................................................................................................. 26 2.4.4 GPRS Module ....................................................................................................................................... 29 2.4.5 GPRS antenna ....................................................................................................................................... 32 2.5 PDU................................................................................................................................................................ 32 2.5.1 AC PDU ................................................................................................................................................ 33 2.5.2 DC PDU ................................................................................................................................................ 33 2.6 Intelligent Power Meter .................................................................................................................................. 35 2.6.1 Appearance ............................................................................................................................................ 35 2.6.2 Pins........................................................................................................................................................ 36 2.6.3 Specification ......................................................................................................................................... 37 2.7 Bluetooth electric door lock ........................................................................................................................... 37 2.7.1 Appearance ............................................................................................................................................ 38 2.7.2 Pins........................................................................................................................................................ 38 2.8 Bluetooth controller ....................................................................................................................................... 39 2.8.1 Appearance ............................................................................................................................................ 39
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
iv
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Contents
2.8.2 Pins........................................................................................................................................................ 39 2.8.3 Specification ......................................................................................................................................... 40 2.9 Storage Battery ............................................................................................................................................... 40
3 Safety Precautions ....................................................................................................................... 41 3.1 Overview ........................................................................................................................................................ 41 3.2 Local Safety Regulations ............................................................................................................................... 41 3.3 Grounding Requirements ............................................................................................................................... 41 3.4 Human Safety ................................................................................................................................................. 42 3.5 Equipment Safety ........................................................................................................................................... 42 3.6 Electrical Safety ............................................................................................................................................. 42
4 Installation and Commissioning.............................................................................................. 45 5 Maintenance ................................................................................................................................. 46 5.1 Routine Maintenance...................................................................................................................................... 46 5.2 Troubleshooting.............................................................................................................................................. 49 5.3 Component Replacment ................................................................................................................................. 56
6 Monitoring Function .................................................................................................................. 74 6.1 LCD User Interface ........................................................................................................................................ 74 6.2 Web User Interface ......................................................................................................................................... 78
A Technical Specifications ........................................................................................................... 90 B LCD Menu ................................................................................................................................... 94 C Acronyms and Abbreviations ................................................................................................ 102
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
v
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
1 Overview
1
Overview
1.1 Designation Explanation The TP48200T-D20A1 & D20A2 is an integrated outdoor backup alternating current-to-direct current (AC-to-DC) power system that employs -48 V, 50 A rectifiers and outputs a maximum of 200A current. The TP48200T-D14A1 & D14A2 is an integrated outdoor backup alternating current-to-direct current (AC-to-DC) power system that employs -48 V, 50 A rectifiers and outputs a maximum of 100A current.
1.2 Typical Networking The TP48200T-D20A1 & D20A2 & D14A1 & D14A2, AC power supply, automatic transfer switch (ATS), alternating current distribution box (ACDB), storage batteries, and related devices constitute a site power solution. Figure 1-1 shows the positioning of the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 in the typical site power solution. Figure 1-1 TP48200T-D20A1 & D20A2 & D14A1 & D14A2 in the typical site power solution
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
1
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
1 Overview
1.3 Configuration The TP48200T-D20A1 & D20A2 & D14A1 & D14A2 is a cabinet that houses the fans, rectifiers, monitoring unit, sensors, power distribution unit (PDU), intelligent power meter and Bluetooth electric door lock. Table 1-1 Configuration Item
Composition
AC input mode
TP48200T-D20A1
Cabinet (13U space for customer equipments and two-layer rack for storage batteries)
220V three-phase five-line (L1, L2, L3, N, PE)
R4850G1 (2 to 4 PCS)
ECC500
PDU
110V three-phase five-line (L1, L2, L3, N, PE)
Intelligent power meter
Bluetooth electric door lock
Battery temperature sensor
220V single-phase three-line (L, N, PE)
Temperature sensor in direct-cooling unit
Temperature and humidity sensor
Door status sensor
Water sensor (optional)
Smoke sensor (optional)
Cabinet (13U space for customer equipments and two-layer rack for storage batteries)
110V dual-live-wire (L1, L2, N, PE)
R4850G1 (2 to 4 PCS)
ECC500
PDU
110V dual-live-wire (L1, L2, PE)
Intelligent power meter
Bluetooth electric door lock
Battery temperature sensor
220V single-phase three-line (L, N, PE)
Temperature sensor in direct-cooling unit
Temperature and humidity sensor
Door status sensor
Water sensor (optional)
Smoke sensor (optional)
Cabinet (5U space for customer equipments and one-layer rack for storage batteries)
220V three-phase five-line (L1, L2, L3, N, PE)
R4850G1 (2 PCS)
ECC500
110V three-phase five-line (L1, L2,
TP48200T-D20A2
TP48200T-D14A1
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
2
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Item
1 Overview
Composition
TP48200T-D14A2
Issue 01 (2012-06-01)
AC input mode
PDU
Intelligent power meter
Bluetooth electric door lock
Battery temperature sensor
Temperature sensor in direct-cooling unit
Temperature and humidity sensor
Door status sensor
Water sensor (optional)
Smoke sensor (optional)
L3, N, PE)
220V single-phase three-line (L, N, PE)
Cabinet (5U space for customer equipments and one-layer rack for storage batteries)
110V dual-live-wire (L1, L2, N, PE)
R4850G1 (2 PCS)
ECC500
PDU
110V dual-live-wire (L1, L2, PE)
Bluetooth electric door lock
Battery temperature sensor
Temperature sensor in direct-cooling unit
220V single-phase three-line (L, N, PE)
Temperature and humidity sensor
Door status sensor
Water sensor (optional)
Smoke sensor (optional)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
3
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
1 Overview
Figure 1-2 TP48200T-D20A1 interior
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Monitoring unit (ECC500) (16) Bluetooth Electric door lock
Issue 01 (2012-06-01)
(2) Door status sensor (5) Space for rectifiers (8) TEC
(11) Fan assembly (14) Temperature and humidity sensor (17) Space for Bluetooth controller
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(12) CMUA for fan assembly (15) Air filter
4
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
1 Overview
Figure 1-3 TP48200T- D20A2 interior
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Monitoring unit (ECC500) (16) Bluetooth Electric door lock
Issue 01 (2012-06-01)
(2) Door status sensor (5) Space for rectifiers (8) TEC
(11) Fan assembly (14) Temperature and humidity sensor (17) Space for Bluetooth controller
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(12) CMUA for fan assembly (15) Air filter
5
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
1 Overview
Figure 1-4 TP48200T- D14A1 interior
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Air filter (16) Bluetooth Electric door lock
Issue 01 (2012-06-01)
(2) Door status sensor (5) Space for rectifiers (8) TEC
(11) Fan assembly (14) Monitoring unit (ECC500) (17) Space for Bluetooth controller
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(12) CMUA for fan assembly (15) Temperature and humidity sensor
6
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
1 Overview
Figure 1-5 TP48200T- D14A2 interior
(1) Alternating current power distribution unit(AC PDU) (4) Intelligent power meter (7) Central monitoring unit type A (CMUA) for thermoelectric cooler (TEC) (10) GPRS antenna (13) Air filter (16) Bluetooth Electric door lock
Issue 01 (2012-06-01)
(2) Door status sensor (5) Space for rectifiers (8) TEC
(11) Fan assembly (14) Monitoring unit (ECC500) (17) Space for Bluetooth controller
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
(3) Direct current power distribution unit(DC PDU) (6) Space for customer equipments (9) Base
(12) CMUA for fan assembly (15) Temperature and humidity sensor
7
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
1 Overview
1.4 Features The TP48200T-D20A1 & D20A2 supplies stable power to -48 V DC equipment and provides a maximum current of 200 A. The TP48200T-D14A1 & D14A2 supplies stable power to -48 V DC equipment and provides a maximum current of 100 A.
Easy Installation The modules of monitoring unit (ECC500) and rectifiers are hot-swappable. This facilitates the system installation, saves maintenance time, and reduces the operational expenditure (OPEX).
High Efficiency The TP48200T-D20A1 & D20A2 & D14A1 & D14A2 uses rectifiers with a 96% efficiency record.
Low Imbalance Degree of Current Equalization The imbalance degree of current equalization for rectifiers is less than 5%.
Remote Monitoring OPEX is reduced when the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 performs comprehensive power management and battery management functions by connecting to the element management system (EMS).
Wide Range of AC Input Voltage The AC input voltage of the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 ranges from 85 V AC to 300 V AC phase voltage.
Safety and Regulatory Design The TP48200T-D20A1 & D20A2 & D14A1 & D14A2 complies with Conformite Europeenne (CE) standards, the power distribution components comply with CE standards, and the rectifier complies with underwriters laboratory (UL), CE, and Technical Watch-Over Association (TUV) standards.
High Protection Level The cabinet protection level is IP55.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
8
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2
2 Component Description
Component Description
2.1 Cabinet Dimensions (H x W x D) of the TP48200T-D20A1 & D20A2 cabinet (excluding the base) are 2060 mm x 700 mm x 700 mm (81.1 in. x 27.56 in. x 27.56 in.). Dimensions (H x W x D) of the base are 180 mm x 700 mm x 700 mm (7.09 in. x 27.56 in. x 27.56 in.). Figure 2-1 shows the TP48200T-D20A1 & D20A2 cabinet. Figure 2-1 TP48200T-D20A1 & D20A2 cabinet
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
9
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Dimensions (H x W x D) of the TP48200T-D14A1 & D14A2 cabinet (excluding the base) are 1400 mm x 700 mm x 700 mm (55.1 in. x 27.56 in. x 27.56 in.). Dimensions (H x W x D) of the base are 180 mm x 700 mm x 700 mm (7.09 in. x 27.56 in. x 27.56 in.). Figure 2-2 shows the TP48200T-D14A1 & D14A2 cabinet. Figure 2-2 TP48200T-D14A1 & D14A2 cabinet
Table 2-1 TP48200T-D20A1 & D20A2 & D14A1 & D14A2 cabinet height distribution Item
TP48200T-D20A1 & D20A2
TP48200T-D14A1 & D14A2
Customer equipment
13 U (557.85 mm [21.96 in.]) (not included the space for storage batteries)
5 U (222.25 mm [8.75 in.]) (not included the space for storage batteries)
Storage batteries
16U (755.6 mm [29.75 in.]) for two layers
8 U (355.6 mm [14.00 in.]) for one layer
Embedded power system
AC PDU: 3 U (133.35 mm [5.25 in.])
AC PDU: 3 U (133.35 mm [5.25 in.])
DC PDU: 4U (177.8 mm [7.0 in.])
DC PDU: 4U (177.8 mm [7.0 in.])
Monitoring unit (ECC500
1U (44.45mm [1.75in.])
1U (44.45mm [1.75in.])
Recitifers
2U (88.9mm[3.50in.])
2U (88.9mm[3.50in.])
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
10
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
2.2 Temperature Control Unit 2.2.1 Direct-Cooling Unit The direct-cooling unit extends the area for exchanging air inside and outside the cabinet, speeds up air circulation, and reduces the operating temperature in the cabinet. The fan assembly houses two centrifugal fans. The fans direct air into the cabinet through the lower part of the door and out of the cabinet through the top cover of the cabinet.
Appearance Figure 2-3 shows the fan assembly. Figure 2-4 shows a centrifugal fan. Figure 2-3 Fan assembly
Figure 2-4 Centrifugal fan
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
11
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Specifications Table 2-2 Technical specifications of fan assembly Item
Specifications
Rated voltage
–48 V DC
Rated power
2 x 34 W
Air flows Figure 2-5 The direct-cooling unit air flows
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
12
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
CMUA for fan assembly Figure 2-6 Ports of the CMUA
(1) PWR
(2) SMOKE
(3) IN0, IN1, IN2
(4) GATE
(5) ELU
(6) ALM & RUN Indicators
(7) COM_IN
(8) COM_OUT
(9) TEM.FAN
(10)TEC
(11) FAN_INT
(12) FAN_EXT
Table 2-3 Ports of the CMUA Silkscreen
Function
PWR
Power input port.
SMOKE
Reserved.
IN0, IN1, IN2
Reserved.
GATE
Reserved.
ELU
Reserved.
ALM & Indicators
RUN
Indicate CMUA status.
COM_IN
Connects to the monitoring unit.
COM_OUT
Reserved.
TEM.FAN
Connects to the temperature sensor.
TEC
Reserved.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
13
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Silkscreen
Function
FAN_INT
Connects to the fan on the left in the fan assembly.
FAN_EXT
Connects to the fan on the right in the fan assembly.
Table 2-4 Indicator description Silk Screen
Color
Status
Meaning
RUN
Green
Blinks at 0.5 Hz.
The board functions normally and communicates properly with upper-level equipment.
Blinks at 4 Hz.
The board functions normally, but fails to communicate with the upper-level equipment. If the board does not communicate with the upper-level equipment within one minute, the communication fails.
ON/OFF
The board is not performing self-test after being powered on.
Steady off
No alarm is generated.
Steady on
An alarm is generated, and the board must be replaced.
Blinks at 0.5 Hz.
An alarm is generated. It may be caused by a fault on the board or in a port. Therefore, the board must be replaced as required.
ALM
Red
CMUA Jumper Slot The CMUA has three jumper slots SW1, SW2, and SW3 for setting its working mode in different cabinets. Figure 2-7 shows jumper slots on the CMUA. Figure 2-7 Jumper slots on the CMUA (plan view)
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
14
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-8 shows settings for jumper slots on the CMUA. Figure 2-8 Settings for Jumper slots on the CMUA
2.2.2 TEC A TEC consists of semiconductor refrigeration chips, a cold-end heat sink, a hot-end heat sink, an internal fan (cold-end fan), an external fan (hot-end fan), and a controller. Figure 2-9 shows the TEC components.
Appearance
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
15
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-9 TEC components
1. Semiconductor refrigeration chip 4. Internal fan
2. Cold-end heat sink 5. External fan
3. Hot-end heat sink 6. Controller
Specifications Table 2-5 Technical specifications Item
Specifications
Rated voltage (V DC)
–48 V DC
Rated refrigeration capacity (L32/L32)
190 W
Maximum power input
380 W
Heating capacity
300W
Ambient range
–40˚C to +40˚C
Humidity range
5%–100% RH
Storage environment
–40˚C to +70˚C Complies with the ETS 300 019-1-1, CLASS 1.2 requirements.
Altitude
≤ 4700 m
Transportation performance
Complies with the ETS 300 019-1-2, CLASS 2.3
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
16
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Item
2 Component Description
Specifications requirements.
IP protection level
IP55 (cabinet), which complies with the International Electrotechnical Commission (IEC) 60529.
Anti-corrosion performance of the external air circulation system
Circular salt-fog test: The TEC passes the circular salt-fog test required by the IEC68-2-52 for 10 circles.
Damp heat test: The TEC passes the damp heat test required by the IEC 68-2-38 for 10 days.
Mould growth test: The TEC passes the mould growth test required by the IEC 68-2-10 for 28 days.
UL94 HF-1 level of sealing materials.
UL94 V0 level of shielding materials and printed circuit board (PCB).
UL94 V1 level of other materials.
Complies with the IEC 60950-1, EN 60950-1, and UL 60950-1. (The withstand voltage is greater than 750 V DC.)
The internal fan is configured with a grille protection cover, which complies with the IP3X requirement (Your fingers do not contact dangerous components in any direction.) Warning signs are attached to the internal fan.
Flame spread rating
Safety
Service life
10 years
Failure rate
< 1%
Fan service life (internal fan L10/25˚C and external fan L10/40˚C)
≥ 70,000 hours
Mean time between failures (MTBF)
> 100,000 hours
Dimensions (H x W x D, including the flange)
200 mm x 180 mm x 400 mm
Weight
6.4kg
Positive polarity protection of DC power supply
Supported
Operating voltage
36V–60V
Temperature sensor
Monitoring range:-20℃–80℃(±2℃)
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
17
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Air flows Figure 2-10 TEC air flows
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
18
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
CMUA for TEC Figure 2-11 Ports of the CMUA
(1) PWR
(2) SMOKE
(3) IN0, IN1, IN2
(4) GATE
(5) ELU
(6) ALM & RUN Indicators
(7) COM_IN
(8) COM_OUT
(9) TEM.FAN
(10)TEC
(11) FAN_INT
(12) FAN_EXT
Table 2-6 Ports of the CMUA Silkscreen
Function
PWR
Power input port.
SMOKE
Reserved.
IN0, IN1, IN2
Reserved.
GATE
Reserved.
ELU
Reserved.
ALM & Indicators
RUN
Indicate CMUA status.
COM_IN
Connects to the monitoring unit.
COM_OUT
Reserved.
TEM.FAN
Connects to the temperature sensor.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
19
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Silkscreen
Function
TEC
Connects to the TEC.
FAN_INT
Connects to the internal fan of the TEC.
FAN_EXT
Connects to the external fan of the TEC.
Table 2-7 Indicator description Silk Screen
Color
Status
Meaning
RUN
Green
Blinks at 0.5 Hz.
The board functions normally and communicates properly with upper-level equipment.
Blinks at 4 Hz.
The board functions normally, but fails to communicate with the upper-level equipment. If the board does not communicate with the upper-level equipment within one minute, the communication fails.
ON/OFF
The board is not performing self-test after being powered on.
Steady off
No alarm is generated.
Steady on
An alarm is generated, and the board must be replaced.
Blinks at 0.5 Hz.
An alarm is generated. It may be caused by a fault on the board or in a port. Therefore, the board must be replaced as required.
ALM
Red
CMUA Jumper Slot The CMUA has three jumper slots SW1, SW2, and SW3 for setting its working mode in different cabinets. Figure 2-12shows jumper slots on the CMUA.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
20
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-12 Jumper slots on the CMUA (plan view)
Figure 2-13 shows settings for jumper slots on the CMUA. Figure 2-13 Settings for Jumper slots on the CMUA
2.3 Rectifier 2.3.1 Appearance The rectifier converts the AC input power into stable -48 V DC power. The TP48200T-D20A1 & D20A2 & D14A1 & D14A2 can be configured with two, three, or four rectifiers. Figure 2-14 shows the rectifier.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
21
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-14 rectifier
2.3.2 Panel The rectifier panel provides the run indicator, alarm indicator, and fault indicator. Figure 2-15 shows the rectifier panel. Figure 2-15 rectifier panel
(1) Run indicator
(2) Alarm indicator
(3) Fault indicator
Table 2-8 Indicator description of rectifier Indicator
Color
Status
Run indicator
Green
Alarm indicator
Yellow
Description
Measures
Steady on
The rectifier output is normal.
The rectifier runs properly, and no measure is required.
Off
The rectifier has no output.
Replace the rectifier if the AC input is normal.
Off
No alarm is generated.
No measure is required.
Steady on
The rectifier generates a prewarning for power limiting due to overtemperature.
Check that the air vent is not blocked and the ambient temperature is within a normal range.
The rectifier generates an alarm for shutdown due to ambient overtemperature or undertemperature protection.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
22
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Indicator
Fault indicator
Color
Red
2 Component Description
Status
Description
Measures
The rectifier generates an alarm due to AC input overvoltage or undervoltage protection.
Check that the electrical grid voltage is within a normal range.
The rectifier is hibernated.
No measure is required.
Off
The rectifier is not faulty.
No measure is required.
Steady on
The rectifier is locked due to output overvoltage.
Pull out the rectifier and reinsert it after 1 minute.
There is no output because the rectifier is faulty.
Replace the rectifier.
The rectifier is loading an application program.
The rectifier automatically recovers after loading, and no measure is required.
Blinking at 4 Hz
2.4 Monitoring Unit 2.4.1 Appearance The monitoring unit (model: ECC500) consists of a main control module, a basic input/output (I/O) module, a GPRS module and three reserved slots. The main control module and Basic I/O module are mandatory, and other modules are optional. All modules in the ECC500 are hot-swappable. Figure 2-16 ECC500 architecture
(1) Main control module (4) Basic I/O module
(2) Filler panel
(3) GPRS module
Table 2-9 ECC component functions Component
Silkscreen
Configuration
Function
Main control module
SMU03A
Mandatory
Provides an LCD to query and set local parameters.
Monitors and manages input energy.
Provides an operating status indicator.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
23
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Component
Basic IO module
GPRS module
Silkscreen
MUS01A
MUC01A
2 Component Description
Configuration
Mandatory
Optional
Function
Provides TCP/IP and RS485 ports for northbound communication. TCP/IP stands for transmission control protocol/Internet protocol.
Provides RS485 ports for southbound communication.
Intelligently manages storage batteries.
Generates alarms.
Manages intelligent southbound components.
Manages assets.
Monitors southbound components over serial ports.
Receives alarms generated by dry contacts and sensors for detecting battery temperatures, water, smoke, and ambient temperature and humidity.
Provides RS485 ports for southbound communication.
Enables the ECC500 to communicate with the NetEco in out-of-band (by GPRS) mode.
Provides six digital parameter input ports and two dry contact outputs.
2.4.2 Main Control Module Figure 2-17 shows the front panel of the main control module. Figure 2-17 Front panel of the main control module
(1) Indicators (4) Fast Ethernet (FE) port
Issue 01 (2012-06-01)
(2) LCD (5) RS485/RS232 port
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
(3) Buttons (6) COM1 port
24
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual (7) COM2 port
2 Component Description (8) Universal Serial Bus (USB) port
Indicators Table 2-10 Indicator description Silk Screen
Color
Status
Description
Run indicator
Green
Off
The main control module is faulty or has no DC input.
Blinking (on for 1s and then off for 1s)
The main control module runs properly and communicates with the NetEco.
Blinking (on for 0.125s and then off for 0.125s)
The main control module runs properly but does not communicate with the NetEco properly.
Off
No critical or major alarm is generated.
Steady on
A critical or major alarm is generated.
Alarm indicator
Red
LCD You can view information and set parameters on the LCD. You can set and query parameters using the four buttons on the front panel. Table 2-11 describes the button functions.
Buttons Table 2-11 Button description Button
Definition
Description
▲ or ▼
Up or down
Allows you to view menu items and set the value of a menu item.
Cancel
Returns to the previous menu without saving the settings of the current menu item.
Enter
Enters the main menu from the standby screen, enters a submenu from the main menu, or saves menu settings.
Note: After a menu is displayed, the standby screen is displayed if no button is pressed for 5 minutes.
Issue 01 (2012-06-01)
After a menu is displayed, the LCD screen becomes dark if no button is pressed for 5 minutes.
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
25
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Ports Table 2-12 Port description Silk Screen
Description
FE
Northbound port, connecting to the network or NetEco
RS485/RS232
Reserved
COM1
Reserved
COM2
Reserved
USB
Reserved
Figure 2-18 FE pin definition
Table 2-13 FE pin definition Pin
Signal
Description
1
TX+
FE transmit
2
TX-
3
RX+
6
RX-
FE receive
2.4.3 Basic I/O module Figure 2-19 shows the front panel of the Basic I/O module.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
26
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-19 Front panel of the Basic I/O module
(1)ELU
(2)SMOKE
(3)DI_1
(4)DI_2
(5)DI_3
(6)AI_1
(7)AI_2
(8)TEM_HUM
(9)WATER
(10)CAN
(11)12V/1A
(12)COM1
(13)GATE
(14)COM2
(15)COM3
(16)DC input terminals
(17)Indicators
Indicators Table 2-14 shows the indicator description of the Basic I/O module. Table 2-14 Indicator description Silk Screen
Color
Meaning
Status
Description
PWR
Green
Power indicator
Steady on
The power supply is normal.
Off
The input/output (I/O) module is faulty or has no DC input.
Run indicator
Blinking (on for 1s and then off for 1s)
Communication is normal between the I/O module and the main control module.
Blinking (on for 0.125s and then off for 0.125s)
Communication fails between the I/O module and the main control module.
Off
Reserved.
RUN
ALM
Issue 01 (2012-06-01)
Green
Red
Alarm indicator
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
27
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Ports Table 2-15 Port description Silk Screen
Description
Remarks
ELU
I2C&1-WIRE
Connects to an electronic label board.
DI_1
Direct-cooling unit alarm or TEC alarm
Default setting:
If the dry contact is open, an alarm is generated.
If the dry contact is close, no alarm is generated.
DI_2
TEC alarm
DI_3
Direct-cooling unit alarm
AI_1
4-20mA analog input
Connects to a battery temperature sensor.
TEM_HUM
Ambient temperature and humidity
Connects to a humidity and temperature sensor.
WATER
Water intrusion
Connects to a water sensor.
SMOKE
Smoke generation
Connects to a smoke sensor.
CAN
Southbound CAN port
Connects to a southbound component.
12V
Power output ports
10.5–13.5 V
COM1
Two-wire RS485 port
Connects to the intelligent power meter.
GATE
Gate dry contact input
Default setting:
AI_2
If the dry contact is closed, no alarm is generated.
If the dry contact is open, an alarm is generated.
COM2
Southbound RS485 port
Reserved.
COM3
Southbound RS485 port
Reserved.
DC input terminals
RTN+ port: positive DC input terminal
–48 V DC input port
NEG–: negative DC input terminal
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
28
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Pin definition Figure 2-20 Pin definition
Table 2-16 Pin definition Silk Screen
Pin
Pin definition
WATER
1
12V
2
WATER
3
GND
4
-
1
12V
2
ENV_TEMP
3
12V
4
ENV_HUM
TEMHUM
2.4.4 GPRS Module Figure 2-21 shows the front panel of the GPRS module.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
29
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-21 Front panel of the GPRS module
(1) DO_1
(2) DO_2
(3) DI_1
(4) DI_2
(5) DI_3
(6) DI_4
(7) DI_5
(8) DI_6
(9) ANT
(10) Indicators
(11) SIM card
Frequency Band Upstream (module to BTS) : 824-849MHz/880 -915 MHz/1710 -1785 MHz/1850 -1910 MHz Downstream (BTS to module) : 869 -894 MHz/925-960 MHz/1805 -1880 MHz/1930 -1990 MHz
Indicators The Table 2-17 describes the indicators. Table 2-17 Indicator description Silk Screen
Color
Status
Description
PWR1
Yellow
Steady on
The power supply is normal.
Off
The power supple is faulty or has no DC input.
Steady on
The GPRS module is normal.
Off
The GPRS module is faulty or has no DC input.
Off
The GPRS module is not powered on.
PWR2
GPRS
Issue 01 (2012-06-01)
Yellow
Green
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
30
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Silk Screen
Color
2 Component Description
Status
Description
Steady on
A call is being set up over GPRS.
Blinking (on for 0.1s and then off for 0.025s)
Data is being transmitted over GPRS.
Blinking (on for 0.1s and then off for 2.9s)
The ECC500 is registered with the network, but no data is being transmitted.
Blinking (on for 0.1s and then off for 0.9s)
The ECC500 is searching for a network because of the absence of a subscriber identity module (SIM) card.
Ports Table 2-18 describes the ports of the GPRS module. Table 2-18 Port description Silk Screen
Function
Remarks
DO_1
Dry contact output
Reserved.
Dry contact input
Default(If the dry contact is closed, an alarm is generated.
DO_2 DI_1 DI_2 DI_3 DI_4 DI_5
If the dry contact is open, no alarm is generated.), can be modified. Definitions of DI_1 to DI_6 vary based on solution. You can query their definitions on the LCD, as shown in Figure 2-22.
DI_6 Figure 2-22 Default setting of DI of GPRS module
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
31
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
2.4.5 GPRS antenna Figure 2-23 GPRS antenna
(1) GPRS antenna
(2) GPRS module
2.5 PDU PDUs are classified into the DC PDU and AC PDU. The DC PDU distributes DC power to the TP48200T-D20A1 & D20A2 & D14A1 & D14A2, while the AC PDU distributes AC power.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
32
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
2.5.1 AC PDU Figure 2-24 AC PDU of TP48200T-D20A1 & D14A1
Figure 2-25 AC PDU of TP48200T-D20A2 & D14A2
Table 2-19 Circuit breaker distribution Item
TP48200T-D20A1 & D14A1
TP48200T-D20A2 & D14A2
AC input
1 x 63A/3P MCB
1 x 100A/2P MCB
AC output
3 x 10A MCB
3 x 10A MCB
1 x 10 A maintenance socket
1 x 10 A maintenance socket
1 x 10A RCD
1 x 10A RCD
NOTE
If TP48200T-D20A1 & D20A2 is configured with four rectifiers, the recommended AC output current summation should be less than 14A.
2.5.2 DC PDU Figure 2-26 shows the DC PDU.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
33
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-26 DC PDU
Figure 2-27 TP48200T-D20A1 & D20A2 battery branch
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
34
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Figure 2-28 TP48200T-D14A1 & D14A2 battery branch
Table 2-20 Circuit breaker distribution Item
Specification
Battery low voltage disconnection(BLVD)
10 x 10 A MCB
Load low voltage disconnection(LLVD)
2 x 100A MCB
1 x 80A MCB
2 x 50A MCB
3 x 25A MCB
2 x 10A MCB
Battery branch
TP48200T-D20A1 & D20A2:
2 x 125 A MCB
TP48200T-D14A1 & D14A2:
1 x 125 A MCB
2.6 Intelligent Power Meter 2.6.1 Appearance Figure 2-29 Appearance of intelligent power meter
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
35
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
2.6.2 Pins Figure 2-30 Pins of intelligent power meter
Table 2-21 Pins of the intelligent power meter Pin
Definition
1、2
Working Power
3、4
RS485
5
A phase voltage
6
B phase voltage
7
C phase voltage
8
Zero-voltage line
10
The current transformer interface
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
36
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
2.6.3 Specification Table 2-22 Specifications of the intelligent power meter Category Voltage
Item Measurement range
Specifications
Line voltage: 30V-600V
Phase voltage: 20V-400V
Overload capacity
800V
Measurement range
200Ma-100A
Overload capacity
200A
Single phase power
0-48000 W/var/VA
Total power
0-96000 W/var/VA
Measurement range
45 Hz -60Hz
Power factor
Measurement range
-1 to 1
Accuracy
Current
0.5%(10-100A)
Current
Power
Voltage
Phase voltage: 0.5% (20-400V)
Line voltage:1.0%
Power
1.0% ( U*I)
Power factor
1.0%
Frequency
45Hz-60Hz ±0.1Hz
Energy
1.0% (0.5C-1-0.5L)
2.7 Bluetooth electric door lock The Bluetooth electric door lock can be connected to the Bluetooth controller.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
37
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
2.7.1 Appearance Figure 2-31 Appearance of Bluetooth electric door lock
2.7.2 Pins Figure 2-32 RJ45 female connector
Table 2-23 Pins definition of the Bluetooth electric door lock Pin
Definition
3
+12V
6
Signal
8
GND
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
38
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
2.8 Bluetooth controller 2.8.1 Appearance Figure 2-33 Bluetooth controller
2.8.2 Pins Figure 2-34 Pins of the Bluetooth controller
Table 2-24 Pins definition of the Bluetooth controller Pin
Definition
1
AC power input
2
AC power input
3
connect to Pin4
4
connect to Pin3
5
-12V
6
+12V
7
control the Bluetooth lock(+)
8
control the Bluetooth lock(-)
9
-
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
39
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
2 Component Description
Table 2-25 Connection between the Bluetooth controller and the Bluetooth electric door lock Pins of the Bluetooth controller
Pins of the Bluetooth electric door lock
Definition
7
3
+12V
7
6
Signal
8
8
GND
2.8.3 Specification Table 2-26 Bluetooth controller specifications Item
Specifications
Rated current
4A
Rated voltage
125V
Operating Limit voltage
200V AC
Withstanding voltage 1 minute
1500V AC
Insulation resistance at 500V DC
1500MΩ
Contact resistance at 1A DC
3 MΩ
Solder inter diameter
1.2mm
Dimensions
193x110x90 mm
Operating Temperature
-45ºC a 85ºC
2.9 Storage Battery Storage batteries store electrical energy and power loads when the D.G. and mains supply no power or insufficient power. The TP48200A-D20A1 & D20A2 can be configured with two groups (8 pieces, 12V/100 Ah batteries for power monobloc) backup. The TP48200A-D14A1 & D14A2 can be configured with one group (4 pieces, 12V/100 Ah monobloc) batteries for power backup. The maximum dimensions for each storage battery are 295 mm x 125 mm x 560 mm. NOTE
Storage batteries are prepared by customer.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
40
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
3 Safety Precautions
3
Safety Precautions
3.1 Overview
CAUTION To minimize the risk of personal injury and damage to equipment, read and follow all the precautions in this document before performing any installation or maintenance. The "NOTE", "CAUTION", and "WARNING" marks in other documents do not represent all the safety instructions. They are only supplements to the safety instructions. Only trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment, and they must understand basic safety precautions to avoid hazards. To ensure safety of humans and the equipment, pay attention to the safety symbols on the equipment and all the safety instructions in this document. Huawei will not be liable for any consequence caused by the violation of the safety operation regulations and design, production, and usage standards. NOTE
The safety precautions described in this section are also applicable to other Huawei equipment.
3.2 Local Safety Regulations When operating Huawei equipment, you must follow the local laws and regulations. The safety instructions in this document are only supplements to the local laws and regulations.
3.3 Grounding Requirements Equipment to be grounded must meet the following requirements:
When installing the device, always make the ground connection first and disconnect it at the end.
Do not damage the ground conductor or operate the device in the absence of a properly installed ground conductor. Conduct the electrical inspection carefully.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
41
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
3 Safety Precautions
The device (or system) must be connected permanently to the protection ground before an operation. Before operating the device, check the electrical connection of the device to ensure that it is securely grounded.
3.4 Human Safety
Do not operate the device or cables during lightning strikes.
To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to telecommunication network voltage (TNV) circuits.
Before operating the device, wear electrostatic discharge (ESD) clothes, ESD gloves, and an ESD wrist strap.
Do not wear jewelry or watches when you operate the device.
In the case of fire, immediately leave the building or the equipment room, and turn on the fire alarm bell or make an emergency call. Do not enter a building that is on fire.
The temperature of some equipment parts may be rather high. Do not touch the surface of such equipment parts to avoid getting burn.
3.5 Equipment Safety
The device must be fixed securely on the floor or to other immovable objects such as walls and mounting racks before operation.
Do not block the ventilation while the device is operating.
Tighten the thumbscrews by using a tool after initial installation and subsequent access to the panel.
After the installation, remove packing materials from the equipment area.
3.6 Electrical Safety High Voltage
DANGER
The high voltage power supply provides power for the device operation. Direct or indirect contact (through damp objects) with high voltage and AC mains supply may result in fatal danger.
Non-standard and incorrect high voltage operations may result in fire and electric shock.
The personnel who install the AC facility must be qualified to perform high voltage and AC operations.
You must abide by the local rules and regulations when bridging and wiring AC cables.
During the installation of the AC power supply facility, follow the local safety regulations.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
42
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
3 Safety Precautions
Dedicated tools must be used during high voltage and AC operations. Avoid using ordinary tools.
When the operation is performed in a damp environment, ensure that the device is dry. When water is found in the rack or the rack is damp, switch off the power supply immediately.
High Electrical Leakage
Ground the device before powering it on. Otherwise, personal injury or device damage may be caused by high leakage current.
If a "high electrical leakage" tag is present on the power terminal of the device, you must ground the device before powering it on.
Do not install or remove power cables when the device is on. Transient contact between the core of the power cable and the conductor may generate electric arcs or sparks, which may cause fire or hurt human eyes.
Before installing or removing the power cable, turn off the power switch.
Before connecting a power cable, check that the label on the power cable is correct.
Power Cable
Power Output All output circuits are evaluated as SELV circuits.
CAUTION Outputs are energy hazards (>240 VA)
Electrostatic Discharge
CAUTION The static electricity generated by human bodies may damage the electrostatic-sensitive components on boards, for example, the large-scale integrated (LSI) circuits.
Human body movement, friction between human bodies and clothes, friction between shoes and floors, or handling of plastic articles causes static electromagnetic fields on human bodies. These static electromagnetic fields cannot be eliminated until the static is discharged.
To prevent electrostatic-sensitive components from being damaged by the static on human bodies, you must wear a well-grounded ESD wrist strap when touching the device or handling boards or application-specific integrated circuits (ASICs).
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
43
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
3 Safety Precautions
Figure 3-1 shows how to wear an ESD wrist strap. Figure 3-1 Wearing an ESD wrist strap
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
44
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
4
4 Installation and Commissioning
Installation and Commissioning
The detailed installation and commissioning refer to the TP48200T-D20A1 & D20A2 & D14A1 & D14A2 Quick Installation Guide.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
45
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
5
Maintenance
5.1 Routine Maintenance Maintain TP48200T-D20A1 & D20A2 & D14A1 & D14A2 periodically based on site requirements. The recommended maintenance interval is 6 months. If faults are identified, clear them immediately. Table 5-1 Routine maintenance Maintenance Item
Maintenance Task Check Item
Check Method
Repair When
Measures
Output voltage
Whether the output voltage of the DC PDU is within the range of –42 V DC to –58 V DC.
Measure the voltage.
The voltage is beyond the range of –42 V DC to –58 V DC.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
Switch on the circuit breaker on the DC PDU, set the multimeter to DC, and then measure the output voltage of the DC PDU.
46
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Maintenance Item
Maintenance Task Check Item
Check Method
Repair When
Measures
Component
Whether a component burns, smokes, sparks, or produces an unusual odor
Observe and smell the component.
A component burns, smokes, sparks, or produces an unusual odor.
If a short circuit occurs, rectify the fault.
If a cable diameter does not match the load, replace it.
If there is a burnt componen t, replace it.
Whether the fan is covered by dust
Fan
View the fan.
Whether the fan surface is damaged and whether the rotational speed, noise, and vibration are in the normal range
Dust accumulates on the fan.
Clear the dust on the fan.
The fan rotates unstably or slowly.
Replace the fan.
The fan is damaged.
Cabinet surface
Whether the paint and the electroplated coating on the surface of the cabinet are in good condition
View the cabinet surface.
Surface rust appears on the cabinet or paint peels off.
Polish the rust and repaint the cabinet.
Door lock
Whether surface rust appears on the door lock and rust continues to spread over the surface
Observe and open the lock.
The door lock is too rusty.
Replace the lock.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
47
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Maintenance Item
Maintenance Task Check Item
Check Method
Repair When
Measures
Environment inside the cabinet
Whether there are fingerprints or any other stains on the interior of the cabinet
View the interior of the cabinet.
There is foreign matter, fingerprints, or stains in the cabinet.
Clean up stains, fingerprints, and foreign matter using a brush or cotton cloth.
Whether there is unnecessary adhesive tape or cable ties on the cables
Whether there is tape, cable ties, wastepaper, or packing bags in the cabinet View the air filter.
Overtemperature alarms are frequently raised for the power system, and the temperature inside the cabinet is much higher than the ambient temperature.
Replace the air filter.
Dust accumulates on the air filter.
Air filter
Issue 01 (2012-06-01)
Whether the air filter is covered by dust
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
48
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
5.2 Troubleshooting Common Faults Table 5-2 Common faults and troubleshooting methods Fault Type
Fault Analysis
Handling Method
AC phase loss
AC input cable fault
1.
Grid fault or D.G. fault
Check whether the DC input cable is correctly and securely connected. If the cable is not correctly and securely connected, reconnect the cable. If the insulation layer is aged, replace the cable.
2.
Check whether the AC input voltage is excessively low using a multimeter, and check whether the AC undervoltage (lower than 180V AC) alarm is generated. If the AC input voltage is excessively low and the AC undervoltage alarm is generated, check whether there is short-circuit or electric leakage on the AC input loop. If there is short-circuit or electric leakage, replace the cable.
3.
If the AC input is the mains supply, contact the mains supplier for troubleshooting. If the AC input is from the D.G., check the D.G. by referring to the Diesel Generator User Manual.
1.
Check whether the DC input cable is correctly and securely connected. If the cable is not correctly and securely connected, reconnect the cable.
2.
Check whether the AC input switch is OFF. If the AC input switch is OFF, check whether faults such as short-circuit or open circuit exist on the AC input loop.
3.
If the AC input is the mains supply, contact the mains supplier for troubleshooting. If the AC input is from the D.G., check the D.G. by referring to the Diesel Generator User Manual.
4.
If the power-off duration is short, supply DC power using batteries. If the power-off duration is long, start other systems for power supply.
AC power off
Issue 01 (2012-06-01)
AC input cable fault
Grid fault or D.G. fault
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
49
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Fault Type
Fault Analysis
Handling Method
AC overvoltage and undervoltage
Improper setting of monitoring unit AC undervoltage or overvoltage threshold
1.
Check whether the AC undervoltage or overvoltage alarm threshold is properly set. If the threshold is excessively high or low, lower or raise the threshold according to the actual conditions.
2.
Mains supply grid fault or D.G. fault
If the AC input is the mains supply, contact the mains supplier for troubleshooting. If the AC input is from the D.G., check the D.G. by referring to the Diesel Generator User Manual.
Improper setting of monitoring unit DC undervoltage or overvoltage threshold
1.
Check the alarm thresholds of the DC overvoltage and undervoltage. If the thresholds are not proper, reset the thresholds according to the actual conditions.
2.
Rectifier module fault
When the storage battery is powering the load, remove all the rectifiers, and then insert each rectifier one by one. If an overvoltage alarm is generated after a rectifier is inserted, the voltage of the rectifier exceeds the upper threshold. Then replace the rectifier.
Communication failure between modules
1.
Battery loop fault
Check whether the rectifier module is in position or whether contact is proper. If the monitoring unit is inserted in an incorrect position, insert it correctly. If the contact is not proper, remove and then insert it.
2.
Check whether the battery loop is short-circuited or has other faults.
3.
Check whether the batteries are faulty. If the batteries are faulty, replace them.
DC overvoltage or DC undervoltage
Charging overcurrent
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
50
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Fault Type
Fault Analysis
Handling Method
Load shutdown
Load circuit breaker set to OFF
1.
Check whether the load detection cable is securely connected. If the cable is not connected securely, connect it correctly.
Contactor fault
2.
Excessively high setting of monitoring unit load shutdown voltage
If the load circuit breakers switch to OFF, check whether the load circuit is short circuit or overcurrent. Switch the load circuit breakers to ON after repairing the load circuit.
3.
Check whether the contactor is faulty and whether it can be connected and disconnected. If the contactor is faulty, replace it.
Battery shutdown
Battery fuse failure
Issue 01 (2012-06-01)
Output undervoltage due to greater load power than 4. configured rectifier module power
Check whether the monitoring unit load shutdown voltage is set excessively high. If it is set excessively high, set it according to the actual situation.
5.
Check whether the load power is higher than the configured rectifier module power. If the load power is higher than the configured rectifier module power, add a rectifier module. If the load power exceeds the maximum supported power of the system, lower the load power.
1.
Check whether the mains supply is off or the voltage of storage batteries is lower than the “Battery Shutdown Voltage”.
2.
Check whether the battery shutdown permission is set.
3.
Check whether the battery cables or the connectors are faulty. If the cables or connectors are faulty, replace them.
4.
Check whether the contactor is faulty and whether it can be connected and disconnected. If the contactor is faulty, replace it.
Battery loop fault 1.
Contactor fault
Battery fault
Check whether cables of the battery loop or connectors are faulty. If the cables or connectors are faulty, replace them.
Temperature sensor fault
Improper setting of monitoring unit battery parameters
Contactor fault
2.
Check whether the contactor is faulty and whether it can be connected and disconnected. If the contactor is faulty, replace it.
3.
Check whether batteries are faulty. If the batteries are faulty, replace them.
4.
Check whether temperature sensor is faulty. If the temperature sensor is faulty, replace it.
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
51
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Fault Type
Fault Analysis
Handling Method
Ambient overtemperature or undertemperature alarm
Improper setting of monitoring unit temperature alarm parameters
1.
(The alarm is generated only when the temperature sensor is installed.)
Overtemperature or 2. undertemperature in the shelter with the temperature sensor
Check whether monitoring temperature alarm thresholds are according to local conditions. If thresholds are not proper, set thresholds accordingly.
unit set the the
Check whether the temperature control device in the shelter is faulty. If the temperature control device is faulty, repair it. The alarm is automatically cleared when the temperature in the shelter is adjusted to the proper range.
Temperature sensor fault
3.
Check whether the temperature sensor is faulty. If the temperature sensor is faulty, replace it.
Ambient overhumidity or underhumidity alarm
Improper setting of monitoring unit humidity alarm parameters
1.
Check whether monitoring unit humidity alarm thresholds are set according to local conditions. If the thresholds are not proper, set the thresholds accordingly.
(The alarm is generated only when the humidity sensor is installed.)
Overhumidity or underhumidity in the shelter with the humidity sensor
2.
Check whether the floor of the shelter is wet. If the floor is wet, use a cotton cloth to wipe the floor and ensure it is dry or use other dehumidifiers.
3.
Humidity sensor fault
If the alarm persists when the humidity is proper, check whether the humidity sensor is faulty.
Battery cabin overtemperature
1.
Improper setting of monitoring unit battery temperature alarm parameters
Check whether monitoring unit battery temperature alarm thresholds are properly set. If the thresholds are not proper, set the thresholds accordingly.
2.
Check whether the temperature in battery room is excessively high. If temperature is excessively high, alarm can be cleared when temperature is lowered.
3.
Check the charging current. If the current is excessively strong, switch equalized charging to float charging and check whether the charging current is weakened. If the charging current is still excessively strong, adjust the current limit to reduce the charging current. If the preceding steps do not work, replace the faulty battery.
4.
Check whether the temperature sensor is faulty. If the temperature sensor is faulty, replace it.
Battery overtemperature or undertemperature alarm
Issue 01 (2012-06-01)
Battery charging overcurrent
Temperature sensor fault
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
the the the the
52
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Fault Type
Fault Analysis
Handling Method
Door alarm
Opened cabinet door
1.
The alarm is cleared after the cabinet door is closed.
Door status sensor fault
2.
If the alarm persists after the cabinet door is closed, check whether the door status sensor is faulty.
Water immersion alarm
Shelter water accumulation
1.
(The alarm is generated only when the water sensor is installed.)
Water sensor fault
Check whether the floor of the shelter is wet. If the floor is wet, use a cotton cloth to wipe the floor and ensure it is dry or use other dehumidifiers.
2.
If the alarm persists after the water is drained, check whether the water sensor is faulty.
Smoke alarm
Smoke in the shelter
1.
Smoke sensor fault
Check whether the smoke caused by fire pervades in the shelter. If there is fire, extinguish the fire and ventilate the shelter.
2.
If the alarm persists when there is no smoke, check whether the smoke sensor is faulty.
1.
Check whether the ALM indicator on the panel of the rectifier module is on. If the ALM indicator is on, remove the rectifier module and insert the rectifier module after the indicator is off.
2.
Disconnect AC input to the rectifier module and restart the rectifier module later on. If the alarm persists, replace the rectifier module.
1.
Check whether the mains voltage is over the AC overvoltage alarm threshold (300 V) of the rectifier module or below the AC undervoltage alarm threshold (85 V). For the power supply network with long-time overvoltage or undervoltage, negotiate with the maintenance personnel of the electricity department to improve the power supply network.
2.
If the alarm persists when the input voltage of the rectifier module is proper, check whether the rectifier module is proper. If the rectifier module is faulty, replace it.
(The alarm is generated only when the door status sensor is installed.)
(The alarm is generated only when the smoke sensor is installed.)
Rectifier module fault
Rectifier module shutdown
Poor contact of the rectifier module
Rectifier module fault
Input overvoltage or undervoltage of the rectifier module
Rectifier module fault
Rectifier module protection
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
53
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Fault Type
Fault Analysis
Handling Method
Communication Failure between rectifier and monitoring unit
Signal cable connection fault of the rectifier module
1.
Rectifier module out of position
Check whether the rectifier module is in position or whether contact is proper. If the monitoring unit is inserted in an incorrect position, insert it correctly. If the contact is not proper, remove and then insert it.
Poor contact of the rectifier module
2.
If the alarm persists, replace the rectifier module.
Rectifier module fault
The load fuse is faulty.
1.
Load circuit breaker set to OFF
Check whether the load fuse detection cable is securely connected. If the cable is not connected securely, connect it correctly.
2.
Check whether the load circuit breaker is in the OFF position. If it is, switch it to the ON position.
3.
Check whether the load fuse is damaged. Use a multimeter to measure the voltage at both ends of the fuse. If the voltage is close to 0 V, the fuse is normal. Otherwise, the fuse is blown. Replace the fuse.
4.
If the alarm persists after the fuse is replaced, check the new fuse. If the new fuse is blown or the load circuit breaker is automatically switched to the OFF position, the load power on this route may be excessive or a short circuit may occur. In this case, you need to rectify the fault on this load loop.
1.
Check the observation window on the AC surge protector. If the color of the window is red, replace the surge protector.
2.
Check whether the fault detection cables of the AC surge protector are correctly connected or whether the cables are in good condition. If the cables are not in good condition, replace and reconnect them.
3.
If the cable connection is proper, it indicates that the alarm loop is faulty. Replace the user interface module.
Load Fuse Alarm
AC surge protector fault
Issue 01 (2012-06-01)
AC surge protector fault
User interface module fault
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
54
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
TEC faults When a TEC becomes faulty, it transmits alarm signals over one dry contact to EMS software, and the ALM indicator turns on. The spare parts for a TEC includes temperature sensor,internal fan, external fan and TEC refrigeration module. Table 5-3 describes the TEC faults and troubleshooting measures. Table 5-3 TEC faults and troubleshooting measures Symptom
Possible Cause
Measures
The internal and external fans rotate properly, the semiconductor refrigeration chips do not work, the RUN indicator turns on, and no alarm is generated.
The semiconductor refrigeration chips are faulty.
Check that no input undervoltage or overvoltage occurs.
Check that cables properly connect to the semiconductor refrigeration chips.
If no fault is located, replace the CMUA.
The external fan rotates properly, the TEC circuit breaker trips, the RUN indicator turns on, and no alarm is generated.
The input voltages before and after the internal and external fans start are not within normal ranges.
If the input voltage is greater than 4 V, replace the damaged power cable.
If the input voltage is lower than 4 V, replace the CMUA.
The semiconductor refrigeration chips refrigerate properly, the internal and external fans rotate properly, the ALM indicator turns on, and an alarm is generated.
The cables to the temperature sensor are damaged.
If the cables to the fans are damaged, replace the cables.
Cables to the fans are damaged.
If all components are normal but an alarm is generated, reinstall internal and external fans. If an alarm is still generated, replace the TEC refrigeration module or control board .
CMUA faults When a CMUA is working properly, the resistance in the dry contact is low and the RUN indicator is steady on.When a CMUA is transmitting alarm signals, the resistance in the dry contact is high and the ALM indicator is steady on.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
55
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Table 5-4 CMUA faults and troubleshooting measures Symptom
Possible Cause
Measures
The host generates an alarm, and the ALM indicator and RUN indicator turn off.
Measure the input voltage.
Check the power supply circuit breaker.
Check that power cables connect to the correct polarities.
If no fault is located, replace the control board.
The host generates an alarm, and the RUN indicator turns on.
No DC power is supplied to the TEC. Control burned out.
broad
The alarm signal is loose, disconnected, or broken.
Secure the alarm cable.
5.3 Component Replacment
Load disconnection is prohibited when you replace the main components. Take measures to ensure that important loads are always connected during the replacement. For example, keep the circuit breaker of important loads set to ON and storage batteries and AC input are not cut off.
If a load must be disconnected, ask for the customer's prior permission.
The rectifier and the monitoring unit are hot-swappable.
Replacing the rectifier To replace the rectifier, perform the following steps: Step 1 Loosen the screws on the rectifier panel using a flat-head screwdriver. Step 2 Pull the handle of the rectifier outwards, and then remove the rectifier from the plug-in subrack, as shown in Figure 5-1. Step 3 Insert the rectifier into the corresponding slot in the plug-in subrack. Then, loosen the screws on the handle and pull out the handle. Step 4 Slide the rectifier into the plug-in subrack slowly along the guide rails. Then, lock the handle. Step 5 Tighten the screws on the handle, as shown in Figure 5-2. ----End
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
56
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-1 Removing the old rectifier
Figure 5-2 Installing the new rectifier
Replacing the monitoring module To replace a module in the ECC500, perform the following steps: Step 1 Remove the signal cables from old module. Insulate the cables in time and stamp labels. Step 2 Loosen the captive screws on the old module anti-clockwise using the M3 screwdriver. Step 3 Pull out the old module by grasping the handle with both hands, as shown in Figure 5-3. Step 4 Grasp the handles of the new module, and insert the module into the corresponding slot in the ECC500 subrack. Step 5 Push the new module until its front panel is level with that of the ECC500 subrack.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
57
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Step 6 Fold the handle. Step 7 Tighten the captive screws using the M3 screwdriver, as shown in Figure 5-4. Step 8 Connect the cables to the module according to the labels on the cables. Step 9 If the main control module is replaced, set parameters by referring TP48200T-D20A1 & D20A2 & D14A1 & D14A2 Quick Installation Guide. ----End Figure 5-3 Pulling out the old module
Figure 5-4 Installing a new moudle
Replacing the AC SPD To replace the AC SPD, perform the following steps: Step 1 Remove the faulty SPD. Step 2 Insert the new SPD. ----End
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
58
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-5 Replacing the AC SPD
Replacing Circuit breakers To replace a circuit breaker, perform the following steps: Step 1 Disconnect the power supply of a circuit breaker. For example, disconnect the DC input and set the circuit breaker to OFF before replacing the input circuit breaker. Step 2 Remove the cables or copper bars connected to the circuit breaker using a Phillips screwdriver, and then wrap the cables or copper bars using black PVC insulation tape to avoid hazards. Step 3 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver. Then, remove the circuit breaker, as shown in Figure 5-6. Step 4 Press the contact plate at the bottom of the circuit breaker using a flat-head screwdriver again to install the new circuit breaker in the correct position. Then, push the contact plate upwards using the screwdriver. Step 5 Install the cables or copper bars to the circuit breaker using a Phillips screwdriver in the same way. Step 6 Set the circuit breaker to ON and connect power supply of this circuit breaker, as shown in Figure 5-7. ----End Figure 5-6 Removing the circuit breaker
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
59
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-7 Installing the circuit breaker
Replacing temperature and humidity sensor To replace a temperature and humidity sensor, perform the following steps: Step 1 Open the front door of the cabinet, press the latch in the front of the temperature and humidity sensor, and then remove the cover of the temperature and humidity sensor. Step 2 Loosen the two screws on holder of the temperature and humidity sensor, and then remove the holder, as shown in Figure 5-8. Step 3 Loosen the crimping screws on holder of the temperature and humidity sensor by using the flat-head screwdriver. Record the installation positions of the cables, and then remove the cables. Step 4 Correctly connect the cables to the wiring terminal on the new temperature and humidity sensor holder and secure the crimping screws by using the small flat-head screwdriver. Step 5 Install the holder of the new temperature and humidity sensor on the cabinet by securing the captive screws. Step 6 Install the cover on the holder of the temperature and humidity sensor. ----End Figure 5-8 Temperature and humidity sensor
(1) Cover of the temperature and humidity sensor
Issue 01 (2012-06-01)
(2) Holder of the temperature and humidity sensor
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
(3) Screw on the temperature and humidity sensor holder
60
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Replacing Fan assembly To replace the fan assembly, perform the following steps: Step 1 Switch off the circuit breaker of the fan assembly. Step 2 Loosen the screws on top of the cabinet as shown in Figure 5-9. Figure 5-9 Loosen the screws on top of the cabinet
Step 3 Open the top cover and secure the butterfly nut, as shown in Figure 5-10.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
61
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-10 Open the top cover
Step 4 Remove the power cables of the fans. Step 5 Loosen the screws on top of the fan assembly, as shown in Figure 5-11.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
62
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-11 Removing the fan assembly
Step 6 Install the new fan assembly, as shown in Figure 5-12. Figure 5-12 Installing the fan assembly
Step 7 Install the power cables of the fans. Step 8 Close the top cover. Step 9 Tighten the screws on top of the cabinet as shown in Figure 5-13.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
63
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-13 Tighten the screws on top of the cabinet
----End
Replacing TEC To replace the TEC, perform the following steps: Step 1 Power off the TEC. 1.
Switch off the TEC circuit breaker on the DC PDU or power system.
2.
Remove the power cables and alarm cables.
Step 2 Remove the TEC refrigeration module, as shown in Figure 5-14.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
64
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-14 Removing the TEC refrigeration module
Step 3 Install a new TEC refrigeration module. 1.
Secure a new TEC refrigeration module to the door using the removed screws.
2.
Reinstall the cover to the temperature control door using the removed screws.
3.
Install power cables to the correct poles.
4.
Install the dry contact alarm cables to the correct poles.
Step 4 Power on the TEC. 1.
Switch on the TEC circuit breaker on the DC PDU or power system.
2.
Power on the TEC for a self-check and a refrigeration function test.
3.
Check that the ALM indicators on the temperature controller and monitoring device turn off.
4.
After the TEC runs properly for 5 minutes, check the refrigeration function.
----End
Replacing CMUA To replace the CMUA, perform the following steps: Step 1 Switch off the CMUA circuit breaker on the DC PDU or power system. Step 2 Remove the CMUA. 1.
Issue 01 (2012-06-01)
Remove the two M4 screws from the CMUA cover, and then remove the CMUA cover, as shown in Figure 5-15.
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
65
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-15 Removing the CMUA cover
2.
Label the cables and then remove these cables.
3.
Remove the four M3 screws on CMUA board and then remove the CMUA board , as shown in Figure 5-16.
Figure 5-16 Removing the CMUA board
Step 3 Install a new CMUA board. 1.
Install a new CMUA board using the four removed screws.
2.
Install jumper caps on the jumper slot, by referring to 2.2.1 CMUA Jumper Slot or 2.2.2 CMUA Jumper Slot.
3.
Connect all the removed cables to the CMUA.
4.
Reinstall ther cover using the two removed screws.
Step 4 Power on the CMUA. 1.
Switch on the CMUA circuit breaker on the DC PDU or power system.
2.
Power on the CMUA for a self-check and a refrigeration function test.
3.
Check that the ALM indicators on the temperature controller and monitoring device turn off.
4.
After the CMUA runs properly for 5 minutes, check the refrigeration function.
----End
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
66
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Replacing the Air filter To replace the air filter, perform the following steps: Step 1 Loosen the screws with the crosshead screwdriver and then remove the air filter. Step 2 Install the air filter in the original position and fasten the screws with the crosshead screwdriver. ----End Figure 5-17 Removing the air filter
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
67
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Figure 5-18 Installing the air filter
Replacing the Door lock cylinder To replace the lock cylinder, perform the following steps: Step 1 Open the door lock using a key to the degree as shown in the following figure. Step 2 Unscrew the lock cylinder to be replaced using a Phillips screwdriver. Step 3 Secure a new lock cylinder using screws. ----End Figure 5-19 Replacing the lock cylinder
Replacing the Door lock To replace the lock, perform the following steps: Step 1 Disconnect the cable between the Bluetooth controller and the door lock. Step 2 Unscrew the lock rod to be replaced using a Phillips screwdriver.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
68
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Step 3 Remove the door lock. Step 4 Secure a new lock using screws. Step 5 Connect the cable between the Bluetooth controller and the door lock. ----End Figure 5-20 Replacing the door lock
Replacing the Door status sensor To replace the door status sensor, perform the following steps: Step 1 Open the front door and remove the case of the door status sensor, as shown in Figure 5-21. Figure 5-21 Removing the case of the door status sensor
Step 2 Record the connections of the alarm cables and then disconnect them. Step 3 Loosen the screws on the door status sensor and then remove the sensor. Step 4 Install a new door status sensor in position and tighten the screws. Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
69
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Step 5 Install the alarm cables of the new door status sensor according to the recorded connections, and then install the case. ----End
Replacing the Intelligent Power Meter To replace the intelligent power meter, perform the following steps: Step 1 Loosen the screws on the baffle plate and then remove the baffle plate. Step 2 Press the contact plate at the bottom of the intelligent power meter using a flat-head screwdriver. Then, remove the intelligent power meter. Figure 5-22 Removing the intelligent power meter
Step 3 Press the contact plate at the bottom of the intelligent power meter using a flat-head screwdriver again to install the new intelligent power meter in the correct position. Step 4 Install the baffle plate and tighten the screws. ----End Figure 5-23 Installing the intelligent power meter
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
70
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Replacing the GPRS antenna To replace the GPRS antenna, perform the following steps: Step 1 Remove the GPRS cable from the GPRS module, as shown in Figure 5-24. Figure 5-24 Removing the GPRS cable
Step 2 Remove the GPRS antenna, as shown in Figure 5-25. Figure 5-25 Removing the GPRS antenna
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
71
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
5 Maintenance
Step 3 Install the GPRS antenna, as shown in Figure 5-26. Figure 5-26 Installing the GPRS antenna
Step 4 Installing the GPRS cable to the GPRS module, as shown in Figure 5-27. Figure 5-27 Installing the GPRS cable
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
72
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
5 Maintenance
73
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
6
Monitoring Function
6.1 LCD User Interface Selecting a Display Language After the ECC500 is powered on, the screen for selecting a display language is displayed. You can select Chinese, English or other language by pressing ▲ or ▼ and enter the standby screen by pressing Enter.
Querying Active Alarms This section describes how to query active alarms on the LCD, as shown in Figure 6-1. The parameter values in Figure 6-1 are for reference only. Figure 6-1 Querying active alarms
NOTE
110215 indicates February 15, 2011. The alarm severity and date are displayed alternatively.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
74
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Setting Parameters Quickly This section describes how to quickly set the number of battery strings and rated battery capacity on the LCD, as shown in Figure 6-2. The parameter values in Figure 6-2 are for reference only. Figure 6-2 Setting parameters quickly
NOTE
To open the Settings page, Quick Setting page, and Control page, you need to enter a password. The default user name is admin and the default password is 001. You can add or delete users, and change the user name and password.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
75
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Setting Alarm Parameters Figure 6-3 Setting alarm parameters
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
76
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-4 Setting DO alarm status
LCD Menu Hierarchy Figure 6-5 shows the LCD main menu.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
77
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-5 LCD Menu hierarchy Main Menu
Active Alarm
Running Status
Settings
Control
Quick Settings
Site Summary
Alarm Setting
Site Summary
Qty of Battery
PSU Summary
Site Summary
Batt Summ
Rated Capacity
PSU
PSU Summary
PSU Summary
Set Date
Batt Summ
VRLA Batt Summ
PSU
Set Time
VRLA Batt
LVD Setting
Clr Alarm Hist
IP Address
ECC500
GPRS
Alarm History
ECC500
Comm Para
Subnet Mask
Gateway
System Para
Batt Test Log
6.2 Web User Interface You can perform the following operations over the WebUI:
View the system status, including the PSU status, battery status, and active alarm information.
Configure system parameters.
Configure network parameters, including IP addresses, host communications addresses and baud rates under master/slave protocol.
Control the system, such as choosing battery boost or floating charge and resetting PSUs.
Add or delete users, and change user names and passwords.
Upgrade software online.
Query and export historical logs and alarms.
Configure alarm parameters, alarm severities, and the relationship between alarms and dry contacts.
Set the system date and time, site and storage battery type, save, download, and upload configuration files.
Query electronic label information.
Configure site information including date and site name and deal with configuration files and so on.
Set the IP address, gateway, and subnet mask of the SMU on the LCD before logging into the WebUI.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
78
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Login Web Page Step 1 Connect an SMU to an Ethernet. Step 2 Set the IP address, subnet mask, and gateway on the LCD based on those assigned by the customer. Step 3 Enter the IP address of the SMU in the Internet Explorer address box and press
.
Step 4 On the login page shown in Figure 6-6, set User Name to admin and Password to 001, and then press Login. Figure 6-6 Login page
Setting the Internet Explorer Make sure exporting historical logs successfully, need to set the Internet Explorer. Setting method as follows: Step 1 Open the Internet Explorer. Step 2 Choose Tools > Internet Options. Step 3 On the Security tab, choose Internet and click Customer Level as shown in Figure 6-7. After set Internet, please set Local intranet in the same method. Step 4 Select Enable under Initialize and script ActiveX controls not marked as safe. ----End
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
79
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-7 Internet options interface
Step 5 Select Enable for all the options.. ----End
Querying System Status To view the information about the site, active alarms, PSUs, batteries, power distribution, TCU and fan, click System Status, as shown in Figure 6-8
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
80
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-8 System Status
Configuring System Parameters You can configure the site, PSUs, and batteries in the System Configuration pane shown in Figure 6-9 Figure 6-9 System Configuration
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
81
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Configuring Network Parameters In the Network Configuration pane, you can set the IP address, subnet mask, and gateway under System IP, the host communications address and baud rate under Master Slave Protocol, the SNMP version under SNMP, the trap IP address under SNMP Trap, and the server IP addresses and port number under NetEco. Figure 6-10 shows the Network Configuration pane. Figure 6-10 Network Configuration
Setting Control Parameters You can set control parameters for the site, PSUs, storage batteries, and PDU in the Control pane shown in Figure 6-11.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
82
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-11 Control
Managing Users You can create and delete users and modify user information in the User Management pane shown in Figure 6-12. Users are classified into three types: admin, engineer, and operator. Different user types have different operation rights. Only admin users have user management rights.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
83
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-12 User Management
Upgrading Software You can upgrade SMU and PSU software in the Upgrade pane shown in Figure 6-13 To upgrade software, perform the following steps: Step 1 Click Browse to select the software and then click Send. Step 2 After the software information is displayed under Available package active, select the software and click Activate. The software upgrade progress is displayed. A message is displayed when the upgrade is successful. ----End
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
84
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-13 Upgrade
Exporting Historical Logs To download configuration files and log files, perform the following steps: Step 1 Click Log History. Step 2 Click Download under One-click Download. The message "Are you sure to download the current configuration file and log file?" is displayed. Step 3 Click OK. The configuration files and log files are downloaded in about 2 minutes. ----End You can export battery testing records in Hypertext Markup Language (HTML) files by clicking Export. Figure 6-14 shows the Log History pane.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
85
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-14 Log History
Exporting Historical Alarms You can download historical alarms in the History Alarms pane shown in Figure 6-15. To export historical alarms in HTML files, click Export. To clear historical alarms, click Clean. Figure 6-15 Historical Alarms
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
86
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Configuring Alarm Parameters You can set Alarm Enable, Alarm Level, and Relay in the Alarm Configuration pane shown in Figure 6-16. Figure 6-16 Alarm Configuration
Configuring Site Parameters You can set the date, time, site, and storage batteries type, and save, download, and upload configuration files in the Site Configure pane shown in Figure 6-17.
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
87
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Figure 6-17 Site Configure
Energy Saving You can set Basic Parameters, Control For Different Rates, Control for Exceeding Max Power, Daily Electric Consum Mode, Monthly Electric Consum Mode in the Energy Saving pane shown in Figure 6-18. Figure 6-18 Energy Saving
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
88
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
6 Monitoring Function
Reading Electronic Labels You can query electronic label information about system components such as the SMU, power distribution subrack, and PSUs in the Electronic Label pane. To export electronic label information in HTML files, click Export. Figure 6-19 Electronic Labels
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
89
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
A
A Technical Specifications
Technical Specifications
Table A-1 Technical specifications Category
Item
Specifications
Environmental conditions
Operating temperature
–10ºC to +45ºC (14ºF to +113ºF)
Storage temperature
–40°C to +70°C (–40°F to +158°F)
Transportation temperature
–40°C to +70°C (–40°F to +158°F)
Operating humidity
5%–100% RH
Storage humidity
5%–100% RH
Altitude
0-4000 m (0-13123.2 ft) When the altitude ranges from 2000 m (6561.6 ft) to 4000 m (13123.2 ft), the operating temperature is derated by 1ºC (1.8ºF) for each additional 200 m (656.16 ft).
AC input
Input mode
TP48200T-D20A1 & D14A1:
220V three-phase five-line (L1, L2, L3, N, PE)
110V three-phase five-line (L1, L2, L3, N, PE)
220V single-phase three-line (L, N, PE)
TP48200T-D20A2 & D14A2:
Input voltage
Issue 01 (2012-06-01)
110V dual-live-wire (L1, L2, N, PE)
110V dual-live-wire (L1, L2, PE)
220V single-phase three-line (L, N, PE)
85V AC - 300 V AC
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
90
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Category
A Technical Specifications
Item
Specifications
Rated voltage
TP48200T-D20A1 & D14A1:
200-240/346-415V AC for 220V three-phase five-line (L1, L2, L3, N, PE)
100-127/200-240 V AC for 110V three-phase five-line (L1, L2, L3, N, PE)
200-240 V AC for 220V single-phase three-line (L, N, PE)
TP48200T-D20A2 & D14A2:
DC output
AC input protection
Issue 01 (2012-06-01)
100-120/200-240 V AC for 110V dual-live-wire (L1, L2, N, PE)
100-120/200-240 V AC for 110V dual-live-wire (L1, L2, PE)
200-240 V AC for 220V single-phase three-line (L, N, PE)
Input frequency
45–65 Hz
Rated frequency
50/60 Hz
Power factor
≥ 0.99
Output voltage range
–42 V DC to –58V DC
Default output voltage
–53.5 V DC
Maximum output power
Number of rectifiers multiplied by the output power of a single rectifier.
Regulated voltage precision
≤ 1%
Peak-to-peak noise voltage
≤ 200 mV (0–20 MHz)
AC input overvoltage protection threshold
Overvoltage protection is performed when the single-phase AC input voltage exceeds the AC input overvoltage protection threshold (300 V AC by default).
AC input overvoltage recovery threshold
When the voltage is restored to 290 V AC, the output resumes.
AC input undervoltage protection threshold
Undervoltage protection is performed when the single-phase AC input voltage is below the AC input undervoltage protection threshold (85 V AC by default).
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
91
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Category
A Technical Specifications
Item
Specifications
AC input undervoltage recovery threshold
When the voltage is restored to 90 V AC, the output resumes.
DC output protection
DC output overvoltage protection threshold
58.5–60.5 V DC
Rectifier
Max output current
50A
Efficiency
The peak point is ≥96.0%
(R4850G1)
≥95.0%(30%-100% load) Output power
3000W
Overvoltage protection
58.5–60.5 VDC (can be set by monitoring unit ) 1.If the overvoltage occurs inside the rectifier due to a fault, the rectifier will latch off. 2.If the output voltage is higher than 63 V and lasts for more than 500 ms, the rectifier will latch off.
EMC
CE
CISPR 22/EN 55022 class B (AC terminal) CISPR 22/EN 55022 class A (DC output terminal)
RE
CISPR 22/EN 55022 Class B
Harmonic
IEC 61000-3-12
Fluctuation and blinking
IEC 61000-3-3
ESD
Contact discharge voltage: 6kV (Class B); air discharge voltage: 8 kV (Class B); Contact discharge voltage: 8kV (Class B); air discharge voltage: 15 kV (Class R); standard: IEC61000-4-2
Issue 01 (2012-06-01)
EFT
The voltage at signal ports is 1 kV, and the voltage at the power ports is 2 kV (criterion B).
RS
10 V/m (criterion A)
CS
The voltage at signal ports is 3V and power ports is 10 V (criterion A).
SURGE
It complies with the IEC61000-4-5 standard. The voltage at the AC power ports in differential mode is ±2 kV. The voltage at the AC power ports in common mode is ±4 kV (criterion B).
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
92
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
A Technical Specifications
Category
Item
Specifications
Others
Surge protection
For AC power ports,
Nominal discharge current 20 kA Max discharge current 40 kA
For DC power ports,
Differential mode: 10 kA Common mode: 20 kA
Structure
MTBF
200,000 hours (at 30°C)
Dimensions (H x W x D)
TP48200T-D20A1 & D20A2:
Cabinet: 2060 mm (81.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.)
Base: 180 mm (7.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.)
TP48200T-D14A1 & D14A2:
Weight
Cabinet: 1400 mm (55.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.)
Base: 180 mm (7.1 in.) x 700 mm (27.56 in.) x 700 mm (27.56 in.)
TP48200T-D20A1 & D20A2: ≤ 200 kg (excluding rectifiers and storage batteries) TP48200T-D14A1 & D14A2: ≤ 160 kg (excluding rectifiers and storage batteries)
Protection level
IP55
Installation
Ground installation
Maintenance
From the front, supporting module-level replacement.
Cooling
Equipment compartment is direct-cooling
Battery compartment is TEC
Cooling capacity
TP48200T-D20A1 & D20A2: 1200W TP48200T-D14A1 & D14A2: 800W
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
93
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
B LCD Menu
B
LCD Menu
Table B-1 LCD Menu Main Menu
Second-Lev el Menu
Third-Level Menu
Fourth-Le vel Menu
Default Value
Range
Active Alarm
-
-
-
-
-
Running Status
Site Summary
System Voltage
-
-
-
Total Load
-
-
-
Ambient Humi 1
-
-
-
Ambient Temp 1
-
-
-
Qty of Battery
-
-
-
Sys. Efficiency
-
-
-
Peak Power
-
-
-
Peak Power Time
-
-
-
System Type
-
-
-
Total Current
-
-
-
Used Capacity
-
-
-
AC Voltage
-
-
-
AC Total Curr
-
-
-
AC Frequency
-
-
-
DC Total Power
-
-
-
PSU
-
-
-
-
Batt Summ
Total Current
-
-
-
Pre Disch Time
-
-
-
BattChargeSta
-
-
-
PSU Summary
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
94
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Main Menu
Second-Lev el Menu
VRLA Batt
Settings
B LCD Menu
Third-Level Menu
Fourth-Le vel Menu
Default Value
Range
Batt Test Sta
-
-
-
Batt Temp 1
-
-
-
VRLA Batt 1
Current
-
-
Capacity
-
-
Capa Percent
-
-
ECC500
MUC01A_DI_6
-
-
-
GPRS
GPRS Slot ID
-
-
-
GPRS Cur Signal
-
-
-
GPRS Status
-
-
-
SIM Card Status
-
-
-
GPRS IP Address
-
-
-
Alarm History
-
-
-
-
Batt Test Log
-
-
-
-
Alarm Setting
Alarm Relay
-
-
-
Site Summary
-
-
-
PSU Summary
-
-
-
PSU
-
--
-
Batt Summ
-
-
-
VRLA Batt
-
-
-
System Type
-
TP48200T_D1 4A2
-
DC Over Volt
-
58.0 V
53.0-60.0 V
DC Ultra Over V
-
60.0 V
53.0-60.0 V
DC Under Volt
-
45.0 V
35.0-47.8 V
DC Ultra UnderV
-
43.0 V
35.0-47.8 V
Shunt Current
-
300 A
0-50
Shunt Voltage
-
75 mV
0-3000 A
Qty of Battery
-
1
0-1500 V
AC Over Volt
-
280 V
100-300 V
Site Summary
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
95
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Main Menu
Second-Lev el Menu
PSU Summary
Issue 01 (2012-06-01)
B LCD Menu
Third-Level Menu
Fourth-Le vel Menu
Default Value
Range
AC Under Volt
-
180 V
60-300 V
System AC Type
-
Single Phase
Single Phase, ThreePhase
AC Fail Time
-
10Min
0-30Min
Dial-up Network
-
Disable
Disable,Enable
Amb Hi Temp Pt
-
40degC
25 - 80degC
Amb Low Temp Pt
-
0degC
-20 -20 degC
Amb Hi Humi Pt
-
80%
0%-100%
Amb Low Humi Pt
-
10%
0%-100%
Amb V-Hi Temp
-
50degC
25 - 80degC
High Power Pt
-
80%
1%-120%
D.G. Function
-
Non
Non,Current Limit,Smart Ctrl
Diesel Capaciey
-
12.5KVA
1 KVA-100 KVA
D.G. start Cap
-
30%
10-100%
D.G. stop Cap
-
90%
10-100%
Air-Con. StPwr
-
3.0KW
0.0 -300.0 KW
Air-Con. WtPwr
-
0.6KW
0.0 -300.0 KW
Max Charge Time
-
12H
6-100H
Min Charge Time
-
0H
0-5H
D.G. Working
-
Close
Close, Open
E04A_ D (0108)Alm Act
-
Open
Close, Open
Record Interval
-
15Min
1 -60 Min
Alarm Voice Dly
-
10Min
1-100 Min
Alarm Voice En
-
No
No,Yes
DST Enable
-
Disable
Disable, Enable
Forbid All Alm
-
No
No,Yes
Walk-in Enabled
-
Disable
Disable,Enable
Seq Start Intv
-
0s
0-20s
High Volt Limit
-
59.5V
58.5-60.5V
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
96
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Main Menu
Second-Lev el Menu
VRLA Batt Summ
Third-Level Menu
Fourth-Le vel Menu
Default Value
Range
High PSU Cap %
-
20%
0-120%
Low PSU Cap %
-
100%
0-120%
Rect Redund Ena
-
Disable
Disable,Enable
Basic Para
Smart Mgmt En
Disable
Disable,Enable
Float Charge
53.5 V
48.0-58.3 V
Boost Charge
56.4 V
48.0-58.3 V
Current Limit
0.15C10
0.05-0.25
Over Current
0.25C10
0.05-0.50
Rated Capacity
100Ah
10-10000 Ah
Install Date
2010-01-01
YYYY-MM-DD
Auto BC Enabled
Enable
Enable, Disable
To BC Current
0.05C10
0.01-0.30
Curr BC Delay
30 Min
2-1440 Min
To BC Capacity
80%
50-100%
Capa BC Delay
10 Min
2-1440 Min
BC to FC Curr
0.01C10
0.01-0.30
BC to FC Delay
30 Min
2-540 Min
Max BC Time
16 H
5-48 H
Cyclic BC Ena
Enable
Enable, Disable
Cyclic BC Intv
30 Day
1-365 Days
Cyc BC
9H
1-24 H
FC BC
Issue 01 (2012-06-01)
B LCD Menu
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
97
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Main Menu
Second-Lev el Menu
Third-Level Menu
B LCD Menu
Fourth-Le vel Menu
Default Value
Range
Test End Volt
46.0 V
43.0-53.0 V
Test End Capa
20.0%
0.0-100.0%
Test End Temp
5degC
-5-15 degC
Test End Time
480Min
1-6000 Min
Mains Fail Test
Disable
Disable,Enable
Batt Test Type
No Test
No Test,Cyclic Test, Plan Test
Short Test Ena
Enable
Enable,Disable
Short Test Intv
30 Day
1-360 Days
ShortT Duration
5 Min
1-240 Min
TC Factor
80 mV/degC
0-500 mV/degC
Nominal Temp
25degC
5-45 degC
0.05C10 DisTime
20.00 H
0.20-50.00 H
0.1C10 Dis Time
10.00H
0.20-50.00 H
0.2C10 Dis Time
4.00 H
0.20-50.00 H
0.3C10 Dis Time
2.42 H
0.20-50.00 H
0.4C10 Dis Time
1.63 H
0.20-50.00 H
0.5C10 Dis Time
1.16H
0.20-50.00 H
0.6C10 Dis Time
0.87 H
0.20-50.00 H
0.7C10 Dis Time
0.61 H
0.20-50.00 H
Duration Battery Test
Temp Comp
Charge Disch
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
98
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Main Menu
Second-Lev el Menu
Third-Level Menu
B LCD Menu
Fourth-Le vel Menu
Default Value
Range
0.8C10 Dis Time
0.50 H
0.20-50.00 H
0.9C10 Dis Time
0.42 H
0.20-50.00 H
1.0C10 Dis Time
0.35H
0.20-50.00 H
Capacity Coeff
95%
60-1005%
Batt Temp VHigh
Lower DC Volt
Lower DC Volt,BLVD,Do Nothing
Over Temp Volt
50.5V
42.0-53.0 V
Batt High Temp
45degC
25-80 degC
Bat V-High Temp
53degC
25-80 degC
Batt Low Temp
–5degC
-20-20 degC
Batt V-Low Temp
–10degC
-20-20 degC
BLVD Enabled
-
Enable
Enable, Disable
BLVD Mode
-
By Voltage
By Voltage,By Capacity,By Time
BLVD Voltage
-
43.2 V
35.0-47.8 V
BLVD Recon Volt
-
51.5 V
37.0-53.0 V
LLVD1 Enabled
-
Disable
Disable ,Enable
ECC500
MUC01A_DI_1
-
Normal Close
Normal Close ,Normal Open
Comm Para
Network Mode
-
IP
-
IP Address
-
192.168.0.10
-
Subnet Mask
-
255.255.255.0
-
Gateway
-
192.168.0.1
-
Host Comm Addr
-
0
0~31
Comm Baudrate
-
9600
9600,19200
Other
LVD Setting
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
99
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Main Menu
Second-Lev el Menu
System Para
Control
Site Summary
Batt Summ
Issue 01 (2012-06-01)
B LCD Menu
Third-Level Menu
Fourth-Le vel Menu
Default Value
Range
DHCP
-
Disable
Disable,Enable
Phone Number (1-3)
-
-
-
Account(1-3)
-
-
-
Password
-
-
-
NetEco Main IP
-
58.251.159.33
-
NetEco Bak IP
-
58.251.159.33
-
NetEco Port
-
31220
-
LUI Language
-
ENGLISH
English , Chinese
Set Date
-
-
-
Set Time
-
-
-
Set Time Zone
-
GMT +08:00
-
Save As Def Cfg
-
Yes
-
Restore Def Cfg
-
Yes
-
Restore Manu Cfg
-
Yes
-
Logout
-
Yes
-
Set Site Name
-
-
-
Set Batt Type
-
NA
-
LCD Contrast
-
5
-
Auto/Man Ctrl
-
Auto
Auto ,Manual
Network Detect
-
Yes
-
Clear PeakPower
-
No
Yes, No
Clr ATS Alarm
-
No
No, Yes
Clr D.G.Fault
-
No
-
E04A_D(01-08)
-
Open
Open, Close
Smoke 1 Reset
-
Yes
-
BC/FC Ctrl
-
Float Charge -
Float Charge, Boost Charge
Battery Test
-
Stop
Stop, Start
Reset Batt Cap
-
Yes
-
Clear Batt Alm
-
Yes
-
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
100
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
Main Menu
Second-Lev el Menu
Third-Level Menu
Fourth-Le vel Menu
Default Value
Range
Short Test
-
Stop
Stop, Start
LLVD1 Control
-
Connect
Connect, Disconnect
BLVD Control
-
-
-
Current Limit
-
121%
1~121%
DC Votage Ctrl
-
53.2V
42.0~58.0 V
On/Off Control
-
On
On,Off
Reset
-
Yes
-
Clear Rect Lost
-
Yes
-
Clr Phase Fail
-
Yes
-
PSU
-
-
-
-
Clr Alm Hist
-
-
-
-
Qty of Battery
-
-
1
0-50
Rated Capacity
-
-
100 Ah
10 Ah-10000Ah
Set Date
-
-
-
-
Set Time
-
-
-
-
IP Address
-
-
-
-
Subnet mask
-
-
-
-
Gateway
-
-
-
-
PSU Summary
Quick Settings
B LCD Menu
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
101
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
C
C Acronyms and Abbreviations
Acronyms and Abbreviations
A AC PDU
Alternating Current Power Distribution Unit
ASIC
Application-Specific Integrated Circuit
ATS
Automatic Transfer Switch
D DC PDU
Direct Current Power Distribution Unit
E EMS
Element Management System
I IEC
International Electrotechnical Commission
L LED
Light Emitting Diode
LSI
Large-scale Integration
O OPEX
Operational Expenditure
P PDU
Power Distribution Unit
PMU
Power Monitoring Unit
Issue 01 (2012-06-01)
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
102
TP48200T-D20A1 & D20A2 & D14A1 & D14A2 User Manual
C Acronyms and Abbreviations
S SELV
Safety Extra-low Voltage
T TCU
Issue 01 (2012-06-01)
Temperature Control Unit
Huawei Proprietary and Confidential Copyright © Huawei Technologies Co., Ltd
103