Z1: MITSUBISHI NC (TV-300, (TV-300, 400)
This se section tion deals deals with the configuratio nfiguration n of the the ladd ladder diag diagram ram,, differe ifferenc nce es from from the F AN U C NC, N C, and other ther fre fr equentl quently y aske asked d questions questions abo about the M I T SUBI SU BI SHI SH I N C for TV T V -300 and TV TV -400. -400. Refer to the secti sectio on indi i ndica cated ted bel bel ow to find find the answer answer to to each question. Classification of Questions I tem
Questi Questio ons
Z1 - 1
N C soft software ware l oading adin g method method
Z1 - 2
GOP GO P softwar software e l oadi oading ng method method
Z1 - 3
I nput / output method method using usi ng RS-232 RS -232C C i nterface nterf ace connec connector tor
Z1 - 4
Sequenc Sequence e data i nput / output method method using usi ng RS-232C i nterface nterf ace connector
Z1 - 5
I nput / output method method using usi ng memo memorr y car car d
Z1 - 6
Sequence Sequence data i nput / output meth method od using usi ng memo memorry card
Z1 - 7
P arame arameter ter sett settii ng method method
Z1 - 8
Displayed Di splayed ver version sion data
Z1 - 9
Address Addresse es of M I TSU BI SHI SH I N C
Z1 - 10
Configu Configuration ration of PL C-I /F scre scree en for for M I TSU BI SHI SH I N C
Z1 - 11
Config Confi gurati ur atio on of l adde adder diagram
Z1 - 12 Z1 - 13 Z1 - 14 Z1 - 15 Z1 - 16 Z1 - 17 Z1 - 18 Z1 - 19 Z1 - 20
Z1 (3/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 1.
NC SOFTWARE LOADING METHOD
NC software loading may become necessary if the NC malfunctions or software enhancement is required. NC software loading requires the NC software memory card and the IC card holder. The method is described below. 1) Connect the I C card holder to the NC board after switching off the NC power.
2) I nsert the main program software I C card into the I C card holder. 3) Set the rotary switch CS2 on the NC board (FCA50MM) to "B". Enlarged view of N C board (near 7-segment L EDs) L ED
LED
B CS1
CS2
Z1 (4/36)
SW1
SW2
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
4) Switching on the power automatically starts wri ting the program from the I C card to the F ROM . Data in the FROM cassette is being deleted: Er Data is being wri tten into the FROM cassette: Pr Writing into the F ROM cassette is successful: 07 Writing into the FROM cassette is not successful: −7 Writing into the FROM cassette takes approx. 1 minute after the power is switched on. 5) Remove the I C card after switching off the power. I f wri ting into the F ROM cassette is successful, return the setti ng of the rotary switch CS2 to "0".
Z1 (5/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 2.
GOP SOFTWARE LOADING METHOD
GOP software loading may become necessary if the GOP malfunctions or software enhancement is required. GOP software loading requires the GOP memory card. 1) I nsert the memory card into the card slot on the right side of the operation panel after switching off the NC power. The machining centers shipped around December of 1997 or later have a card slot for the memory card on the right side of the GOP panel. 2) Switch on the power by pressing the first and tenth square contact positions from the top in the leftmost column on the GOP-2 screen simultaneously.
MORI
SEIKI
msc-802
3) The indicator above the cycle start switch lights upon the start of wri ting to the ROM. 4) The indicator above the cycle start switch turns off in approx. 1 minute. The machine ready indicator and the chuck clamp indicator light upon completion of writing to the ROM. 5) Remove the memory card from the card slot after switching off the power. See "Z2: GOP".
Z1 (6/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 3.
INPUT / OUTPUT METHOD USING RS-232C INTERFACE CONNECTOR
The method of inputting / outputting programs, etc. using external I/O devices such as the data store is described below. 1) Check the settings of the communication parameters. The communication parameters are classified into "DATA IN", "DATA OUT ", "TAPE MODE ", etc. by use. Determine the I/O device for each use on the screen below. One of the five values from "0" to "4" can be set for DE V. NO.
Set the communication parameters including the baudrate and the stop bit for each DEV. NO.
Z1 (7/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
2) Display the GOP PARAM ETE R screen and cancel the WRI TE PROTE CT setting.
3) Display the DATA INP UT / DATA OUT PU T screens. To transfer a program under Nos. O9000 to O9999, it is necessary to set "0" for parameters #1121 and #1122. Check whether the WRI TE PROTE CT switch is ON or OFF at the field. A program under Nos. O9000 to O9999 cannot be transferred when "C" is displayed at the field for the main program. I n this case, change the settings of the above parameters. Also check the device name and the baudrate at #12 DE VI CE NO. I nput data on the screen shown below.
The status of the WRITE PROTECT switch is displayed.
Z1 (8/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
The screen shown below is used to output the data.
4) Select the data input / output item. Normally, key in a code number of the desired data item shown in the screen above in #( ). To output the main program, key in the corresponding data indicated below. - To output only one program #(1) DATA (O number) - To output all programs #(1) DATA (AL L ) - To output the specified range of a program #(1) DATA (the beginning of the specifi ed O number) (the end of the specifi ed O number) 5) Check if the communication cable is correctly connected to the external I /O device and the RS-232C interface connector on the right side of the operation panel. The front of the operation panel has two types of RS-232C interface connector, "NC" and "GOP ". Connect the cable to the connector "NC". After checking the communication cable is connected correctly, prepare the external I /O device to transfer the data.
NC
GOP Conversational program
Main program
Offset data
Conversational programming parameters, etc.
Sequence data, etc.
See "Z2: GOP".
Parameters
Z1 (9/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 4.
SEQUENCE DATA INPUT / OUTPUT METHOD USING RS-232C INTERFACE CONNECTOR
The method of inputting / outputting sequence data and alarm messages using external I /O devices such as the data store is described below. 1) Check the settings of the communication parameters. See the previous i tem. 2) Press the emergency stop button. (Failure to press this button may cause the axis influenced by gravitation to move down.) 3) Display the OPE N SET UP PARAM screen.
4) Press the Y key and the INPUT key. 5) Press the menu selection key F2 (PL C), and press the page selection key four times. 6) Set "0" for bit 2 of #6451.
Z1 (10/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
7) Display the GOP PARAM ETE R screen and cancel the WRI TE PROTE CT setting. (The WRI TE PROTECT setting is canceled when the key symbol disappears from the screen.)
8) Press the function selection key F 0 . 9) Press the menu selection key F3 (FI LE ). 10) Press the menu selection key F4 (4RUN / SP), and press the 1 key and the INPUT key to stop the PL C.
Z1 (11/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
CAUTI ON: If "DATA PROTECTI NG" is displayed when executing the PL C stop operation, it indicates that "1" remains set for bit 2 of PL C parameter #6451, for which setting of "0" is specifi ed in 6). I n thi s case, set "0". I f the PL C stop operation is executed before canceling the WRI TE PROTECT setting, "DATA PROTECTING" is displayed when keying in data on the PL C-I /F screen for input / output operation which is described in the next item, disabling the input / output operation. I n this case, return the PL C to the RUN state on the screen shown in 10), and execute the PL C stop operation again before the input / output operation. 11) To input / output the sequence data, display the DATA I NPUT / DAT A OUTPUT screens, respectively. < Example > Use the screen shown below to input the data.
Z1 (12/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
12) Prepare the data store for sending / receiving data as follows. Connect the RS-232C cable to the connector marked with "NC" on the name plate. Check if the setting of the communication parameters, including the baudrate and the stop bit, at the data store (F-30) is as specifi ed below. The following are standard settings. After matching the parameter settings between the data store and the machine, place them in the transfer standby state. To input / output the sequence data To output the message SPE ED 4800 S-BIT 2 CODE I SO DC3 93H EOB (I SO) CRLF %OUT (T) YES %OUT (B) YES
To input the message (∗.MES) To input the message (∗.MNT) SPE ED 4800 S-BIT 2 CODE ASC DC3 93H EOB (I SO) LF %OUT (T) NO %OUT (B) YES
The names of files to be transferred are as follows. Sequence data: ∗∗∗??LNK.DAT ∗∗∗??LNK.MNT Message: ∗∗∗??? (EN , FR, GE, I T, J A, SP). ME S ∗∗∗??? (EN , FR, GE, IT , J A, SP). MNT The extensions for the ladder diagrams include ∗.DAT and ∗.MNT, and those for the messages include ∗.MES and ∗.MNT. NOTE 1 • ∗.MNT @
.DAT• C ∗.MNT
∗
@ .DAT • ∗
Data store NOTE 2 ∗.MES• C ∗.MNT
@ .MNT •
(Sequence data)
@ .MNT • ∗
NC
Memory card @ .MNT • ∗
(Message)
∗
@ .MNT • ∗
NOTE 1: L oading of files with the extension ∗.DAT using the memory card requires changing the extension to ∗.MNT. NOTE 2: L oading of files with the extensions ∗.MES and ∗.MN T requires different settings of the parameters for the data store. Refer to the above standard settings of the parameters.
Z1 (13/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
"∗∗∗" indicates the three least significant digits of the ladder diagram Nos. 184∗∗∗ and 182∗∗∗. Both "??" and "???" indicate the version. < Example > ∗∗∗ = 012 (TV-300, 400 <10, 12 tools>) 20 tools>) ∗∗∗ = 226 (TV-300, 400 < Sequence: ?? = A1 (two characters) Message: ??? = A01 (three characters) 13) Send / receive the sequence data or the message as follows. K ey in the following values in #( ) DATA ( ) at the bottom of the DATA I NPU T / DATA OU TP UT screens, and press the INPUT key. #( ) DAT A ( ) I nput of the sequence data #(99) DATA ( 250) Output of the sequence data #(99) DATA ( 250) I nput of the message [∗.ME S] #(98) DAT A ( ) I nput of the message [∗.MNT] #(99) DATA ( 270) Output of the message #(99) DATA ( 270) 14) If sending / receiving of the sequence data or the message is successful, "DATA I NP UT COMP L ET E" or "DATA OUTPUT COMP L ETE " is displayed. 15) Press the function selection key OF FSE T/PARAM . . 16) Press the menu selection key F2 (PL C), and press the page selection key four times. 17) Reset "1" for bit 2 of #6451.
18) Switch off the NC power once and switch it on again. (Switching on the NC power automatically places the PL C and the WRI TE PROT ECT setting in the RUN state and the write protect on state, respectively.)
Z1 (14/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
19) I f the sequence data or the alarm message has been transferred, display the S/W MODU L E TRE E screen to check the version.
Check if the version of the sequence data or the alarm message is correct, referring to the following. PL Cu: Sequence data version PL Ce: Alarm message data version (alarm language)
Z1 (15/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 5.
INPUT / OUTPUT METHOD USING MEMORY CARD
The method of inputting / outputting programs, etc. using the memory card is described below. 1) Display the GOP PARAM ETE R screen and cancel the WRI TE PROTE CT setting.
2) Display the MEMORY CARD screen.
Z1 (16/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Use keys
and
to select the menu.
3) Select the item to be input / output from . 4) The names of the files in the memory card are displayed. To input a fil e, select the file to be input using the cursor control keys on the NC operation panel. The names of the files in the memory card are displayed.
The names of the files in the NC memory are displayed. To output a file, select the file to be output using the cursor control keys on the NC operation panel. To output all files in the NC memory, key in (desired file name.PRG) (ALL ). The names of the files in the NC memory are displayed.
To output the offset data or the parameters, key in the file name.
Z1 (17/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
5) After keying in the file name using the data entry keys, pressing the START / STOP soft-key starts the input / output of the file. [ Supplemental remarks ] Each file name has an extension. I f "PROGRAM " is selected to transfer a file, only the file names with the extension "∗.PRG" in the memory card are displayed.
Only the names of the files with the extension "∗.PRG" in the memory card are displayed.
Therefore, if files have been created for programs, etc. on external devices such as a personal computer and the files are to be transferred using the memory card, use the extensions corresponding to the files as indicated below. Otherwise, the file names wil l not be displayed, disabling the input operati on. File
Extension
Program
∗
Offset data
∗
Common variable
∗
Parameter
∗
Maintenance data
∗
. PRG . OFS . CMN . PRM . MNT
The drawing Nos. for the memory card are as follows. 512 K B: E51019A01 1 MB: E51020A01 2 MB: E51021A01
Z1 (18/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 6.
SEQUENCE DATA INPUT / OUTPUT METHOD USING MEMORY CARD
The method of inputting / outputting sequence data and alarm messages using the memory card is described below. 1) Press the emergency stop button. (Failure to press this button may cause the axis influenced by gravitation to move down.) 2) Display the OPE N SET UP PARAM screen.
3) Press the Y key and the INPUT key. 4) Press the menu selection key F2 (PL C), and press the page selection key four times. 5) Set "0" for bit 2 of #6451.
Z1 (19/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
6) Display the GOP PARAM ETE R screen and cancel the WRI TE PROTE CT setting. (The WRI TE PROTECT setting is canceled when the key symbol disappears from the screen.)
7) Press the function selection key F 0 . 8) Press the menu selection key F3 (FI LE ). 9) Press the menu selection key F4 (4RUN / SP), and press the 1 key and the INPUT key to stop the PL C.
Z1 (20/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
CAUTI ON: If "OPERATI ON ERROR" is displayed when executing the PL C stop operation, it indicates that "1" remains set for bit 2 of PL C parameter #6451, for which setting of "0" is specifi ed in 5). I n thi s case, set "0". 10) Display the MEMORY CARD screen. I nput / output data on the screen shown below.
The names of files to be transferred are as follows. Sequence data: ∗∗∗??LNK.DAT ∗∗∗??LNK.MNT Message: ∗∗∗??? (EN , FR, GE, I T, J A, SP). ME S ∗∗∗??? (EN , FR, GE, IT , J A, SP). MNT The extensions for the ladder diagrams include ∗.DAT and ∗.MNT, and those for the messages include ∗.MES and ∗.MNT. NOTE • ∗.MNT @
C ∗.MNT .DAT•
∗
@ .DAT • ∗
(Sequence data)
@ .MNT • ∗
NC
Data store
@ .MNT •
C ∗.MNT .MES•
∗
@ .MNT •
Memory card ∗
(Message)
∗
@ .MNT • ∗
NOTE: L oading of files with the extension ∗.DAT using the memory card requires changing the extension to ∗.MNT.
Z1 (21/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
"∗∗∗" indicates the three least significant digits of the ladder diagram Nos. 184∗∗∗ and 182∗∗∗. Both "??" and "???" indicate the version. < Example > ∗∗∗ = 012 (TV-300, 400 <10, 12 tools>) 20 tools>) ∗∗∗ = 226 (TV-300, 400 < Sequence: ?? = A1 (two characters) Message: ??? = A01 (three characters) 11) Send / receive the sequence data or the message as follows. K ey in the following values in #( ) DATA ( ) at the bottom of the DATA I NP UT / DATA OUTPU T screens. #( ) DAT A ( ) I nput of the sequence data #(selected file name) DATA ( 250) Output of the sequence data #(desired file name) DATA ( 250) I nput of the message #(selected file name) DATA ( 270) Output of the message #(desired file name) DATA ( 270) 12) After keying in the file name using the data entry keys, pressing the START / STOP soft-key starts the input / output of the file. 13) If sending / receiving of the sequence data or the message is successful, "DATA I NP UT COMP L ET E" or "DATA OUTPUT COMP L ETE " is displayed. 14) Press the function selection key OFFSET/PARAM. . 15) Press the menu selection key F2 (PL C), and press the page selection key four times. 16) Reset "1" for bit 2 of #6451.
Z1 (22/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
17) Switch off the NC power once and switch it on again. (Switching on the NC power automatically places the PL C and the WRI TE PROT ECT setting in the RUN state and the write protect on state, respectively.) 18) I f the sequence data or the alarm message has been transferred, display the S / W M ODU L E TRE E screen to check the version.
Check if the version of the sequence data or the alarm message is correct, referring to the following. PL Cu: Sequence data version PL Ce: Alarm message data version (alarm language)
Z1 (23/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 7.
PARAMETER SETTING METHOD
The TV-300 and TV-400 series (MSC-802) use the MI TSU BI SHI NC with a different configuration of the screens from that of the FANUC NC. Different parameters such as SE RVO and PC parameters are set on different screens. Therefore, the screen appropriate for the parameters to be set needs to be displayed. Failure to perform the following operations prevents the screens from being displayed to protect the setting from operational errors. Z1 - 7 - 1.
PARAMETER SETTING ITEMS
Different screens need to be displayed for different parameter #to be set. Also, the parameter #to be set needs to be displayed using the page selection key with the corresponding screen displayed, for lack of the parameter #search function. Parameter setting items are classified as follows. - BASE #1001 to #1999 - AXI S #2001 to #2119 - SE RVO #2201 to #2999 - SPI NDL E #3001 to #3999 - MC-E RR #4001 to #5124 - PL C #6000 to #6496 #6000 to #6015 10 msec timer #6010 to #6095 100 msec timer #6096 to #6103 100 msec timer #6200 to #6223 Counter #6301 to #6348 Data table #6401 to #6496 PL C parameters - MACRO #7001 to #7313 - PSW #7501 to #7573 - PROCESS #8001 to #8306 - I /O PAR #9001 to #9530 Normally, only "PROCESS" and "I/O PAR" are displayed. To display other items, display the OPEN SETUP PARAM screen and press the Y key and the INPUT key, as described in the next item.
Z1 (24/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 7 - 2.
PARAMETER CHANGING PROCEDURE
The procedure for changing the parameter settings is described below. 1) Display the OPE N SET UP PARAM screen.
2) Press the Y key and the INPUT key, and the BASE SPEC. PARAM screen is displayed.
Z1 (25/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
3) After performing the above operation, press the menu selection key (MENU) to select the parameter to be changed.
F5
4) After selecting the parameter to be changed, press the page selection key repeatedly until the desired parameter #is displayed. K ey in parameter #and the desired setting value in the data entry fields, #( ) DATA ( ), respectively, then press the INPUT key.
For the PL C parameters, key in parameter #and only the bit to be changed in the data entry fields, #( ) DATA ( ), respectively. Pressing the INPUT key completes the setting.
Z1 (26/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 8.
DISPLAYING VERSION DATA
To check the version data of the TV-300 or TV-400 series (MSC-802), display the S/W MODU L E TREE screen.
MP: NC version PL Cu: L adder diagram version (sequence data) PL Ce: L adder diagram version (alarm message) To check the version data of the GOP software, display the GOP PARAM ETE R screen.
Please check the version before contacting the Development Department at MORI SEI K I , or M itsubishi Electric.
Z1 (27/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 9.
MITSUBISHI NC ADDRESSES
Addresses used in ladder diagrams are described below. Two kinds of addresses, bit-unit addresses (X, Y, M, G, and E) and byte-unit addresses (D and R), are used. Timers and counters (T, Q, and C) are used in units of bit as a contact, but count data is stored in units of byte. Since addresses are categorized into bit-unit and byte-unit addresses, there is no bit address such as R104.0, which is used with F AN UC. (For example, while address "R" can be in either bits or bytes for F ANUC, i t can only be in bytes for the MI TSU BI SH I . Therefore, it is necessary to copy data from byte-unit address "R" to a bit-unit address to check which bit of address "R" is ON in the sequence. On the PL C-I /F screen, data in addresses is displayed in 16 bits.) The addresses of the MI TSU BI SHI NC are compared with those of the FAN UC NC below. Signal Name Input signal
FANUC X
MITSUBISHI
Unit
Use
X0 to XF F
bit
Machine side input signals
X100 to X13F
bit
Operation panel input signals 1
R80 to R83
byte
Operation panel input signals 2 (In ladder diagrams, data is transferred from byte-unit addresses R80 to R83, to internal relay bit-unit address "G".)
Output signal
Y
Y0 to YFF
bit
Machine side output signals
Y100 to Y13F
bit
Operation panel output signals 1
byte
Operation panel output signals 2
R180 to R183
(In ladder diagrams, data is transferred from byte-unit addresses R180 to R183 to internal relay bit-unit address "G".) NC• ¨ PC
NC• ©PC
F
G
X140 to X15F
bit
PL C switches
X180 to X27F
bit
NC side status indication
R0 to R99 Y160 to Y17F Y180 to Y2FF
byte bit bit
R100 to R199
byte
NC side status indication PL C switches Operation instructions to the NC side Operation instructions to the NC side
Z1 (28/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Signal Name FANUC Internal R relay
MI TSUBISHI M0 to M5119
Unit bit
G0 to G3071
K eep relay
K
R2900 to R2923
byte
Data table
D and R
R2801 to R2895
byte
D0 to D1023
byte
R500 to R549
Timer
Counter
R1900 to R2799
byte
T0 to T95
byte
FTM
Q0 to Q135
byte
C
C0 to C23
byte
TM R
Z1 (29/36)
Use I nternal relays Address "M" is used as an internal relay. Address "G" is used as the destination for sending the alarm output address and also the byteunit data after converting it into the bit-unit data. K eep relays Data is set for #6401 to #6448 on the parameter [BIT SELECT] screen. I n ladder diagrams, data is transferred from byte-unit addresses R290 to R2923 to bitunit address G0 to G399. For details, see the LADDER DIAGRAM [ADDIT IONAL MATERIALS]. Data tables Data is set for #6301 to #6348 on the parameter [PL C DAT A] screen. I n ladder diagrams, the data remain in these addresses. Registers (not backed up) I n ladder diagrams, these addresses are directly used. Registers (backed up) I n ladder diagrams, these addresses are directly used. Variable timers T0 to T15 = 10 msec T16 to T95 = 100 msec Data is set for #6000 to #6095 on the parameter [PLC TIMER] screen. Fixed timers Q0 to Q39 = 10 msec Q40 to Q135 = 100 msec The settings of these timers cannot be changed. Counters
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 10.
CONFIGURATION OF MITSUBISHI NC PLC-I/F (SELF-DIAGNOSIS DATA) SCREEN (IN HEXADECIMAL NOTATION)
The ladder diagram is often referred to in order to check the status of the machine when trouble occurs or when performing maintenance. The PL C-I/F screen is available for the MI TSU BI SHI NC, as well as the FAN UC NC. Characteristics of each type of address are described below. 1) Display the PL C-I /F screen.
2) K ey in an address to be checked in the device field, and press the INPUT key. The screen has two DEVI CE fields. K eying in two addresses in these DEVI CE fields allows these addresses to be checked simultaneously. 3) I f a bit device is selected, 8 points including the address keyed in are displayed on the first li ne. The address displayed in the leftmost position is the address of bit 0. The address keyed in is in the corr esponding bit, with the bits arranged in the ascending order from the right. I f a byte device is selected, 16 bits are split on two lines, with the high-order and low-order bits displayed on the upper and lower lines, respectively.
Z1 (30/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Data in different types of address are displayed differently, as follows. (1) Data in bit-unit addresses 1 Bit-unit addresses such as X and Y are in hexadecimal notation. The leading address on each line starts with "0" or "8". "0" to "7" are displayed on the lines on which the leading addresses start with "0", while "8" to "F" are displayed on the lines on which the leading addresses start with "8". For example, the PL C-I /F screen is shown below when "X14" and "Y2E" are entered in the left and right DEVI CE fields, respectively.
"X14" is in bit 4 on the li ne with the leading address "X10", and "Y2E" is in bit 6 on the line with the leading address "Y28". (2) Data in bit-unit addresses 2 Bit-unit addresses such as M and G are in decimal notation. For example, the PL C-I /F screen is shown below when "M1414" is entered in the left DEVICE field.
"M1414" is in bit 6 on the line with the leading address "M1408".
Z1 (31/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
(3) Data in byte-unit addresses Byte-unit addresses such as D and R are in hexadecimal notation. For example, the PL C-I /F screen is shown below when "R156" is keyed in the left DEVI CE field.
High-order bits "8" to "F" and low-order bits "0" to "7" are displayed on the upper and lower lines for R156, respectively. (4) Set values of the counter The preset and present values of the counter can be checked on the PL C-I /F screen. The preset and present values are displayed at "counter No. + 2000" and "counter No. + 3000", respectively.
The preset and present values of counter No. 1 are "25" and "1", respectively.
Z1 (32/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
Z1 - 11.
HOW TO DISPLAY LADDER DIAGRAM
The ladder diagram is often called out in order to check the status of the machine when trouble occurs or when performing maintenance. The method of displaying the ladder diagram is described below. 1) Press the function selection key F 0 .
2) Press the menu selection key F4 (LADDER). 3) Press the menu selection key F2 (2CIRCUT).
Z1 (33/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
4) Press the menu selection key F5 (ME NU ). 5) Press the menu selection key F2 (6MONIT). 6) Press the menu selection key F5 (ME NU ). 7) Press the menu selection key F1 (
).
8) K ey in an address to be checked and press the INPUT key. For example, the screen shown below will be displayed when "M772" is keyed in.
Contact number
9) To check conti nuous circuit blocks, press the menu selection key F1 (9SET). 10) K ey in the contact number of the address to be checked and press the INPUT key. To check the continuous circuit blocks of "M772", key in the contact number "188".
Z1 (34/36)
TROU BL ESHOOTI NG (Z1: MI TSU BI SHI NC) I 74115A01E
As shown above, the ladder diagram can be called out in two modes: the search mode in which searching for the desired address is possible and the setting mode in which continuous circuit blocks can be monitored. I n the search mode, specifi ed circuit blocks that are not conti nuous can be displayed block by block on one screen. For example, how the ladder diagram is used when "M895" does not turn on. The diagram indicates that "M804" needs to turn on for "M895" to turn on, and that "X133" needs to turn on for "M804" to turn on.
K ey in the address in the MON I T mode to search for the coil .
I n the setting mode, key in a contact number to display the ladder diagram. To advance to the next page or to return to the previous page, key in "+" or " −", and press the INPUT key.
K ey in a contact number i n the MONI T mode to display the ladder diagram.