EDMY041427
Split Type Air Conditioners - Cooling Only FTKC-N Series
EDMY041427
Cooling Only
1. 2. 3. 4.
FTKC25NVMM FTKC35NVMM FTKC50NVMM FTKC60NVMM
RKC25NVM RKC35NVM RKC50NVM RKC60NVM
Power Power Supply Supply ............... ....................... ................ ................ ................ ................ ............... ............... ................ ................ ............2 ....2 Functions.. Functions.......... ............... ............... ................ ................ ............... ............... ................ ................ ................ ............... ................ ..........3 .3 Specificat Specifications ions........ ............... ............... ................ ................ ................ ............... ................ ................ ............... ................ ............4 ....4 Dimension Dimensions s ............... ....................... ............... ................ ................ ............... ................ ................ ................ ............... ...............6 ........6 4.1 Indoor Indoor Unit............... Unit..................... ............. .............. ............. ............. .............. ............. .............. .............. ............. .............. ............. .......6 .6 4.2 Outdoor Outdoor Unit................... Unit......................... ............. .............. .............. .............. .............. .............. .............. .............. .............. ............7 .....7
5. Wiring Wiring Diagrams...... Diagrams............. ............... ................ ................ ............... ................ ................ ............... ................ ................ ..........8 ..8 5.1 Indoor Indoor Unit............... Unit..................... ............. .............. ............. ............. .............. ............. .............. .............. ............. .............. ............. .......8 .8 5.2 Outdoor Outdoor Unit................... Unit......................... ............. .............. .............. .............. .............. .............. .............. .............. .............. ............9 .....9
6. Piping Piping Diagrams............ Diagrams.................... ................ ............... ................ ................. ................ ................ ................ ................1 ........10 0 6.1 Indoor Indoor Unit............... Unit..................... ............. .............. ............. ............. .............. ............. .............. .............. ............. .............. ............10 .....10 6.2 Outdoor Outdoor Unit................... Unit......................... ............. .............. .............. .............. ............. ............. .............. ............. ............. ............11 .....11
7. Capacity Capacity Tables ................ ........................ ............... ............... ................ ................ ................ ................ ............... .............13 ......13 7.1 Cooling Cooling Only.............. Only.................... ............. .............. .............. ............. ............. .............. ............. ............. .............. .............. ..........13 ...13 7.2 Capacity Capacity Correc Correction tion Factor Factor by the the Length Length of Refrige Refrigerant rant Piping Piping (Reference) ..................................................... ............................................................................................ .......................................15 15
8. Operation Operation Limit................... Limit........................... ............... ............... ................ ................ ............... ................ ................. ............16 ....16 9. Sound Sound Level Level ............... ....................... ............... ............... ................ ................ ................ ................ ................ ................ ............17 ....17 9.1 Measurin Measuring g Location............. Location................... ............. .............. ............. ............. .............. ............. .............. ............... .............17 ......17 9.2 Indoor Indoor Unit............... Unit..................... ............. .............. ............. ............. .............. ............. .............. .............. ............. .............. ............17 .....17 9.3 Outdoor Outdoor Unit................... Unit......................... ............. .............. .............. .............. ............. ............. .............. ............. ............. ............18 .....18
10.Electric Characteristics..........................................................................19 11.Installation Manual ................................................. ...................... ..................................................... ...............................20 .....20 11.1 25/35 25/35 Class Class ............. .................... ............. ............. .............. .............. .............. .............. .............. .............. ............. ............. ...........20 ....20 11.2 50/60 50/60 Class Class ............. .................... ............. ............. .............. .............. .............. .............. .............. .............. ............. ............. ...........30 ....30
12.Operation Manual..................................................................................40 13.Optional Accessories .................................................. .......................... .................................................. ..........................65 65 13.1 Option List .................................................... .............................................................................................. ..........................................65 65 13.2 Air Direction Direction Adjustment Grille........................................ 66 13.3 Air Direction Direction Adjustment Grille........................................ 67
Split Type Air Conditioners FTKC-N Series
1
Power Supply
EDMY041427
1. Power Su Supply
Note:
2
Indoor Unit
Outdoor Unit
FTKC25NVMM
RKC25NVM
FTKC35NVMM
RKC35NVM
FTKC50NVMM
RKC50NVM
FTKC60NVMM
RKC60NVM
Power Supply 1 phase, 220 - 230 - 240 V, 50 Hz 1 phase, 220 - 230 V, 60 Hz
Power Supply Intake ; Outdoor Unit
Split Type Air Conditioners FTKC-N Series
EDMY041427
Functions
2. Functions Category
Basic Function
Functions
Inverter (with inverter power control) Operation limit for cooling (°CDB) Operation limit for heating (°CWB)
Compressor
Comfortable Airflow
Comfort Control
Operation
Lifestyle Convenience
Note:
M M M M M V M V V N V N N 5 0 N 5 0 3 6 / 3 / 6 5 / 0 / 2 5 5 0 2 C 5 C C K C K K T T K F R F R
19.4 19.4 ~ 46 ~ 46
Category
Health & Clean
Functions
M M M M M V M V V N V N N 5 0 N 5 0 3 6 / 3 / 6 5 / 0 / 2 5 5 0 2 C 5 C C K C K K T T K F R F R
Air-purifying filter
—
—
Photocatalytic deodorising filter
—
—
Air-purifying filter with photocatalytic deodorising function
—
—
—
—
PAM control
Standby electricity saving
—
Titanium apatite photocatalytic air-purifying filter
Oval scroll compressor
—
—
Air filter (prefilter)
Swing compressor
Wipe-clean flat panel
Rotary compressor
—
—
Washable grille
—
—
Reluctance DC motor
MOULD PROOF operation
—
—
Power-airflow flap
—
Heating dry operation
—
—
Power-airflow dual flaps
—
Good-sleep cooling operation
—
—
WEEKLY TIMER operation
Power-airflow diffuser
—
—
—
—
Wide-angle louvres
Timer
24-hour ON/OFF TIMER
Auto-swing (up and down)
NIGHT SET mode
Auto-swing (right and left)
—
—
Auto-restart (after power failure)
3-D airflow
—
—
Self-diagnosis (digital, LED) display
COMFORT AIRFLOW operation
—
Wiring error check function
—
—
Auto fan speed
Indoor unit quiet operation
Anti-corrosion treatment of outdoor heat exchanger
NIGHT QU QUIET mo mode (a (automatic)
—
—
—
—
OUTDOOR UNIT QUIET operation (manual)
Multi-split / split ty type co compatible in indoor unit
—
Flexible power supply correspondence
INTELLIGENT EYE operation
—
—
Chargeless
Quick warming function
—
—
Either side drain (right or left)
Hot-start function
—
—
Automatic defrosting
—
—
Automatic operation
—
—
Programme dry operation
Fan only
New POWERFUL operation (non-inverter)
—
—
Inverter POWERFUL operation
Priority-room setting
—
—
COOL / HEAT mode lock
—
—
HOME LEAVE operation
—
—
ECONO operation
Indoor unit ON/OFF button
Signal receiving sign
R/C with back light
—
—
Temperature display
—
—
Worry Free (Reliability & Durability)
Flexibility
Remote Control
Remote Controller
10 m 10 10 m
Power selection
—
—
5-room centralised controller (option)
—
—
Remote control adaptor (normal open pulse contact) (option)
—
—
Remote control adaptor (normal open contact) (option)
—
—
DIII-NET co compatible (a (adaptor) (o (option)
—
—
Wireless
Wired
—
—
: Available — : Not available
Split Type Air Conditioners FTKC-N Series
3
Specifications
EDMY041427
3. Spec Specif ific icat atiions ons 50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V Model
Indoor Unit Outdoor Unit
Moisture Removal Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) COP (Rated) Liquid Piping Connections Gas Drain Heat Insulation Max. Interunit Piping Length Max. Interunit Height Difference Chargeless Amount of Additional Charge of Refrigerant Indoor Unit Front Panel Colour H M Airflow Rate L SL Type Fan Fan Motor Output Speed Air Direction Control Air Filter Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) Temperature Control Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H / M / L / SL Level Outdoor Unit Casing Colour Type Compressor Model Motor Output T ype Refrigerant Oil Charge Type Refrigerant Charge
20
20
mm mm kg kg
FTKC25NVMM Shiny Pure White 9.0 (318) 6.7 (237) 4.4 (155) 3.5 (124) Cross Flow Fan 16 5 Steps, Quiet, Auto Right, Left, Horizontal, Downwards Removable / Washable / Mildew Proof 0.19 - 0.18 - 0.17 / 0.19 - 0.18 39 93.3 - 94.2 - 95.6 / 93.3 - 94.2 Microcomputer Control 283 × 770 × 203 263 × 840 × 344 8 10
FTKC35NVMM Shiny Pure White 9.2 (324) 6.9 (244) 4.6 (162) 3.6 (127) Cross Flow Fan 16 5 Steps, Quiet, Auto Right, Left, Horizontal, Downwards Removable / Washable / Mildew Proof 0.27 - 0.26 - 0.24 / 0.27 - 0.26 57 96.0 - 95.3 - 99.0 / 96.0 - 95.3 Microcomputer Control 283 × 770 × 203 263 × 840 × 344 8 10
dB(A)
38 / 33 / 25 / 22
39 / 34 / 26 / 23
W
RKC25NVM Ivory White Hermetically Sealed Swing Type 1YC25BXD 860 FW68DA 0.350 R-32 0.5
RKC35NVM Ivory White Hermetically Sealed Swing Type 1YC25BXD 860 FW68DA 0.350 R-32 0.7
27.1 (957)
27.1 (957)
W A W % A mm mm kg kg
Propeller 20 3.21 - 3.12 - 2.93 / 3.21 - 3.12 661 93.6 - 92.1 - 94.0 / 93.6 - 92.1 2.5 550 × 658 × 275 616 × 788 × 359 28 32
Propeller 20 4.33 - 4.14 - 3.96 / 4.33 - 4.14 933 97.9 - 98.0 - 98.2 / 97.9 - 98.0 2.5 550 × 658 × 275 616 × 788 × 359 32 34
dB(A)
47 - 48 - 48 / 49 - 50
49 - 49 - 50 / 49 - 50
3D089134A
3D089135A
m³/min (cfm)
W Steps
A W %
L kg m³/min (cfm)
H
Type Fan Fan Motor Output Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) Starting Current Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H Level Drawing No.
Note:
g/m
kW Btu/h kcal/h L/h A W % W/W mm mm mm
Capacity Rated (Min. ~ Max.)
Airflow Rate
m m m
FTKC25NVMM RKC25NVM 2.5 (1.2 ~ 3.4) 8,500 (4,100 ~ 11,600) 2,150 (1,030 ~ 2,920) 1.2 3.4 - 3.3 - 3.1 / 3.4 - 3.3 700 93.6 - 92.3 - 94.1 / 93.6 - 92.3 3.57 φ 6.4 φ 9.5 φ 16.0 Both Liquid and Gas Pipes 15 12 10
The data are based on the conditions shown in the table below. Cooling Piping Length
Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB / 24°CWB
4
7.5 m
FTKC35NVMM RKC35NVM 3.5 (1.3 ~ 4.1) 11,900 (4,400 ~ 14,000) 3,010 (1,120 ~ 3,530) 1.9 4.6 - 4.4 - 4.2 / 4.6 - 4.4 990 97.8 - 97.8 - 98.2 / 97.8 - 97.8 3.54 φ 6.4 φ 9.5 φ 16.0 Both Liquid and Gas Pipes 15 12 10
Conversion Formulae kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35.3
Split Type Air Conditioners FTKC-N Series
EDMY041427
Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V Model
Indoor Unit Outdoor Unit
g/m
20
20
mm mm kg kg
FTKC50NVMM Shiny Pure White 14.3 (504) 12.4 (437) 10.1 (356) 9.0 (317) Cross Flow Fan 43 5 Steps, Quiet, Auto Right, Left, Horizontal, Downwards Removable / Washable / Mildew Proof 0.19 - 0.18 - 0.18 / 0.19 - 0.18 34 81.3 - 82.1 - 78.7 / 81.3 - 82.1 Microcomputer Control 290 × 1,050 × 237 361 × 1,145 × 364 12 17
FTKC60NVMM Shiny Pure White 15.4 (544) 13.5 (478) 11.4 (402) 9.9 (350) Cross Flow Fan 43 5 Steps, Quiet, Auto Right, Left, Horizontal, Downwards Removable / Washable / Mildew Proof 0.21 - 0.20 - 0.19 / 0.21 - 0.20 40 86.6 - 87.0 - 87.7 / 86.6 - 87.0 Microcomputer Control 290 × 1,050 × 237 361 × 1,145 × 364 12 17
dB(A)
42 / 37 / 32 / 29
44 / 39 / 34 / 31
W A W % A mm mm kg kg
RKC50NVM Ivory White Hermetically Sealed Swing Type 2YC40BXD 1,300 FW68DA 0.650 R-32 1.2 49.5 (1,748) 45.8 (1,617) Propeller 53 6.51 - 6.22 - 5.92 / 6.51 - 6.22 1,411 98.5 - 98.6 - 99.3 / 98.5 - 98.6 3.5 735 × 825 × 300 784 × 960 × 390 43 48
RKC60NVM Ivory White Hermetically Sealed Swing Type 2YC40BXD 1,300 FW68DA 0.650 R-32 1.2 53.4 (1,886) 45.8 (1,617) Propeller 53 7.80 - 7.50 - 7.11 / 7.80 - 7.50 1,700 99.2 - 98.6 - 99.6 / 99.2 - 98.6 3.5 735 × 825 × 300 784 × 960 × 390 43 48
dB(A)
48 / 44
52 / 46
3D089136
3D089137
kW Btu/h kcal/h L/h A W % W/W mm mm mm
Capacity Rated (Min. ~ Max.) Moisture Removal Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) COP (Rated) Liquid Piping G as Connections Drain Heat Insulation Max. Interunit Piping Length Max. Interunit Height Difference Chargeless Amount of Additional Charge of Refrigerant Indoor Unit Front Panel Colour H M Airflow Rate L SL Type Fan Fan Motor Output Speed Air Direction Control Air Filter Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) Temperature Control Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H / M / L / SL Level Outdoor Unit Casing Colour Type Compressor Model Motor Output Type Refrigerant Oil Charge Type Refrigerant Charge H Airflow Rate SL Type Fan Fan Motor Output Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) Starting Current Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H / SL Level Drawing No.
Note:
m m m
FTKC50NVMM RKC50NVM 5.2 (1.6 ~ 5.9) 17,700 (5,500 ~ 20,100) 4,470 (1,380 ~ 5,070) 2.9 6.7 - 6.4 - 6.1 / 6.7 - 6.4 1,445 98.0 - 98.2 - 98.7 / 98.0 - 98.2 3.60 φ 6.4 φ 12.7 φ 18.0 Both Liquid and Gas Pipes 30 20 10
m³/min (cfm)
W Steps
A W %
W L kg m³/min (cfm)
The data are based on the conditions shown in the table below. Cooling Piping Length
Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB / 24°CWB
Split Type Air Conditioners FTKC-N Series
7.5 m
FTKC60NVMM RKC60NVM 6.0 (1.8 ~ 6.9) 20,500 (6,100 ~ 23,500) 5,160 (1,550 ~ 5,930) 3.9 8.0 - 7.7 - 7.3 / 8.0 - 7.7 1,740 98.9 - 98.2 - 99.3 / 98.9 - 98.2 3.45 φ 6.4 φ 12.7 φ 18.0 Both Liquid and Gas Pipes 30 20 10
Conversion Formulae kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35.3
5
Dimensions
EDMY041427
4. Dimensions 4.1
Indoor Unit
FTKC25/35NVMM AIR FLOW (INDOOR)
THE MARK (→) SHOWS PIPING DIRECTION
) E C R N A O M . F N E R I O M C F 0 A R 3 P E S P (
REAR 770 LEFT
RIGHT INCLUDING MOUNTING PLATE 50MIN. (SPACE FOR MAINTENANCE) MAINTENANCE)
205 203
FRONT PANEL FIXING SCREWS (INSIDE)
MANUFACTURER' S LABEL 3 8 2
SIGNAL RECEIVER
TERMINAL BLOCK WITH EARTH TERMINAL (INSIDE)
OPERATION LAMP TIMER LAMP BOTTOM
INDOOR UNIT ON/OFF SWITCH
FLAPS
GAS PIPE φ9.5 CuT (THE LENGTH OF PIPE OUTSIDE THE UNIT : ABOUT 350 )
ROOM TEMP. THERMISTOR (INSIDE) INSIDE)
LIQUID PIPE φ6.4 CuT (THE LENGTH OF PIPE OUTSIDE THE UNIT : ABOUT 400 )
DRAIN HOSE (CONNECTING PART I.D. φ14 O.D. φ16 THE HOSE LENGTH OF OUTSIDE THE UNIT IS ABOUT 450) 450 )
770
SIGNAL TRANSMITTER MODEL NAME PLATE 58
50MIN. (SPACE FOR MAINTENANCE) MAINTENANCE)
REQUIRED SPACE
6 1
549
101
6
BLADE ANGLE
18
UP/DOWN (AUTOMATIC)
DAIKIN
COOLING 5˚ 3 6 1
3 8 2
5˚
45˚
45 ˚ FAN
5 4 .5
54
WALL HOLE FOR EMBEDDED PIPING φ65 HOLE
RIGHT/LEFT (MANUAL )
5˚
WIRELESS REMOTE CONTROLLER (ARC433A88)
2 7 1
3 . 1 4
DRY
STANDARD LOCATIONS OF WALL HOLES 4 5 ˚
45˚
3 . 1 4
WALL HOLE φ65 HOLE
˚ 4 5
3D089148
FTKC50/60NVMM THE MARK (→) SHOWS PIPING DIRECTION 1050 REAR
LEFT
AIR FLOW (INDOOR) (FOR PERFORMANCE AND MAINTENANCE ) REAR
RIGHT
INCLUDING ( INSTALLATION PLATE ) 239 237
0 9 2
BOTTOM
MIN.50 MODEL NAME (SPACE FOR MAINTENANCE) MAINTENANCE) PLATE
) E C R N A O M 0 F 3 . R E N O I C F M A R P E S ( P
MIN.50 (SPACE FOR MAINTENANCE) MAINTENANCE)
REQUIRED SPACE
TERMINAL BLOCK WITH EARTH TERMINAL (INSIDE) INSIDE)
FRONT GRILLE FIXING SCREWS (INSIDE) INSIDE) SIGNAL RECEIVER OPERATION LAMP TIMER LAMP DRAIN HOSE FOR VP13 (CONNECTING PART I.D. 14.0, O.D. 18.0) (THE HOSE LENGTH OF LIQUID PIPE φ6.4 CuT OUTSIDE THE UNIT : (THE LENGTH OF PIPE OUTSIDE ABOUT 530) THE UNIT : ABOUT 480) 480 )
GAS PIPE φ12.7 CuT (THE LENGTH OF PIPE OUTSIDE THE UNIT : ABOUT 430 )
INDOOR UNIT ON/OFF SWITCH ROOM TEMP. THERMISTOR (INSIDE) INSIDE) SIGNAL TRANSMITTER (18) 18)
(58) 58)
FLAPS
MODEL NAME PLATE
HORIZONTAL BLADE BLADE ANGLES (AUTOMATIC)
1050 893.5
COOLING
) 3 6 1 (
DRY
10˚ 40˚ 10˚
35˚
40˚
2 5
5˚ 35˚
VERTICAL BLADE (MANUAL ) 60
5˚
(ARC433A105)
6
5 0 ˚ 5 0 ˚
5˚ 55˚
0 3
5 . 5 5 0 1 9 2
5˚
FAN
WIRELESS REMOTE CONTROLLER
5 2. 5
5 . 4 1
55˚
WALL HOLE FOR EMBEDDED PIPING φ80 HOLE
99.5
STANDARD LOCATIONS OF WALL HOLES
2 5
WALL HOLE φ80 HOLE
3D089150
Split Type Air Conditioners FTKC-N Series
EDMY041427
4.2
Dimensions
Outdoor Unit
RKC25/35NVM DRAIN OUTLET (I.Dφ15.9 HOSE FOR CONNECTION WITH DRAIN JOINT) JOINT ) 470
1 1
0 0 1
0 5 1
50
50
7 9 2
BRAND NAME LABEL
HANDLE 13.5
12
6 58
0 0 3
50
0 5
2 75
0 5 1
96 379
0 4
WALL HEIGHT ON AIR OUTLET SIDE =LESS THAN 1200
MINIMUM SPACE FOR AIR PASSAGE 4-HOLES FOR ANCHOR BOLTS (M8 OR M10) M10)
0 0 1
MANUFACTURE'S LABEL 8
50
OUTDOOR AIR THERMISTOR
LIQUID STOP VALVE (φ6.4 CuT) CuT)
WIRING INLET 0 5 5
SERVICE PORT 8 6 8 1 0 1
155
GAS STOP VALVE (φ9.5 CuT) CuT) IN CASE OF REMOVING STOP VALVE COVER
INDICATION INDICATION LABEL (INDONESIA) INDONESIA) FOR INDONESIA MODEL ONLY
3D089153
RKC50/60NVM DRAIN OUTLET (I.D.φ15.9 HOSE FOR CONNECTION ) 8 25
MINIMUM SPACE FOR AIR PASSAGE
WALL HEIGHT ON AIR OUTLET SIDE =LESS THAN 1200
0 0 1
78
325 1 24
0 0 1
5 80
6 2 3
0 5 3
50
50 50
0 0 5 3 3 3
0 1
0 0 3
0 0 1
0 5 3
IN CASE OF REMOVING STOP VALVE COVER
5 2
4-HOLES FOR ANCHOR BOLTS (M8 OR M10) M10)
NAME PLATE BRAND NAME PLATE
WIRING INLET
0 5 3
OUTDOOR AIR TEMPERATURE THERMISTOR
TERMINAL STRIP WITH EARTH TERMINAL
5 3 7
4 6 9 8
LIQUID STOP VALVE (φ6.4 CuT) SERVICE PORT
1 55 160
18 30 GAS STOP VALVE (φ12.7 CuT)
3D083536B
Split Type Air Conditioners FTKC-N Series
7
Wiring Diagrams
EDMY041427
5. Wiring Dia Diagrams 5.1
Indoor Unit
FTKC25/35NVMM
PCB2
S27 1
BLK
LED1
H1P
BLK
LED2
H2P
BLK
PCB1
S26 9
BLK
FIELD WIRING. TRANSMISSION CIRCUIT
BLK
GRN/YLW
FG
BLK
RECTIFIER
BLK
9
3 GRN
BLK
H3
+
1
BLK
V1
MR10
H2 H1
S1W
3
WHT
2
BLK
1
F1U 3.15A
t˚
2
RED
X1M
+ R1T SIGNAL RECEIVER
IPM200 1
2
S32
1
6
9
12
1
BLK BLK BLK
CAUTION NOTE THAT OPERATION WILL RESTART AUTOMATICALLY AUTOMATICALLY I F THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN.
10
INDOOR W L Y G U R L O B
D E R
K L B
T H W
K K K K K K K L L L L L L L B B B B B B B
6 M t˚
S403
S200 BLK BLK
BLK BLK
WIRELESS REMOTE CONTROLLER
5
1 S6
OUTDOOR
1
M
M1S
S602
1 4
K L B
S601
FG F1U H1~H3 H1P~H2P M1F M1S PCB1~PCB3 R1T, R2T S6~S602 S1W X1M
1
M1F
R2T
NOTE) NOTE)
S21
1. PCB3 IS SHOWS THE CASE OF OPTION CONNECTION.
: FRAME GROUND : FUSE : HARNESS : PILOT LAMP : FAN MOTOR : SWING MOTOR : PRINTED CIRCUIT BOARD : THERMISTOR : CONNECTOR : OPERATION SWITCH : TERMINAL STRIP : PROTECTIVE EARTH
PCB3
OPTION
3D058454D
FTKC50/60NVMM
PCB3
S49 1
LED1 H1P
S46 1
BLK
1
PCB1
BLK
~
BLK BLK
LED2 H2P
X1M
FU1 F1U
H1
3.15A C102
V1 MR10
BLK
H2
1 2
RED
3
C101
BLK
GRN/YLW
H3
TRANSMISSION CIRCUIT
9
BLK
SW1
CAUTION NOTE THAT OPERATION WILL RESTART AUTOMATICALLY IF THE MAIN POWER SUPPLY IS TURNED OFF AND THEN BACK ON AGAIN.
FG
S21 t˚ HA
7
RTH1 R1T
4
S1 RED
BLU BRN
MS
ORG
1 S47 1 3
S32 1
2
K K K K L L L L B B B B
PCB2 WIRELESS REMOTE CONTROLLER
OUTDOOR
FIELD WIRING.
BLK
9
3
GRN
BLK
LED3 H3P
BZ
BLK WHT
2
S48 1
SIGNAL RECEIVER
3
K L B
S41 15 13 11 9 7
WHT
M1F
D G W K U E R L N L R O Y P B
BZ C101, C102 FG F1U H1P~H3P MR10 M1F M1S PCB1~PCB3 R1T, R2T S1~S49 SW1 V1 X1M
: BUZZER : CAPACITOR : FRAME GROUND : FUSE : PILOT LAMP : MAGNETIC RELAY : FAN MOTOR : SWING MOTOR : PRINTED CIRCUIT BOARD : THERMISTOR : CONNECTOR : OPERATION SWITCH : VARISTOR : TERMINAL STRIP : PROTECTIVE EARTH
t˚ R2T
M
INDOOR
M1S
3D088910
8
Split Type Air Conditioners FTKC-N Series
EDMY041427
5.2
Wiring Diagrams
Outdoor Unit
RKC25/35NVM
3D088772A
RKC50/60NVM
Split Type Air Conditioners FTKC-N Series
9
Piping Diagrams
EDMY041427
6. Pipin iping g Dia iag gra rams ms 6.1
Indoor Unit
FTKC25/35NVMM
FTKC50/60NVMM
INDOOR UNIT
7.0 CuT
INDOOR UNIT
HEAT EXCHANGER
4.8 CuT T u C 0 . 7
(7.9 CuT) CuT)
THERMISTOR ON HEAT EXCH.
7.0 CuT HEAT EXCHANGER
7.0 CuT
FIELD PIPING (6.4 CuT) CuT)
THERMISTOR ON HEAT EXCH.
CROSS FLOW FAN
M
CROSS FLOW FAN FIELD PIPING (6.4 CuT) CuT)
FAN MOTOR FIELD PIPING (9.5 CuT) CuT)
9.5 CuT FIELD PIPING (12.7 CuT) CuT)
REFRIGERANT FLOW COOLING
4D075755A
10
M FAN MOTOR (12.7 CuT) CuT)
REFRIGERANT FLOW COOLING
4D083425C
Split Type Air Conditioners FTKC-N Series
EDMY041427
6.2
Piping Diagrams
Outdoor Unit
RKC25NVM
OUTDOOR UNIT OUTDOOR TEMPERATURE THERMISTOR
6.4 CuT HEAT EXCHANGER T
7.0 CuT u C 4. 6
R E G N R A O H T C S I X E M R T A E E H H T
6.4 CuT
6.4 CuT 6.4 CuT
M
FAN MOTOR
MOTOR OPERATED VALVE
MUFFLER WITH FILTER
T u C 4 . 6
PROPELLER FAN
R E N I A R T S
T u C 4 . 6
DISCHARGE PIPE THERMISTOR
T u C 8 . 4
T u C 5 . 9
LIQUID STOP VALVE
9.5 CuT COMPRESSOR
GAS STOP VALVE
MUFFLER MUFFLER
ACCUMULATOR
FIELD PIPING (6.4 CuT) CuT) FIELD PIPING (9.5 CuT) CuT)
REFRIGERANT FLOW COOLING
3D089192A
RKC35NVM
OUTDOOR UNIT 7.0 CuT T
HEAT EXCHANGER
OUTDOOR TEMPERATURE THERMISTOR
7.0 CuT u C .5 9
R E G N A R O H T C S I X E M T R A E E H H T
6.4 CuT6.4 CuT
M
FAN MOTOR
6.4 CuT
MOTOR OPERATED VALVE
MUFFLER WITH FILTER
T u C 4 . 6
PROPELLER FAN
R E N I A R T S
T u C 9 . 7
DISCHARGE PIPE THERMISTOR
T u C 8 . 4
T u C 5 . 9
LIQUID STOP VALVE 9.5 CuT
COMPRESSOR
MUFFLER MUFFLER ACCUMULATOR
GAS STOP VALVE
FIELD PIPING (6.4 CuT)
REFRIGERANT FLOW COOLING
FIELD PIPING (9.5 CuT)
3D089185A
Split Type Air Conditioners FTKC-N Series
11
Piping Diagrams
EDMY041427
RKC50/60NVM
OUTDOOR UNIT 7.0 CuT
HEAT EXCHANGER OUTDOOR TEMPERATURE THERMISTOR
7.0 CuT
HEAT EXCHANGER THERMISTOR
6.4 CuT
MUFFLER WITH FILTER
MOTOR OPERATED VALVE
MUFFLER WITH FILTER
FILTER
T u C 9 . 7
M T u C 4 . 6
PROPELLER FAN
MUFFLER DISCHARGE PIPE THERMISTOR
LIQUID STOP VALVE
FIELD PIPING (6.4 CuT) CuT)
12.7 CuT COMPRESSOR
ACCUMULATOR
12.7 CuT
GAS STOP VALVE
FIELD PIPING (12.7 CuT) CuT)
REFRIGERANT FLOW COOLING 3D090240
12
Split Type Air Conditioners FTKC-N Series
EDMY041427
Capacity Tables
7. Capa Capaci city ty Table ables s 7.1
Cooling Only
FTKC25NVMM FTKC25NVMM + RKC25NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V) AFR
9
BF
0.10
IN I NDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB
EDB
°C
°C
TC
SHC
20 PI
TC
SHC
25 PI
TC
SHC
30 PI
TC
SHC
PI
TC
SHC
14.0
20
2.46
2.03
0.54
2.35
1.98
0.59
2.23
1.93
0.64
2.28
1.95
0.66
2.21
16.0
22
2.57
2.00
0.54
2.46
1.95
0.60
2.34
1.90
0.65
2.40
1.92
0.66
18.0
25
2.68
2.12
0.55
2.57
2.08
0.60
2.46
2.03
0.65
2.51
2.05
19.0
27
2.73
2.27
0.55
2.62
2.22
0.60
2.51
2.18
0.65
2.57
22.0
30
2.90
2.20
0.55
2.79
2.16
0.60
2.68
2.12
0.66
24.0
32
3.01
2.15
0.56
2.90
2.11
0.61
2.79
2.08
0.66
Symbols:
32
35
40 PI
TC
SHC
PI
1.92
0.69
2.10
1.86
0.74
2.33
1.89
0.70
2.21
1.84
0.75
0.67
2.44
2.03
0.70
2.33
1.98
0.75
2.20
0.67
2.50
2.17
0.70
2.38
2.13
0.75
2.74
2.14
0.67
2.67
2.12
0.70
2.56
2.08
0.76
2.86
2.10
0.68
2.79
2.08
0.71
2.67
2.04
0.76
Notes:
AFR
: Airflow rate
(m³/min.)
BF
: Bypass factor
EWB
: En Entering we wet bu bul b temp.
(°C)
EDB
: En Entering dr dry bu bulb te temp.
(°C)
TC
: Total capacity
(kW)
SHC
: Sensible heat capacity
(kW)
PI
: Power input
(kW)
1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5 m Level difference : 0 m
3D089843
FTKC35NVMM FTKC35NVMM + RKC35NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V) AFR
9.2
BF
0.12
IN I NDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB
EDB
20
25
°C
°C
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
14.0
20
3.16
2.37
0.72
3.16
2.37
0.82
3.13
2.36
0.91
3.16
2.37
0.93
3.10
16.0
22
3.60
2.47
0.77
3.44
2.39
0.84
3.28
2.32
0.92
3.36
2.36
0.94
18.0
25
3.75
2.58
0.77
3.59
2.51
0.85
3.44
2.44
0.92
3.52
2.48
0.94
19.0
27
3.83
2.72
0.77
3.67
2.65
0.85
3.51
2.58
0.92
3.60
2.62
22.0
30
4.06
2.62
0.78
3.90
2.56
0.85
3.75
2.50
0.93
3.84
24.0
32
4.21
2.55
0.79
4.06
2.49
0.86
3.90
2.44
0.93
4.00
Symbols:
30
32
35
40 PI
TC
SHC
PI
2.34
0.98
2.93
2.26
1.05
3.26
2.31
0.98
3.10
2.23
1.06
3.42
2.43
0.99
3.26
2.36
1.06
0.95
3.50
2.58
0.99
3.34
2.51
1.06
2.53
0.95
3.74
2.50
1.00
3.58
2.44
1.07
2.47
0.96
3.90
2.44
1.00
3.74
2.38
1.07
Notes:
AFR
: Airflow rate
BF
: Bypass factor
(m³/min.)
EWB
: En Entering we wet bu bul b temp.
(°C)
EDB
: En Entering dr dry bu bulb te temp.
(°C)
TC
: Total capacity
(kW)
SHC
: Sensible heat capacity
(kW)
PI
: Power input
(kW)
1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5 m Level difference : 0 m
3D089844
Split Type Air Conditioners FTKC-N Series
13
Capacity Tables
EDMY041427
FTKC50NVMM FTKC50NVMM + RKC50NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V) AFR
14.3
BF
0.07
IN I NDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB EDB
20
25
30
32
35
°C
°C
TC
S HC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
14.0
20
5.11
3.86
1.11
4.88
3.74
1.22
4.65
3.63
1.33
4.75
3.68
1.36
4.60
16.0
22
5.34
3.79
1.12
5.11
3.68
1.23
4.88
3.58
1.34
4.99
3.62
1.37
18.0
25
5.57
3.98
1.13
5.34
3.88
1.24
5.11
3.78
1.34
5.23
3.83
19.0
27
5.69
4.21
1.13
5.45
4.11
1.24
5.22
4.01
1.35
5.35
22.0
30
6.03
4.06
1.14
5.80
3.97
1.25
5.57
3.89
1.36
24.0
32
6.26
3.95
1.15
6.03
3.88
1.25
5.80
3.80
1.36
Symbols:
40 PI
TC
SHC
PI
3.61
1.43
4.36
3.49
1.54
4.84
3.56
1.44
4.60
3.45
1.54
1.38
5.08
3.77
1.44
4.84
3.67
1.55
4.06
1.38
5.20
4.00
1 .45
4.96
3.91
1.55
5.70
3.94
1.39
5.56
3.89
1.45
5.32
3.80
1.56
5.94
3.85
1.40
5.80
3.80
1.46
5.56
3.72
1.57
Notes:
AFR
: Airflow rate
(m³/min.)
BF
: Bypass factor
EWB
: En Entering we wet bu bul b temp.
(°C)
EDB
: En Entering dr dry bu bulb te temp.
(°C)
TC
: Total capacity
(kW)
SHC
: Sensible heat capacity
(kW)
PI
: Power input
(kW)
1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the the figures in the above tables. (Figures out of the tables should not be used for calculation.) 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5 m Level difference : 0 m
3D089845
FTKC60NVMM FTKC60NVMM + RKC60NVM (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V) AFR
15.4
BF
0.08
IN I NDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB EDB
20
25
30
32
35
°C
°C
TC
S HC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
14.0
20
5.90
4.34
1.34
5.63
4.20
1.47
5.36
4.07
1.60
5.48
4.12
1.64
5.31
16.0
22
6.16
4.26
1.35
5.90
4.13
1.48
5.63
4.01
1.61
5.75
4.07
1.65
18.0
25
6.43
4.46
1.36
6.16
4.34
1.49
5.89
4.22
1.62
6.03
4.28
19.0
27
6.56
4.69
1.36
6.29
4.58
1.49
6.03
4.47
1.62
6.17
22.0
30
6.96
4.52
1.37
6.69
4.42
1.50
6.42
4.32
1.63
24.0
32
7.23
4.40
1.38
6.96
4.31
1.51
6.69
4.22
1.64
Symbols:
40 PI
TC
SHC
PI
4.04
1.72
5.03
3.90
1.85
5.59
3.99
1.73
5.31
3.86
1.86
1.66
5.86
4.21
1.74
5.58
4.09
1.86
4.53
1.66
6.00
4.46
1 .74
5.72
4.34
1.87
6.58
4.38
1.67
6.41
4.32
1.75
6.14
4.22
1.88
6.86
4.28
1.68
6.69
4.22
1.76
6.41
4.13
1.89
Notes:
AFR
: Airflow rate
(m³/min.)
BF
: Bypass factor
EWB
: En Entering we wet bu bul b temp.
(°C)
EDB
: En Entering dr dry bu bulb te temp.
(°C)
TC
: Total capacity
(kW)
SHC
: Sensible heat capacity
(kW)
PI
: Power input
(kW)
1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the the figures in the above tables. (Figures out of the tables should not be used for calculation.) 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5 m Level difference : 0 m
3D089846
14
Split Type Air Conditioners FTKC-N Series
EDMY041427
7.2
Capacity Tables
Capa Capacity city Corre Correcti ction on Fact Factor or by by the Len Length gth of of Refrig Refrigera erant nt Pipin Piping g (Refer (Referen ence) ce) The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping — the distance between the indoor unit and the outdoor unit.
7.2.1
25/35 Class Cooling (R-32) (%) 100
r o t c a f n o i t c e r r o c y t i c a p a C
90
Range of the refrigerant additional charge
80
5
10
15 (m)
Piping length
7.2.2
(R20651)
50/60 Class Cooling (R-32) (%) 100
r o t c a f n o i t c e r r o c y t i c a p a C
90
80 Range of the refrigerant additional charge
5
10
15 Piping length
Note:
20
25
30 (m) (R20375)
The graphs show the factor when additional refrigerant of the proper quantity is charged.
Split Type Air Conditioners FTKC-N Series
15
Operation Limit
EDMY041427
8. Oper Opera atio tion Limit imit RKC25/35NVM
50 46
40 ) B D C ˚ ( . p m e t r o 30 o d t u O
n o i t a r e p o s u o u n i t n o C
d o i r e p n w o d l l u P
20 19.4 0
10 14 Notes : The graph is based on the following conditions. · Equivalent piping length 7.5m 0m · Level difference · Air flow rate High
20
23
28 30
Indoor temp. (˚CWB)
4D073983E
RKC50/60NVM
50 46
40 ) B D C ˚ ( . p m e 30 t r o o d t u O
n o i t a r e p o s u o u n i t n o C
d o i r e p n w o d l l u P
20 19.4 0
10 14 Notes : The graph is based on the following conditions. conditions. • Equivalent piping length 7.5m • Level difference 0m • Air flow rate High
16
20
23
28 30
Indoor temp. (˚CWB)
4D083533A
Split Type Air Conditioners FTKC-N Series
EDMY041427
Sound Level
9. Sound Level 9.1
Measuring Location Indoor Unit
Outdoor Unit
1m
1m
m 8 . 0
MICROPHONE
MICROPHONE
Notes:
1. Operation Operation sound sound is measured measured in an anecho anechoic ic chamber. chamber. 2. The data data are based based on the condition conditions s shown shown in the table below. below. Cooling Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB / 24°CWB
9.2
Piping Length 5m
Indoor Unit
FTKC25NVMM 70 L E 60 V E L E R U ) r 50 S a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 D ( B N d A 30 B E V A T C 20 O
FTKC35NVMM 70
OVER ALL (dB) dB)
NC-70
50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L) NC-60
A
38
25
(B.G.N IS ALREADY RECTIFIED) RECTIFIED ) OPERATING CONDITIONS
NC-50
POWER SOURCE 220-240/22 220-240/220-23 0-230V 0V
50/60Hz 50/60Hz
JIS STANDARD 220-240/220-230V 50/60Hz (H)
NC-40
220-240/220-230V
50/60Hz (L)
Cooling NC-30
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) Hz)
NC-20
FTKC50NVMM 70 L E 60 V E L E R U ) r 50 S a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 D ( B N d A 30 B E V A T C 20 O
A
NC-60
42
32
(B.G.N IS ALREADY RECTIFIED) RECTIFIED ) OPERATING CONDITIONS
NC-50
P OWER SO URCE 220-240/220-230V
50/60Hz
JIS STANDARD NC-40
220-240/220-230V
50/60Hz (H)
220-240/220-230V
50/60Hz (L)
Cooling NC-30
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) Hz)
NC-60
A
(H)
(L)
39
26
(B.G.N IS ALREADY RECTIFIED) RECTIFIED ) OPERATING CONDITIONS
NC-50
POWER SOURCE
220-240/220-230V 220-240/220-230V 50/60 Hz
JIS STANDARD 220-240/220-230V 50/60 Hz (H)
NC-40
220-240/220-230V 50/60 Hz (L)
Cooling NC-30
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
63
NC-20
4D089379
125 250 500 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCY (Hz) Hz)
70
OVER ALL (dB) dB) 50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L)
63
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V
FTKC60NVMM
NC-70
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
50/60Hz
L E 60 V E L E R U ) r 50 S a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 D ( N B 30 A d B E V A T C 20 O
4D089376
8000
OVER ALL (dB) dB)
NC-70
NC-20
8000
Split Type Air Conditioners FTKC-N Series
4D089508
OVER ALL (dB) dB)
NC-70
50/60Hz
L E 60 V E L E R U ) r 50 S a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 D ( B N d A 30 B E V A T C 20 O
50/60Hz
SCALE 220-240/220-230V 220-240/220-230V NC-60
A
(H)
(L)
44
34
(B.G.N IS ALREADY RECTIFIED) RECTIFIED ) NC-50
OPERATING CONDITIONS P OWER S OURCE
220-240/220-230V
50/60Hz
JIS STANDARD 220-240/220-230V 50/60Hz (H)
NC-40
220-240/220-230V 50/60Hz (L)
Cooling NC-30
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz) Hz)
NC-20
8000
4D089509
17
Sound Level
9.3
EDMY041427
Outdoor Unit
RKC25NVM 70 L E 60 V E L E R U ) r 50 S a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 D ( B N d A 30 B E V A T C 20 O
RKC35NVM
COOLING 50Hz SCALE 220-230-240V NC-60
70
OVER ALL (dB) dB)
NC-70
A
60Hz 220-230V
47-48-48
49-50
(B.G.N IS ALREADY RECTIFIED) RECTIFIED ) OPERATING CONDITIONS
NC-50
POWER S OURCE
220-240/220-230V
50/60Hz (H)
JIS STANDARD (JIS9612) JIS9612) 220-240/220-230V 220-240/220-230V
NC-40
50/60Hz (H)
NC-30
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
4D089535A
8000
RKC50NVM OVER ALL (dB) dB)
NC-70
NC-60
NC-50
A
48
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz (H)
JIS STANDARD NC-40
220-240/220-230V 50/60Hz (H)
NC-30
63
18
SCALE
50/60Hz 220-240/220-230V( 220-240/220-230V (H)
(B.G.N IS ALREADY RECTIFIED) RECTIFIED )
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
500 1000 2000 4000 125 250 OCTAVE BAND CENTER FREQUENCY (Hz) Hz)
OVER ALL (dB) dB)
NC-70
50Hz SCALE 220-230-240V NC-60
A
60Hz 220-230V
49-49-50
49-50
(B.G.N IS ALREADY RECTIFIED) RECTIFIED ) OPERATING CONDITIONS
NC-50
POWER SO URCE
220-240/220-230V
50/ 60Hz (H)
JIS STANDARD (JIS9612) JIS9612 ) 220-240/220-230V 220-240/220-230V
NC-40
50/60Hz (H)
NC-30
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
63
NC-20
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
4D089392A
8000
RKC60NVM
70 L E V 60 E L E R U ) r S a S b 50 E µ R 2 P 0 D 0 0 . N 0 U =40 O B d S 0 D ( N B A d 30 B E V A T C 20 O
L E 60 V E L E R U ) r 50 S a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 D ( B N d A 30 B E V A T C 20 O
COOLING
NC-20
8000
4D088836A
70 L E 60 V E L E R U ) r 50 S a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 D ( B N d A 30 B E V A T C 20 O
OVER ALL (dB) dB)
NC-70
NC-60
SCALE
50/60Hz 220-240/220-230V (H)
A
52
(B.G.N IS ALREADY RECTIFIED) RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz (H)
JIS STANDARD NC-40
220-240/220-230V 50/60Hz (H)
NC-30
APPROXIMATE THRESHOLDHEARING FORCONTINUOUS NOISE
63
NC-20
125 250 500 1000 2000 4000 8000 OCTAVE BAND CENTER FREQUENCY (Hz) Hz)
4D088837A
Split Type Air Conditioners FTKC-N Series
EDMY041427
Electric Characteristics
10.Electric Characteristics Indoor Unit
Outdoor Unit
Power supply Hz - Volts
Voltage range
Compressor MCA
MFA
RHz
50 - 220 50 - 230 FTKC FTKC2 25NVM 5NVMM M
RKC25 KC25NV NVM M
Max. 50 Hz, 264 V Min. 50 Hz, 198 V
50 - 240 60 - 220 60 - 230
8.50
10
46
Max. 60 Hz, 253 V Min. 60 Hz, 198 V
50 - 220 50 - 230 FTKC FTKC35 35NV NVMM MM
RKC3 RKC35N 5NVM VM
Max. 50 Hz, 264 V Min. 50 Hz, 198 V
50 - 240 60 - 220 60 - 230
FTKC FTKC50 50NV NVMM MM
RKC5 RKC50N 0NVM VM
10
66
Max. 60 Hz, 253 V Min. 60 Hz, 198 V Max. 50 Hz, 264 V Min. 50 Hz, 198 V
50 - 240 60 - 220 60 - 230
13.50
15
58
Max. 60 Hz, 253 V Min. 60 Hz, 198 V
50 - 220 50 - 230 FTK C6 C60NV MM MM
RKC60NV M
Max. 50 Hz, 264 V Min. 50 Hz, 198 V
50 - 240 60 - 220 60 - 230
W
13.50 Max. 60 Hz, 253 V Min. 60 Hz, 198 V
15
69
FLA
IFM W
FLA
3.0
0.22
0.19
2 .9
0.21
0 .1 8
2 .7
20
0.20
16
0.17
3 .0
0.22
0.19
2 .9
0.21
0.18
4.1
0.22
0.27
3 .9 9.25
50 - 220 50 - 230
RLA
OFM
3 .7
0.21 20
0.20
0.26 16
0.24
4 .1
0.22
0.27
3 .9
0.21
0.26
6.3
0.19
0.19
6 .0
0.18
0.18
5 .8
53
0.17
43
0.18
6.3
0.19
0.19
6 .0
0.18
0.18
7.6
0.20
0.21
7 .3
0.19
0.20
6.9
53
0.18
43
0 .1 9
7.6
0.20
0.21
7.3
0 .1 9
0 .2 0
Symbols:
Notes:
MCA
: Min. circuit amps (A)
MFA MFA
: Max Max.. fus fuse e amp amps s (A) (A)
RHz RHz
: Rat Rated ed oper operat atin ing g fre frequ quen ency cy (Hz (Hz))
RLA
: Rat Rate ed loa load d amp amps s (A) (A)
OFM OFM
: Out Outdo door or fan fan moto motorr
1. RL R LA is based on the following conditions. Indoor temp. 27°CDB / 19°CWB Outdoor temp. 35°CDB 2. Maximum allowable voltage variation between phases is 2%. 3. Select wire wire size based on the larger larger value of MCA. MCA. 4. Instead Instead of fuse, use circuit circuit breaker. breaker. 5. Be sure to install install an earth leak detector detector.. (This unit uses an inverter, which means that an earth leak detector capable of handling high harmonics must be used in order to prevent malfunctioning of the earth leak detector.)
IFM
: Indoor fan motor
W
: Fan motor ra rated ou output (W (W)
FLA
: Fu Ful l load am amps (A (A) 3D089021
Split Type Air Conditioners FTKC-N Series
19
Installation Manual
EDMY041427
11.Installation Manual 11.1
20
25/35 Class
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
21
Installation Manual
22
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
23
Installation Manual
24
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
25
Installation Manual
26
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
27
Installation Manual
28
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Installation Manual
3P363835-16C
Split Type Air Conditioners FTKC-N Series
29
Installation Manual
11.2
30
EDMY041427
50/60 Class
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
31
Installation Manual
32
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
33
Installation Manual
34
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
35
Installation Manual
36
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Installation Manual
37
Installation Manual
38
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Installation Manual
3P363835-17C
Split Type Air Conditioners FTKC-N Series
39
Operation Manual
EDMY041427
12.Opera 12. Operation tion Manual
40
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
41
Operation Manual
42
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
43
Operation Manual
44
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
45
Operation Manual
46
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
47
Operation Manual
48
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
49
Operation Manual
50
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
51
Operation Manual
52
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
53
Operation Manual
54
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
55
Operation Manual
56
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
57
Operation Manual
58
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
59
Operation Manual
60
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
61
Operation Manual
62
EDMY041427
Split Type Air Conditioners FTKC-N Series
EDMY041427
Split Type Air Conditioners FTKC-N Series
Operation Manual
63
Operation Manual
EDMY041427
3P363834-9B
64
Split Type Air Conditioners FTKC-N Series
EDMY041427
Optional Accessories
13.Optional Accessories 13.1 Option List 13.1 13.1.1 .1 Indo Indoor or Unit Unit Option Name
Note:
1
Titanium Titanium apatit apatite e photoc photocatalyt atalytic ic air-pur air-purifying ifying filter (without (without frame) frame)
2
Remote controller loss prevention with chain
25/35/50/60 Class ★
KAF970A46 KKF917A4
Standard accessory
★
13 13.1 .1.2 .2 Outd Outdoo oorr Unit Unit Option Name 1
Air direction adjustment grille
2
Drain plug
Split Type Air Conditioners FTKC-N Series
25/35 Class
50/60 Class
KPW937B4
KPW945A4
KKP937A4
65
Optional Accessories
EDMY041427
13.2 13. 2 > Air Dire Directi ction on Adju Adjustm stmen entt Grille Grille
4P202735-1
66
Split Type Air Conditioners FTKC-N Series
EDMY041427
Optional Accessories
13.3 13. 3 > Air Dire Directi ction on Adju Adjustm stmen entt Grille Grille
3P089958-2C
Split Type Air Conditioners FTKC-N Series
67
Warning
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer.
Cautions on product corrosion 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Specifications, Specifications, designs and other content appearing in this brochure are current as of August 2014 but subject to change without notice. c All rights reserved