selection of fuses for the protection of transformers
A client requires to justi jus tify fy the choice of the despatched despatc hed fuses… fuses… This file must help you to answer.
THE BEST?? IT’S ME!!!
KEEP IN MIND Generally, it is sufficient to use the Generally, selection tables. For case not covered by the standard selection tables, you must know characteristics of: s
the transformer,
s
the breaking system,
s
the fuses.
We will make an example with SM6 fuses.
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d s i i e v v e r
0 4 0 4/ 2 0 s
Merlin Gerin
s
Square D
s
Telemecanique
Selection of fuses for the protection of transformers
Medium voltage fuses used in MV/LV substations are coordinated with the output rating of the transformer. transformer. Their time/current characteristics are designed to protect medium voltage distribution systems from transformer faults and low voltage faults upstream of LV protection devices. The fuses may be simply connected in series with the switch-disconnector or equipped with strikers in a fuse-switch combination to automatically open the switch when a fuse blows, thereby preventing continued operation on one or two remaining phases. In a “ transformer transformer protection” protection” c ubicle, the fuse-switch fuse-switch combination can b e replaced by a circuit breaker.
1 - RULES GOVERNING FUSE SELECTION
Generally, to select the right fuse, it is sufficient to use the Generally, SM6 fuse selection tables (see page 1 1). The fuse fuse rating is determined d etermined for an ambient amb ient temperature not exceeding 40 °C °C maximum or a mean daily value of 35 °C. If these values are exceeded, over-rated fuses must be used to avoid unnecessary fuse-blowing due to these temperatures. For cases not covered by the standard selection tables, the applicable fuse selection rules and criteria must be respected according to the type of load and the environment (fuse-switch combination).
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
e d r e v i s 0 0 4 0 4 / 2
page 2
Selection of fuses for the protection of transformers
2 - SOME DEFINITIONS
SYSTEM SYSTE M CHAR CHARACTER ACTERISTI ISTICS CS Rated voltage Ur The highest phase-to-phase voltage (in kV) of the system on which the fuse is installed Short-circuit current Ik The maximum maximum current in the event of a three-phase short-circuit short-circ uit on the system
TRANSFORMER CHARACTERISTICS: output power “P” expressed in kVA, short-circuit circuit voltage “U “ Uk %”, s shortservice ce volt voltage age “ Us” in kV, s servi s operation with or without overload. s
We write: Rms value of the rated current “Irt” Irt =
P Us •
3
Short-circuit voltage “Uk (%)” The supply voltage for which the short-circuit current is equal to I nt, expressed as a percentage of the rated voltage. Short-circuit current “Ik” The current corresponding to a solid short-circuit across the terminals of the secondary winding of the transformer. Ik =
Irt x 100 Uk %
Transformer inrush current “Ie” Ie = the peak transient current when the transformer is energised. “X” = Ie Irt Time constant “t0” The time constant for the damping of the transient conditions that occur when the transformer is energised.
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
e d r e v i s
0 4 0 4/ 2 0
page 3
Selection of fuses for the protection of transformers
2 - SOME DEFINITIONS
FUSE CHARACTERISTICS:
(cont’d)
s
rated current “Irf” The current that the fuse can withstand continuously without abnormal heating.
minimum interrupting current I3 The minimum current that can blow and interrupt the fuse. I3 is the lower limit of the current zone within which the fuse is capable of interrupting. The value of I3 is generally between 3 and 6 Inf (4.5 Irf according to standard UTE 64-210). s
Remark: a medium voltage fuse can blow without interrupting the flow of current. This is always the case for current values less than I 3 . The arc is sustained, destroying the fuse and its environment. Fuses therefore must never be exposed to currents in the zone between I nf and I 3 .
time/current characteristics of the selected range of fuses Given in the supplier documentation (see example on page 12 for the Merlin Gerin Fusarc CF range). s
short-circuit breaking capacity I1 This is the maximum prospective current that the fuse can interrupt. It is the maximum fuse test value. This current is very high, generally between 20 kA and 63 kA. s
resistance of a cold fuse Rcold Supplied by the fuse manufacturer. s
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 0 4 0 4/ 2
page 4
Selection of fuses for the protection of transformers
3 - CRITERIA APPLICABLE TO THE SELECTION OF FUSES FOR THE PROTECTION OF TRANSFORM TRANSFORMERS ERS
RULES GOVERNI GOVERNING NG FUSE SELECTI SELECTI ON MUST M UST RESPECT:
The rated voltage of the fuse U rf (in kV) must be greater than or equal to the rated voltage of the system. Urf ≥ Ur It must be respect the operating voltage tolerances tolerances specified spec ified by the fuse manufa manufacture cturerr (an excessively high rated fuse voltage could result in high overvoltages on the system when the fuse blows).
The short-circuit breaking capacity I1 (in kAmp) must be greater than or equal to the short-circuit current of the system Iksystem. I1 ≥ Ik
The fault current on the transformer secondary to be interrupted must be greater than or equal to I 3. Ik ≥ 3I
The resistance of a cold fuse must be multiplied by a coefficient that depends on the cubicle characteristics. To account for the increase in the resistance of the fuse when heated and for the installation of fuses in SM6 cubicles (higher air temperature), the resistance of the cold fuse must be multiplied by a coefficient that depends on the cubicle characteristics (volume, etc.). P = 1.9 Rcold x Irt2 Rcold = the resistance of a cold fuse. 1.9 = coefficient obtained from tests. Maximum power for fuses in SM6 cubicles: s 100 W if ambient temperature < 40 °C s 80 W if ambient temperature 40 °C < θ < 55 °C
Operating conditions must be considered. brief transformer overloads To account for these brief overloads, the following coefficient is applied to the rated current of the transformer transformer.. s
I rf ≥ Irt continuous transformer overloads If the transformer is required to operate with a continuous overload, i.e. for a period of several hours or more, the fuse rating must be greater than or equal to 1.3 I overload. s
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
We choose: Irf ≥ 1.3 Ioverload
page 5
Selection of fuses for the protection of transformers
transient inrush currents The transients produced when a transformer is energised vary according to the moment the voltage is applied (with respect to zero voltage) and the remanent flux density of the magnetic circuit. The asymmetry and the magnitude of the current are maximum when energisation occurs at zero voltage and the remanent flux density on the same phase is maximum. Before selecting selecting a fuse, it is therefore necessary to determine the rms value of the inrush current and its duration.
3 - CRITERIA APPLICABLE TO THE SELECTION OF FUSES FOR THE PROTECTION OF TRANSFORM TRANSFORMERS ERS (cont’d)
s
In practice, it is possible to use a simple rule that takes these requirements into account to avoid premature ageing of fuses. This rule consists in checking, on the fuse time/current curve, that the maximum current that blows the fuse at time T, corresponding to the time constant of the transformer, transformer, is always greater g reater than the transformer inrush current. c urrent. Imin. min. fuse fuse blow > X x Irt Ie
X =
Irt
- X and T are coming from the transformer supplier’s characteristics table. - If the transient characteristics charac teristics of the transformer are are unknown, an empirical rule may be used. This consists in checking that the fuse-blowing current at 0.15 s is g reater than X x Ir where: X = 12 for transformers with low kVA kVA ratings. X = 10 for transformer with rating greater than1,000 kVA kVA Example from France Transfo documentation: T transformer time constant X = Ie /Irt and Uk% of the transformer as a function of its output P (kVA (kVA rating). P
25
50
10 0
125
160
200
250
315
400
50 0
630
800
1,000
1,250 1,600
2,000
2,500
T
0.1
0.1
0.15
0.2
0.2
0.22
0.22
0.25
0.25
0.3
0.3
0.3
0.35
0.35
0.4
0.45
0.45
X
15
14
14
12
12
12
12
12
12
11
11
10
10
9
9
8
8
4
4
4
4
4
4
4
4
4
6
6
6
6
6
6
Uk %
4
4
Ie/Ir
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
inrush current of a 1,000 kVA transformer
page 6
Selection of fuses for the protection of transformers
4 - FUSE CHARACTERISTICS IN ACCORDANCE WITH THE TYPE OF CUBICLE
FUSED SWITCH, WITH THE FUSE AND SWITCH CONNECTED IN SERIES AND OPERATING INDEPENDENTLY (EX. PM CUBICLE) The switch interrupts its rated current under normal operating conditions (100 interruptions at a power factor of 0.7). The fuses protect against short-circuits. The fuses are not equipped with striker releases and the switch is therefore not opened automatically when a fuse blows.
FUSE-SWITCH COMBINATIONS (EX. QM, QMB, QMC CUBICLES) The operation of the switch and the fuses is linked. The fuses fuses are equipped equipp ed with strikers that open the switch when a fuse blows to prevent continued operation on the remaining one or two phases. The The switch is capab le of interrupting interrupting a fault current. It can be ac tuated tuated b y opening releases in the event of internal transformer fault (DGPT relays, relays, Buccholz relays, etc.) or by indirect relays supplied by the current transformers or toroids for overload protection (QMC cubicle). The fuse ratings must satisfy the requirements of standards IEC 60 282-1 and IEC 62271-105
Type of fuses: Fusarc CF or Solefuse with strikers or other brands. “Medium” type stricker: minimum minimum energy for fuse-blown tripp tripping ing = 0.5 Joules. Joules.
The selection of fuses for fuse-switch combination units depends on the transition current I40 and the short-circuit current seen from the primary. Standard IEC 62 271-105 defines the conditions that ensure coordinated
performance of the fuses and the switches used in combination units.
the transition current of the combination unit depends both on the time/current characteristics of the fuses and on the opening time of the switch. s
Switch opening is initiated by the fuses near the transition point of a 3-phase fault. The fastest fuse blows, thereby interrupting one of the phases, and its striker commands the opening of the switch. The two remaining phases are then faced with a lower current (87%) which will be interrupted either by the switch or by the remaining two fuses. The transition point is where the switch opens at the same time as the remaining two fuses blow. At this point, the switch takes over from the fuses, thereby defining the minimum breaking breaking capacity c apacity required for the switch.
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
page 7
Selection of fuses for the protection of transformers
4 - FUSE CHARACTERISTICS IN ACCORDANCE WITH THE TYPE OF CUBICLE
From a practical standpoint, the transition current is determined by the plotting a time equal to 0.9 times the switch opening op ening time by b y the fuses on the minimum time/current characteristic curve of the fuse (i.e. using a current tolerance of - 6.5 %). minimum time/current characteristic (- 6.5%)
t (s)
(cont’d)
transition point 0.9 x the opening time of the switch by the fuses (this opening time is 0.04 s for the SM6, 0.06 for the RM6)
switch opens at the same time as the remaining two fuses blow
I (A)
Itransfer
I40 fuse striker commands opening of the switch
3-phase fault detected by the first fuse
The current corresponding to this point is the value of the 3-phase transition current (I40) This current must not be greater than the rated transition current, which is the current specified by the manufacturer of the combination unit and checked by series TD Itransfer tests. I40 < I transfer The rated transition current (Itransfer) corresponds to the breaking capacity of the switch switch (see page 9). VARIOUS VARIOUS CURRENTS ARE DISPA DISPATCHED TCHED BETWEEN EACH EACH ITEM ITEMS S OF OF THE SYSTEM: SYSTEM : fuse switch combination SM6 PM or QM cubicle MV Itransfer fuse
MV/LV transformer
LV fuse
load Z
I1 Irf I3
Ik
I
Ie
Ik
Ir
I1
BC Itransfer
BC
r
Isc I40 Imini fuse blow Ie I3 min. interrupting current Irf
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
h c t i w s
e s u f
r e m r Irt o f s n a r t
Remark: all the currents are expressed as rms values except for the current I e , which is expressed as a peak value.
page 8
Selection of fuses for the protection of transformers
4 - FUSE CHARACTERISTICS IN ACCORDANCE WITH THE TYPE OF CUBICLE
BREAKING CAPACITY OF THE SM6 SWITCH AS A FUNCTION OF THE SERVICE VOLTAGE (under transition current conditions). Itransfer= breaking capacity
(cont’d)
Breaking capacity = BC (A)
2,600 2,400 2,200 2,000 1,800 1,600
Itransferfor 15 kV Us (kV)
1,400 0
5
10
15
20
25
TRANSITION CURRENT OF THE FUSE-SWITCH COMBINATION I 40 The transition current of the fuse-switch combination must be lower than the fault current observed on the primary during a solid short-circuit across the secondary terminals of a transformer. A solid short-circuit across ac ross the secondary terminals of a transformer transformer leads to high values of the TRV TRV (Transient (Transient Recovery Voltage) Voltage) which whic h the switch may not be able to handle. Consequently the selected fuse must be able to clear such a fault by itself, without making use of the switch. In pratice, this condition makes it necessary to check that the transition current of the switch-fuse combination, calculated as indicated in paragraph 8.102-3 of IEC 62 271-105, is less than the current observed on the primary. I40 < Ik
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
page 9
Selection of fuses for the protection of transformers
5 - APPLICATION EXAMPLES
LET US CHECK THAT THE FUSE 31.5 AMPS IS SITTING 20 KV/630 KVAMPS TRANSFORMER PROTECTION determination of the transformer characteristics Irt = 18 Amp s Ie = 198 Amp s Ik = 450 Amps s
determination of the fuse characteristics Irf > 1.4 Int (see p. p. 5) so Irf > 18x 1.4 =25.2 Amps; the selected fuseis 31.5 Amps On page 6, we find that for a 630 kVA transformer, T = 0.3 s On the curve (see page 12), for 0.3 s and a 31.5 Amps fuse, we find I z 160 Amps Amps < Ie, this fuse is not acceptable. So, we try with Irf = 40 Amps ; I z 210 Amps Amps > Ie, the 40 Amps fuse is OK. We find I40 on the curve page 12 for a time value of the SM6 0.036 s (0.9 time the opening opening time of the the fuse ; 0.04 for SM SM6 6 ; 0.06 for RM6). I40 = 360 Amp s I3 = 135 Amp s I1 = 40 kA s
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
page 10
Selection of fuses for the protection of transformers
These values meet the previous p revious requirement.
5 - APPLICATION EXAMPLES (cont’d) transfor mer
Int
Ie
fuse
Irf
Isc
I3
Iminifufu
I40
I1
switch
Itransfer
315 kVA
Fusarc CF
9A
25 A
41 A
1 08 A
130 A
210 A
630 kVA
Fusarc CF
18 A
31.5 A
101 A
198 A
160 A
N
630 kVA
Fusarc CF
18 A
40 A
135 A
19 8 A
210 A
360 A
O
23 0 A T
C
3 • 20
}
R
E
C
(see page 3)
See fuse documentation
Selection table for the SM6 Rating Rating in A. no overload - 5 °C < θ < 40 °C Please Please consult c onsult us for overload s and operation over 40 °C. °C.
oper operat atin ing g tran transf sfor orme merr out outpu putt rati rating ng (kVA) voltage
type type of fuse
(kV)
25
50
T 40 kA
Irt • 100 4 See pages 8 and 11
We find page 8 of the technical leaflet AC0479 about fuse for Irf = 40 Amps I3 = 135 and and L = 442 442 mm mm
R
45 0 A
Ie = X • Irt X = 11 (see page 6)
630
O
40 kA
100
rated voltage
125
16 0
200
250
3 15
400
500
63 0
8 00
1,600 0 2,00 2,000 0 2,50 2,500 0 (kV) (kV) 1,000 1, 1 ,250 1,60
UTE NFC standards: 13.100, 64.210 Solefuse 5.5
6.3
16
31.5
31.5
63
63
63
63
63
10
6.3
6.3
16
16
31.5
31.5
31.5
63
63
63
63
15
6.3
6.3
16
16
16
16
16
43
43
43
43
43
63
20
6.3
6.3
6.3
6.3
16
16
16
16
43
43
43
43
43
7.2 24 63
general case, UTE NFC standard: 13.200 Solefuse 3.3
16
16
31.5
31.5
31.5
63
63
10 0
100
5.5
6.3
16
16
31.5
31.5
63
63
63
80
80
1 00
125
6.6
6.3
16
16
16
31.5
31.5
43
43
63
80
1 00
125
125
10
6.3
6.3
16
16
16
31.5
31.5
31.5
43
43
63
80
80
10 0
12
13.8
6.3
6.3
6.3
16
16
16
16
31.5
31.5
31.5
43
63
63
80
17.5
15
6.3
6.3
16
16
16
16
16
31.5
31.5
31.5
43
43
63
80
20
6.3
6.3
6.3
6.3
16
16
16
16
31.5
31.5
31.5
43
43
63
22
6.3
6.3
6.3
6.3
16
16
16
16
16
31.5
31.5
31.5
43
63
200
7.2
24 63
Fusarc CF 3,3
16
25
40
50
50
80
80
100
125
125
200
5,5
10
16
31,5
31,5
40
50
50
63
80
100
12 1 25
12 1 25
16 1 60
160
6,6 10
10 6,3
16 10
25 16
31,5 20
40 25
50 31,5
50 40
63 50
80 50
80 63
100 80
12 125 80
12 125 100
16 160 10 0
125
13,8
6,3
10
16
16
20
25
31,5
31,5
40
50
50
63
80
80
100
7,2
200 125
12
125
17.5
15
6,3
10
10
16
16
20
25
31,5
40
50
50
63
80
80
100
125
125
20
6,3
6,3
10
10
16
16
25
25
31,5
40
40
50
50
63
80
100
125 24
22
6,3
6,3
10
10
10
16
20
25
25
31,5
40
40
50
50
80
80
100
in bold characters characters fuses from SIBA SIBA
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
page 11
Selection of fuses for the protection of transformers
Time/current charact eristi cs of a f use from the Fusarc Fusarc CF range range (Merlin Gerin)
5 - APPLICATION EXAMPLES (cont’d) T (s) 4
10 8 6 4 A 3 , 6
2 3
10 8 6 4
A A A A A A A A A 0 6 0 5 5 0 0 3 0 , 4 1 1 2 2 1 5 6 8 3
A 0 0 1
2 2
10 8 6 4 2 1
10 8 6 4 2 0
10 8 6 4 2 0,3 -1
10 8 6 4 2
0,036
-2
10 8 6 4
te a e d t
5 9 9 / 0 1 -
2
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
I (A)
160 210
10
1
2
4
6
8 10
2
2
4 I40 = 360
6
8 10
3
2
4
6
8 10
4
These curves are an average. average. The current accuracy accuracy is ± 10% page 12
Selection of fuses for the protection of transformers
6 - IDENTIFICATION PLATE
FUSE RATI RATING NG PLATE PLATE ON THE FRONT OF THE CUBICLE (QM ) In accordance with standard IEC 62 271-105, the front plate of the cubicle indicates that the use of the fuses at a permanent service current must be in accordance with the reference list
fuses see reference list IEC 62271-105 :2002 04 0 03 3 006 006 u
}
fixed fixed indications
} serial indication
Remark: if a customer does not use the fuses specified by the reference list, he must ensure with the technical department that the fuses installed are compatible with the requirements of IEC 62 271-105, the perfor mance of the SM6 switch and the cubicle environment (heat dissipation).
7 - SAFETY PRECAUTIONS
SAFETY PRECAUTIONS FOR ON-SITE FUSE REPLACEMENT When a fault occurs downstream of the switch, one or two fuses generally “blow”, the other(s) remaining intact. The characteristics of the remaining fuse or fuses are modified by the fault since they have been exposed to a current that may have been high enough to damage the fuse elements without actually blowing the fuse (the active part of a fuse is made up of a number of parallel elements).
It is therefore necessary, in the event of a downstream fault cleared by the protection cubicle, to change all three fuses and dispose of them immediately to avoid all possibility of subsequent use.
IF YOU HAVE ANY TROUBLE… Please contact the MV Technical Technical Department.
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
-
ed d i s i e v v e r 0 4 0 4/ 2 0
page 13
Selection of fuses for the protection of transformers
8 - BIBLIOGRAPHY
STANDARDS UTE C64-210 (May 1994) Appareillage à haute tension pour courant alternatif. Fusibles à haute tension pour postes de transformation public de type intérieur. s
UTE C13-100 (April (April 2001) 2001) Postes de livraison établis à l’intérieur d’un bâtiment et alimentés par un réseau réseau de distribution distribution pub lique de deuxième catégorie. catégorie. s
UTE C13-200 (April 1987) Installations électriques à haute tension : règles
s
IEC 60 288-1 (January 2002) Current-limiting Current-limiting fuses. s
IEC 62 271-105 (August 2002) High-voltage fuse-switch combination units for alternating current.
s
IEC 60 787 (1983) Application guide for the selection of high voltage fuse replacement elements for use in circuits comprising transformers.
s
PUBLICATIONS Merlin Gerin Cahier Technique publication no. 155 “MV public distribution networks throughout the world” by Christian Puret (ENSERG). s
Merlin Gerin Cahier Technique publication no. 128 “Design and utilisation of MV limiting fuses” by Olivier Bouilliez (Centrale Lyon).
s
Merlin Gerin Cahier Technique publication no. 70 “Guide d’utilisation des transformateurs de distribution” by Guy Bournerie (ENSIEG). s
Merlin Gerin Catalogue “MV distribution factory built assemblies - SM6 range”.
s
Merlin Gerin Catalogue “MV distribution switchgear fuses Fusarc Solefuse”.
s
MV fuse brochures Driescher, Wickmann, Siba, Mesa, Siemens, Alsthom.
s
Revue générale d’électricité (June 88 p. 3-11) “Des condensateurs pour tenir la tension et réduire les pertes dans les réseaux EDF”. s
Asea Revue 1984 n°3 p. 14-19 “Coupe-circuit intérieur intérieur pour une plus p lus grande p rotection”. rotection”. s
IEEE IEEE power ap parat. & syst. (trans.) July 82 p. p . 2056-60 “Characteristics of high-voltage current-limiting fuses for distribution systems”.
s
te a e d t
5 9 9 / 0 1 -
3 • 3 • B
Journal des électriciens (July/August 90 p. 28-30) “Départs moteurs”. moteurs”. s
-
ed d i s i e v v e r 0 4 0 4/ 2 0
s
Exploitation Exploitation c ellules VM6 (J. Lescure).
page 14