REVISIONS
Scenario1_BTS3900A+RRU+TP48200A+MW Note: 1. The scenario use GF tower site for an example, and if the site is RF mast, hardware installation is same; 2. We suggests that there should be 1U free space between two DCDU-12B;
Jumper 7/8'feeder AC power cable DC cable Grounding cable Fiber IF cable Ethernet cable
REV
Site type
Outdoor,GF tower
AC Power supply
380V
Powe equipment
RTN905/RTN950
Transmission port type
FE/GE
Other equipment
DCDU-12B
BTS3900A free space
9U
TP48200A free space
9U
OJO BTS Layout
AC iuput MCB requirement
3*25A
DC MCB distribution
LLVD:2*63A,2*32A; BLVD:2*16A,1*10A;
Battery
BAT:1*125A,
2*190AH
BTS3900A DC
TP48200A
FAN(1U) SLPU(1U) DCDU-12C (1U)
Blank(1U)
POWER SUBRACK AC/DC
BBU(2U) DCDU-12B-1 (1U)
DDF(1U) DCDU-12B(1U)
RTNxxx
AC BOX
RFC FAN DCDU-12A (1U)
R F U
R F U
R F U
R F U
R F U
R F U
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
4/21/2015
caibin
Scenario1_BTS3900A+RRU+TP48200A+MW_MCB Distribution LLVD
63A 63A
32A
32A 16A 16A
Note: 1. 1~6RRUs share 1 DCDU-12B, When RRU more than 6, need add 1 DCDU-12B. 2. We suggests that there should be 1U free space between two DCDU-12B for RRU cable route conveniently.
BAT
BLVD
10A 125A 125A
BTS3900A DC
TP48200A
DCDU-12C (1U) DCDU-12B(1U)
BBU(2U)
DCDU-12B in TP distribution for IDU(MW)
DCDU-12B-1 (1U)
BAT
DCDU-12B-2 (1U)
BAT
DCDU-12A (1U)
BTS3900A DC
TP48200A
FAN(1U) SLPU(1U) DCDU-12C (1U)
Blank(1U)
RTN9xx
POWER SUBRACK AC/DC
BBU(2U)
RRU Power distribution
DCDU-12B-1 (1U) DDF(1U)
DCDU-12B-2 (1U)
1
DCDU-12B(1U)
2
3
5
4
6
7
8
RTNxxx
RFC FAN DCDU-12A (1U)
R F U
R F U
R F U
R F U
R F U
R F U
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
DCDU-12B-2
DCDU-12B-1 LOAD 0 LOAD 1 LOAD 2 LOAD 3 LOAD 4 LOAD 5
D C DU-12B_1
1
2
D C DU-12B_2
7
8
3
4
5
6
LOAD 6
LOAD 7
LOAD 8
LOAD 9
reservation
reservation
reservation
reservation
reservation
reservation
reservation
reservation
RRU DC distribution from 3G_2100M RRUs, then 4G_1800M RRUs
Scenario1_BTS3900A+RRU+TP48200A+MW_Monitor Cable between TP&BTS BTS3900A
RJ485/RS232
TP48200A
Mon1
FAN
Mon0 COM_IN
DCDU-12C B F A
Ethernet cable
COM_OUT
SMU02B
TMC11H
COM_OUT
COM_IN
UIM02C UEIU
UMPTb1
PSU
PSU
PSU
PSU
UPEU
DCDU-12B
COM_OUT
COM_IN
FMU
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
DCDU-12A
MRFU d
MRFU d
MRFU d
CPRI1
CPRI1
CPRI1
CPRI0
CPRI0
CPRI0
RFC
Note: for temporary scenario, BBU install at TP cabinet, the monitor cable from TP to BBU, BBU side is port “Monitor0”at UPEU board.
Scenario1_BTS3900A+RRU+TP48200A+MW_Transmission Cable between RTN&BTS BTS3900A
TP48200A
FAN FE/GE
Ethernet cable
SLPU
TMC11H
UFLP
0
IN 1 SIDE
0
OUT 1 SIDE
DCDU-12C B F A
UEIU
RTN905
EG6
1
2
3
4
UPEU
UMPTb1
DCDU-12B
FMU
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
DCDU-12A
MRFU d
MRFU d
MRFU d
CPRI1
CPRI1
CPRI1
CPRI0
CPRI0
CPRI0
RFC
NOTE: If use the RTN950, the transmission cable should connect to the GE electrical port 3 of EG4 board.
Scenario1_BTS3900A+RRU+TP48200A+MW_Antenna&Feeder Sysyterm & Color Ring Sector A Blue 2100M_3G TX RX
900M_GSM TX RX 1
2
3
4
1800M_4G TX RX 5
6
900M_GSM TX RX 1
Sector A
RRU3939
1800
2
3
4
1800M_4G TX RX 5
6
2100M
1800M
RRU3839
RRU3939
2100
AISG cable
MFRU 900M
900
1800
Sector C Yellow 2100M_3G TX RX
900M_GSM TX RX 1
2
3
4
1800M_4G TX RX 5
6
900M_GSM TX RX 1
Sector B
Sector B
1800M
900
Sector B Red 2100M_3G TX RX
2100M
1800M
RRU3839
RRU3939
2100
AISG cable
MFRU 900M
900
1800
Sector D White 2100M_3G TX RX
2
3
1800M_4G TX RX
4
5
6
Sector B
2100M
1800M
RRU3839
RRU3939
2100
AISG cable
MFRU 900M
2100M RRU3839
900
1800
2100
AISG cable
MFRU 900M
REVISIONS
Temporary Scenario_TP48200A+RRU+MW
REV
OJO BTS Layout
Note: 1. The scenario use GF tower site for an example, and if the site is RF mast, hardware installation is same; 2. We suggests that there should be 1U free space between two DCDU-12B;
Site type
Outdoor,GF tower
AC Power supply
380V
Powe equipment
RTN905/RTN950
Transmission port type
FE/GE
Other equipment
DCDU-12B
TP48200A free space
9U
AC iuput MCB requirement
3*25A
DC MCB distribution
LLVD:2*63A,2*32A; BLVD:2*16A,1*10A;
Battery
BAT:1*125A,
AC
BAT LLVD BLVD 63A 63A 32A 32A 16A 16A 10A 125A 125A PSU
PSU
PSU
PSU
B F A
AC power cable DC cable Grounding cable Fiber IF cable Ethernet cable
UIM02C
SMU02B
2*190AH
UEIU UPEU
UMPTb1 DDF(1U)
RTN905
EG6
1 3
2 4
Free space(1U)
AC BOX
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
4/21/2015
caibin
REVISIONS
Scenario2_DBS3900A+TP48200A_Micro on pole Note: 1. The scenario use GF Micro on pole site for an example 2. the AC cable,RRU fiber,RRU DC cable need use PVC pipe protection. 3. we suggest customer install 1pcs ODF in APM30H cabinet
AC power cable DC cable Grounding cable Fiber
Site type
Outdoor,GF tower
AC Power supply
380V
Powe equipment
RTN905/RTN950
Transmission port type
FE/GE
Other equipment
DCDU-12B
APM30H DC free space
9U
TP48200A free space
9U
REV
OJO BTS Layout
AC iuput MCB requirement
3*25A
DC MCB distribution
LLVD:2*63A,2*32A; BLVD:2*16A,1*10A;
Battery
BAT:1*125A,
4/21/2015
2*190AH
Fiber pigtail
TP48200A Blank(1U)
POWER SUBRACK AC/DC
AC BOX
DDF(1U) DCDU-12B(1U)
APM30H DC FAN(1U) SLPU(1U) DCDU-12C (1U)
BBU(2U) DCDU-12B-1 (1U)
ODF
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
caibin
Scenario2_DBS3900A+TP48200A_Micro on pole _MCB Distribution LLVD
63A 63A
32A
BAT
BLVD
32A 16A 16A
10A 125A 125A
BTS3900A DC
TP48200A
DCDU-12C (1U) DCDU-12B(1U)
BBU(2U) DCDU-12B-1 (1U)
BAT BAT
TP48200A Blank(1U)
RRU Power distribution
POWER SUBRACK AC/DC DDF(1U)
1
DCDU-12B(1U)
2
3
4
5
6
APM30H DC FAN(1U) SLPU(1U) DCDU-12C (1U)
BBU(2U) DCDU-12B-1 (1U)
ODF
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
B A T T E R Y
DCDU-12B-1
DC distribution from 2G_900M, then 3G_2100M, at last 4G_1800M RRU
Scenario2_DBS3900A+TP48200A_Micro on pole_Monitor Cable between TP&APM30H TP48200A
SMU02B UIM02C RJ485/RS232
PSU
PSU
PSU
PSU
Mon1 Mon0 Ethernet cable(Monitor cable from TP to BBU)
APM30H DC FAN
COM_IN
COM_OUT
DCDU-12C B F A
UEIU
UMPTb1
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
UPEU
DCDU-12B
Scenario2_DBS3900A+TP48200A_Micro on pole_Transmission Cable between ODF&BBU
TP48200A FE/GE1(optical port)
SMU02B UIM02C
Fiber pigtail
PSU
PSU
PSU
PSU
APM30H DC FAN
SLPU
UFLP
0
IN 1 SIDE
0
OUT 1 SIDE
DCDU-12C B F A
Battery
Battery
Battery
Battery
Battery
Battery
Battery
Battery
UEIU UMPTb1
UPEU
DCDU-12B-1
ODF