Type MCGG 22, 42, 52, 53, 62, 63 & 82 Overcurrent Relay for Phase and Earth Faults
Type MCGG 22, 42, 52, 53, 62, 63 & 82 Overcurrent Relay for Phase and Earth Faults
Figure 1: Relay type MCGG 62 withdrawn from case.
Features • Choice of 4 inverse time curves and 3 definite time ranges by switched selection.
• Accurately follows time curves to BS142 and IEC60255. • High resetting ratio. • Fast resetting time.
• Wide setting range of 0.05 x In to 2.4 x In in steps of 0.05 x In.
• Positive, calibrated settings by means of switches.
• Time multiplier range 0.05 to 1 on all seven characteristics.
• Internal dc auxiliary power supply operating over a wide input range.
• Separate LED indicators provided on each measuring board to show time delayed and instantaneous operations. • LED start indicators provided to facilitate testing. • Separate output contacts provided for time delayed phase fault, instantaneous phase fault, time delayed earth fault and instantaneous earth fault operations. • Low ac burden. • Suitable for use with separate direction relay.
2
• Separate test mode with trip test feature. • Indication of power to the measuring board. • Non-volatile memory for time delayed and instantaneous LED indicators.
MCGG 53 Two phase overcurrent (with polyphase measurement) plus earth fault with instantaneous elements.
Models available MCGG 22 Single phase overcurrent with instantaneous element.
MCGG 62 Three phase overcurrent with instantaneous elements.
MCGG 42 Two phase overcurrent with instantaneous elements.
Associated publications: Midos System R6001 Directional Relay R6003
MCGG 63 Three phase overcurrent (with polyphase measurement), with instantaneous element.
MCGG 52 Two phase overcurrent plus earth fault with instantaneous elements.
3 phase 2 phase Single phase Measuring overcurrent overcurrent or earthfault boards † inst † inst † inst
Model MCGG MCGG MCGG MCGG MCGG MCGG MCGG
MCGG 82 Three phase overcurrent plus earth fault with instantaneous elements.
22 42 52 53 62 63 82
Application The relay can be used in applications where time graded overcurrent and earth fault protection is required. The relay can be used to provide selective protection for overhead and underground distribution feeders. Other applications include back-up protection for transformers, generators and HV feeder circuits and the protection of neutral earthing resistors. With all the current/time characteristics available on one relay, a standard relay can be ordered before detailed coordination studies are carried out – a distinct advantage for complex systems. Also, changes in system configuration can be readily accommodated.
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
●
● ●
For applications where the instantaneous earth fault element is required to have a sensitive setting whilst remaining stable on heavy through faults the use of a stabilising resistor is recommended. The current transformers for this application must satisfy the criteria detailed under ‘Current transformer requirements’ in Technical Data. The total impedance of the relay and the series stabilising resistor is usually low enough to prevent the current transformers developing voltages over 2kV during maximum internal faults, but in some applications a non-linear resistor is required to limit this voltage. Non-standard resistance values and non-linear voltage limiting devices are available.
An instantaneous element with low transient overreach is incorporated within each phase or earth fault measuring board. This can be easily disabled in applications where it is not required.
3
1 2 3 2 3 1 4
Case size 4 6 8 8 6 6 8
Description This range of MCGG relays is designed so that versions are available with separate measuring boards for each phase or earth fault input; alternatively, phase inputs may be combined on to one board for polyphase measurement (see table). These boards, together with the other circuits of the relay, are contained in a single plug-in module which is supplied in a size 4, 6 or 8 Midos case. The case incorporates one or two terminal blocks for external connections. Removal of the module automatically short circuits the current transformer connections by means of safety contacts within the case terminal block. For added security, when the module is removed, the CT circuits are short circuited before the connections to the output contacts and the dc supply are broken. The relay uses solid state techniques, each measuring board utilising a microcomputer as a basic circuit element. The current measurement, whether performed on a single phase or polyphase input, is performed via an analogue-to-digital converter. Application diagrams are provided in Figures 2 to 8 (inclusive) showing typical wiring configurations.
Each measuring board has a built-in ‘power off’ memory feature for the time delayed and instantaneous LED indicators. Power to each measuring board may be tested whilst the relay is in service, without affecting the current measurement. A test mode is also available to carry out a trip test on the output relays. During this test, current measurement is inhibited. When required, directional control can be exercised over the relay by connecting an output contact from direction relay type METI to the terminals provided. Separate output contacts, capable of circuit breaker tripping, are provided for time delayed phase faults, instantaneous phase faults, time delayed earth fault and instantaneous earth fault operations.
Switch position (0) (1) ● ● ●
Operating characteristic Trip test
● ● ●
Standard inverse
t=
0.14 (I0.02 – 1)
sec SI
Very inverse
t=
13.5 (I – 1)
sec VI
●
Extremely inverse
t=
80 (I2 – 1)
sec EI
● ●
Long time earth fault t =
120 (I – 1)
sec LT
● ● ● ● ●
● ● ●
Definite time 2 seconds
D2
Definite time 4 seconds
D4
Definite time 8 seconds
D8
● ● ● ● ● ● ●
Table1: Operating time characteristics with corresponding switch positions.
Relay settings Separate setting switches for each measuring board are provided on the relay frontplate. These are used to select the required time/current characteristic, current and time multiplier settings. Selection of time characteristics
The current/time characteristic selection is carried out by means of three switches (identified by symbol on the nameplate). Table 1 gives the basic operating characteristic and the settings of the switches. Time multiplier setting
The time given by each of the operating characteristics must be multiplied by the time multiplier to give the actual operating time of the relay. This control is marked xt = Σ where Σ is the sum of all the switch positions. The range of multiplication is from 0.05x to 1.0x in steps of 0.025.
4
This acts as a conventional time multiplier on the current dependent characteristics and gives the following time ranges for the definite time characteristics. Operating characteristics s 2 4 8
Time range s 0.1 to 2.0 in 0.05s steps 0.2 to 4.0 in 0.1s steps 0.4 to 8.0 in 0.2s steps
Trip test
Current setting
Current measurement is inhibited by setting the curve selection switches to 111. This causes all three LEDs to flash once per second. If the reset push button is then pressed for approximately six seconds, both output relays associated with that measuring board will operate.
Time delayed element
The current setting control is marked Is = Σ x In where Is is the current setting in amps, Σ is the sum of all the switch positions and In is the relay rated current in amps. Each measuring board provides a setting range of 0.05 x In to 2.4 x In in steps of 0.05 x In.
Power supply healthy test
If, whilst the relay is in service, the reset button is pressed, all the LEDs are illuminated, indicating that there is power to the measuring boards. The LEDs are reset on releasing the push button. During this test, normal current measurement is not inhibited.
Instantaneous element
The setting control of the instantaneous element is marked Iinst = Σ x Is where Σ is the sum of the switch positions and Is is the time delayed element setting. When all switches are set to the left (at zero), or when the lowest switch is set to infinity regardless of the positions of the other five switches, the instantaneous feature is rendered inoperable. The range of adjustment of finite settings is from 1x to 31x in unity steps.
A
S2
A
P1
P2
B
Figure 2: Type MCGG 22 nameplate
S1 B
C
C
Phase rotation
Directional control PhA (See Note 4)
TMS setting
24
Inst setting
Curve selection
23
(See Note 2)
27
IA
Time delayed trip Inst. trip
µC PhA
Is
Indicator reset
RL1–1
28
Input circuit Ph
Current setting Ph
I>Is
5
RL1 2
Case earth 1
2
5
6
7
8
9
10
13
14
15
16
Vx
+VE –VE
13 14 26
Output circuits Ph
Power supply circuits
RL2 2 Case earth connection
23
24 26
27
(See Note 3)
28
Module terminal block viewed from rear
(b) (c)
RL1–2
2
CT shorting links make before (b) and (c) disconnect. Short terminals break before (c). Long terminals
2. When directional control is required the contacts of the directional relays should be connected as shown. Contacts must close to inhibit overcurrent relay. 3. Earthing connections (CTs) are typical only. 4. CT connections are typical only.
Figure 3: Application diagram (10 MCGG 22 02): static modular overcurent relay type MCGG 22. Single phase with instantaneous element. 5
Phase fault time delayed trip output contacts
1
RL2–1
8 10 9
RL2–2
16 15
MCGG 22
Notes: 1. (a)
7 6
Phase fault instantaneous trip output contacts
A
A
P2
P1
S2
B
S1
Directional control PhA
C C
B Phase rotation (See Note 4)
TMS setting
Inst setting
Curve selection
Indicator reset
49 50
(See Note 2)
21
IA
Is
RL1 2
Time delayed trip Inst. trip
µC PhA
Input circuit Ph
23
Current setting Ph
I> Is
45
25 29
30
6
33
34
7
8
35
36
9
10
37
38
11
12
13
14
41
42
15
16
1
2
3
4
5
IC
Inst setting
Curve selection
18
45
46
19
20
47
48
21
22
49
50
23
24
25
26
27
28
Input circuit Ph
27
+VE –VE
28 13
1
38
RL2–2
41
Phase fault instantaneous trip output contacts
I> Is
MCGG 42
CT shorting links make before (b) and (c) disconnect. Short terminals break before (c). Long terminals
(b) (c)
36
42
Current setting Ph
Case earth connection
Module terminal block viewed from rear (with integral case earth strap)
Phase fault time delayed trip output contacts
Power supply circuits
14
(See Note 3) Notes: 1. (a)
29
37
Time delayed trip Inst. trip
µC PhC
Is
RL2–1
26
Vx
17
34
RL1–2
30 TMS setting
46 Case earth
35 33
RL2 2
24
Directional control PhC
RL1–1
Output circuits Ph
22
2. When directional control is required the contacts of the directional relays should be connected as shown. Contacts must close to inhibit overcurrent relay. 3. Earthing connections are typical only. 4. CT connections are typical only.
Figure 4: Application diagram (10 MCGG 42 03): static modular overcurent relay type MCGG 42. Two phase with instantaneous element.
P2
A A
P1 S2
B
S1
C
Directional control PhA
TMS setting
49
Inst setting
Curve selection
Indicator reset
50
B
C
(See Note 2)
(See Note 4)
Phase rotation
21
IA
Is 22
Input circuit Ph
23
Directional control PhC
Current setting Ph
RL1 2
Time delayed trip
µC PhA
Inst. trip
I >I s
RL1–1
Output circuits Ph
33
RL2 2
34
RL1–2
TMS setting
45
Inst setting
Curve selection
RL2–1
IC
Is
26
29
Directional control E/F
30
2
3
4
5
6
33
34
7
8
35
36
9
10
37
38
11
12
Input circuit Ph
13
14
41
42
16
43
44
17
18
45
46
19
20
47
48
21
22
49
50
23
24
25
26
27
28
38
RL2–2
RL3–1 Inst setting
Curve selection
Notes: 1. (a) (b) (c)
–VE
7
5
13 14 17
Power supply circuits
Input circuit
Current setting
Inst. trip
RL3–2
I >I s
RL4–1 RL4 2
8
9 16 15
3. Earthing connections are typical only. 4. CT connections are typical only.
Figure 5: Application diagram (10 MCGG 52 03): static modular overcurent relay type MCGG 52. Two phase plus earth fault with instantaneous elements. 6
Earth fault time delayed trip output contacts
10
MCGG 52
2. When directional control is required the contacts of the directional relays should be connected as shown. Contacts must close to inhibit overcurrent relay.
2 1
Output circuits
RL4–2
Case earth connection
CT shorting links make before (b) and (c) disconnect. Short terminals break before (c). Long terminals
RL3 2
Time delayed trip
µC
Is 28
Vx
Phase fault instantaneous trip output contacts
6
27
+VE
42 41
I >I s
44
(See Note 3)
Module terminal block viewed from rear (with integral case earth strap)
Current setting Ph
TMS setting
43
E/F
15
µC PhC
36 37
Time delayed trip Inst. trip
25
1
29
Phase fault time delayed trip output contacts
30
24
46
Case earth
35
Earth fault instantaneous trip output contacts
P2
A A
P1 S2
B
Directional control PhA
S1
C
49
TMS setting
Inst setting
Is
µC Ph
Indicator reset
Curve selection
50
B
C
(See Note 2)
(See Note 4)
Phase rotation
21
IA
RL1 2
Time delayed trip Inst. trip
22
Current setting Ph
23
Directional control PhC
RL1–1
35
Output circuits Ph
I >I s
33
RL2 2
34
RL1–2
29 30
24
RL2–1
45
36 37
46
38
25
RL2–2
IC
41
26
29
30
6
33
34
7
8
35
36
9
10
37
38
11
12
13
14
41
42
15
16
43
44
17
18
45
46
19
20
47
48
2
3
4
5
21
22
23
24
25
26
27
Directional control E/F
RL3–1 Inst setting
27
Curve selection
5
RL3 2
Time delayed trip
µC
E/F
49
Inst. trip
Is 13
+VE
14
–VE
17
50
Module terminal block viewed from rear (with integral case earth strap
CT shorting links make before (b) and (c) disconnect. Short terminals break before (c). Long terminals
(b) (c)
Input circuit
Current setting
I >I s
2
RL4–1
Earth fault time delayed trip output contacts
8
RL4 2
10 9
RL4–2
Case earth connection
(See Note 3)
28
Power supply circuits
RL3–2
1
Output circuits
28
Notes: 1. (a)
7 6
TMS setting
43 44
Vx
Phase fault instantaneous trip output contacts
42
Input circuit Ph
Case earth 1
Phase fault time delayed trip output contacts
16
Earth fault instantaneous trip output contacts
15
MCGG 53
2. When directional control is required the contacts of the directional relays should be connected as shown. Contacts must close to inhibit overcurrent relay.
3. Earthing connections are typical only. 4. CT connections are typical only.
Figure 6: Application diagram (10 MCGG 53 02): static modular overcurent relay type MCGG 53. Two phase (with polyphase measurement), plus earth fault with instantaneous elements.
P2
A A
P1 S2
B
S1
C
Directional control PhA
TMS setting
49
Inst setting
Curve selection
Indicator reset
50
B
C
(See Note 2)
(See Note 4)
Phase rotation
21
IA 22
Directional control PhB
Input circuit Ph
Current setting Ph TMS setting
47
Time delayed trip
µC PhA
Is
RL1–1
Inst. trip
Inst setting
33
RL1 2
I>Is Curve selection
Output circuits Ph
48 23
IB 24
Case earth 1
13
14
29
30
33
34
35
36
37
38
41
42
45
46
47
48
49
50
Directional control PhC
Input circuit Ph
Current setting Ph
34
RL1–2
TMS setting
38
RL2–2
I>Is
Inst setting
25
IC 26
Vx
22
23
24
25
26
(See Note 3)
27
28
Notes: 1. (a) (b) (c)
+VE –VE
13 14 1
Power supply circuits
Input circuit Ph
Current setting Ph
Case earth connection
Time delayed trip Inst. trip
I>Is
MCGG 62
CT shorting links make 2. When directional control is required the contacts before (b) and (c) disconnect. of the directional relays should be connected as shown. Short terminals break before (c). Contacts must close to inhibit overcurrent relay. Long terminals
3. Earthing connections are typical only. 4. CT connections are typical only.
Figure 7: Application diagram (10 MCGG 62 03): static modular overcurent relay type MCGG 62. Three phase with instantaneous element. 7
41 42
Curve selection
µC PhC
Is
36 37
RL2 2
28 45
29
Phase fault time delayed trip output contacts
30
RL2–1
46
21
Module terminal block viewed from rear (with integral case earth strap)
µC PhB
Is
27
Time delayed trip Inst. trip
35
Phase fault instantaneous trip output contacts
P2
A A
P1 S2
B
Directional control PhA
S1
C
49
TMS setting
Inst setting
Is
µC Ph
Indicator reset
Curve selection
50
B
C
(See Note 2)
(See Note 4)
Phase rotation
21
IA
RL1 2
Time delayed trip Inst. trip
22
Directional control PhB
Current setting Ph
47
RL1–1
Output circuits Ph
I> Is
35 33
RL2 2
34
RL1–2
29
Phase fault time delayed trip output contacts
30
48
RL2–1
23
38
24
Directional control PhC Case earth
36 37
IB RL2–2
41
Phase fault instantaneous trip output contacts
42
45 46
29
25
30
1
2
3
4
5
6
33
34
7
8
35
36
9
10
37
38
11
12 41
42
IC
13
14
15
16
17
18
45
46
19
20
47
48
21
22
49
50
23
24
25
26
27
28
26
Input circuit
27
28
Vx
+VE –VE
13 14 1
Case earth connection
(See Note 3) Notes: 1. (a)
Module terminal block viewed from rear (with integral case earth strap)
Power supply circuits
CT shorting links make before (b) and (c) disconnect. Short terminals break before (c). Long terminals
(b) (c)
MCGG 63
2. When directional control is required the contacts of the directional relays should be connected as shown. Contacts must close to inhibit overcurrent relay.
3. Earthing connections are typical only. 4. CT connections are typical only.
Figure 8: Application diagram (10 MCGG 63 02): static modular overcurent relay type MCGG 63. Three phase (with polyphase measurement) with instantaneous element.
A
A B
P2 S2
P1 S1
C C
B
Directional control PhA
TMS setting
50
N
Phase rotation
Indicator reset 49
(See Note 2) 21 (See Note 4)
IA
Is 22
Directional control PhB
Case earth 29
30
6
33
34
7
8
35
36
9
10
37
38
11
12
13
14
41
42
15
16
43
44
17
18
45
46
19
20
47
48
21
22
49
50
1
2
3
4
5
23
24
25
26
27
28
Is 24
TMS setting
25
IC
Is
43
28
2. When directional control is required the contacts of the directional relays should be connected as shown. Contacts must close to inhibit overcurrent relay.
(See Note 3)
–VE
34
RL1–2
29
Phase fault time delayed trip output contacts
30 36 37
Inst. trip
38
RL2–2
I>Is
13 14 17
Inst setting
Power supply circuits
RL3–1
41
Phase fault instantaneous trip output contacts
Is
µC E/F
5
Inst. trip
RL3–2
Time delayed trip Inst. trip
RL3 2
RL4–1
Earth fault time delayed trip output contacts
8 10 9
Output circuits E/F
MCGG 82
Case earth connection
3. Earthing connections are typical only. 4. CT connections are typical only.
Figure 9: Application diagram (10 MCGG 82 03): static modular overcurent relay type MCGG 82. Three phase plus earth fault with instantaneous elements (4 wire system). 8
2 1
Curve selection
I>Is
7 6
Time delayed trip
I>Is Inst setting
Input circuit Current setting E/F E/F
Curve selection
µC PhC
TMS setting
27
Vx
RL2 2
Time delayed trip
µC PhB
35 33
Curve selection
Inst setting
Input circuit Current setting Ph Ph
44
+VE
RL1–1 Output circuits Ph
42 45
26
CT shorting links make before (b) and (c) disconnect. Short terminals break before (c). Long terminals.
Inst. trip
I>Is
Input circuit Current setting Ph Ph
46
Directional control E/F
RL1 2
Time delayed trip
RL2–1
IB
Notes:
(b) (c)
TMS setting
23
Module terminal block viewed from rear (with integral case earth strap)
1. (a)
47
Curve selection
µC PhA
Input circuit Current setting Ph Ph
48
Directional control phase PhC
Inst setting
RL4–2 RL4 2
16 15
Earth fault instantaneous trip output contacts
Technical Data Ratings
AC current (In)
1A or 5A
Frequency
50/60Hz
DC supply (Vx)
24/54V, 48/125V or 110/250V
Burdens
AC Burden
Less than 0.25 VA for 1A relays and less than 0.5VA for 5A relays, at unity power factor and at rated current on any setting. The impedance of the relays over the whole of the setting range (5% to 240% rated current) is less than 0.25Ω for 1A relays and less than 0.02Ω for 5A relays and is independent of current.
DC burden
Relay rating
Relay type MCGG
MCGG
MCGG
MCGG
22, 63
42, 53
52, 62
82
24/54
1.5W
2.5W
3.0W
4.0W
48/125
2.0W
3.0W
3.5W
4.5W
110/250
2.5W
3.5W
4.0W
5.0W
The figures above are maxima under quiescent conditions. With output elements operated they are increased by up to 2.5W per element. Current transformer requirements
Relay and CT secondary rating (A)
Nominal output (VA)
Accuracy class
Accuracy Limiting lead limit current resistance – (X rated current) one way (ohms)
1
2.5
10P
20
1
5
7.5
10P
20
0.15
Note: For 5A applications with longer leads, the CT rating can be increased in steps of 2.5VA where each step of 2.5VA is equivalent to additional 0.06Ω lead resistance. Instantaneous earth fault element
For installations where the earth fault element is required to have a sensitive setting whilst remaining stable on heavy through faults, the use of a stabilising resistor is recommended, the value of which will vary according to the specific application. If assistance is required in selecting the appropriate value, please consult the Applications Department of ALSTOM T&D Protection & Control Ltd.
9
Time delayed settings (Is), phase/ earth fault measuring range: 5% to 240% of In in 5% steps.
Setting ranges
Instantaneous setting (Iinst) 1 x –31 x
Is in 1 x 1s steps
Operating time
Time delayed element Operating characteristics selectable to give:
Shown in Figure 10 Standard inverse IDMT Very inverse IDMT Extremely inverse IDMT Long time earth fault IDMT Definite time 2s, 4s, 8s
Time multiplier setting
0.05 to 1.0 in 0.025 steps (applicable to all time characteristics)
Instantaneous elements
Shown in Figure 11 For settings of 5 x Is and above: <35ms at 2x instantaneous setting
Accuracy – reference conditions
Current setting (Is)
Reference range 0.05In to 2.4In for MCGG 22, 42, 52, 62, 82 and E/F element of MCGG53. 0.2In to 2.4In for phase fault elements of MCGG 53 and 63.
Input current
Time characteristic
Reference range
Standard inverse Very inverse Long time inverse
2 x Is to 31 x Is
Extremely inverse
2 x Is to 20 x Is
Definite time
1.3 x
Ambient temperature
20°C
Frequency
50Hz to 60Hz
Time multiplier setting
1x
DC auxiliary voltage
Reference ranges
Is to 31 x Is
24V to 54V 48V to 125V 110V to 250V
10
100
10
Operating time t (seconds)
Definite 8 seconds
Definite 4 seconds Longtime standby earth fault 120 t= I–1 Standard inverse 0.14 t = 0.02 I –1
Definite 2 seconds
1.0
Very inverse 13.5 t= I–1
Figure 10: Time delayed overcurrent element – operation time characteristics.
Extremely inverse 80 t= 2 I –1 0.1 1
10
100
I( x Is) Current (multiple of setting)
240 220 200 180
Operating time (ms)
160 140 120 100
Iinst = 1Is
80 2Is
60 40
5-31Is
4Is
3Is
20 0 1
10 Current (multiple of instantaneous setting)
Figure 11: MCGG instantaneous operating times (various settings). 11
100
Accuracy – influencing quantities
On settings 0.05 to 1.0 ±2% or ±30ms whichever is the greater
Time multiplier Ambient temperature operative range
–25°C to +55°C
Variations over this range Setting current
±5%
Time characteristic
Time variation
Standard inverse Very inverse Long time inverse
±5%
Extremely inverse
±7.5%
Definite time
±3%
Frequency Setting current
±1% over the range 47 – 62Hz
Operating time
±2% or ±30ms whichever is the greater, over the range 47–52Hz or 57–62Hz.
DC auxiliary voltage
Vx dc(V)
Operative range (V)
24/54
19 – 60
48/125
37.5 – 150
110/250
87.5 – 300
Variations over these ranges Setting current
±1%
Operating time
±2% or ±30ms whichever is greater
Accuracy – general
Current setting Time delayed element Instantaneous elements All other settings
Is to 1.1 x Is Iinst = 1 x Is 1.0 x Iinst to 1.1 x Iinst Iinst ±5% 1.0 x
Operating time Time characteristic
Accuracy
Standard inverse Very inverse Long time inverse
±5%
Extremely inverse
±7.5% ±30ms whichever is greater
Definite time
±3%
Repeatability (within basic accuracy claim) Pick-up current
Better than ±1%
Operating time
Better than ±2% or ±30ms whichever is greater.
Overshoot time
Less than 30ms (when the input current is reduced from any value within the operative range to zero). 12
Resetting current
Time delayed and instantaneous elements: not less than 95% of time delayed current setting.
Resetting and disengaging times
Less than 70ms (when the input current is reduced from any value within the operative range to zero).
Transient overreach
System time constant up to 30ms: 5%
(instantaneous elements)
System time constant up to 100ms: 12%
Thermal withstand
Continuous withstand
2 x Is or 2.6 x In whichever is lower, with a minimum of 1 x In
Short time withstand
For 1s: 100 x maximum For 3s: 57 x maximum
In with 400A
In with 230A
Operation indicators
Each measuring board is fitted with two red LED indicators, one showing time delayed operation and the other showing instantaneus operation. The reset button provided on the frontplate resets all the operation indicators. The green timer start indicator illuminates when the input current exceeds the setting current Is to facilitate testing of the module. This indicator is self resetting. LED covers are available to eliminate any undesired LED indication. Contacts
Changeover Make MCGG 52, 53, 82
Phase fault time delayed element
1
1
Phase fault instantaneous element
1
1
Earth fault time delayed element
1
1
Earth fault instantaneous element
1
1
MCGG 22, 42, 62, 63 Time delayed element
1
1
Instantaneous element
1
1
13
Contact ratings
Make and carry for 0.2s and 300V ac or dc
7500VA subject to maxima of 30A
Carry continuously
5A ac or dc
Break
ac – 1250VA dc – 50W resistive 25W, L/R = 0.04s
subject to maxima of 5A and 300V
Durability Loaded contact
10,000 operations minimum
Unloaded contact
100,000 operations minimum
Directional control
Directional control can be exercised over each pole individually by connecting the output contact of a relay type METI across appropriate case terminals. Relay type
Direction control terminals
MCGG 22
23,24
MCGG 42
45, 46, 49, 50
MCGG 52, 53
43 to 46, 49, 50
MCGG 62, 63
45 to 50
MCGG 82
43 to 50
Note: The directional control circuits are isolated from all other circuits but are electrically connected to the relay case. These circuits must not, therefore, be insulation or impulse tested to the case. High voltage withstand
Dielectric withstand IEC 60255-5: 1977
2kV rms for 1 minute between all case terminals connected together and the case earth terminal, with the exception of the directional control terminals. 2kV rms for 1 minute between terminals of independent circuits, with terminals on each independent circuit connected together. 1kV rms for 1 minute across open contacts of output relays.
High voltage impulse IEC 60255-5: 1977
14
Three positive and three negative impulses of 5kV peak, 1.2/50µs, 0.5J between all terminals and case earth and between adjacent terminals, with the exception of the directional control terminals, (see note).
Electrical environment
High frequency disturbance IEC 60255-22-1: 1988 Class III
2.5kV peak between independent circuits and case earth. 1kV peak across terminals of the same circuit. Note: The directional control terminals comply with class II and will withstand 1kV peak between all independent circuits, and 500V peak across the directional control terminals.
DC supply interruption IEC 60255-11: 1979
AC ripple on dc supply IEC 60255-11: 1979 Fast transient disturbance IEC 60255-22-4: 1992 Class IV
Electrostatic discharge IEC 60255-22-2: 1996 Class II
Surge immunity IEC 61000-4-5: 1995 Level 4
EMC compliance 89/336/EEC
EN50081-2: 1994 EN50082-2: 1995 Product safety 73/23/EEC
The unit will withstand a 10ms interruption in the auxiliary supply, under normal operating conditions, without de-energising. The unit will witstand 12% ac ripple on the dc supply. 4kV, 2.5kHz applied directly to auxiliary supply. 4kV, 2.5kHz applied directly to all inputs. 4kV discharge in air with cover in place 4kV contact discharge with cover removed. 4kV peak, 1.2/50µs between all groups and case earth. 2kV peak, 1.2/50µs between terminals of each group. Compliance with the European Commission Directive on EMC is claimed via the Technical Construction File route. Generic Standards were used to establish conformity. Compliance with the European Commission Low Voltage Directive.
EN 61010-1: 1993/A2: 1995 EN 60950: 1992/A11: 1997
15
Compliance is demonstrated by reference to generic safety standards.
Atmospheric environment
Temperature IEC 60255-6: 1988
IEC 60068-2-1: 1990 IEC 60068-2-2: 1974
Storage and transit –25°C to +70°C Operating –25°C to +55°C Cold Dry heat
Humidity IEC 60068-2-3: 1969
56 days at 93% RH and 40°C
Enclosure protection IEC 60529: 1989
IP50 (dust protected)
Mechanical environment
Vibration IEC 60255-21-1: 1988
16
Response Class 1 Endurance Class 1
Cases 52
MCGG 22 Size 4 MCGG 42 Size 6
4 holes Ø4.4
97
23.5
MCGG 62 Size 6 All dimensions in mm.
MCGG 63 Size 6
168
159
MCGG 52 Size 8 MCGG 53 Size 8 Push button projection 10 max.
MCGG 82 Size 8
99 Panel cut-out: Flush mounting fixing details.
The dimensions of the cases are shown in Figures 12, 13 and 14. 32
212
25 min.
157 max.
177
103
11
Flush mounting.
Figure 12: Case outline size 4.
103.6 4 holes Ø4.4
149
23.5
All dimensions in mm. 159
168
Push button projection 10 max.
151 Panel cut-out: Flush mounting fixing details. 32
Flush mounting.
Figure 13: Case outline size 6.
17
25 min.
157 max.
177
155
212
11
155.4
4 holes Ø4.4
200
24
159
168
Push button projection 10 max.
203 Panel cut-out: Flush mounting fixing details.
32
Flush mounting.
All dimensions in mm.
Figure 14: Case outline size 8.
Information Required with Order Relay type (see models available). Rated current and frequency. DC auxiliary voltage range. Requirement for LED cover part GJ0280 001. (These self adhesive LED covers can be supplied to cover the instantaneous LED when used in auto-reclose applications as the LEDs remain on during normal use).
18
25 min.
157 max.
177
206
212
11
19
ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email:
[email protected] Internet: www.alstom.com ©1999 ALSTOM T&D Protection & Control Ltd Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
Publication R6054X
089920 CPS Printed in England.