Moulded Case Circuit Breaker (MCCB)
1
Comprehensive range : 25A - 1600A in different frame sizes
2
Compact dimension - space economy
3
Identical front plate cut out - lends uniformity
4
Interchangeable line & load connection -Offers flexibility of mounting
1
Comprehensive range : 25A - 1600A in different frame sizes
2
Compact dimension - space economy
3
Identical front plate cut out - lends uniformity
4
Interchangeable line & load connection -Offers flexibility of mounting
Moulded Case Circuit Breaker (MCCB)
The STAN DAR D ran ge of Mou lde d Cas e Cir cui t Bre ake rs (MC CBs ) are designed for circuit protection of low voltage distribution system. They are suit able for appl icat ion as main break ers and for prote ctio n of branch and feeder circuit & connected equipments / load. The se MCC Bs pro vi de ove rl oad and sh ort ci rcu it pro tec tio n fo r all
circuit elements. They are designed for use in Switchboards, Control Panels, Combination Starters, in separate enclosures and meet the requirements of lighting, distribution and power circuits. Standard offers a comprehensive range of MCCBs employing world class technology technology and fully conform to the latest IS / IEC-60947-2. IEC-60947-2.
Features
• • • • •
•
Comprehensive range : 25A - 1600A in different frame sizes. Compact dimension - space economy. Identical front plate cut out - lends uniformity. Interchangeable line & load connection -Offers flexibility of mounting. Adju stab le / f ront acce ssib le ther mal and magn etic sett ing. (The rmal setting for overload adjustable from 70% - 100% of the rated current & magnetic setting for short circuit adjustable 4-10 times / 5-10 times). Available in Single pole, 3 pole and and 4 pole with switched neutral version.
Electrical & mechanical life
Rat ed Cur rent ( A)
Mec hani cal Li Li fe
El e ctr i cal Li Li fe
In < 100
8 50 0
150 0
10 0 < I n £ 31 5
7 00 0
100 0
31 5 < I n £ 63 0
4 00 0
100 0
63 0 < I n £ 80 0
2 50 0
5 00
• • • •
Suitable for use as Switch Disconnectors Disconnectors / Isolators. Isolators. Trip Free Mechanism - The breaker trips internall y in case of fault, even if the knob is in the ON position. Mounting possible in vertical or horizontal horizontal position or ± 15° in vertical plane. Complete range of accessories. (Under Voltage Release, Shunt Trip, Auxili ary Swi tches, Ro tary Han dles, E xtended Terminals , Back Studs, Phase Barriers, Terminal Shrouds, Enclosures and Earth Leakage Relay).
Moulded Case Circuit Breaker (MCCB)
Construction
The MCCB comp ris es of swi tchi ng mech anis m, cont act sys tem, arc extinguishing device and tripping unit all contained in a compact Moulded Case and Cover. The insulat ing case and cover are made of high strengt h, heat resis tant, flame retardant resin bonded thermo setting material which provides:•
• •
The insulated enclosure with high withstand capacity against thermal and mechanical stresses. Protection against secondary fire hazards.
•
Increased safety of operating personnel.
Interphase insulation of a high dielectric strength, making the MCCB considerably compact and light weight.
Switching mechanism Control mechanism
Push to trip
Overload & short circuit adjustment
Trip Trip bar
Instantaneous trip release
Instantaneous trip release
Moulded Case Circuit Breaker (MCCB)
SKB-1 & 2
MCCB Adjustable Type - Three Pole Rating (Amps.)
MCCB Adjustable Type - Four Pole (wSN) Cat No.
SKB-1
SKB-2
25
ISLAST0025
ISLANT0025
32
ISLAST0032
ISLANT0032
50
ISLAST0050
ISLANT0050
63
ISLAST0063
ISLANT0063
80
ISLAST0080
100
Rating (Amps.)
Cat No. SKB-1
SKB-2
25
ISLASF0025
ISLANF0025
32
ISLASF0032
ISLANF0032
50
ISLASF0050
ISLANF0050
63
ISLASF0063
ISLANF0063
ISLANT0080
80
ISLASF0080
ISLANF0080
ISLAST0100
ISLANT0100
100
ISLASF0100
ISLANF0100
125
ISLAST0125
ISLANT0125
125
ISLASF0125
ISLANF0125
160
ISLAST0160
ISLANT0160
160
ISLASF0160
ISLANF0160
200
ISLAST0200
ISLANT0200
200
ISLASF0200
ISLANF0200
250
-
ISLANT0250
250
-
ISLANF0250
Moulded Case Circuit Breaker (MCCB)
Technical information - SKB1 & 2
Standard conformity Rated operational voltage Rated Insulation Voltage Type of relea se Utilisation Category Rated frequency Ambi ent temp Operating altitude Humidity Rated impulse voltage
: : : : : : : : : :
IEC 60947-2/IS:1 3947-2 500V AC 750V AC Therm omagn etic A 50/60 Hz 40 oC (50 oC on request) 2000 meters 0 - 90% 8 KV
Frame No. of Poles Standard current range / ratings (I n)
SKB1
SKB2
1P / 3P / 4PwSN
1P / 3P / 4PwSN
25-200*
25-250*
70-100% of In
70-100% of In
A
Thermal release setting (Adjustable) Magnetic release setting for current rating : 25A - 63A
400A
400A
80A - 125A
800A
800A
160A - 250A
1600A
1600A
50A -125A AM Frame
-
-
160A -250A AM Frame
-
-
32
73.5
52.5
Rated short circuit making capacity (Peak) Icm
KA
Rated ultimate short circuit breaking
(160-200A)
(25-125A)
(25-250A)
capacity (Icu), KA
240V
25
50
40
(at different voltages)
415V
16
35
25
440V
16
35
25
500V
12
25
18
100%
75%
75%
Ics = % Icu Weight
SP (Single Pole)
Kg
0.7
0.7
TP (Triple Pole)
Kg
1.8
1.8
FPwSN (Four Pole Switched Neutral)
Kg
2.4
2.4
Terminal capacity (Cable)
Sq.mm
(Bus bar width) Recommended Torque
Nm
70 (upto 100A)/150 (125A-250A) mm
25 (125A-250A)
10
10
•
•
Internal Accessories Auxiliary Switch (1 C/O or 2C/O) Shunt Trip
•
•
Under Voltage Release
•
•
Alarm Switch (1 C/O) Factory Fitted
•
•
Earth Fault Relay
•
•
Rotary Handle
•
•
External Accessories
*
Back Studs
•
•
Extended Terminals (above 63A)
+
+
Dolly Extension
-
-
Phase Barriers
+
+
Terminal Shrouds
•
•
Dolly pad locking Device
•
•
Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A
• Available, - Not Available, + Supplied alongwith the MCCB above 63A..
1P - Single Pole 3P - Three Pole 4PwSN - Four Pole with Switched Neutral
Moulded Case Circuit Breaker (MCCB)
Accessories - SKB-1 & 2
Shunt trip
Voltage
Cat No.
100-110Vac
ISLLSTD110
220-240Vac
ISLLSTD240
380-415Vac
ISLLSTD415
Under Voltage Release Voltage
Cat No.
100-110Vac
ISLUVRD110
220-240Vac
ISLUVRD240
380-415Vac
ISLUVRD440
Auxiliary contac t (250Vac/250Vdc) Acces sorie s
Cat No.
1-Changeover
ISLLASD1CO
2-Changeover
ISLLASD2CO
Rotary handle Access ories
Cat No.
Di rect Mo unt ing
I SL LRRHD 30
Back studs Access ories
Cat No. ISLLBSA250
Trip al arm cont act
Extended terminals Cat No.
Acces sorie s
Cat No.
3 Pole
ISLAX0062
Factory fitted
ISLLALA1C0
4 Pole
ISLAX0059
3 Pole
ISLAX0061
4 Pole
ISLAX0050
Access ories 125A 160A - 250A
Moulded Case Circuit Breaker (MCCB)
Time current characteristics - SKB-1 & 2
SKB1/2 Frame MCCB 25 to 63 Amp.
SKB1/2 Frame MCCB 80 to 250 Amp.
10000
10000 A 0 8
25A 32A
1000
A 0 0 1 A
1000
5 2 1
50A 63A
100
) s d n o c e s ( e m i T
100
) s d n o c e s ( e m i T
10
1
A 0 6 1
A 0 0 2
A 0 5 2
10
1
0.1
0.1
0.01
0.01
0
0 10
100
100
1000
RMS current (A)
1000
RMS current (A)
Dimensional details (in mm)
46
100 35
2 1 1
45.5
Scale-1.5
45.5
8
136
35
35
45 17
35
35
5 3 1
4 2 5 1 2 1 1 9
2 9
5 2
35 105 Dia. 6.0 (4 Off) Mounting Holes
3P
70 140 Dia. 6.0 (4 Off) Mounting Holes
4PwSN
5 3
29
12.5
91 83
25
25
25
DIA 10.0 HOLES
3P With Extended Terminals
Moulded Case Circuit Breaker (MCCB)
SKB-3 & 4
MCCB Adjustable Type - Three Pole Rating (Amps.)
MCCB Adjustable Type - Four Pole (wSN)
Cat No. SKB-3
SKB-4
160
ISLCNT0160
ISLCHT0160
200
ISLCNT0200
250 315
Rating (Amps.)
Cat No. SKB-3
SKB-4
160
ISLCNF0160
ISLCHF0160
ISLCHT0200
200
ISLCNF0200
ISLCHF0200
ISLCNT0250
ISLCHT0250
250
ISLCNF0250
ISLCHF0250
ISLCNT0315
ISLCHT0315
315
ISLCNF0315
ISLCHF0315
400
ISLCNT0400
ISLCHT0400
400
ISLCNF0400
ISLCHF0400
500
ISLCNT0500
ISLCHT0500
500
ISLCNF0500
ISLCHF0500
630
ISLCNT0630
ISLCHT0630
630
ISLCNF0630
ISLCHF0630
800
ISLCNT0800
ISLCHT0800
800
ISLCNF0800
ISLCHF0800
Moulded Case Circuit Breaker (MCCB)
Technical information - SKB 3 & 4
Standard conformity Rated operational voltage Rated Insulation Voltage Type of relea se Utilisation Category Rated frequency Ambi ent temp Operating altitude Humidity Rated impulse voltage
: : : : : : : : : :
IEC 60947-2/IS:1 3947-2 500V AC 690V AC Ther momag neti c A 50/60 Hz 40 oC (50 oC on request) 2000 meters 0 - 90% 8 KV
Frame
SKB 3
SKB 4
3P/4PwSN
3P/4PwSN
160-800*
160-800*
70-100% of In
70-100% of I n
Adjustable
Adjustable
160 - 315A
5-10 times I n
5-10 times In
400 - 800A
4-10 times I n
4-10 times In
KA
73.5
105
240V 380V 415V
50 35 35
70 50 50
500V
25
35
75%
50%
No. of Poles Standard current ratings (I n )
A
Thermal release setting (Adjustable) Magnetic release setting
Rated short circuit making capacity (Peak) I cm Rated ultimate short circuit breaking capacity(Icu), KA (at different voltages)
Ics = % Icu Weight TP (Triple Pole)
Kg
9.2
9.2
FPwSN (Four Pole with Switched Neutral)
Kg
11.6
11.6
Sq.mm
-
-
mm
40
40
Auxiliary Switch (1 C/O or 2 C/O)
•
•
Shunt Trip
•
•
Under Voltage Release
•
•
Alarm Switch (1 C/O) # Factory Filled
•
•
Earth Fault Relay
•
•
Rotary Handle
•
•
Back Studs
•
-
Extended Terminals
+
•
Dolly Extension
•
•
Phase Barriers
+
-
Terminal Shrouds
-
-
Dolly pad locking Device
•
•
Terminal capacity (Cable) (Busbar width)
Internal Accessories
External Accessories
* Current Ratings - 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A.
3P - Three Pole
• Available, - Not Available, + Supplied alongwith the MCCB as standard.
4PwSN - Four Pole with Switched Neutral
** Terminals at Front # Terminals at back / rear
Moulded Case Circuit Breaker (MCCB)
Accessories - SKB-3 & 4
Shunt trip
Voltage
Cat No.
18-30Vac, 12-36Vdc
ISLLSTC030
100-110Vac
ISLLSTC110
220-240Vac
ISLLSTC240
380-415Vac
ISLLSTC415
Under Voltage Release Voltage
Cat No.
100-110Vac
ISLUVRC110
220-240Vac
ISLUVRC240
380-415Vac
ISLUVRC440
Auxiliary contac t (250Vac/250Vdc) Acces sories
Cat No.
1-Changeover
ISLLASC1CO
2-Changeover
ISLLASC2CO
Rotary handle Acces sorie s
Cat No.
Di rect Mo unt ing
IS LLRRH C3 0
Back studs Acces sorie s
Cat No. ISLLBSC###
Extended terminals Access ories 250A 315A - 500A 630A - 800A
Trip alarm cont act Cat No.
Acces sories
Cat No.
3 Pole
ISLCX0019
Factory fitted
ISLLALC1C0
4 Pole
ISLCX0023
3 Pole
ISLCX0020
4 Pole
ISLCX0025
3 Pole
ISLCX0027
4 Pole
ISLCX0028
Moulded Case Circuit Breaker (MCCB)
Time current characteristics - SKB-3 & 4
SKB3/4 Frame MCCB 250 to 800 Amp. 10000 A 0 5 2
A 5 1 3
1000 1
A 0 0 5
100
A 0 0 8
) 10 s d n o c e s ( e 1 m i T
0.1
0.01
0 100
1000
10000
RMS current (A)
Dimensional details (in mm) - SKB-3 & 4
B 54.5
206 70 70
0 0 1
24.5
A
B
A
B
Scale-1.10 17.5
8 58.9
2 . 7 2 5 3 2 2
2 9
30
40 70 208
70
208 70 Fixing Hole
3P
5 7 3
4PwSN
52
102
40 160-400A, A=40, B=30 500-800A, A=20, B=50
3P With Extended Terminals
Moulded Case Circuit Breaker (MCCB)
SKB 5, 6 & 7
MCCB Fixed Type - Single Pole
MCCB Fixed Type - Three Pole Cat No.
Cat No.
SKB-6
Rating (Amps.)
SKB-5
SKB-6
SKB-7
25
ISLGNS0025
25
ISLGST0025
ISLGNT0025
ISLGHT0025
32
ISLGNS0032
32
ISLGST0032
ISLGNT0032
ISLGHT0032
50
ISLGNS0050
50
ISLGST0050
ISLGNT0050
ISLGHT0050
63
ISLGNS0063
63
ISLGST0063
ISLGNT0063
ISLGHT0063
80
ISLGNS0080
80
ISLGST0080
ISLGNT0080
ISLGHT0080
100
ISLGNS0100
100
ISLGST0100
ISLGNT0100
ISLGHT0100
125
ISLGNS0125
125
ISLGST0125
ISLGNT0125
-
Rating (Amps.)
MCCB Fixed Type - Four Pole (wSN) Rating (Amps.)
Cat No. SKB-5
SKB-6
SKB-7
25
ISLGSF0025
ISLGNF0025
ISLGHF0025
32
ISLGSF0032
ISLGNF0032
ISLGHF0032
50
ISLGSF0050
ISLGNF0050
ISLGHF0050
63
ISLGSF0063
ISLGNF0063
ISLGHF0063
80
ISLGSF0080
ISLGNF0080
ISLGHF0080
100
ISLGSF0100
ISLGNF0100
ISLGHF0100
125
-
-
-
Moulded Case Circuit Breaker (MCCB)
Technical information - SKB 5, 6 & 7
Standard conformity Rated operational voltage Rated Insulation Voltage Type of relea se Utilisation Category Rated frequency Ambi ent temp Operating altitude Humidity Rated impulse voltage
: : : : : : : : : :
IEC 60947-2/IS:1 3947-2 500V AC 750V AC Therm omagn etic A 50/60 Hz 40 oC (50 oC on request) 2000 meters 0 - 90% 8 KV
Frame No. of Poles Standard current range / rating (I n )A Thermal release setting
SKB-5
SKB-6
SKB-7
1P / 3P / 4PwSN
1P / 3P / 4PwSN
3P / 4PwSN
16-160*
16-160*
16-160*
Fixed
Fixed
Fixed
Magnetic release setting for current rating : 16A - 32A
A
350
350
350
40A - 50A
A
500
500
500
63A - 80A
A
800
800
800
100A - 160A
A
1000
1000
1000
KA
17
32
52.5
capacity (Icu), KA
240V
16
25
40
(at different voltages)
415V
10
16
25
440V
10
14
16
500V
7.5
10
12
100%
75%
50%
Rated short circuit making capacity (Peak) Icm at 415V AC Rated ultimate short circuit breaking
Ics = % Icu Weight
SP
Kg
0.35
0.35
0.35
TP
Kg
0.93
0.93
0.93
4PwSN
Kg
1.2
1.2
1.2
Sq.mm
70
70
70
mm
10
10
10
Nm
2.5
2.5
2.5
Auxiliary Switch (1 C/O or 2C/O)
•
•
•
Shunt Trip
•
•
•
Under Voltage Release
•
•
•
External Accessories
• • •
• • •
• • •
Terminal capacity (cable) Bus bar (width) Recommended Torque Internal Accessories
Earth Fault Relay Rotary Handle Back Studs
-
-
-
Extended Terminals (above 63A)
+
+
+
Dolly Extension
-
-
-
Phase Barriers
+
+
+
•
•
•
•
•
•
Terminal Shrouds Dolly pad locking Device *
†
Current Ratings - 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 150A, 160A
1P - Single Pole
• Available, - Not Available, + Supplied alongwith the MCCB as standard.
3P - Three Pole
D Availa ble
4PwSN - Four Pole with Switched Neutral
in s ingle pole
† Avail able in 3P & 4P
Moulded Case Circuit Breaker (MCCB)
Accessories - SKB-5, 6 & 7
Shunt trip
Voltage
Cat No.
18-30Vac, 12-36Vdc
ISLLSTG030
100-110Vac
ISLLSTG110
220-240Vac
ISLLSTG240
Under Voltage Release Voltage
Cat No.
100-110Vac
ISLUVRG110
220-240Vac
ISLUVRG240
380-415Vac
ISLUVRG440
Auxiliary contac t (250Vac/250Vdc) Acces sorie s
Cat No.
1-Changeover
ISLLASG1CO
2-Changeover
ISLLASG2CO
Rotary handle Acces sories
Cat No.
Direct Mounting
ISLGD000
Direct Mounting
ISLGRN30
Extended terminals Acces sories 16A - 160A
Trip al arm cont act Cat No.
Acces sorie s
Cat No.
3 Pole
ISLGX0012
Factory fitted
ISLLALA1C0
4 Pole
ISLGX0046
Moulded Case Circuit Breaker (MCCB)
Time current characteristics - SKB-5, 6 & 7
SKB5/6/7 Frame MCCB 25 to 125 A mp. 10000 A 5 2 A 2 3
1000
A 0 5
A 3 6
A 0 8
100
A 0 0 1
A 5 2 1
) s d n o c e s ( e m i T
10
1
0.1
0.01
0 10
100
1000
RMS current (A)
Dimensional details (in mm) - SKB-5, 6 & 7 (1 Pole)
11.4 70.5 12
6 4 . 7 8 7
0 4 2 4 1
11.2 20
33.5 77.5
26.25 83.5 96
Moulded Case Circuit Breaker (MCCB)
Dimensional details (in mm) - SKB-5, 6 & 7 (3 Pole)
38 5 2 . 6 2
38
5 2 . 6 2
e l o h 4 9 g n i x i F
5 1
12.5
26.26 18
83.5
78.50
D1A 10.0 HOLES
18
18
26
3P with Extended Terminal
3P
Dimensional details, in mm - SKB-5, 6 & 7 (3 Pole)
104.50 26.25
26.25
83.50 26.25
77.50 71
0 0 0 0 . . 0 2 2 0 1 1
0 0 . 4 9
ON
Four Pole with Switched Neutral
OFF
26.25
97.00
2 nos. mounting holes for m4 screws
Moulded Case Circuit Breaker (MCCB)
SKB-8 & 9
MCCB Fixed Type - Three Pole Rating (Amps.)
MCCB Fixed Type - Four Pole (wSN) Cat No.
SKB-8
SKB-9
25
ISLFNT0025
ISLFHT0025
32
ISLFNT0032
50
Rating (Amps.)
Cat No. SKB-8
SKB-9
25
ISLFNF0025
ISLFHF0025
ISLFHT0032
32
ISLFNF0032
ISLFHF0032
ISLFNT0050
ISLFHT0050
50
ISLFNF0050
ISLFHF0050
63
ISLFNT0063
ISLFHT0063
63
ISLFNF0063
ISLFHF0063
80
ISLFNT0080
ISLFHT0080
80
ISLFNF0080
ISLFHF0080
100
ISLFNT0100
ISLFHT0100
100
ISLFNF0100
ISLFHF0100
125
ISLFNT0125
ISLFHT0125
125
ISLFNF0125
ISLFHF0125
160
ISLFNT0160
ISLFHT0160
200
ISLFNF0200
ISLFHF0200
200
ISLFNT0200
ISLFHT0200
250
ISLFNF0250
ISLFHF0250
250
ISLFNT0250
ISLFHT0250
Moulded Case Circuit Breaker (MCCB)
Technical information - SKB 8 & 9
Standard conformity Rated operational voltage Rated Insulation Voltage Type of relea se Utilisation Category Rated frequency Ambi ent temp Operating altitude Humidity Rated impulse voltage
: : : : : : : : : :
IEC 60947-2/IS:1 3947-2 500V AC 750V AC Ther momag neti c A 50/60 Hz 40 oC (50 oC on request) 2000 meters 0 - 90% 8 KV
Frame
SKB 8
SKB 9
3P / 4PwSN
3P / 4PwSN
25-250*
25-250*
Thermal releas e sett ing
Fixed
Fixed
Magneti c releas e setti ng for current rating
Fixed
Fixed
25A - 32A
500A
500A
40A - 80A
800A
800A
100A - 125A
1250A
1250A
160A - 250A
1600A
1600A
73.5
105
No. of Poles Standard Current ratings (In)
A
Rated short circuit making capacity (Peak) Icm kA Rated ultimate short circuit breaking capacit y(Icu), kA
240V
50
70
(at different voltages)
380V
35
50
415V
35
50
500V
25
35
100%
100%
2.9 / 3.8
2.9 / 3.8
M8
M8
185 18
185 18
Auxil iary Switc h (1 C/ O or 2 C/O)
•
•
Shunt Trip
•
•
Under Voltage Release
•
•
Alarm Swit ch (1 C /O) # (Factory Fitted)
•
•
Earth Fault Relay
•
•
Rotary Handle
•
•
Back Studs
•
•
Extended Terminals (above 63A)
+
+
Ics = % Icu Weight TP (Tripl e Pole) / FPwSN
Kg
Terminal Type Termina l capacit y (Cable) (Bus bar width)
Sq.mm mm
Internal Accessories
External Accessories
Dolly Extension
-
-
Phase Barriers
+
+
Terminal Shrouds (only in 3P MCCB)
•
•
Dolly pad locking Device
•
•
*
Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A
3P - Three Pole
•
Available, - Not Available, + Supplied alongwith the MCCB above 63A.
4PwSN - Four Pole with Switched Neutral
#
Factory Fitted
Moulded Case Circuit Breaker (MCCB)
Accessories - SKB-8 & 9
Shunt trip
Voltage
Cat No.
18-30Vac, 12-36Vdc
ISLLSTF030
100-110Vac
ISLLSTF110
220-240Vac
ISLLSTF240
380-415Vac
ISLLSTF415
Under Voltage Release Voltage
Cat No.
100-110Vac
ISLUVRF110
220-240Vac
ISLUVRF240
380-415Vac
ISLUVRF440
Auxiliary conta ct (250Vac/250Vdc) Access ories
Cat No.
1-Changeover
ISLLASF1CO
2-Changeover
ISLLASF2CO
Rotary handle Acces sories
Cat No.
D irec t M oun ti ng
IS LL RRHF3 0
Trip al arm cont act
Extended terminals Cat No.
Acces sorie s
Cat No.
3 Pole
ISLFX0048
Factory fitted
ISLLALF1C0
4 Pole
ISLFX0045
3 Pole
ISLFX0049
4 Pole
ISLFX0046
Acces sories 160A 200A - 250A
Moulded Case Circuit Breaker (MCCB)
Time current characteristics - SKB-8 & 9
SKB8/9 Frame MCCB 25 to 250 Amp. 10000
1000
100
) s d n o c e s ( e m i T
10 250A 200A 1 80A/125A/160A 63A/100A 0.1
32A/50A 25A
0.01 0.005 0
1
10
100
RMS current (A)
Dimensional details, in mm - SKB-8 & 9
30 TERMINAL HIGHT SUITABLE FOR M8 SCREWS
TERMINALS SUITABLE FOR 22mm WIDE STRIP OR 185mm2 CABLE
5 5
4 HOLES FOR MS SCREWS
. S R T C G N I X I F 0 7 1
35
. S R T C G N I X I F 0 9 1
FIXING CTRS.
6 . 8 7
94 100
35
35 114 135
104.5
T hr ee P ol e
Four P ole with S witch Neutral
Moulded Case Circuit Breaker (MCCB)
SKB 10 & 11
Adjustabl e t hermal (80- 100%) & f ixed magnetic setti ng Rating (Amps.)
Cat No. Three pole
Four pole (wSN)
SKB 10 - Icu 36kA
Adjustable thermal & a djustabl e magnetic setting Rating (Amps.)
Cat No. Three pole
Four pole (wSN)
SKB 10 - Icu 36kA
250
ISLLSEBT0250
ISLLSEBF0250
250
ISLLSECT0250
ISLLSECF0250
315
ISLLSEBT0315
ISLLSEBF0315
315
ISLLSECT0315
ISLLSECF0315
400
ISLLSEBT0400
ISLLSEBF0400
400
ISLLSECT0400
ISLLSECF0400
500
ISLLSEBT0500
ISLLSEBF0500
500
ISLLSECT0500
ISLLSECF0500
630
ISLLSEBT0630
ISLLSEBF0630
630
ISLLSECT0630
ISLLSECF0630
250
ISLLNFBT0250
ISLLNEBF0250
250
ISLLNFCT0250
ISLLNECF0250
315
ISLLNFBT0315
ISLLNEBF0315
315
ISLLNFCT0315
ISLLNECF0315
400
ISLLNFBT0400
ISLLNEBF0400
400
ISLLNFCT0400
ISLLNECF0400
500
ISLLNFBT0500
ISLLNEBF0500
500
ISLLNFCT0500
ISLLNECF0500
630
ISLLNFBT0630
ISLLNEBF0630
630
ISLLNFCT0630
ISLLNECF0630
SKB 11 - Icu 50kA
SKB 11 - Icu 50kA
Moulded Case Circuit Breaker (MCCB)
Technical information - SKB 10 & 11
Standard conformity Rated operational voltage Rated Insulation Voltage Type of relea se Utilisation Category Rated frequency Ambi ent temp Operating altitude Humidity Rated impulse voltage
: : : : : : : : : :
IEC 60947-2/IS:13 947-2 415V AC 750V AC Therm omag netic A 50/60 Hz 40 oC (50 oC on request) 2000 meters 0 - 90% 8 KV
Frame
SKB 10
SKB 11
3P/4P
3P/4P
250, 315, 400, 500
250, 315, 400, 500
80-100% I n
80-100% In
250A - 400A
4000A
4000A
500A - 500A
6300A
6300A
=
=
=
=
kA
75.6
105
240V
kA
50
65
415V
kA
36
50
Ics = % Icu
%
100
75
No. of Poles Standard Current Ratings (I n )
A
Thermal release setting (Adjustable) Magnetic release setting for current rating
Trip Unit
Adjustable Thermal & fixed magnetic setting Adjustable Thermal & adjustable magnetic setting Rated S.C. Making Capacity at 415V (Icm) Rated Ultimate S.C breaking capacity (Icu) at
Rated Service S.C Breaking Capacity at 415V Weight Terminal capacity (Max.) Bus bar width
Kg
6/7
6/7
Sq. mm
1x240 (250A-400A)
1x240 (250A-400A)
2x185 (500A)
2x185 (500A)
30
30
140x254x109
140x254x109
mm
Overall dimension (W X H X D) Internal Accessories #
Auxillary Switch
1C/O or 2C/O
=
=
Shunt Trip (bulit-in auxillary contact)
=
=
Under Voltage release
=
=
=
=
Rotary Handle - Extended
=
=
Extended Terminals
=
=
Dolly Extension
=
=
Phase Barriers
=
=
Dolly pad locking device
=
=
Earth Fault Relay
=
=
Alarm Switch External Accessories
• Available
# Only 2 accessories at a time can be fitted in the MCCB
Moulded Case Circuit Breaker (MCCB)
Accessories - SKB-10 & 11
Alar m s witc h
Voltage
Cat No.
Rati ng
Conf igura tion
240Vac
ISLLB000
1A
1NO + NC
Under Voltage Release
Shunt trip with Auxilary switch
Voltage
Cat No.
Voltage
Cat No.
110Vac
ISLLS110
110Vac
ISLLU110
240Vac
ISLLS240
240Vac
ISLLU240
415Vac
ISLLS415
415Vac
ISLLU440
Note: Shunt Trip release is provided with built-in auxiliary contact
Note: The break er trip s if the supp ly volt age dips belo w 70%- 35% of the rated voltage. The break er cann ot be swit ched ON unle ss ther e is a supp ly to the UVR. (NVNC feature). Suplied with external mounting Electronic Power pack to operate on AC supplies.
Auxiliary switch Voltage
Cat No.
Curren t r atin g (AC12)
Configuration
250Vac
ISLLA1CO
4A
1NO + 1NC
250Vac
ISLLA2CO
4A
2(1NO + 1NC)
Dolly pad lock
Rotary handle Acces sories With door interloack and 300mm remote shaft
Voltage
Cat No.
Dolly extension D ol ly pad l oc kin g d ev ice
ISLLRN30
Extended terminal with phase barrier Cat No. Extended terminals (250A - 400A)
ISSLX0013
Extended terminals (500A - 630A)
ISSLX0014
Phase barriers
ISSLLX0004
Cat No. ISCPSMLLX009 IS LLP 00 0
Moulded Case Circuit Breaker (MCCB)
Time current characteristics - SKB-10 & 11, Three Pole
g n i t n u o M
Time current characteristics - SKB-10 & 11, Four Pole
40
18.75
58.75
58.75
5 1 5 3
7 . 5 7
5 . 2 0 1
4 3. 75
43 .7 5 186
4 3. 75
4 4 5 5 2 3
Moulded Case Circuit Breaker (MCCB)
2 0 1
1 5 1
0 2 1
9 0
8 T
7 B
6 E
u c I
5 S
u c I f o % = s c I
4 L
e m a r F
3 L
D I t c u d o r P
1 I
g n i
t t a i R g i t D n e ) r h t r ( u A 2 c r 1 - e 9 k a e r B
A 0 5 2
A 5 1 3
A 0 0 4
A 0 0 5
A 0 3 6
0 5 2 0
5 1 3 0
0 0 4 0
0 0 5 0
0 3 6 0
s e l o p f o . o N
e s a e l e R f o e p y T
2 H
c i g o l e d o C
0 5 2 = ) A ( g n i t a R t n e r r u c r e k a e r B
e l o s P t e i l e g o e r i p h D f T h t o . 8 o N T
c l i e n b o a d r t t c s e u i e j x l E d F t A i / s l i c g i c n a t i e t o D e i m s r n n r h e t g e h g a 7 a v T M M l a m B r e h T
t i g i D h t 5
t i g i D d r 3
% u s I c a f s o c I
% % % 0 5 0 0 7 5 1
n o i t a n g i s e D
S N H
D I t c u d o r P
s B C C M 0 1 B K S
t i g e 0 i D m 1 a h r B t F K 4 S
A n A k o k 6 0 i t t i 5 3 g a i n D i g h t s e 6 D u E F c I
g n i t a R t n e l r a r u C s m r a e A s h 0 c T 5 I : 2 e , h t i p l y e w T o e e P m s 3 a a , r e d F l e e x 0 R i 1 , F A B i c t K K S 6 3 e n B = g C u a C I c M , M , l l u e b a c i a r I t t s % s u u j d 0 d n 0 I 1 A
0 5 2 0 T e B l p E S m L a L x I E S
Moulded Case Circuit Breaker (MCCB)
SKB-0
MCCB Adjustable Type - Three Pole
MCCB Adjustable Type - Four Pole (wSN)
Rating (Amps.)
SKB-0
Rating (Amps.)
SKB-0
1000
ISLDNT1000
1000
ISLDNF1000
1250
ISLDNT1250
1250
ISLDNF1250
1600
ISLDNT1600
1600
–
Moulded Case Circuit Breaker (MCCB)
Technical information - SKB 0
Standard conformity Rated operational voltage Rated Insulation Voltage Type of relea se Utilisation Category Rated frequency Ambi ent temp Operating altitude Humidity Rated impulse voltage
: : : : : : : : : :
IEC 60947-2/IS:1 3947-2 500V AC 690V AC Ther momag neti c A 50/60 Hz 40 oC (50 oC on request) 2000 meters 0 - 90% 8 KV
Frame
SKB 0
3P/4PwSN
No. of Poles Standard current ratings (I n )
A
Thermal release setting (Adjustable)
70-100% of In
Magnetic release setting
Adjustable
800 - 1600A Rated short circuit making capacity (Peak) I cm Rated ultimate short circuit breaking capacity(Icu), KA (at different voltages)
1000-1600*
4000-10,000A KA
105
240V 380V
70 50
415V
50
500V
35
Ics = % Icu
75%
Weight TP (Triple Pole)
Kg
17#/19**
FPwSN (Four Pole with Switched Neutral)
Kg
22/25
Sq.mm
-
mm
45** upto 1000A 60** upto 1250A
Terminal capacity (Cable) (Busbar width)
65** upto 1600A 35.5# upto 1600A
Internal Accessories Auxiliary Switch (1 C/O or 2 C/O)
•
Shunt Trip
•
Under Voltage Release
•
Alarm Switch (1 C/O) # Factory Filled
•
External Accessories Earth Fault Relay
•
Rotary Handle
•
Back Studs
•
Extended Terminals
•
Dolly Extension
•
Phase Barriers
•
Terminal Shrouds
-
Dolly pad locking Device
•
* Current Ratings - 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A.
3P - Three Pole
• Available, - Not Available, + Supplied alongwith the MCCB as standard.
4PwSN - Four Pole with Switched Neutral
** Terminals at Front # Terminals at back / rear
Moulded Case Circuit Breaker (MCCB)
Accessories - SKB-0
Shunt trip
Voltage
Cat No.
100-110Vac
ISLLSTD110
220-240Vac
ISLLSTD240
380-415Vac
ISLLSTD415
Under Voltage Release Voltage
Cat No.
100-110Vac
ISLUVRD110
220-240Vac
ISLUVRD240
380-415Vac
ISLUVRD440
Auxiliary contac t (250Vac/250Vdc) Acces sorie s
Cat No.
1-Changeover
ISLLASD1CO
2-Changeover
ISLLASD2CO
Rotary handle Acces sories
Cat No.
Di re ct Moun ti ng
IS LLRR HD3 0
Moulded Case Circuit Breaker (MCCB)
Dimensional details (in mm) - SKB-0 (3 Pole)
Moulded Case Circuit Breaker (MCCB)
Dimensional details (in mm) - SKB-0 (4 Pole with switched neutral)
S. No.
Rating
A
B
T
1.
800A
70
45
6x2
2.
1000A
70
45
15
3.
1250A
82
60
15
4.
1600A
87
65
18
Time current characteristics - SKB-0
SKB 0 Frame MCCB 800 to 1600 Amp. 10000 A 0 0 8
1000
A 0 0 0 1
A 0 5 2 1
100
) s d n o c e s ( e m i T
A 0 0 6 1
10
1
0.1
0.01
0
1000
10000
RMS current (A)
Moulded Case Circuit Breaker (MCCB)
Earth fault relay
Th e ear th fau lt det ect io n sy st em fo r us e wi th STAN DA RD MC CBs comprises of a core balance transformer (CT) coupled to an advanced RCD relay. The relay may be used to trip a circuit breaker via a shunt trip or an under voltage release in the event of an Earth Fault. The relay and one o f th e fo ur a vail able CT’s is all that is requi red for a complete earth fault sensing system suitable for the control of a circuit breaker in a circuit upto 800A fitted with either a shunt trip or an under voltage release. The simple arrangement and a small number of interconnection necessary ensure that EFR is easily selected and installed. Th e rel ay is su it ab le for 22 0-2 40V AC sup pl y wi th the fl exi bi li ty of choosing the sensitivity between 300mA to 2A and time delay should be selected by the DIP switches provided on the facia of the relay.
Features • • • • • • • •
No nuisance tripping DIN rail mounting Adjustable time delay Choice of sensitivity from 300mA upto 2A Trip indication LED(Red) ON indication LED(Green) Test push button Reset push button
Other external accessories • • • •
Dolly Pad locking device Phase Barriers Back Studs Extended terminals
• Dolly Extension
Moulded Case Circuit Breaker (MCCB)
Technical data
Supply Voltage
:
220V / 240V AC, 50 / 60Hz
Changeover contact
:
5A-15A 240V AC
Sensitivity
:
300mA, 500mA, 1A, 2A
Tim e d elay (m.s ec.)
:
200, 500, 1000, 5000
The ear th fau lt rel ay is su ppl ied wi th the CT bas ed on the cur ren t rating. To operate the EFR a shunt trip or an under voltage release is necessary which has to be ordered separately.
Coil Voltage
Cat No.
25-100
ISEF1100
125-200
ISEF2200
250-400
ISEF3400
500-800
ISEF4800
Dimensional details (in mm) - Core balance current transformer
Size
MCCB Current Rating
Internal Dimension
Shape
1
25-100A
60mm
Circular
2
125-200A
95mm
Circular
3
250-400A
145mm
Circular
4
500-800A
300 x 80 mm
Rectangular
5
1000-1600A
On Request
Rectangular
Moulded Case Circuit Breaker (MCCB)
General purpose enclosure
Enclosures made of special grade CRCA steel are available for housing SKB-1 to SKB-9 Frame MCCBs upto 800A. They are manufactured with latest technology using CNC Punch and Brake presses to attain highest degree of perfection. The enclosures are painted with latest techniques in powder coating using epoxy polyester and polyester resin based powder paints to ensure smooth, scratch resistant surface coatings. They are suitable for wall mounting & adequate knockouts are provided for cable entry.
Description
Cat. No.
SKB-5/6/7 Frame SP
ISEGSP
SKB-5/6/7 Frame TP
ISEGTP
SKB-5/6/7 Frame FP
ISEGFP
SKB-1/2 Frame SP
ISEASP
SKB-1/2 Frame TP
ISEATP
SKB-1/2 Frame FP
ISEAFP
SKB-8/9 Frame TP
ISEFTP
SKB-8/9 Frame FP
ISEFFP
SKB-3/4 Frame TP (400A)
ISECTP
SKB-3/4 Frame FP (400A)
ISECFP
SKB-3/4 Frame TP (800A)
ISECTP
SKB-3/4 Frame FP (800A)
ISECFP
Dimensional details (in mm)
Description
W
D
h
H
AxB
SKB-5/6/7 Frame
190
81
300
310
160x360
SKB-1/2 Frame
260
108
560
570
160x480
SKB-8/9 Frame
260
122
560
570
160x480
SKB-3/4 Frame
440
122
960
975
280x802
540
122
960
975
380x802
upto 400 A SKB-3/4 Frame upto 800 A
W
h
B
A
H
D
Moulded Case Circuit Breaker (MCCB)
Ambient temperature compensation chart (SKB 1/2, SKB 3/4, SKB 5/6)
) i , g n i t a r t n e r r u c f o % ( r o t c a f n o i t a s n e p m o C
40°C Ref SKB 0 40°C Ref SKB 1/2 40°C Ref SKB 8/9 40°C Ref SKB 3/4 40°C Ref SKB 5/6/7
Ambient tempera ture (°C)
Ambient temperature compensation chart (SKB 1/2, SKB 3/4, SKB 5/6)
IS:13703 HBC Fuse - Upstream Device Product
) SKB 1/2 T E S W O L ( E C I V E D M A E R T S N W O D B SKB 3/4 C C M D R A D N A T S SKB 0
Rating
KA @
(A)
415V
25
Current Rating of HBC Fuses 80
100
125
160
200
250
315
400
500
630
800
25
1200
1400
1800
2400
3200
4500
5500
8000
12000
14000
23000
32
25
1200
1400
1800
2400
3200
4500
5500
8000
12000
14000
23000
40
25
350
1400
1800
2400
3200
4500
5500
8000
12000
14000
23000
50
25
300
1400
1800
2400
3200
4500
5500
8000
12000
14000
23000
63
25
250
1400
1800
2400
3200
4500
5500
8000
12000
14000
23000
80
25
300
450
2400
3200
4500
5500
8000
12000
14000
23000
100
25
400
650
3200
4500
5500
8000
12000
14000
23000
125
25
550
3200
4500
5500
8000
12000
14000
23000
160
25
650
1300
5500
8000
12000
14000
23000
200
25
1200
1300
8000
12000
14000
23000
250
50
1000
8000
12000
14000
23000
315
50
2000
12000
14000
23000
400
50
2500
14000
23000
500
50
3500
23000
630
50
5500
800
50
6000
The above table gives fault currents in amperes till which level the downstream breakers shall act prior to the upstream fuse.
Moulded Case Circuit Breaker (MCCB)
Discrimination data standard MCCB upstream device instantaneous trip set at high
Product Rating
SKB 1/2
SKB 3/4
SKB 0
SKB 1/2
kA@ 25
23
40
50
63
80
SKB 3/4 100 125 106 ALL 250
315
400
SKB 0
(A)
415V
500
630
800
600
800
1000 1250 1600
63
25
800 800 800 1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
80
25
1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
100
25
1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
125
25
1600 1600 2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
160
25
2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
200
25
2500 3000 4000 5000 6300 8000 7400 8300 9200 9200 9200
315
50
4000 5000 6300 8000 7400 8300 9200 9200 9200
400
50
5000 6300 8000 7400 8300 9200 9200 9200
500
50
6300 8000 7400 8300 9200 9200 9200
630
50
8000 7400 8300 9200 9200 9200
800
50
7400 8300 9200 9200 9200
1000
50
9200 9200 9200
1250
50
9200 9200
1600
50
9200
The above table gives fault current in amperes till which level the downstream breakers shall act prior to the upstream breaker
Selection & application
Transformer Protection
Ie =
kVA × 1000
Primary side For the protection of transformer with a circuit breaker connected to the primary side (LT primary) the no load inrush current of the transformer must be considered. The peak value of the first current wave often reaches 10-15 times the rated current and may sometimes reach as high as 20-25 times. However, the transient decays very quickly (in a few m.sec.). Thus the MCCB selected should have a magnetic setting which will not be actuated by the momentary inrush current.
Secondary side STANDARD MCCBs can be used for protection of transformer on the LT side (secondary side) as an outgoing protective device. The rate d c urren t o f t he t rans form er is calcu late d a s f ollo ws :
√3 × Ue
Amps
‘Ue’ is the Rated Voltage at the LT side
The Breaking capacity of the breaker for protection can be calculated as :
Ib =
Where
Ie
×
10 –3 Kiloamperes
Z%
‘I b’ is the rated breaking capacity, ‘I e’ the rated current
‘Z%’ is the percentage impedance of transformer (specified by the manufacturer)
Moulded Case Circuit Breaker (MCCB)
Selection table for transformer protection MCCB Rating in Amperes Transformer rating (KVA) S KB -5 1 0k A S KB -6 1 7k A S KB -7 2 5k A S KB -1 2 5k A S KB -2 3 5k A S KB -2 3 5k A S KB -3 3 5k A S KB -3 5 0k A S KB -0 5 0k A 16
25
25
25
25
25
25
25
40
40
40
40
40
40
63
100
100
100
100
100
100
100
160
160
160
160
160
160
250
250
250
250
250
200
315
315
250
400
400
315
500
500
400
630
630
500
800
800
630
1000
750
1200
Selection table for DG set protection
Generator set protection STANDARD MCCBs can be used for the effective protection and control of Diesel Generating set against overload and short circuits. The Curre nt rati ng of MCCB to be sele cted is calc ulat ed a s f ollo ws : kVA =
DG Set Rating (kVA)
MCCB Rating (Amps)
10
16
kVA
16
25
√3 × Ue
25
40
63
100
10
160
16
250
20
315
25
400
31
500
40
630
63
1000
750
1200
√ 3 Ue × Ie or
Ie =
Where, kVA = Rating of the DG Set Ue = Rated Voltage Ie = Rated Current The MC CB rat ing se lected is gr eater t han or equal to the rated current value
Typical installation
A
1000 kVA transformer 10 meters 8sc 300 mm 2
B 70 meters 4c 120 mm 2
C
20 meters 2c 16 mm 2 D
Moulded Case Circuit Breaker (MCCB)
Feeder/cable protection An es ti ma ti on of th e pr os pe ct iv e sh or t- ci rcu it cu rr en t (p sc ) in an installation is an important consideration in the selection of the appropriate protective device. Th e ma gn it ud e of th e sh or t- ci rc ui t cu rr en t (r ms va lu e of th e AC component) at a point in the installation will depend upon; (A) Prospective short-circui t current at the origin of the installat ion. (B) The amount of resistance in the circuit between the origin of the installation and the point at which the short circuit occurs. (C) The type of short-circuit, phase to phase or phase to earth or phase to neutral. It is possible to arrive at a maximum prospective short circuit value at the origin by taking the transformer kVA rating and its impedance and calculating from the expression :
The selection of STANDARD MCCB for feeder /cable protection depends on the total load to be protected and the prospective short-circuit current (psc) at the point of installation.
PSC at A
Aapproximately 27kA
PSC at B resistance A to B (a)
0.30m W
= 25kA
PSC at C +resistance A to B
0.30m W
+resistance B to C1
10.70m W
11.00m W = 12kA
PSC at D SCkA =
Transformer rating (kVA) × 100
+resistance A to B
0.30m W
√3 × Secondary voltage × % impedance of transformer
+resistance B to C
10.70m W
To cal cula te the resi stan ce in the LV ci rcuit , obtai n detai ls of leng ths and sizes of cables between the source of supply and the point under calculation. Using the table provided, determine the sum of cable resistances and then simply read off the estimated fault current from the relevant transformer curve on the graph. The valu es assu me a s ymmet rica l fault acros s the three phas es. In a single circuit, for line to neutral faults, take the cable resistance value from the table and double it.
+resistance C to D
46.00m W (b )
57.00m W = 3kA
(a) 2 cables per phase divided by 2 (b) 2 core cable, multiplied by 2 The abo ve cal culati ons ha ve an inbuil t safe ty mar gin a s they assum e a no impedance fault condition which would not be the case in practice.
Estimating the prospective short circuit current
40
2000 kVA
1500 kVA
30 ) A k ( t n e r r u C t l u a F
1250 kVA 1000 kVA
800 kVA
20
500 kVA
10
315 kVA 200 kVA 100 kVA
0 0.1
1.0
10 Total Circuit Resistance ( µ ohm)
100
Moulded Case Circuit Breaker (MCCB)
Maximum resistance of copper conductors at 20°C (m ohm)
Nominal Cross-sectional Area (mm2)
5m
10m
1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
90.50 60.50 37.10 23.10 15.40 9.1 5 5.75 3.64 2.62 1.94 1.34 0.96 0.77 0.62 0.49 0.34 0.30 0.23 0.18 0.14
181.00 121.00 37.10 46.10 30.8 0 18.3 0 11.50 7.27 5.24 3.87 2.68 1.93 1.53 1.24 1.00 0.75 0.63 0.47 0.37 0.2 8
Cable length 15m
20m
182.00 74.10 111.00 69.20 92.20 46.20 61.60 27.50 36.6 0 17.30 23.00 10.9 0 14.5 0 7.86 10.48 7.74 5.81 5.36 4.02 3.86 2.10 3.06 2.30 1.86 2.48 1.49 1.98 1.51 1.13 0.90 1.20 0.94 0.70 0.55 0.73 0.42 0.57
30m
148.00 138.00 92.40 54.90 34.50 21.80 15.70 11.6 0 8.04 5.79 4.59 3.72 2.97 2.26 1.80 1.41 1.10 0.8 5
40m
123.00 73.20 46.00 29.10 21.00 15.5 0 10.7 0 7.72 6.12 4.96 3.96 3.0 2 2.80 1.88 1.46 1.13
50m
60m
91.50 57.20 36.40 26.20 19.40
110.00 69.00
70m
43.6 0 31.40 23.20 16.1 0 11.6 0 9.1 8 7.44 5.96 4.5 2 3.61 2.85
13.40 9.65 7.65 6.20 4.96 3.7 7 3.00 2.35 1.83 1.42
2.2 0 1.78
80m
80.50 103.5 0 50.90 58.20 36.7 0 41.90 27.10 31.00 18.8 0 21.40 13.6 0 15.40 10.7 0 12.20 8.6 8 9.9 2 6.94 7.93 5.28 6.03 4.21 4.81 3.29 3.76 2.56 2.93 2.15 2.51
90m
65.40 47.20 34.8 0 24.10 17.40 13.8 0 11.20 8.9 2
100m
6.7 9 5.41 4.23 3.29 2.8 8
72.70 52.40 38.70 26.8 0 19.3 0 15.3 0 12.40 9.9 1 7.5 4 6.01 4.70 3.66 3.2 5
Selection table for motor protection
Motor Rating
KW
HP
Apprx. Full Load Current (A) at 415V
Direct On Line MCCB Rating/Type
Star/Delta MCCB Rating/Type
SKB-1
SKB-3/4
SKB-1
SKB-3/4
SKB-0
10
7.5
14
25
-
25
-
-
12.5
9
17
25
-
25
-
-
15
11
21
25
-
25
-
-
20
15
28
32
-
32
-
-
25
19
35
40
-
40
-
-
30
22
41
50
-
50
-
-
40
30
52
80
-
63
-
-
50
37
69
100
-
80
-
-
60
45
80
-
-
100
-
-
75
55
97
-
-
125
-
-
100
75
125
-
-
160
-
-
125
90
156
-
250
-
-
-
150
112
190
-
315
-
250
-
175
130
225
-
315
-
315
-
200
149
255
-
315
-
315
-
220
160
275
-
400
-
400
-
250
186
320
-
400
-
500
600
300
224
375
-
500
-
500
600
350
261
449
-
630
-
630
600
400
298
505
-
630
-
630
600
T h e f i g u re s s h o w n a re based on following motor starting conditions : Direct online 7 X full load current for 5 seconds. Star/Delta 4 X full load current for 12 seconds.