LG Air Conditioner Conditioner Technical Solutions (LATS) Multi V Model Selection Program User Guide Ver 1.7.11.26
LATS User Guide
Table of Contents 1. LATS OVERVIEW
4
LATS Introducti Introduction on ............ .......................... ............................ ........................... .......................... .............4 LATS Multi V Model Selection Program Prog ram .............................. ................... ..................... .......... 5 System Requirements for LATS .......... ..................... ...................... ..................... ................. ....... 6
2. LATS MULTI V MODEL SELECTION PROGRAM
7
Introduction Introduct ion ............. .......................... ........................... ........................... ........................... .................. ....7 Installation Installati on ............. .......................... ........................... ........................... ........................... .................... ......9 Usage Description : Tree Mode ..............................................11 ■
Step 1. Create Project ························································ 12
■
Step 2. Select Model··························································· 23
■
Step 3. Modify the length of pipe arrangement arrangement ·························· 29
■
Step 4. Check System ························································· 30
■
Step 5. Write the report ······················································ 32
39 Usage Description : CAD Mode Mode.......... ..................... ...................... ..................... ............... .....39 ■
Step 1. Create Project ························································ 40
■
Step 2. Select Model··························································· 48
■
Step 3. Draw System and Design Piping···································· 59
■
Step 4. Check System ························································· 70 2
LATS User Guide
Table of Contents 1. LATS OVERVIEW
4
LATS Introducti Introduction on ............ .......................... ............................ ........................... .......................... .............4 LATS Multi V Model Selection Program Prog ram .............................. ................... ..................... .......... 5 System Requirements for LATS .......... ..................... ...................... ..................... ................. ....... 6
2. LATS MULTI V MODEL SELECTION PROGRAM
7
Introduction Introduct ion ............. .......................... ........................... ........................... ........................... .................. ....7 Installation Installati on ............. .......................... ........................... ........................... ........................... .................... ......9 Usage Description : Tree Mode ..............................................11 ■
Step 1. Create Project ························································ 12
■
Step 2. Select Model··························································· 23
■
Step 3. Modify the length of pipe arrangement arrangement ·························· 29
■
Step 4. Check System ························································· 30
■
Step 5. Write the report ······················································ 32
39 Usage Description : CAD Mode Mode.......... ..................... ...................... ..................... ............... .....39 ■
Step 1. Create Project ························································ 40
■
Step 2. Select Model··························································· 48
■
Step 3. Draw System and Design Piping···································· 59
■
Step 4. Check System ························································· 70 2
LATS Overview ■
Step 5. W rite the report ······················································ 73
3. TIPS FOR USING MULTI V MODEL SELECTION PROGRAM
74
Set Scale in Multi V Model selection program ............................74 Assign one load for one indoor unit in Multi V Model selection program75 Draw orthogonal pipes in Multi V Model selection program ..........76
4. CONTACT INFORMATION
78
3
1. LATS Overview
LATS I ntroduction LATS Multi V Model Selection Program System Requirements for LATS
LATS Introduction LATS (LG Air Conditioner Technical Solution) program is a total design solution for LG system air conditioners. It consists of load calculation program and model selection program for system air conditioners. Load calculation program and model selection program can be selectively used. Although users use different load calculation program other than LATS, they can use LATS model selection program.
Note : System air conditioners mean the devices that can operate multiple in door units with one outdoor unit. It is referred as system air conditioners or multi v air conditioners. Each indoor unit can be operated separately and independently.
Note : LG provides various technical data like products, architecture information, maintenance information, etc by the homepage, www.lgeaircon.com. LATS programs and user guides are automatically updated on this site.
LATS Overview
LATS Multi V Model Selection Program LATS Multi V Model Selection program selects the specific model for system air conditioners. It can select products, pipe arrangements, electric design by using AutoCAD. This program is classified as Tree Mode and Cad Mode. For simple piping work, Tree Mode is used. Users can select models even they do not have CAD drawings for building, because they have Tree Mode in a program.
Note : LATS provides auto update feature. When users start LATS program, an auto update notification message appears to guide you a new version of a program.
5
LATS Overview
System Requirements for LATS This is the hardware requirements for using LATS.
Item
Description
CPU
Intel PII,500MHz
Chip Set
Intel
Main Memory
128 MB
Disk capacity/speed
> 40 GB / 5400rpm / < 15ms access
Graphics
Integrated / PCI based
Audio
Integrated / PCI based
This is the software requirements for using LATS.
Item
Description
OS
Windows 98 SE, Windows NT, Windows XP & Windows 2000
Web Browser
Above Internet Expiorer 5.0
Application Software
MS Excel, MS Access
Caution: To get an output as a report form, Micosoft Excel program should be installed on users’ computers before they use LATS program.
6
2. LATS Multi V Model Selection Program
Introduction Installation Usage Description
Introduction LATS Multi V Model Selection program can be operated in two types of modes. Tree Mode is displayed as a tree form, for a simple piping work. When there is no CAD drawing for a building, this program can provide the proper quantity of indoor/outdoor air conditione rs, cutoff, additional refrigerant amounts, etc. However, sometimes users should rearrange the drawing to be transformed by CAD. To do so, users should manage the drawing work on CAD Mode at first.
Caution: Drawings that were managed at CAD Mode at first can be transformed into Tree Mode. However, the drawings that were managed at Tree Mode at first cannot be transformed into CAD Mode. In this case, users should select new CAD Mode to design the piping work. The file that is designed at CAD Mode can be outputted as .dxf file. It can be opend and edited in AutoCAD.
1. Create Project Enter the location information and design condition. Psychrometric chart automatically calculates a dry bulb temperature, wet bulb temperature, and relative humidity of current air. Then load information related to cooling and heating is entered. If users have already used LATS Load program, the result value can be simply loaded by a button. It there is no result, users can manually insert the cooling and heating load as a KW unit.
2. Select Model Outdoor unit automatically sets its entire heat load value. Proper indoor units for each room can be selected by dragging indoor icon or double clicking the box. After indoor air conditioners are chosen, outdoor air conditioners can be chosen by double clicking the outdoor unit icon. Basically, Auto Select Mode is recommended for this.
LATS Multi V Model Selection Program
3. Modify the length of pipe arrangement Users should modify the default length of pipe into an actual length. Users can directly insert the length by double clicking the line. Elbow or curve line should be considered. Combination rate and total length can be checked at any time during the design. After this work is completed, Auto Piping button should be clicked. A meesage that tells the success of auto selection feature appears. The size of pipe and model name of branch are automatically decided based on EPDB (Engineering Product Data Book) data that http://www.lgeaircon.com provides. EPDB is a PDF file that contains the specification information, piping information, etc of products.
4. Check System Click System Check button to check the entire system including model selection, piping work, validation, cooling/heating simulation, etc. Schematic Diagram provides the wire connection picture of indoor/outdoor air conditioners. The quantity of an additional refrigerants that users should install according to the quantity and information for cutoff devices on el ectric leakage is calculated automatically.
5. Write the report The result is outputted as a Microsoft Excel file. Comments, customer information, title, table of contents, system selection, product lists, piping drawings, wire connection picture, etc are covered. For a written estimate, the product price and installation cost can be inserted by vendors.
Note: Tree Mode is based on a system, while CAD Mode is based on a floor. One system matches with one outdoor unit. Tree mode has one outdoor unit and its related hierarchy.
8
LATS Multi V Model Selection Program
Installation 1. Access www.lgeaircon.com to download LATS-Multi V program. Execute the LATS-Multi V program on your local computer. InstallShield Wizard for LATSMultiV appears. Click Next.
2. License Agreement window appears. Read it carefully and click Yes. .
9
LATS Multi V Model Selection Program
3. Customer Information window appears. Enter your User Name and Company Name. For Serial Number, enter latsmultiv. Then click Next.
4. Installation is completed. Click Finish.
10
LATS Multi V Model Selection Program
Usage Description : Tree Mode LATS Multi V Model Selection program can be operated in two types of modes. Tree Mode is displayed as a tree form, for a simple piping work. When there is no CAD drawings for a building, this program can provide the proper quantity of i ndoor/outdoor air conditioners, cutoff, additional refrigerants, etc. However, sometimes users should rearrange the drawing to be transformed by CAD. For CAD Mode, users can manage the drawing work on CAD at first. Following introduces how to use LATS Multi V Model selection program in Tree Mode. This is the main flow of using LATS Multi V model selection program.
11
LATS Multi V Model Selection Program
Step 1. Create Project 1
1. Click
icon or click “Start Programs LGE ” LATSMultiV” to run LATS Multi v model selection program. Then the program runs and this screen shot appears. 2
This is the initial screen display of LATS Multi v model selection program. Following explains each menu and button.
1 2
3 3
1
Menu
File
Menu
Description
New Project
This menu creates a new project.
Open Project
This menu opens a project that users select.
Close Project
This menu closes a project. If you want to open a new project, you should close the previous one first.
View Project
This menu shows a project. 12
LATS Multi V Model Selection Program
Save Project
This menu saves a project.
Save Project As
This menu saves a project as a specific name.
Delete Project
This menu deletes a project
Export
This menu exports a project as a GCSI file.
Exit
This menu closes a project and finishes a program.
System
Menu
Description
Create System
This menu creates a system.
Copy System
This menu copies a system.
Delete System
This menu deletes a system.
System setting
This menu sets a system.
Space Load Summary
This menu shows a space load summary.
Auto Piping
This menu automatically selects Y branch, header and pipe diameter automatically.
System check
System Check supports validatio n check and performance simulation. - Validation check : It check total piping length, longest pipe length after 1st branch, each pipe length and all the validation in PDB. - Performance simulation : It simulates system’s performance from combination, design condition, pipe length and defrosting factor.
System Invalidation property
This menu checks the proper connectivity and number of included sub items.
Generate reports
This menu generates the final report as a Micosoft excel file.
13
LATS Multi V Model Selection Program
View
Menu
Description
Tool Bar
This menu shows Tool bar on your program display.
Status Bar
This menu shows Status bar on your program display.
System Log Viewer
This menu positions a window on your program display that shows a system log.
Project Navigator
This menu shows the left panel on your program display. You can control the size of this part with and closes this part with .
System View
This menu shows System panel, Indoor Units List and System Information.
Schematic Diagram
This menu shows a hierarchical diagram among outdoor unit, indoor unit, brances and pipes.
System preview
This menu shows a current system in a full view to help users watch the entire system easily.
Option
This menu sets the term of project auto save period. Selected box size is also set at CAD Option.
14
LATS Multi V Model Selection Program
Language
Menu
Description
English
This menu shows the current display in English.
Korean
This menu shows the current display in Korean.
Spanish
This menu shows the current display in Spanish.
French
This menu shows the current display in French.
German
This menu shows the current display in German.
Italian
This menu shows the current display in Italian.
User Setting
Users can set their own language that is provided at the above menu.
Help
Menu
Description
LATS Help
2
This menu shows the help contents for LATS.
About LATS
This menu shows the version and information of LATS.
View Update Info
This menu shows the updated information of view.
LATS-Multi V
Menu
Description
Project Information
This menu shows project information.
Model Selection
This menu is selected when users select models in a program.
Generate Report
This menu generates final report that is created after users use LATS-Multi V program. 15
LATS Multi V Model Selection Program
3
Project
Menu
Description
Create Project
This menu creates a new project.
View Project Info
This menu shows a project information.
Open Project
This menu opens a popup window to select a project to open, which is already made.
Delete Project
This menu deletes a project.
Close Project
This menu closes a project. If you want to open a new project, you should close the current one first.
2. Press Create Project button to see this window.
1 2 4
3 5 6
7
1 Date that the project is created 2 Project Name 3 Path of the project to save it 16
LATS Multi V Model Selection Program
4 Project Unit
SI/IP: For heat load calculation unit, LATS includes SI, which is an international standard and IP, which is an English standard. US and middle east use IP while Europe uses SI. Some countries use IP for quantity and SI for l ength. This kind of mixed usage is also possible. Simulation Mode: Users select Cooling mode to make their projects based on cooling operation. In this case, the usage is focused on cooling. Users select Heating mode to make their projects based on heating operation. In this case, the usage is focused on heating. 5
Outdoor Unit Type Users can decide the outdoor unit type that they want from the drop down button.
6
Detailed Comments for the project Users enter their detailed comments on this blank. Users check the checkbox of Use CAD to use CAD Mode.
7 Direction button
User can move next step.
Note :
Tree mode shows the design as a tree shape.
Cad mode shows the design on an existing CAD drawuing. Output can be transformed as a DXF file and opened at Auto CAD to be editted.
17
LATS Multi V Model Selection Program
Caution: Be sure to active Use CAD option if you are using CAD drawing for model selection. To Use Tree mode, do not check it.
From this Create Project window, enter t he project information. Then click Next. - Date that the project is created - Project Name - Path of the project to save it - Project Unit - Simulatino Mode - Outdoor Unit Type - Detailed Comments for the project
3. Select country and city. Then input design condition. 1
Change the design condition if the given values do not satisfy your requirements. If you change one of the following air property (DBT,WBT,RH), psychometric process will be executed. Other related values will be found. Click Next.
2
1 Insert the country, State/Province and City information. 2 Dry bulb temperature, Wet bulb temperature and Relative humidity should be inserted. This information should be inserted for each indoor and
outdoor also in Cooling a nd Heating condition.
18
LATS Multi V Model Selection Program
4. When selecting Open Load, you can load the result calculated by LATS-LOAD. Clik Open load button. - Open load You can open the load information that was previously calculated by LATS Load program. - Add floor/Add space If you do not use the previously calculated value of LATS Load program, you can manually insert the floor information with this button. - Remove row, Remove all These row buttons are activated only when floors are added manually in advance. This button removes the currently added row or removes all rows. After you complete your setting, click Next.
5. From this window you can select the pre-calculated heat load of Load program. Select one and click OK.
19
LATS Multi V Model Selection Program
6. The pre-calculated information is displayed as follows. If you do not have the pre-defined value, click Add floor or Add space to add a new row. To remove it, click Remove all button. If LATS LOAD values are not available, manual load entry can also be done simply by adding values in columns Click Next.
7. Input Customer & contractor Information. It will be printed out on your final report. After filling all data, click Finish. Then model selection window appears.
20
LATS Multi V Model Selection Program
This is the initial display of Tree mode. Following is a description for menus and icons.
21
LATS Multi V Model Selection Program
Icon
Description Save project, Ctrl + S System setting, Ctrl + 4 New system, Ctrl + 1 Copy system, Ctrl + 2 Delete system, Ctrl + 3 Auto piping sets the pipe arrangement automatically. F5 System Check checks if the current system is available to be installed and designed. F6 System Validation property checks if the o utdoor unit, indoor unit and brances has proper relation and hierarchy. F7 Toggle description System load summary sees the system load entirely. Ctrl + 5 View reports, F8 System preview Open/Close, Toggle Navigator, Ctrl + P System panel that shows a window that you work on currently Control line Power cable Pipe line
22
LATS Multi V Model Selection Program
Step 2. Select Model From this window, you can start selecting outdoor units, indoor units, branch pipes and header pipes according to our design. Initial window for Multi V program looks like this.
1. Double click on stand-by box. Then this window appears. Choose the type of equipments that you want and click OK. Following is a description for these types.
Menu Indoor Units Y branch
Description Indoor Units This equipment is used for large volume of systems. Pipe can have two brances. Numbers are set before a specific model name is assigned. Specific model is assigned after auto piping.
4 header
Pipe has 4 branches.
7 header
Pipe has 7 branches.
10 header
Pipe has 10 branches. Header is rarely used because of the difficulty in installat ion. This is used for small volume system.
2. If you choose Indoor Unit, this window appears to view the detailed information. Then click OK. Following is an example of choosing an indoor unit and 4 header.
23
LATS Multi V Model Selection Program
At this display, select equipment and design pipes. By simply double clicking an item, you can add or modify the hierarchy of the system.
24
LATS Multi V Model Selection Program
3. At this screen, if you double click Outdoor unit, Y-Branch or indoor unit, a window that displays detailed information of an item is shown. Following is an example of the result after you double click Y-Branch. After viewing it, click OK.
4. Double click room to assign load. This window appears. Select room load and click OK. Then room load is assigned.
25
LATS Multi V Model Selection Program
Then as you see below, the room that you double clicked turned to have Floor-001(room1) information. Like this, choose other rooms to assign heat load.
26
LATS Multi V Model Selection Program
5. Double click Indoor Unit or Drag & Drop Indoor Unit from Toolbar to select indoor unit. This popup window appears. Check the ratio (IDU capacity over Design load). If you want to select accessory, click accessory button. Like this, finish assigning undoor unit selection. Then click OK.
6. Double click Outdoor unit icon after finishing indoor units selection. Outdoor unit window appears. Outdoor unit information supports these types:. - Search Model : It lists models according to a category. - Full Model : It lists all models in same ODU type. - Auto Selection : It lists the supporting model to designed system. (below 100% combination) We recommend you using auto selection. If you use defrosting factor, check Defrosting factor
27
LATS Multi V Model Selection Program
Then as you see below, the outdoor unit icon has its model name.
28
LATS Multi V Model Selection Program
Step 3. Modify the length of pipe arrangement 1. If you want to change pipe length, double click pipe length value. This window appear. Change pipe length as you want. Pipe length should be the equivalent length. You have to check system property window which is notified at the next window. (Combination, total pipe length)
2. Click Auto Piping button at the left part of initial window, to select Y branch, Header and pipe diameter automatically. Firstly, pipe’ s diameter will be decided according to pipe length that is after 1 st branch and capadity of indoor units, and then Auto piping will select a appreciate branch models or Header models More detailed information, limitation and rules are documented in PDB.
3. This window appears to confirm your selection. Click OK. If any problem is not occurred, All branch and header models are selected automatically. If Y branch or Header do not exists, you have to change pipe design or check branch or header in PDB
29
LATS Multi V Model Selection Program
Step 4. Check System 1. Click System Check to simulate the system. System Check supports validation check and performance simulation.
Menu
Validation check
Description It checks total piping length, the longest pipe length afterst 1branch, each pipe length and all validation in PDB. It checks the combination ratio, which should be within 50 ~ 130%. The indoor unit and outdoor unit should be maximum 130 percentage. (if Model type is PLUS II, Any model can be combinated by 200%) (PLUS I) If the position of outdoor unit is higher than indoor unit, it can be maximum 40 meters. For the opposite case, it should be 50 m eters. (PLUS II) If the position of outdoor unit is higher than indoor unit, it can be maximum 100 meters. For the opposite case, it should be 100 meters. More detailed information, limitation and rules are documented in EPDB.
Performance simulation
It simulates system’s performance from combination, design condition, pipe length and defrosting factor.
Caution: * We can guarantee the operatoin only within 130% Combination. (PLUS II Models only) If you want to connect more than 130% combination, please contact us and discuss the requirement like below. 1) If the operation of indoor unit is more than 130%, low airflow operation is recommended in all the indoor units. 2) If the operation of indoor unit is more than 130%, additional refrigerant is needed according to the headquarter guidance.
Each indoor unit capacity is simulated and changed. After system is checked, this window appears. Click OK.
30
LATS Multi V Model Selection Program
2. Press Schematic Diagram button to see this display. Check Additional refrigerant amounts and Wiring design. If you want to go back to Tree mode, you can press Tree button of the left part of initial window.
31
LATS Multi V Model Selection Program
Step 5. Write the report 1. Click Generate Report on the left part of initial window. Select the sheet of reports to make. Then click OK.
32
LATS Multi V Model Selection Program
These are the examples of final report. This is the cover of final report.
33
LATS Multi V Model Selection Program
This is the air conditioning proposal. It covers the proposal information and costs including installation, accessories, etc.
This is the table of contents.
34
LATS Multi V Model Selection Program
This is the load output. It contains building location, design conditions, This is the model selection summary. Outdoor units, Indoor units, pipes and cooling and heating loads, etc. accessories are included. 35
LATS Multi V Model Selection Program
This is the result of system check. It includes design condition, outdoor/indoor information, pipes, etc.
36
LATS Multi V Model Selection Program
This is the pipe design tree illustration and schematic diagram for electric wires.
37
LATS Multi V Model Selection Program
This is the model selection cost analysis sheet. It totally covers outdoor units, indoor units, pipes and branch/header common pipes. This document can be used as an estimation sheet.
38
LATS Multi V Model Selection Program
Usage Description : CAD Mode LATS Multi V Model Selection program can be operated in two types of modes. Tree Mode is displayed as a tree form, for a simple piping work. When there is no CAD drawings for a building, this program can provide the proper quantity of i ndoor/outdoor air conditioners, cutoff, additional refrigerants, etc. However, sometimes users should rearrange the drawing to be transformed by CAD. For CAD Mode, users can manage the drawing work on CAD at first. Following introduces how to use LATS Multi V Model selection program in CAD mode. This is the main flow of using LATS Multi V model selection program.
39
LATS Multi V Model Selection Program
Step 1. Create Project 1
1. Click
icon or click “Start Programs LGE ” LATS-MultiV” to run LATS Multi V model selection program. Then the program runs and this screen shot appears. 2
This is the i nitial screen display of LATS Multi V model selection program. Following explains each menu and button.
1 2
3 3
1
Menu
File
Menu
Description
New Project
This menu creates a new project.
Open Project
This menu opens a project that users select.
Close Project
This menu closes a project. If you want to open a new project, you should close the previous one first.
View Project Save Project
This menu shows a project. This menu saves a project. 40
LATS Multi V Model Selection Program
Save Project As
This menu saves a project as a specific name.
Delete Project
This menu deletes a project
Export
This menu exports a project as a GCSI file.
Exit
This menu closes a project and finishes a program.
System
Menu
Description
Create System
This menu creates a system.
Copy System
This menu copies a system.
Delete System
This menu deletes a system.
System setting
This menu sets a system.
Space Load Summary
This menu shows a space load summary.
Auto Piping
This menu automatically selects Y branch, header and pipe diameter automatically.
System check
System Check supports validatio n check and performance simulation. - Validation check : It checks total piping length, the longest pipe length after 1st branch, each pipe length and all validation in PDB. - Performance simulation : It simulates system’s performance from combination, design condition, pipe length and defrosting factor.
System Invalidation property
This menu checks the proper connectivity and number of included sub items.
Generate reports
This menu generates the final report as a Micosoft excel file.
41
LATS Multi V Model Selection Program
View
Menu
Description
Tool Bar
This menu shows Tool bar on your program display.
Status Bar
This menu shows Status bar on your program display.
System Log Viewer
This menu positions a window on your program display that shows a system log.
Project Navigator
This menu shows the left panel on your program display. You can control the size of this part with and closes his part with .
System View
This menu shows System panel, Indoor Units List and System Information.
Schematic Diagram
This menu shows a hierarchical diagram among outdoor unit, indoor unit, brances and pipes.
System preview
This menu shows a current system in a full view to help users watch the entire system easily.
Option
This menu sets the term of project auto save period. Selected box size is also set at CAD Option.
42
LATS Multi V Model Selection Program
Language
Menu
Description
English
This menu shows the current display in English.
Korean
This menu shows the current display in Korean.
Spanish
This menu shows the current display in Spanish.
French
This menu shows the current display in French.
German
This menu shows the current display in German.
Italian
This menu shows the current display in Italian.
User Setting
Users can set their own language that is provided at the above menu.
Help
Menu
Description
LATS Help
2
This menu shows the help contents for LATS.
About LATS
This menu shows the version and information of LATS.
View Update Info
This menu shows the updated information of view.
LATS-Multi V
Menu
Description
Project Information
This menu shows project information.
Model Selection
This menu is selected when users select models in a program.
Generate Report
This menu generates final report that is created after users use LATS-Multi V program. 43
LATS Multi V Model Selection Program
3
Project
Menu
Description
Create Project
This menu create a new project.
View Project Info
This menu shows a project information.
Open Project
This menu opens a popup window to select a project to open, which is already made.
Delete Project
This menu deletes a project.
Close Project
This menu closes a project. If you want to open a new project, you have to close the previous one first.
2. Press Create Project button to see this window.
1 2 4
3 5 6
1 Date that the project is created 2 Project Name 3 Path of the project to save it 4 Project Unit 44
LATS Multi V Model Selection Program
SI/IP: For heat load calculation unit, LATS includes SI, which is an international standard and IP, which is an English standard. US and middle east use IP while Europe uses SI. Some countries use IP for quantity and SI for length. This kind of mixed usage is also possible. Simulation Mode: Users select Cooling mode to make their projects based on cooling operation. In this case, the usage is focused on cooling. Users select Heating mode to make their project based on heating operation. In this case, the usage is focused on heating. 5
Outdoor Unit Type Users can decide the outdoor unit type that they want from the drop down button.
6
Detailed Comments for the project Users enter their detailed comments on this blank. Users check the checkbox of Use CAD to use CAD Mode.
Note :
Tree mode shows the design as a tree shape.
Cad mode shows the design on an existing CAD drawuing. Output can be transformed as a DXF file and opened at Auto CAD to be editted.
Caution: Be sure to active Use CAD option if you are using CAD drawing for model selection. To Use Tree mode, do not check it.
45
LATS Multi V Model Selection Program
From this Create Project window, enter the project information. Then click Next. - Date that the project is created - Project Name - Path of the project to save it - Project Unit - Simulatino Mode - Outdoor Unit Type - Detailed Comments for the project
3. Select country and city. Then input design condition. 1
Change design condition if the given values do not satisfy your requirements. If you change one of the following air property (DBT,WBT,RH), psychometric process will be executed. Other related values will be found. Click Next.
2
1 Insert the country, State/Province and City information. 2 bulb temperature, Wet bulb temperature and Relative humidity should be inserted. This Dry information should be inserted for each indoor and outdoor both in Cooling and Heating condition.
4. When selecting Open Load, you can load the result calculated by LATS-LOAD. Click Open load button. - Open load You can open the load information that was previously calculated by LATS Load program. 46
LATS Multi V Model Selection Program
- Add floor/Add space If you do not use the previously calculated value of LATS Load program, you can manually insert the floor information with this button. - Remove row, Remove all These two buttons are activated only when floors are added manually in advance. This button removes the currently added row or removes all rows. After you complete your setting, click Next.
5. From this window you can select the pre-calculated heat load of Load program. Select one and click OK.
6. The pre-calculated information is displayed as follows. If you do not have the pre-defined value, click Add floor or Add space to add a new row. To remove it, click Remove all button. If LATS LOAD values are not available, manual load entry can also be done simply by adding values in columns. Click Next.
47
LATS Multi V Model Selection Program
7. Input Customer & contractor Information. It will be printed out on your final report. After filling all data, click Finish. Then model selection window appears.
Step 2. Select Model From this window, you can start selecting outdoor units, indoor units, branch pipes and header pipes according to our design. Initial window for Multi V program looks like this.
1. Click
icon to import CAD files, DWG files, onto this initial window for CAD Mode.
48
LATS Multi V Model Selection Program
This is the description for icons in CAD drawing tool bar.
Icon
Description
Icon
Description
Undo
Delete units
Redo
Insert Climb
Zoom in
Insert Y Brances and headers
Zoom out
Create network
Zoom zone
Rotate units in 90 degrees.
Fit for the screen
Rotate units
Pan
Unit Selection
Grid
Insert Outdoor unit
Orthogonal
Insert Indoor unit
Import AutoCAD drawing, dxf file
Insert Space
Export Drawing to dxf file
Insert pipes
Unit Selection
Lef Arrow
Top Arrow
Y-Branch Auto Arrow
49
LATS Multi V Model Selection Program
2. From the popup window, choose a dwg file that you want. Then click Open. This will open CAD drawing with message “CAD file is successfully open.” Click on this pop-up window. Then following CAD file is loaded.
50
LATS Multi V Model Selection Program
3. It would support 2 scale modes. To input text directly, you should know the drawing scale. Choose proper scale for opening CAD drawing and then click Set. To use drawing line, after inputting line length, click Draw scale line and you should draw the line equal to the length you inputted in CAD drawing. After finishing the scaling, click Exit. You can see the imported CAD drawing like this. If it is out of screen area, click
Fit Window icon for resizing it.
4. Click
the New Room icon for specifying load to different location. Then this window appears. When selecting Open Load, You can load the result calculated by LATS-LOAD program. Add floor or Add space as required. For adding and removing Floor or Space, first click on the row and then click Add or Remove. If LATS LOAD values are not available, manual load entry can also be done simply by adding values in columns. Click on one row and double click the blank to insert the value. Then click OK.
51
LATS Multi V Model Selection Program
5. Click your cursor on a specific location (in CAD drawing) where you want to locate this load information. Likewise choose other locations by repeating the above step.
52
LATS Multi V Model Selection Program
6. Click
the New Indoor Unit icon. This window appears.
Choose indoor unit type and model. Click Accessory (if any required)
7. This window appears. Choose accessories if it is required. Then click OK.
53
LATS Multi V Model Selection Program
8. Then click your cursor at the specific location where you want to locate your indoor unit. Repeat the same steps to locate other indoor units. You can use copy paste command also for locating other i ndoor units.
54
LATS Multi V Model Selection Program
9. Click
to connect room information and IDU.
55
LATS Multi V Model Selection Program
Caution: You have to connect the middle of Room to the middle of IDU, with your mouse. (marked “X” in middle point).
10. Adjust indoor unit direction by clicking Indoor Unit and then Rotate Angle icon. This window appears. Fill in the required rotation angle and then click OK. You can see pipe connecting point (as dash) at this location of indoor unit.
Caution: All rotation will be taken place by considering initial position as reference.
56
LATS Multi V Model Selection Program
11. Click outdoor unit icon. This window will appear Outdoor unit window appears. Outdoor unit information supports these types:. - Search Model : It lists models according to a category - Full Model : It lists all models in same ODU type - Auto Selection : It l ists supporting model to designed system. (below 100% combination) We recommend you using auto selection. If you use defrosting factor, check Defrosting factor Other optional accessories can also be chosen by clicking Accessories button. After selecting above value, click OK.
57
LATS Multi V Model Selection Program
12. Click your cursor at a specific location where you want to locate your outdoor unit. You can see outdoor unit icon like the sign on this picture.
Caution: One outdoor unit should have only one system.
58
LATS Multi V Model Selection Program
Step 3. Draw System and Design Piping
1. Click
New Equipment icon to see this window. Select Y-branch or Header if it is required. Then click OK.
Menu Indoor Units Y branch
Description Indoor Units This equipment is used for large volume of systems. Pipe can have two brances. Numbers are set before a specific model name is assigned. Specific model is assigned after auto piping.
4 header
Pipe has 4 branches.
7 header
Pipe has 7 branches.
10 header
Pipe has 10 branches. Header is rarely used because of the difficulty in installation. This is used for small volume system.
Caution: Assigning heat load for room, indoor unit, outdoor unit and pipes has no specific fixed order. You can start assigning any of them first.
59
LATS Multi V Model Selection Program
2. Then click your cursor at a specific location where you want to locate your new equipment unit, Y-Branch. You can adjust Y-branch direction by clicking Y-branch and then Rotate Angle icon. You can adjust Y-branch direction by clicking Y-branch and then Rotate Angle icon. This window appears. Fill in the required rotation angle and then click OK. You can see pipe connecting point (as dash) at this location of indoor unit. All rotation will be taken place by considering initial position as reference.
60
LATS Multi V Model Selection Program
3. Click
New Pipe icon. Then click & drag left button of your mouse on the drawing and finally release this button at indoor/Y-branch, which is the end point of that pipe. You can see drawn pipe between outdoor and Y-branch or Y-branch and Indoor units like the above sample. Connect pipes between various unit, outdoor unit, Y-branch/header and indoor units.
61
LATS Multi V Model Selection Program
When you connect the indoor units, Y- branch and outdoor units, they should be connected with line, which starts from the red dot and ends at the red dot.
Caution: Use Ortho On/Off option for drawing orthogonal pipe. After drawing pipes, right click on the pipe (on white color indenter in the middle of pipe) and drag it slightly with Shift Key pressed for locating your pipe orthogonally. You have to connect the object to the object clearly. If you move your pointer near to the connection mark, the pointer would be attached to t he connection point.
62
LATS Multi V Model Selection Program
Note:
Outer line of indoor unit has small white rectangle, when it is clicked. Left click a mouse and move the mouse to move indoor units. Or click
to insert an exact angle value for rotation.
4. In the Floor Viewer panel on your initial window, you can add new floor. Right click on Floor0 and choose Add Floor.
63
LATS Multi V Model Selection Program
5. After adding floor, right click on the same floor (Floor1 icon) and click Edit icon to see a popup window. Fill in the floor height from outdoor unit and then click Ok. To import CAD drawing, repeat the above step. After adding floor, perform the same operation like the above explanation. Add Room, Indoor Units, Y-branch/Header and Pipes on the new floor like the explanation above.
6. Click
New Climb icon for connecting added floor (Floor1) to the previous floor (Floor0). This popup window appears. Select the floor to link with work floor by climb and click Ok.
64
LATS Multi V Model Selection Program
7. Click your cursor at a specific location where you want to locate Climb piping and connect line. You can see this Icon and message “Connected “Connected to Floor1” Floor1” which shows the connected floor. “Connected “Connected to Floor1” Floor1” is connected with an indoor unit. Then this indoor unit is connected to the ourdoor unit at the Floor1 through the “Connected “Connected from Floor0” Floor0” part. part. Outdoor unit should have only one connection line.
65
LATS Multi V Model Selection Program
As you see, the other floor has the same icon, which says “Connected “Connected from Floor0.” Floor0.” Then this two floors are connected well.
8. Click
Create Network icon for connecting connecti ng network. If the connection connectio n between pipe and Indoor unit, Y-branch or Outdoor unit is not proper you can see an Error message in your Log Viewer with Error Icon located on wrong connection. Reconnect Error Pipe for further processing. You can see a message “Start Creating Network” in your System Log Viewer.
After correcting pipe connection, click Create Network icon again. If pipes are connected properly then Network Completion message will appear in Log Viewer.
66
LATS Multi V Model Selection Program
Note:
Pipe and Indoor unit are not connected tightly. Pipe is not positioned at the red line of an indoor unit. Select a pipe again to connect it to the red point of an indoor unit.
Branch and pipe are not connected well. Select a pipe to connect it to the branch tightly.
67
LATS Multi V Model Selection Program
9. Click Auto Piping icon from the left part of an initial window. Auto Piping command automatically selects Y-branch/Header branch name, pipe diameter and pipe length.
68
LATS Multi V Model Selection Program
10. The this window appears to confirm your selection. Click OK. If any problem is not occurred, All branches and header models are selected automatically. If Y branch or Header exists, you have to change pipe design or check branch or Header in PDB.
69
LATS Multi V Model Selection Program
Step 4. Check System 1. Click System Check to simulate the system. System Check supports validation check and performance simulation. - Validation check : It checks total piping length, the longest pipe length after 1st branch, each pipe length and all validation in PDB. - Performance simulation : It simulates system’s performance from combination, design condition, pipe length and defrosting factor. Each indoor unit capacity is simulated and changed. After system is checked, this window appears. Click OK. If there is an error message. Fix the error and perform these steps again. 1. Create Network 2. Auto piping 3. System Check
2. Click Tree icon for seeing line diagram of this system Pipe length in Tree Mode is equivalent length. So pipe length in CAD mode is not same with that of Tree Mode. Pipe length in CAD mode is real length.
70
LATS Multi V Model Selection Program
This is the interpretation for this result, marked on the above picture.
Menu
Description
Indoor Units
6 indoor units were installed among 8 available units.
Combination
Combination ratio is 98%.
Total Pipe
39.2 m of total 220.0 m pipes are installed for the outdoor unit.
Caution: If the combination ratio does not meet the rule of PDB, the design process stops here and does not move to the next step.
If you try to change the information of units or pipes in this Tree Mode, this message appears. Once you start your project from CAD Mode, you have to modify it and finish it in CAD Mode. In CAD Mode, you can only read the information at Tree Mode.
Caution: Once you click Tree Mode button and enter into the Tree Mode display, you have to click “Create Network ” button again to go back to CAD mode.
71
LATS Multi V Model Selection Program
3.
Press Schematic Diagram button to see this display. Check Additional refrigerant and Wiring design. If you want to go back to Tree Mode, you can press Tree button of the left part of initial window. Click either of these icons for seeing control wire, power line and pipe line.
CL: shows Communication Line PC: shows Power Line Communication PL shows Pipe Line
4. Click Drawing Export icon
. Input the name of exporting file and click Save. You can save your drawing file as a DXF file.
72
LATS Multi V Model Selection Program
Step 5. Write the report 1. Click Generate Report on the left part of initial window. This window appears. Select the sheet of reports to make. Then click OK. Finally press OK for viewing the above chosen report on excel sheet. You can see the final report at the Tree Mode description part of this User Guide.
Caution: You need MS Excel program installed output as a report form.
on your computer to get your
73
3. Tips for using Multi V Model selection program
Set Scale Assign one load for one indoor unit Draw orthogonal pipes
Set Scale in Multi V Model selection program When you open a CAD drawing from AUTO CAD, scale is changed. After you handle your CAD file on LATS, maginify it 10 times to be well fitted for proper scale.
Original CAD file
CAD file Exported from LATS
Tips for using Multi V Model selection program
Assign one load for one indoor unit in Multi V Model selection program When there is two indoor units for one heat load for a room, devide one heat load into two parts. Connect only one heat load for one indoor unit.
Wrong example
Right example
75
Tips for using Multi V Model selection program
Draw orthogonal pipes in Multi V Model selection program Click Grid On/Off icon from the initial window. Then an window appears for you to insert a gap value between grid. Inser the number and you can see the grid on your display.
Click Grid On/Off icon
Grid Display
Click Orthogonal icon from the initial window. When you move units or draw pipes, you can do your work in horizontal or vertical direction by activating Orthogonal function. You can use Orthogonal and Grid function simultaneously.
1. Click Orthogonal button in the Drawing toolbar. 2-1. During moving unit(s), You can move them o nly in horizontal or vertical direction. 2-2. During drawing pipes. You can draw them only in horizontal or vertical direction. 3. To deactivate Orthogonal function, Click Orthogonal button again.
76
Tips for using Multi V Model selection program
Click
Pan icon to pan CAD work window at an arbitrary direction.
1. Click Pan button in the Drawing toolbar. 2. Click and hold left-button of mouse in the CAD window. 3. Move your mouse point in the CAD window. 4. You can see CAD window moves to t he direction that a mouse point moves. 5. Release left-button of mouse. So you can see the moved view position of CAD window. 6. To deactivate Pan function, Click Pan button again, hit any key or click center/right-button of mo use. If you have a mouse with middle-button of wheel-button, you can pan CAD Work window.
1. Click middle-button or wheel-button of mouse i n the CAD Work window. 2. Move your mouse point in the CAD work window. 3. Release middle-button or wheel-button of mouse.
77
4. Contact Information LATS program ownership PM Group, Air conditioner Lab, Digital Appliance Company, LG Electronics.
Question and further information Access this site and insert your question. Then the specific local engineers or managers for each region will contact you. http://www.lgeaircon.com/cac.cssupport.qna.qna.createQuestioner.laf