How to calculate sizing of vacuum circuit breaker electriciansforums.co.uk /threads/how-t /threads/how-to-calculate-sizing-ofo-calculate-sizing-of-vacuum-circuit-bre vacuum-circuit-breaker.21588/ aker.21588/
Discuss How to calculate sizing of vacuum circuit b reaker in the Commerci Commercial al Electrical Talk area at ElectrciansForums.co.uk. Tags: breaker circuit Thread Status:
Not open for further replies. Please make sure you checkout our forum sponsors, many do discounts for members and, they keep the forum free to use.
1. Offline
mooyong
Guest
1/5
Hi- I am looking for some help/ advice please. I'm confused about how How to calculate sizing of vacuum circuit breaker. This project I work on it use 40m0A TP Vacuum circuit breaker to support pump 800 kW 11kV I calculate the current just 49.4 A (800*1000/1.732/11000/0.85 ) I don't know why it use 400 A Someone know please explain me Sorry for bad english i'm not native language
2. Offline
Knobhead
Guest
It’s the smallest size made by most manufacturers. For most the smallest size is now 630A
3. Offline
mooyong
Guest
2/5
Tony said: ↑ It’s the smallest size made by most manufacturers. For most the smallest size is now 630A Thank you for answer but I would like to know I calculate that (49.4A) correct ot not. There have any factor I must consider or not.
4. Offline
Knobhead
Guest
Other than efficiency your calculation is correct. But you asked why a 400A VCB.
5. Offline
caddy
Guest
Tony said: ↑ Other than efficiency your calculation is correct. But you asked why a 400A VCB.
I think he is asking why a would a 50A motor have a 400A breaker protecting it.
6. Offline
mooyong
Guest
caddy said: ↑ I think he is asking why a would a 50A motor have a 400A breaker protecting it. Yes, I mean that why a would a 50A motor have a 400A breaker protecting it.
3/5
7. Offline
Knobhead
Guest
caddy said: ↑ I think he is asking why a would a 50A motor have a 400A breaker protecting it. Ahh it all becomes clear now, 400A is the current carrying capacity of the VCB, protection is provided by a combination of the Current Transformer (CT) ratio and the Overload (O/L) relays. Protection relays are normally rated at 5A = 100% So for your 800KW motor with a Full Load Current (FLC) of 49A you could use 50/5A CT’s with the O/L’s set at say 110% or 100/5A CT’s with the O/L’s set at 55%. Both will give 110% overload protection. By changing the C/T ratio the O/L’s of the VCB can be set to anything up to 400A The transformers show in the schematic 1500KVA @ 11000V will have a FLC of 79A so you could use 100/5A C/T’s with the O/L’s set to 90% this will give slightly above 110% O/L protection. (The protection relays I’m used to dealing with are the old PBO & TJM10 inverse time mechanical relays, so setting them to within 1 or 2% isn’t easy) Sorry for the confusion.
Last edited by a moderator: Aug 31, 2010 8. Offline
nguyenkhoadung9
Guest
Other than efficiency and voltage drop (at CB) your calculation is correct Tony was right, just forlow tony's instruction
9. Offline
GMES
Chief Gorilla
Staff Member Trusted Advisor 4/5
Thread closed due to it being 6 years old.