MANUAL No. 20601E2.3 Published in Apr. 2006 Revised in Jul. 2010
FK-F SERIES TRANSDUCER Model FK-202F TRANSDUCER INSTRUCTION MANUAL
Carefully read and understand understand this manual before before using the product. product.
After reading this manual, manual, store it in a safe location so that that it can be referenced readily as required.
Thank you for purchasing the FK-F series FK-202F transducer. This instruction manual (referred to as “this manual” hereafter) explains handling instructions and cautions regarding the FK-F series FK-202F transducer (referred to as “this unit” hereafter).
- F FK-202F T Tr ansducer I Manual - Instr uction M
Important notice
▊ Important Information ▊ understand this manual before using the the unit. Store this manual in a safe Carefully read and understand location so that it can be referenced readily as required. questions regarding this manual or the the unit, contact your dealer. dealer. If you have any questions When using this product, it is necessary to be knowledgeable about not only the contents of this
manual, but also regarding the instrumentation and equipment connected to this unit. For safety, it is necessary to have standard knowledge regarding safety in addition to the contents described in this manual. When combining this unit with other instrumentation or equipment and then selling or
transferring ownership as an assembly, always make sure to attach this manual as well and provide it to the end user. disposing of this product, make make sure to follow all all local laws and and regulations. regulations. When disposing comprised of the the following following devices. devices. This unit is comprised
-
FL-202F sensor (referred to as FL sensor hereafter) FW-202F extension cable (referred to as FW extension cable hereafter) FK-202F driver (referred to as FK driver hereafter)
During use, it is necessary to build the system structure according to the instructions in this manual. For system structure examples, refer to page 17. contains some explanations explanations for parts of other separately separately sold equipment, equipment, in order This manual contains to explain their attachment to this unit. separately in this manual may differ from their actual The illustrations of parts that are sold separately appearance. product names listed listed in this manual are the trademarks trademarks or registered Any company names and product trademarks of their respective companies. Sensor Technology, Inc. owns owns the copyright to this manual. manual. Unauthorized Unauthorized publication Shinkawa Sensor of this content, and any and all copying/duplication copying/duplication of the content are prohibited.
- F FK-202F T Tr ansducer I Manual - Instr uction M
1
Important notice liability ▊ ▊ Exclusion from liability Sensor Technology, Inc. shall not be liable liable for any damages or injuries arising arising from Shinkawa Sensor not following the instructions indicated in this manual, or from carelessness or neglect while handling this unit or during its installation. installation. shall not be made for any damage, injury, or loss that occurs as a direct or Compensation shall indirect result of the incorrect use, improper use, modification, or disassembly of this product. Sensor Technology, Technology, Inc. will not take any responsibility responsibility for any items items not listed in this Shinkawa Sensor document and in the warranty, including the guarantee of product merchantability, guarantee for specific objectives or specifications, or for violation of patents, whether they are expressed or implied. manual. If a breakdown breakdown occurs in the unit, repairs The warranty for this unit is at the end of this manual. will be performed according to this warranty. Sensor Technology, Inc. will not take any responsibility responsibility for any and all results from Shinkawa Sensor using parts other than those recommended by our company. Confirmati on of the unit and package items ▊ ▊ Confirmation Shinkawa Sensor Technology, Technology, Inc. performs strict quality control and quality inspections to provide reliable products. When the unit first arrives, please check that it is the correct ordered product, that there was no damage to it during its transportation, and that all accessories (ordered items) are provided in the package. If there is damage to the unit or missing accessories (ordered items), contact your dealer immediately.
- F FK-202F T Tr ansducer I Manual - Instr uction M
2
Index
▊ Index ▊ Page Important notice ...................................................................................................................1 Exclusion from liability .......................... ............................ ............................ .......................2 Confirmation of the unit and package package items ........................ ........................... ..................... 2 Chapter 1 Safety Information ................... ..................... ..................... ..................... .................... 5 1.1
Warning Symbols........................... Symbols...... ..................... .................... ..................... .................... ............. 5
1.2
Cautions Cautions when handling ................. ......................... ................. ................. ................ ................. ................. ................. ................. ..............5 ......5
Chapter 2 Introduction ................... ..................... .................... ..................... .................... ........... 7 2.1
Objectives of this unit...............................................................................................7
2.2
Measurement principles...........................................................................................7
2.3
Specifications...........................................................................................................8
2.4
2.5
2.3.1
Specifications of this unit ..................... ..................... ..................... ............. 8
2.3.2
FL sensor specifications.............................................................................9
FL-202F05...........................................................................................................9
FL-202F08...........................................................................................................9
FL-202F08...........................................................................................................9
2.3.3
FW extension cable specifications ..................... ..................... ................. 10
2.3.4
FK driver specifications .................... ..................... ..................... .............. 10
2.3.5
Additional Specification code ................... ..................... .................... ....... 10
2.3.6
Recommended specifications for the monitor cable............ ..................... 11
Outer dimensions and part nomenclature..............................................................12 2.4.1
FL sensor outer dimensions and part part nomenclature .................... ............ 12
2.4.2
FW extension cable outer dimensions and part nomenclature.................14
2.4.3
FK driver outer dimensions and part nomenclature..................................15
System configuration example...............................................................................17
Chapter 3 Installation ..................... .................... ..................... .................... ..................... ......... 18 3.1
3.2
3.3
Installation environment.........................................................................................19 3.1.1
FK driver installation environment ................... ..................... .................... 19
3.1.2
FL sensor installation environment...........................................................20
FK driver installation ..................... ..................... ..................... ..................... .......... 22 3.2.1
Installation of FK-202F-2, FK-202F-3, and FK-202F-4 ....... .......... ....... ....... ..... .. 22
3.2.2
Installation of FK-202F-1.......................................................................23
FL sensor installation.............................................................................................24 3.3.1
When using the VZ-3A bracket (separately (separately sold) ..................... ................ 24
3.3.2
When using the VZ-10A sensor sleeve (separately sold).........................25
3.3.3
Gap adjustment........................................................................................26
- F FK-202F T Tr ansducer I Manual - Instr uction M
3
Index 3.4
Wiring connections ................................................................................................ 27 3.4.1
FW extension cable connection (When using the FW extension cable)...28
3.4.2
FL sensor connection ............................................................................... 29
3.4.3
Monitor (VM monitor) connection ............................................................. 29
3.4.4
Confirmation after completing connection ................................................ 31
3.4.5
Set gap voltage confirmation....................................................................31
Chapter 4 Maintenance/Inspection ........................................................................................... 33 4.1
Periodic inspection.................................................................................................33
4.2
Unit life...................................................................................................................33
4.3
Troubleshooting ..................................................................................................... 34
Chapter 5 Individual characteristics data .................................................................................. 35 5.1
Standard static characteristics ............................................................................... 35
5.2
Sensor temperature characteristics (System cable length: 5m).............................36
5.3
Driver temperature characteristics (System cable length: 5m) .............................. 37
5.4
Static characteristic effect due to power source voltage variation..........................38
5.5
Static characteristic effect by target material..........................................................39
5.6
Static characteristic effect due to target diameter .................................................. 40
5.7
Static characteristic effect by target curved surface...............................................41
5.8
Static characteristic effect due to target end face .................................................. 42
5.9
Static characteristic effect due to side wall.............................................................43
5.10 Frequency characteristics......................................................................................44 Chapter 6 Information About Intrinsically Safe Application........................................................45 6.1
TIIS........................................................................................................................45
6.2
CSA ....................................................................................................................... 46
6.3
ATEX ..................................................................................................................... 48
6.4
NEPSI....................................................................................................................49
6.5
KTL........................................................................................................................52
Appendix
Cable wiring/laying.................................................................................................53
- F FK-202F T Tr ansducer Instr uction M Manual --
4
Chapter 1 For safe usage
Chapter 1 Safety Information Read this section carefully to use this product safely.
1.1
Warning Symbols In this document, rules that must be followed in order to prevent injuries or financial losses to customers, and for the safe usage of this unit, is labeled with the following markings. Make sure to understand the contents of these cautions and make sure to follow their instructions. Warning Symbol WARNING
CAUTION
ATTENTION
Point
Meaning This symbol is used to warn against the possibility of serious or fatal injury. Always follow the instructions to ensure safety. This symbol is used to caution against the possibility of injury. Always follow the instructions to ensure safety. This symbol is used to draw attention to the possibility of property damage. Always follow the instructions to prevent damage to equipment.
The Point is used to emphasize important items or to provide useful information.
1.2
Cautions when handling Be sure to observe the following instructions for safe use of this unit.
▊ Prohibited actions ▊ WARNING
Never disassemble or modify this unit. And do not use the unit under conditions outside the standards specified in the specifications. Doing so may lead to failures of the unit, f ires, or personal injuries.
ATTENTION
Do not use transceivers and other radio equipment/cellular phones near this unit. If this unit or signal cables are exposed to electromagnetic waves, the unit may not satisfy the precision indicated in the specifications.
- F FK-202F T Tr ansducer Instr uction M Manual --
5
Chapter 1 For safe usage
▊ Rules to follow ▊ WARNING
When installing this unit, be sure to follow the procedures described in “Chapter 3 Installation”. If the procedures indicated are not followed, it may lead to failures of the unit, fires, or personal injuries.
ATTENTION •
Before operating this unit, be sure to read the instruction manuals for instruments and equipment that will be connected to this unit. The person handling this unit must have specialized knowledge regarding instrumentation and other devices related to this unit.
•
Before touching this unit, be sure to touch a metal section near by to discharge any static electricity. The device may be damaged if exposed to static electricity from a person’s body.
•
Do not perform insulation resistance measurements or voltage endurance tests at locations other than those with the insulation resistance and voltage endurance specifications indicated. Doing so may damage the unit.
•
When performing a megger test (insulation test) of the signal transmission cable, always disconnect the cable from the unit and the monitor. When reconnecting the cable after a megger test, short the cable to ground first before connecting the cable to discharge any electric charge. Connecting cables in a charged condition to the unit or the monitor may damage the unit.
•
In order to prevent system malfunctions in the case that the unit breaks down, add interlock features to the system.
•
If any one of the following conditions occurs, stop using the unit and contact your retailer. Continuing the usage in an abnormal condition may result in fires or failures.
-
•
When there is a strange odor coming from the unit. When the unit is heating up abnormally.
-
If the unit is dropped
-
If the casing of the unit is damaged
Store this unit in a location away from direct sunlight, under the following conditions. Do not store in a location exposed to high temperatures and/or humidity, or where corrosive gasses are present. -
Temperature: -35 to 80 °C
-
Humidity:
30 to 95%RH (No condensation)
- F FK-202F T Tr ansducer Instr uction M Manual --
6
Chapter 2 Introduction
Chapter 2 Introduction 2.1
Objectives of this unit This unit performs non-contact measurement of the distance (gap) between the FL sensor and the measured object (target), and outputs a voltage signal corresponding to the gap. By combining this unit with our monitor, it is possible to measure the vibration of a rotating shaft, its eccentricity, thrust position, rotating speed etc. The unit is utilized for continuous measurement or monitoring of shafts rotating at high speeds, in turbines, generators, compressors, etc. This unit is not designed for use in any other applications.
2.2
Measurement principles The gap between the FL sensor and the target is found according to the following principles. •
If an approximately 1MHz high frequency current is supplied from the oscillator in this unit to the FL sensor, a high frequency magnetic field is created at the FL sensor.
•
By the interlinkage of high frequency magnetic flux in the target, an eddy current will flow on the target surface.
•
When the eddy current flows on the target surface, a magnetic field is created at the target side, and the sensor impedance will change.
•
The output of the oscillator is detected, and the distance vs. output voltage is made linear by a linearizer electrically, and the result is output.
Therefore, if the following relationships are identified in advance, it is possible to find the gap between the FL sensor and the target by measuring the sensor impedance: •
Relationship between the FL sensor and the target gap
•
Relationship of the sensor impedance
Block diagram
- F FK-202F T Tr ansducer Instr uction M Manual --
7
Chapter 2 Introduction
2.3
Specifications
2.3.1
Specifications of this unit SPECIFICATIONS
CALIBRATION MATERIAL MEASUREING RANGE SCALE FACTOR SCALE FACTOR ERROR*2 (including interchangeability errors) LINEARITY*2 (including interchangeability errors) FREQUENCY RESPONCE*2 MAX. IOUTPUT VOLTAGE*2 SENSOR ABNORMAL OUTPUT VOLTAGE*2 OUTPUT IMPEDANCE*2 CURRENT CONSUMPTION (10kΩ load) OUTPUT NOISE*2 SENSOR TIP DIAMETER CABLE DIAMETER CONNECTOR DIAMETER SYSTEM CABLE LENGTH
OPERATING TEMPERATURE RANGE
NOTICE
JIS SCM440 flat surface
1. CALIBRATION MATERIAL MODEL FK-202F Transducers are calibrated for JIS SCM440 flat surface (more than 15mm dia.). If the measured target is other than JIS SCM440 flat surface, it will present a different characteristics. In such a case, c alibration by the connected equipment (e.g. monitor) side should be required for system operation.
0.25mm to 2.25mm from sensor tip 7.87V/mm Within ±5% of 7.87V/mm (for 5m system) Within ±6.5% of 7.87V/mm (for 9m system) Step : 0.25mm, Linear range : 2mm
Within ±25µ m of 7.87V/mm straight line : 2. SHIELD WIRE CONNECTION (for 5m system) Connect shield wire of signal cable (3-wire shielded cable between Within ±38µ m of 7.87V/mm straight line : driver and minitor) to driver’s “Shield” terminal and monitor’s “COM” (for 9m system) terminal. Linear range : 2mm If this is not adhered to, noise may be caused. DC to 10kHz (-3dB) 3. CONNECTOR ISOLATION, etc. The connector connecting the sensor cable and the extension cable shall be insulated with the attached insulation sleeve (t ransparent Approx. -0.6VDC (Sensor OPEN/Sensor SHORT) shrink tube) or fluoro resin insulation tape. 50Ω Current 5mA(max.) The vinyl-insulating tape shall not be used, which may cause the wiring trouble in the case of temperature more than 80°C. Max. -15mA The connector shall not be located in the oil environment. The oil penetration to cable through the connector may cause the Approx. 15mVpk-pk + power supply noise sensitivity change, due to the change of the cable capacitance. Approx. 5mm or 8mm dia. 4. MEGGER TEST OF SIGNAL CABLE Approx. -23VDC
If megger test is made on the signal cable (3-wire shielded cable), be sure to discharge the charged electric load before connecting the cable to driver. If this causion is not adhered the driver could be dameged.
Approx. 2.7mm or 3.6mm dia. Approx. 7.1mm dia. 5m or 9m Sensor Extension Cable Driver Connector
: : : :
-35 to +177°C -35 to +177°C -35 to +80°C -35 to +125°C
5. SENSOR INSTALLATION Not available for rain water at out door use. It may cause the sensitivity change and insulation down.
RANGE OF TEMPERATURE EX1,7,8 : -20 to +60 °C(Sensor, Extension Cable & Driver) AT EXPLOSION PROOF EX4 : -20 to +85°C(Sensor, Extension Cable & Driver) CONSTRUCTION EX5 : -30 to +80°C(Sensor, Extension Cable & Driver)
TEMPERATURE CHARACTERISTIC
OPERATING HUMIDITY RANGE POWER SUPPLY DIELECTRIC STRENGTH OF DRIVER INSULATION RESISTENCE OF DRIVER
6. SCALE FACTOR ERROR The scale factor error margin provides for examination result in our factory. This regulated value is not applied to the examination result in the site.
Sensor : Less than ±3% of F.S. Extension Cable : Less than ±4% of F.S. Condition : Gap=2mm, Target : JIS SCM440 0 to 80°C (at 20°C standard) Driver : Less than ±3% of F.S. Loop : Less than ±6% of F.S. Condition : Gap=2mm, Target : JIS SCM440 0 to 60°C (at 20°C standard) 30 to 95% RH (non-condensing, non-submerged) (Sensor body : 100%RH) -24VDC ± 10% Between each terminals and mounthing plate : 1mA or less at 500VAC for one minute Between each terminals and mounthing plate : 100MΩ or more at 500VDC Spring lock terminal
7. SAFETY BARRIER In case of the intrinsically safe specification, the approved following safety barrier is recommended. • MTL 796Linear range reduces when intrinsic safety system with barrier. (to approx. 95%)
TERMINAL BLOCK APPLICABLE WIRE 0.2 to 1.5mm2 GAUGE DRIVER MASS Approx. 200g *2 The above specification apply at 25°C with -24VDC power supply and load resistance 10kΩ and JIS SCM440 target (thickness≥5mm).
Sensor
Connector
Extension Cable
Driver
System Cable Length : FK-202F1 : 5m FK-202F2 : 9m
• Dimension of target [recommended for rotational speed measurement] B A
D
D
A
D
C
B
C
- F FK-202F T Tr ansducer Instr uction M Manual --
8
C
Dimension of A ≥ 6 Target B ≥ 7 [recommended] C ≥ 2.5 (mm) D ≥16 Set gap [recommended] 1.0 to 1.5 (mm)
30506E1.8
Chapter 2 Introduction 2.3.2
FL sensor specifications FL-202F05
L1 FL-202F05
Armored L A
Thread size
Without With (Without fluoro resin coating)
T
-
With (With fluoro resin coating)
-
Without With (Without fluoro resin coating)
With (With fluoro resin coating)
Case length
L1
Armored
L3
10mm STEP, 0 - 230mm 10mm STEP, M1 M8 × 1 L1 ≤ L2 - 20mm 20 - 250mm e.g.) 06 = 60mm e.g.) 25 = 250mm 0.1inch STEP, 0 - 9.2inches 0.1inch STEP, U1 1/4-28UNF L1 ≤ L2 - 0.7inches 0.8 - 9.9 inches e.g.) 04 = 0.4inches e.g.) 35 = 3.5inches Specified in mm for M threaded sensor. Specified in inch for UNF threaded sensor.
FL-202F08
T
-
Unthreaded length
FL-202F08
L A
L2
-
Thread size
-
L2 -
Unthreaded length
FL-202F08R Thread size M2
M10 × 1
U2 3/8-24UNF
-
L2 -
R5 = 5mm
03 = 30mm
02 = 0.2inches
12 = 1.2inches
Specified in mm for M threaded sensor. Specified in inch for UNF threaded sensor.
Cable allowable tension
98.1N (10kgf)
- F FK-202F T Tr ansducer Instr uction M Manual --
9
05 10 50 90
0.5m 1.0m 5.0m 9.0m
Case length
Without armored: 30mm With armored: 50mm With fluoro resin coating armored: 75mm
Cable length
L3
Unthreaded length
Cable allowable bending radius
0.5m 1.0m 5.0m 9.0m
Case length
L1
05 10 50 90
L3
10mm STEP, 0 - 230mm 10mm STEP, M2 M10 × 1 L1 ≤ L2 - 20mm 20 - 250mm e.g.) 06 = 60mm e.g.) 25 = 250mm 0.1inch STEP, 0 - 9.2inches 0.1inch STEP, U2 3/8-24UNF L1 ≤ L2 - 0.7inches 0.8 - 9.9inches e.g.) 04 = 0.4inches e.g.) 35 = 3.5inches Specified in mm for M threaded sensor. Specified in inch for UNF threaded sensor.
FL-202F08
Cable length
Cable length 05 10 50 90
0.5m 1.0m 5.0m 9.0m
Chapter 2 Introduction
2.3.3
FW extension cable specifications
L -
FW-202F
Cable length
Armored Without
40
4.0m
Armored
45
4.5m
(Without fluoro resin coating)
80
8.0m
85
8.5m
L A
Armored
T
2.3.4
(With fluoro resin coating)
Cable allowable bending radius
Without armored: 30mm With armored: 50mm With fluoro resin coating armored: 75mm
Cable allowable tension
98.1N (10kgf)
FK driver specifications
FK-202F
-
System cable length 1 5m 2 9m
1 2 3 4
Mounting plate DIN rail (35mm) mount Screw mount (50.8 × 50.8mm) Screw mount (92 × 31mm: for VK replacement) Screw mount multi-pitch (50.8 × 50.8mm and 92 × 31mm)
▊ Terminal Arrangement ▊
2.3.5
Terminal no.
Signal
1
OUTPUT
2
COM
3
-24V
4
Shield (COM)
Additional Specification code
/ EX 1 4 5 7 8
/ GEO
Intrinsically safe TIIS (Ex ia ΙΙC T4) CSA (Ex ia ΙΙC T4) ATEX (EEx ia ΙΙC T4) NEPSI (Ex ia ΙΙC T4) KTL (Ex ia ΙΙC T4)
Geothermal Spec.
- F FK-202F T Tr ansducer Instr uction M Manual --
10
Chapter 2 Introduction 2.3.6
Recommended specifications for the monitor cable Use a commercially sold cable to connect the unit and the monitor. A CVVS 3 core shielded cable (straight) is recommended, but if it is not available, a 3 line multiple core cable for light electrical instruments (individually shielded) can be used. Use cables of sizes AWG. No.20 to 16 (0.5mm 2 to 1.25mm2). Cable name
Note
CVVS 3 core shielded cable (straight)
The CVVS 3 core shielded cable is also recommended in the API STANDARD 670. Recommendation: Copper tape shield (core wire; soft copper wire) (Normally, silver plated braid) Use conduit pipe (cable rack) for wiring.
3 line multiple core cable for light electrical instruments (individually shielded)
Recommendation: Outer shield is aluminum tape, copper tape shield The multipair cable can contain a mixture of vibration signals and displacement signals. However, vibration signals for a high amplitude vibration can affect other vibration signals and displacement signals negatively, and these need to be wired on a separate cable.
- F FK-202F T Tr ansducer Instr uction M Manual --
11
Chapter 2 Introduction
2.4
Outer dimensions and part nomenclature
2.4.1
FL sensor outer dimensions and part nomenclature
L1: Unthreaded length L2: Case length L3: Cable length
- F FK-202F T Tr ansducer Instr uction M Manual --
12
Chapter 2 Introduction
L1: Unthreaded length L2: Case length L3: Cable length
- F FK-202F T Tr ansducer Instr uction M Manual --
13
Chapter 2 Introduction
L3: Cable length
2.4.2
FW extension cable outer dimensions and part nomenclature
L: Cable length
- F FK-202F T Tr ansducer Instr uction M Manual --
14
Chapter 2 Introduction 2.4.3
FK driver outer dimensions and part nomenclature
- F FK-202F T Tr ansducer Instr uction M Manual --
15
Chapter 2 Introduction
- F FK-202F T Tr ansducer Instr uction M Manual --
16
Chapter 2 Introduction
2.5
System configuration example This unit is designed to fulfill the specifications when used under the following configuration. Point
Always combine the components of this unit (FL sensor, FW extension cable, and FK driver) so that it will be configured as follows. If this unit is not configured as shown below, or if the FW extension cable is not used in combining the FL sensor and FK driver, the output characteristics will differ dramatically.
Please use a sensor of sensor cable length 5.0m for a system cable length of 5m.
- F FK-202F T Tr ansducer Instr uction M Manual --
17
Chapter 3 Installation
Chapter 3 Installation WARNING •
Installation work, wiring and connections must be performed by a person with knowledge in instrumentation.
•
Always perform grounding. Never apply power until all wiring work and connection work has been completed. If this is not followed there is a possibility of electrocution.
ATTENTION •
Before touching this unit, be sure to touch a metal section near by to discharge any static electricity. The device may be damaged if exposed to static electricity from a person’s body.
•
Before applying power, make sure that all wiring is properly connected. There is a possibility of damage to the unit and fire if improperly connected.
•
Locate this unit away from motors and relays. Install the input/output signal cables away from power system and control system cables. Noise occurring from the motor or relay can adversely affect the unit. We recommend using separate wiring ducts.
•
Do not pull or bend the FL sensor cables and FW extension cables with excessive force. The conductor in the cable may become cut off. The allowable tension of the FL sensor cables and FW extension cables is 98.1N (10kgf). The allowable bend radius is as follows.
•
Without armored cable:
30mm
With armored cable:
50mm
With fluoro resin coating armored cable:
75mm
After completing installation work, confirm the attachment conditions of the unit.
Point
For information regarding typically recommended cable wiring, and installation methods, refer to the “Appendix: Cable wiring/laying” ( Page 48).
- F FK-202F T Tr ansducer Instr uction M Manual --
18
Chapter 3 Installation
3.1
Installation environment
3.1.1
FK driver installation environment Install the FK driver in a location that satisfies the following environmental and install conditions.
▊ Environmental conditions ▊ •
•
Ambient
Must be in a range between -35 to 80 °C when devices are
temperature :
operating.
Ambient humidity :
Must be in a range between 30 to 95%RH (no condensation) when devices are operating.
•
Vibrational
Must be 10m/s2 or less at 10 to 150Hz.
conditions : •
Air cleanliness :
It is desirable to have an air dust particle amount of 0.2mg/m3 or less. It is also desirable to have an especially low amount of corrosive gasses such as hydrogen sulfide, NOx gas, and chlorine, and conductive particles such as iron dust and carbon. (The allowable amount of hydrogen sulfide and NOx gas is based on JEIDA-29 (1979) CLASS S1.) JEIDA:
Japanese Electronic Industry Development Association
JEIDA-29 (1979) CLASS S1 Hydrogen sulfide : 0.01ppm or less NOx gas: 0.05ppm or less (Ambient temperature: 25 °C ± 5 °C, humidity: 40 to 80%RH)
▊ Install conditions ▊ •
If there are walls or other obstacles at the cable connection surface of the FK driver, make sure to keep spacing as shown in the figure below, and take care not to bend the cable excessively.
•
Do not locate above heat emitting objects.
- F FK-202F T Tr ansducer Instr uction M Manual --
19
Chapter 3 Installation 3.1.2
FL sensor installation environment Install the FL sensor at a location that satisfies the following environmental and install conditions.
▊ Environmental conditions ▊ •
Ambient temperature: Must be in a range between -35 to 117 °C when devices are operating.
•
Vibration conditions:
Must be 10m/s2 or less at 10 to 150Hz. (If the sensor vibrates, an accurate measurement cannot be made.)
Other environmental conditions are the same as the content described in “3.1.1 FK driver installation environment” ( Page 19).
▊ Installation conditions ▊ •
Do not install at a location exposed to rain or other moisture. It can lead to reduced sensitivity of the FL sensor, and reduced insulation.
•
A target surface area of 15 mm dia. centered on the FL sensor is required.
•
When placing other FL sensors next to each other, separate the sensor tops by 40mm or more. If they are placed too close together, the FL sensors will interfere with each other.
•
The FL sensor must be installed on a surface with adequate rigidity, that will not be affected by an outside vibration. If the FL sensor vibrates, an accurate measurement will not be possible.
•
For shapes and dimensions around the FL sensor, refer to the installation example 1-3 below. If a piece of metal other than the target is near the FL sensor, an accurate reading will not be possible. If it is unavoidable to install the FL sensor in the methods of installation examples 4 to 7, check the characteristics at the attachment completed conditions. Installation example 1 (most recommended) Dimension X is to be 9mm or more.
Installation example 2 (recommended) Dimension X is to be 9mm or more. Dimension Y is to be 15mm or more.
- F FK-202F T Tr ansducer Instr uction M Manual --
20
Chapter 3 Installation After constructing as shown in installation example
Installation example 3 (recommended)
2, the area shown by the shaded line in the illustration is filled with resin or other insulating material.
Installation example 4 If dimension X is less than 9mm, it will be affected by the attachment plate.
Installation example 5 If dimension Y is less than 15mm, it will be affected by the attachment plate.
Installation example 6 If the attachment plate around the sensor top is chamfered, it will be affected by the attachment plate.
Installation example 7 If the target and the sensor top are not parallel (dimension X1 and X2 are not the same), it will affect the reading.
Installation example 8 If dimension X is 0.25mm or less, measurement will not be possible. The area 0.25mm or less is a non-sensitive area.
The characteristics of output (V) and gap (mm), are as shown in the graph on the right.
- F FK-202F T Tr ansducer Instr uction M Manual --
21
Chapter 3 Installation
3.2
FK driver installation The FK driver installation method differs according to the model. Secure the required spacing described in the installation conditions, and attach properly. The model number is shown on the label on the FK driver.
3.2.1
•
For FK-202F-2, FK-202F-3, FK-202F-4 ( Page 22)
•
For FK-202F-1 ( Page 23)
Installation of FK-202F-2, FK-202F-3, and FK-202F-4 For FK-202F-2, FK-202F-3, and FK-202F-4, they will be directly mounted on the housing or panel. Point
We recommend attaching the FK driver to the VT-1B driver housing (separately sold). When attaching to other panels or mounts, make sure it is a strong flat surface. Tightening Torque 1.18N ・m (12kgf ・cm) or less
Install according to the following procedures.
1
Attach the FK driver to the VT-1B driver housing (separately sold) and affix with the provided 4 screws (M4 × 12). For the FK-202F-4, there are 8 holes on the mounting plate. Use the 50.8mm 50.8mm pitch holes, or the 92mm
×
31mm
×
pitch holes.
- F FK-202F T Tr ansducer Instr uction M Manual --
22
Chapter 3 Installation 3.2.2
Installation of FK-202F-1 For the FK-202F-1, it will be an attachment to a 35mm DIN rail. Install according to the following procedures.
1
Hook the upper tabs on the back of the FK
2
Push the FK driver into the DIN rail until a
driver onto the DIN rail.
“click” is heard from the slide lock. If it does not fit onto the DIN rail well, pull on the slide lock, and push the FK driver against the DIN rail.
3
Make sure that the upper tabs and the slide lock are securely fixed onto the DIN rail.
Point
It is possible to remove the FK driver by pushing down on the slide lock with a flat tip screwdriver.
- F FK-202F T Tr ansducer Instr uction M Manual --
23
Chapter 3 Installation
3.3
FL sensor installation The following describes the installation of the FL sensor. Install properly according to the conditions described in the installation conditions. •
When using the VZ-3A bracket (separately sold) ( Page 24)
•
When using the VZ-10A sensor sleeve (separately sold) ( Page 25) ATTENTION
Do not drop or otherwise subject the FL sensor to shock.
Point
The installation methods described for the FL sensor in this manual complies with API Standard 670.
3.3.1
When using the VZ-3A bracket (separately sold) Install according to the following procedures.
1
Attach the VZ-3A bracket to the mount
2
Insert the FL sensor into the VZ-3A bracket
(body), and temporarily attach with bolts.
screw hole, and adjust the gap between the FL sensor top face and the target. ( Page 26)
3
Tighten the bolts further, and affix the
4
Retighten the lock nut again at the
VZ-3A bracket.
specified torque.
Installation example
- F FK-202F T Tr ansducer Instr uction M Manual --
24
Chapter 3 Installation 3.3.2
When using the VZ-10A sensor sleeve (separately sold) Use the FL-202F08R sensor. Install according to the following procedures.
1
Remove the jam nut of the FL-202F08R
2
Attach the FL sensor to the VZ-10A sensor
3
Attach the VZ-10A sensor sleeve to the
4
Adjust the gap between the FL sensor top
sensor. (At the Jam nut attachment)
sleeve.
mounting (machine casing).
face and the target.
Installation example
- F FK-202F T Tr ansducer Instr uction M Manual --
25
Chapter 3 Installation 3.3.3
Gap adjustment Point
After completing all wiring connections, it is possible to perform gap adjustment using a tester. In this case, make sure to fully understand the content described in this chapter and complete all connection work, then perform gap adjustment according to the procedures in “3.4.5 Set gap voltage confirmation”( Page 31).
Adjust according to the following procedures.
1
Refer to “5.1 Standard static characteristics” ( Page 35), and prepare a gap gage matching the gap that will produce the desired characteristics. Consider the following items for the gap. Set the gap so that even when the ● target is at the nearest point to the FL sensor, the target will still not come into direct contact with the FL sensor. Set the gap so that it will not go beyond ● the linear range of the connection monitor.
2
Being careful not to scratch the sensor top and target surface, insert the gap gage between the sensor top and target.
3
Adjust the FL sensor to a position where the gap gage just moves freely, and affix in place with the jam nut. Tighten the jam nut with the following torque. Model
Tightening torque
FL-202F05-M1
4.0 N m (41kgf cm)
FL-202F05-U1
1.4 N m (15kgf cm)
FL-202F08-M2
8.5 N m (87kgf cm)
FL-202F08-U2
6.8 N m (69kgf cm)
ATTENTION
Make sure to tighten the jam nut at the specified torque. If tightened with excessive torque, the FL sensor may become damaged. If the tightening torque is too small, it may come loose.
- F FK-202F T Tr ansducer Instr uction M Manual --
26
Chapter 3 Installation
3.4
Wiring connections WARNING ●
Make sure the wiring and connections are performed by a person with knowledge in instrumentation.
●
Always perform grounding. Never apply power until all wiring work and connection work has been completed. If this is not followed there is a possibility of electrocution.
ATTENTION ●
Make sure to tighten the collar of the connector by hand. If it is tightened using a tool, the connector may become damaged. If the installation environment does not allow proper tightening by hand and there is a possibility that it may come loose, tighten by an additional 1/4 turn using a plier after tightening by hand.
●
Do not apply excessive force on the screws of the connector. The connector may become damaged.
●
Do not cut the FL sensor / FW extension cables shorter. It may cause problems, such as not being able to perform up to specifications.
Point
●
When connecting the connectors, make sure that the cable is not twisted. If there is twisting stress on the cable, it may slowly loosen the connection. If a twisting force is applied to the direction where the collar will be loosened, twist the extension cable slightly to the opposite direction of the collar tightening direction before connecting, then connect the connector and tighten the collar.
●
We recommend that excessive extension cables be stored in the cable storage box. If it is unavoidable to store inside the driver housing, do not force excessive cables into the housing.
Connections are performed in the following order. 1. FW extension cable connection (When using the FW extension cable) 2. FL sensor connection 3. Monitor (VM monitor) connection 4. Confirmation after connection completion 5. Confirmation of set gap voltage
- F FK-202F T Tr ansducer Instr uction M Manual --
27
Chapter 3 Installation 3.4.1
FW extension cable connection (When using the FW extension cable) When using the FW extension cable, connect the FL sensor and FW extension cable as shown below. Point
The connection area of the connector must not be used in a condition where it is exposed to water or oil. If water or oil enters the connector, the cable capacity will increase, and will cause a loss in sensitivity.
1
Confirm that there are no foreign objects in the FL sensor and FW extension cable connectors. Foreign objects in the connector will cause faulty connections or faulty characteristics.
2
Insert the extension cable through the provided insulation sleeve (clear heat shrink tube).
3
Connect the FL sensor connector and FW extension cable connectors, and tighten the collar by hand.
4
Cover the insulation sleeve over the
5
Apply hot air on the insulation sleeve, to
connector.
shrink the insulation sleeve.
ATTENTION
Never use vinyl tape to insulate. During extended periods of use or when the connector temperature exceeds 80
°C,
vinyl
electrical tape may harden or the adhesive may deteriorate, leading to a dirty connector and faulty insulation. If no spare insulation sleeve is available, protect the connector with a fluorine resin tape. Recommended insulation tape:
Manufacturer:
Nitto Denko Corporation
Product name:
Nitoflon adhesive tape (903uL)
Temperature spec.: -60 to +180 °C 0.08mm thickness
- F FK-202F T Tr ansducer Instr uction M Manual --
28
Chapter 3 Installation
3.4.2
FL sensor connection Connect the FL sensor as follows. Connection is performed in the same manner when using an FW extension cable.
1
Confirm that there are no foreign objects in the FL sensor (or FW extension cable), and in the FK driver sensor input connector. Foreign objects in the connector will cause faulty connections or faulty characteristics.
2
Connect the FL sensor (or FW extension cable) connector and the sensor input connector, and tighten the collar by hand.
3.4.3
Monitor (VM monitor) connection Connect the monitor as follows.
ATTENTION
When using a cable that has been subject to a megger test, make sure to short the cable to ground before connecting, to discharge any electric charge in the cable. Connecting the cable in a charged condition to the unit or the monitor may damage the unit.
Point
●
We recommend using cables described in “2.3.6 Recommended specifications for the monitor cable” (
Page 11) between the unit and
monitor. Because a small signal is being transmitted, a cable that is not recommended may be subject to interference from external noise, and the measurement may become affected. ●
We recommend using a round crimped terminal (JIS C 2805 equivalent) for the monitor side cable terminal, as it provides a good contact and there is little deterioration from aging.
●
We recommend that the length of the non-shielded area be kept under 100mm.
●
For the terminal block arrangement of the monitor, refer to the instruction manual for the monitor.
1
Remove the insulation so that there is 9mm of exposed wire, and twist the wire.
- F FK-202F T Tr ansducer Instr uction M Manual --
29
Chapter 3 Installation
2
Refer to the following drawing, and connect the signal transmission cable to the FK driver and monitor. Connect to the terminal block of the FK driver according to the following procedures. 1. Use a flat tip screwdriver to push down the operation lever of the terminal block (the orange area). (Recommended flat tip screw driver size: W2.5mm × T0.4mm)
2. Insert the signal transmission cable (the 9mm of exposed wire) all the way into the cable insert port of the terminal block, until it hits the back. 3. Pull out the flat tip screwdriver from the operation lever. The signal transmission cable is locked and the connection is complete. Point
The terminal block is affixed by the 2 screws on the ends of the terminal block. If these screws are loosened for installation or inspection work, make sure to affix the terminal block after work is complete by tightening the screws. Refer to “6. INFORMATION ABOUT INTRINSICALLY SAFE APPLICATION”in case of the intrinsically safe spesification. ( Page 45)
- F FK-202F T Tr ansducer Instr uction M Manual --
30
Chapter 3 Installation 3.4.4
Confirmation after completing connection
Before turning on the power, check the following: ●
Make sure that there are no loose terminals, and that all wiring is connected properly.
●
Check that the power line for the power source is connected to PWR (-24V) of the monitor terminal block. Make sure that the FK driver and FL sensor are installed at locations where the installation
●
environmental conditions are satisfied. Make especially sure that there are no problems with the FK driver and FL sensor installation conditions and that they are not installed at the following types of locations. -
Locations with high temperatures and high humidity
-
Locations with a lot of dust
-
Locations exposed to vibration
-
Locations where there are metal objects other than the target near the sensor
After checking all items, check the set gap voltage values. 3.4.5
Set gap voltage confirmation In the following cases, perform confirmation of set gap voltage in order to maintain the performance of this unit. ●
When supplying power to the unit for the first time.
●
When more than 1 year has passed from the last confirmation.
●
When the performance of this unit has been reduced due to a problem of some sort.
Check the set gap voltage using the following procedures.
1 2
Turn the power ON. In order to stabilize the output, perform warm-up for 5 minutes. (leave alone for 5 minutes). Warm-up is performed in order to collect accurate data.
3
Connect the tester (voltmeter) to IN-COM on the monitor terminal block, and read the voltage.
4
Refer to “5.1 Standard static characteristics” ( Page 35), and make sure that the desired set gap voltage is indicated. Point
Data indicated in “5.1 Standard static characteristics” are measured for a SCM440 flat target (dia. more than 15mm). When the target material or shapes differ, the output characteristics (gain) will differ, and it will be necessary to compensate with later equipment. - F FK-202F T Tr ansducer Instr uction M Manual --
31
Chapter 3 Installation
5
If the desired set gap voltage is not gained, readjust the FL sensor position using the following procedures. 1.
Loosen the jam nut of the FL sensor.
2.
Adjust the FL sensor position so that the desired set gap voltage is gained.
3.
After adjustment, tighten the jam nut of the FL sensor at the specified torque. ( Page 26).
ATTENTION
Always tighten the lock nut at the specified torque. ( Page 26)
The above completes the installation of the unit. In subsequent operations, the measurement precision described in the specifications will be satisfied approximately 5 minutes after turning on the power. In the case that this device does not operate as per the specifications, contact your retailer.
- F FK-202F T Tr ansducer Instr uction M Manual --
32
Chapter 4 Maintenance/Inspection
Chapter 4 Maintenance/Inspection The following is a description of maintenance and inspection procedures for this unit.
4.1
Periodic inspection In order to maintain performance and secure system stability of this unit, check the set gap voltage values once a year. Refer to “3.4.5 Set gap voltage confirmation” ( Page 31) for the check procedures.
4.2
Unit life Even if there is no apparent problem, we recommend that the product be replaced every 10 years. Point
The deterioration of this unit depends on the surrounding environment, and may be even shorter than 10 years. In order to secure system stability, 10 years should be considered a guideline, and early replacement is desirable.
The following is a flowchart for finding out when a replacement is required.
- F FK-202F T Tr ansducer Instr uction M Manual --
33
Chapter 4 Maintenance/Inspection
4.3
Troubleshooting Possible problems with the unit are indicated below.
Symptom
Possible cause
Countermeasure
Output is 0V and does not
Power is not ON.
Turn the power ON.
change.
Is not connected properly.
Refer to “3.4 Wiring connections” ( Page 27), and wire correctly.
The FK driver is faulty.
Replace the FK driver.
Output is approximately
The target is beyond the
-0.6V and does not change.
measurement range.
Refer to “3.4.5 Set gap voltage confirmation”( Page 31) to adjust the
gap. FL sensor failure, or the
Measure the resistance between the
FL sensor cable is
sensor connecter central pin and the
shorted or disconnected.
outer conductor, and if not normal, replace the FL sensor. Normal value: Sensor coil resistance: Approx. 5.5Ω Sensor cable resistance: Approx. 0.25Ω/m
The FW extension cable
Measure the resistance of the
is shorted or
extension cable, and if not normal,
disconnected.
replace the FW extension cable. Normal value: Center conductor resistance: Approx. 0.25Ω/m Outer conductor resistance: 0Ω Center pin to outer conductor resistance: ∞Ω
There is a foreign object
Disconnect the connector, and check
in the connector.
that there are no foreign objects in the connector.
The FK driver is faulty.
Replace the FK driver.
Output is approximately
The target is outside the
Refer to “3.4.5 Set gap voltage
-22V and does not change.
possible measurement
confirmation” (
range.
the gap.
FK driver is faulty.
Replace the FK driver.
- F FK-202F T Tr ansducer Instr uction M Manual --
34
Page 31) and adjust
Chapter 5 Individual characteristics data
Chapter 5 Individual characteristics data Static characteristics, temperature characteristics, and other characteristic data are supplied here. Refer to the characteristics data in this chapter for determination of the gap, etc..
5.1
Standard static characteristics Target material: SCM440 flat face (dia. 15mm or more)
- F FK-202F T Tr ansducer Instr uction M Manual --
35
Chapter 5 Individual characteristics data 5.2
Sensor temperature characteristics (System cable length: 5m)
- F FK-202F T Tr ansducer Instr uction M Manual --
36
Chapter 5 Individual characteristics data
5.3
Driver temperature characteristics (System cable length: 5m)
- F FK-202F T Tr ansducer Instr uction M Manual --
37
Chapter 5 Individual characteristics data
5.4
Static characteristic effect due to power source voltage variation
- F FK-202F T Tr ansducer Instr uction M Manual --
38
Chapter 5 Individual characteristics data
5.5
Static characteristic effect by target material
- F FK-202F T Tr ansducer Instr uction M Manual --
39
Chapter 5 Individual characteristics data
5.6
Static characteristic effect due to target diameter Target material: SCM440
- F FK-202F T Tr ansducer Instr uction M Manual --
40
Chapter 5 Individual characteristics data
5.7
Static effect by target curved surface Target material: SCM440
- F FK-202F T Tr ansducer Instr uction M Manual --
41
Chapter 5 Individual characteristics data
5.8
Static characteristic effect due to target end face Target material: SCM440
- F FK-202F T Tr ansducer Instr uction M Manual --
42
Chapter 5 Individual characteristics data
5.9
Static characteristic effect due to side wall Target and side wall material: SCM440
- F FK-202F T Tr ansducer Instr uction M Manual --
43
Chapter 5 Individual characteristics data
5.10
Frequency characteristics
- F FK-202F T Tr ansducer Instr uction M Manual --
44
Chapter 6 Information About Intrinsically Safe Application
6.1
TIIS (Japanese Only)
- F FK-202F T Tr ansducer Instr uction M Manual --
45
Chapter 6 Information About Intrinsically Safe Application
6-2
CSA
- F FK-202F T Tr ansducer Instr uction M Manual --
46
Chapter 6 Information About Intrinsically Safe Application
- F FK-202F T Tr ansducer Instr uction M Manual --
47
Chapter 6 Information About Intrinsically Safe Application
6-3
ATEX
- F FK-202F T Tr ansducer Instr uction M Manual --
48
Chapter 6 Information About Intrinsically Safe Application
6-4
NEPSI (Chinese Only)
- F FK-202F T Tr ansducer Instr uction M Manual --
49
Chapter 6 Information About Intrinsically Safe Application
- F FK-202F T Tr ansducer Instr uction M Manual --
50
Chapter 6 Information About Intrinsically Safe Application
- F FK-202F T Tr ansducer Instr uction M Manual --
51
Chapter 6 Information About Intrinsically Safe Application
6-4
KTL (Korean Only)
- F FK-202F T Tr ansducer Instr uction M Manual --
52
Appendix
Appendix
Cable wiring/laying
Cable wiring/laying
The following descriptions are typically recommended issues in regards to cable wiring and laying. ●
Cables for pulse signals (phase marker, rotation) are to be on a separate cable from vibration and variation signals.
●
Do not mix signal transmission cables and control/power system cables.
●
All cable constructions are to be with conduit pipe or cable racks.
●
A single ground is installed.
Cable wiring/laying example Good example
Bad example
- F FK-202F T Tr ansducer Instr uction M Manual --
53
▊ Warranty ▊ The warranty conditions for this unit are as follows. 1. Warranty conditions for newly delivered products. The warranty period for the delivered product is 3 years (1 year for special products and software) from the time of shipment from our factory. If a failure occurs in the delivered product due to our fault during this warranty period, we will take responsibility for the replacement/repair of that product. Also, if it becomes necessary to dispatch an engineer within the warranty period, traveling expenses based on our company regulations will be charged. The repair cost at this time will be covered by our company. If one of the following conditions applies, the failure will not be covered by this warranty. (1) Improper handling or use by the customer. (2) If the cause of the problem is due to a reason other than by the fault of our company. (3) If there were modifications or repairs made by a party other than our company or persons specified by our company. (4) Handling, storage, or usage under severe environments exceeding design specification conditions. (5) Problems caused by fires, floods, earthquakes, lightning strikes and other natural disasters. (6) Consumable parts. (7) Other failures that are not at the fault of our company. The warranty here covers the delivered product only, and we will not take responsibility for any direct or indirect damages caused by the malfunction of the delivered product. Warranty periods and coverage of warranties for devices manufactured by those other than our company will be at the responsibilities and conditions of those respective manufacturers, regardless of this document.
2. Warranty conditions for repaired products The Warranty period for repaired items will be 6 months after the date of repairs for that item. Other conditions will be as 1. above.