Fire fighting course in QEC (Quality for Engineering consulting) consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; ; senior Electromechanical Engineer 01226663413
............................................... Course contents 1- Fire science : 1-1 Fire safety… 1-2 Fire alarm… 1-3 Fire fighting…
2- Fire fighting systems: 2-1 water suppression system … 2-1-1 sprinkler system; A) Types of sprinklers B) Zone station C) Sprinkler system design (no. of sprinkler, location, net work) D) Special sprinkler systems :( dry, pre action, deluge)
2-1-2 cabinet systems: (class: I, II, III); 2-1-3 hydrant system; 2-1-4 Siamese connection;
2-2 gaseous suppression system… 2-2-1 Weight of gas cylinder; 2-2-2 sequence of operation;
2-3 fire extinguisher… 2-3-1 class; 2-3-2 material; 2-3-3
Note that:
design;
All tables which
3- Fire fighting tank 4- Fire fighting pumps )1(
"
needed, putted on the
5- fire fittings
"
[email protected]
final pages
Fire fighting course in QEC (Quality for Engineering consulting) consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; ; senior Electromechanical Engineer 01226663413
1- Fire science : 1-1 Fire safety
1-2 Fire alarm -
* The Fire Triangle:
: -
fire rated wall
1-3 Fire fighting
Three things must be present at the same time to produce fire:
“inputs” controller 1. Enough OXYGEN OXYGEN to to sustain - fire , smoke, sensors combustion temperature output 2. Enough HEAT to reach ignition temperature : - - types of sensors: 3. Some FUEL or combustible 30 min, 60min, 120min - smoke, heat , multi material - detector Together, they : - produce the CHEMICAL “escape staircase” FACP REACTION that is fire “Fire Alarm Control Panel”
Take away any of these things and the fire will be extinguished
NFPA: National Fire Protection Association
!!
)2(
"
"
[email protected]
*
Fire fighting course in QEC (Quality for Engineering consulting) consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; ; senior Electromechanical Engineer 01226663413
1- Fire science : 1-1 Fire safety
1-2 Fire alarm -
* The Fire Triangle:
: -
fire rated wall
1-3 Fire fighting
Three things must be present at the same time to produce fire:
“inputs” controller 1. Enough OXYGEN OXYGEN to to sustain - fire , smoke, sensors combustion temperature output 2. Enough HEAT to reach ignition temperature : - - types of sensors: 3. Some FUEL or combustible 30 min, 60min, 120min - smoke, heat , multi material - detector Together, they : - produce the CHEMICAL “escape staircase” FACP REACTION that is fire “Fire Alarm Control Panel”
Take away any of these things and the fire will be extinguished
NFPA: National Fire Protection Association
!!
)2(
"
"
[email protected]
*
Fire fighting course in QEC (Quality for Engineering consulting) consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; ; senior Electromechanical Engineer 01226663413
2- Fire fighting systems:
2-1 water suppression system: 2-1-1 sprinkler system: 2-1-1-a) Types of sprinklers: Firstly: “According to concept of work”
1- Glass bulb type
2- Fusible link type -
-
: -
glass bulb sprinkler body mercury
fusible link
"
"
Deflector :
!
)3(
"
"
[email protected]
!
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Secondly: “According to direction of flow ”
1- Pendent
2- Upright
3- side wall
-direction of flow is up word - fall ceiling not found
-direction of flow down word - fall ceiling is found
" "
"
-direction of flow is linear pendent & upright
"
:
- fall ceiling is found:
"
When ceiling void >= 90 cm
"
"
Pendent, upright, side wall
"
90 =>
pendent, upright
side wall
:
-
-
)4(
"
-
"
[email protected]
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-1-1-b) Zone control station: “ZCS” ZCS
ZCS
Main line ZCS
Discharge line
cross main ZCS
Suction line
branches ZCS
Riser
FF tank
Pump
. * Zone
*
control station: “ZCS” consists of the following components:
1) OS&Y gate valve: “outside screw & yoke” ……. (Normally open)
)5(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2) temperature switch: OS&Y gate valve
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
3) Flow switch: fire
"
switch
"
switch
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
4) Check valve: “none return valve”
)6(
"
"
[email protected]
N
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
5) Pressure gauge: “0.5: 12.1 bar”
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
6) Pressure reducing valve: “PRV” “Where required”
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
7) Test & drain valve: “ normally closed” test
flushing
* must be the lowest point in the net work :
)7(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Zone control station: “ZCS”
N Test & drain
m a e B
ZCS
External additional flushing connection
* must be the lowest point in the net work
.. : ... )8(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-1-1-C) Sprinkler system design: a) No. of sprinkler & its location Steps: 1- Determine the space hazard; “depend on space occupants”
:
NFPA
1- Light hazard
2- Ordinary hazard
3- extra hazard
2- From NFPA tables ; according to hazard We get four important notes which used in our design: a) Maximum spacing between two sprinkler equal to (4.6 m) b) Minimum spacing between two sprinkler equal to (1.8 m) c) Maximum spacing between sprinkler & wall equal to (half of the space between two sprinkler = (4.6\ 2) = (2.3 m) d) Minimum spacing between sprinkler & wall equal to (4” = 10.2cm = 102mm)
3- Making distribution for sprinkler:
A) (length \ 4.6) = B) (width \ 4.6) = C) x, 2x ; y, 2y :
)9(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
:
:
) m 5 * m 10 (
10
5
A) (length \ 4.6) = (10 \ 4.6) = 2.2
=3
)3(
:D
width
B) (width \ 4.6) = (5 \ 4.6) = 1.1
)10(
"
=2 )2(
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
:
C) x, 2x ; y, 2y : :
sprinkler 2X
-:
X Y
X
2X
2X
X
Y
2Y
Y
10 = X
*
X = 1.6 m
6X = 10
5=Y Y = 1.25m
*
4Y = 5
:
a) Maximum spacing between two sprinkler equal to (4.6 m) b) Minimum spacing between two sprinkler equal to (1.8 m) c) Maximum spacing between sprinkler & wall equal to (half of the space between two sprinkler = (4.6\ 2) = (2.3 m) d) Minimum spacing between sprinkler & wall equal to (4” = 10.2cm =
102mm)
)11(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
: -:
)12(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
a) No. of sprinkler & its location b) Net work sizing: Steps:
1- Rooting: ( simple, symmetrical)
2- Sizing: We get the sizing from pipe schedules which depend on (hazard, no. of sprinkler) Locke @ table (22.5.2.2.1 light hazard pipe schedule) , (22.5.3.4 ordinary hazard pipe schedule) , (A.22.5.4 extra hazard pipe schedule ) page “66” in this file.
*
: 22.5.2.2.1 Light hazard pipe schedule Pipe sizing 1” 1.25”
No. of sprinkler 1, 2 3, 4
.
! )13(
"
"
[email protected]
:
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
net work sizing :
light
Design net work :
)14(
"
sizing
"
[email protected]
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
side wall sprinkler
:
Firstly lock @ table 8.7.2.2.1 page 67 for standard side wall sprinkler Where: S
4.25 =
L
3.75 =
:
Secondly lock @ table 8.9.2.2.1 page 67 for extended coverage side wall sprinkler Where: 8.5 :
S
"
L
"
4.25 => 3.75 =
,,,,,,,,,,,,,,,,,,,,,,, 8.5
( .
8.5
) )15(
"
S
"
[email protected]
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-1-1-D) Special sprinkler systems: 1- Wet pipe system
2- Dry pipe system
- Zone station valve is normally open. - Normal condition: 0: 74 C; 1 bar.
- Zone station valve is normally open but after it we put “ clapper arm” to prevent the water from crossing. : clapper arm
- Single acting system
(
-
zone station
) .
-
fire
-
compressed water
compressed air
clapper arm
- Single acting system
:
: .
.
:
:
:
.
:
.
-
)16(
"
"
[email protected]
-
. :
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
3- Pre action system
4- Deluge system
- Zone station valve is normally closed. - Zone station valve is normally closed.
-
SPK
.
zone valve SPK
)
- double acting system
- Single acting system
Nozzle : 1- Single knock: 2- Double knock:
) SD
(
HD
)17(
(
"
"
[email protected]
SPK
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-1-2 cabinet systems: (class: I, II, III); - Manual - Inside the building
:
1- Class I
2- Class II
- it called civil defense cabinet
- normal users
3- Class III - fire hose station -
- D = 2.5 inch
- D = 1 inch or 1.5 inch
- design condition: * 250 GPM * Mini. Pressure 6.9 bar * Max. pressure 12.1 bar note that: - When P>12.1 bar; pressure reducing valve must used “PRV”.
- design condition: * 100 GPM * Mini. Pressure 4.5 bar * Max. pressure 6.9 bar note that: - When P>6.9 bar; pressure reducing valve must used “PRV”.
: : .
.
)18(
"
"
[email protected]
- D = 1 inch and 2.5 inch - design condition: * 250 GPM * Mini. Pressure 6.9 bar * Max. pressure 12.1 bar -note that: - For 1” connection; pressure reducing valve must used “PRV”. - For 2.5” connection; some levels must have “PRV” when P>12.1 bar.
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
- Design of cabinet system: 1- Travel distance: * Standard length reel “
“= 30 meter
Note that: - 30 meter is a travel distance not across distance. - Projector which composed on the reel spewing water through 6 m eter
2- Guide location: “
“
- Escape stair case - Escape corridor - @ car park in ‘main inlet, main exit’
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
-:
-
- Poly line: reel - List properties ‘L I’ enter:
.. )19(
"
..
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-1-2_ hydrant system: - Infra net work - Street fire hydrant 30
hydrant
.
50 hydrant 2
- Location of hydrant: exposed
)20(
"
"
[email protected]
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-1-3 Siamese connection; ZCS
ZCS
Main line ZCS
Discharge line
cross main ZCS
Suction line
branches ZCS
N
FF tank
Pump
Check valve
"
:
.
"
- Siamese connection:* supply the system with water. * connected on the pump discharge. * check valve must be used with it;
.
)21(
Siamese connection
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2.5 inch
dry pipe
Siamese
:
discharge
- Location of Siamese connection: - exposed location - note that; minimum 1 Siamese connection for the project. <<<<<<<<<<<<<<<<<<<<< : .
:
)22(
"
"
[email protected]
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Deluge system
)23(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
3- Fire fighting tank design 3-1 tank capacity “volume”:
Volume = pump flow in GPM * required storage time in minute Where:
- Pump flow
in GPM “calculated”
- required storage time hazard
in minute “depend on hazard”
Light
required storage time in minute
30: 60 min
ordinary 60: 90 min
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
3-2 tank connections & construction: Important notes: a) Same tank “ fire fighting & plumbing” b) Divide the tank in to t wo “2” equal partition.
)24(
"
"
[email protected]
extra 90: 120 min
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
- Puddle flinch: -
puddle flinch
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Connection on tank 1234567-
diameter Fire fighting
Fire fighting suction pipe Fire fighting test line Filling lines Over flow line Drain line Domestic suction pipe Vent pipe
)25(
"
height 25: 30 cm
Fire fighting plumbing plumbing plumbing plumbing plumbing
cm "10 :5" + Inside depression Fire fighting storage hff = vff \ Atank over flow
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Vent pipe:
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, - To avoid cavitations: 1- anti vortex plate 2D where D is suction pipe diameter. 2- The distance between anti vortex plate & depression = 6 inch= 150mm= 15cm.
- Other benefits of this distance are; turbulence
- Trench drain:
: - Drainer pipe - Over flow line - Pump room water plumbing
)26(
"
"
[email protected]
, air bubbles
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
–
-
)27(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
4- Fire fighting pumps 4-1 Fire fighting pumps: 1- Electrical pump
2- Stand by pump a) Diesel
)28(
"
-
b) electrical with generator
It work when: - Failure in elect. pump - elect. Pump not enough for the system demand.
stand by
3- Jockey pump
elect. jockey control panel
"
[email protected]
NFPA
-
pressure main pump
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
4-2 hydraulic calculation: .
jockey
stand by
-
elect.
: 1- cabinet system only
a) Class II
2- sprinkler system only
3- combined system
b) Class I,III
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 4-2-1 cabinet system only:
a) Class II; 100 GPM; 4.5 bar: 6.9 bar
- flow calculation: class II
100 GPM
-
- Head calculation:
Hp = Hst + Hres + Hf Where: - Hp
pump head
- Hst
static head
bar
–
10
- Hres
residual head bar 4.5 = )29(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
- Hf
friction head -
hazen-williams formula
Pl = hf= (4.52 * .) \ (. * . ) Where: -Q
the flow in GPM = 100
-C
friction loss coefficient = 120; from table 22.4.4.7 hazen-williams C values page 67
-D
diameter of the pipe; from table 5-7 pipe schedule page 68 distance of pipe in inch
GPM
inch 1 class II
D
-
-
inch 4
,,,,,,,,,,,,,, Ex:
1’’
4’’, 100 GPM
FF tank
Pump
2’’
2.5’’
2.5’’
25 ft
25 ft
25 ft
25 ft
100 GPM
100 GPM
100 GPM
100 GPM
68
5-7 *
2.5’’
sizing
.D
GPM D
inch 1 class I )30(
"
inch 4 "
[email protected]
- - -
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
: "
-
sections diameter
"
flow
5 4
1’’
1
2
3
4’’, 100 GPM
FF tank
Pump
2’’
2.5’’
2.5’’
25 ft
25 ft
25 ft
25 ft
100 GPM
100 GPM
100 GPM
100 GPM
: sr 1 2 3 4 5
section 1-2 2-3 3-4 4-5
2.5’’
-
GPM D 2’’ 100 100 2.5’’ 4’’ 100 1’’ 100
hf
Lpipe
Leq
Ltotal
Hf
Where: From
Pl = hf= (4.52 * .) \ (. * . )
Lpipe + Leq
hf * Ltotal
Table 6.4.3.1 page 68
Hf
1.1
head )31(
Hp "
"
[email protected]
Hf
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
b) Class I ,III; 2.5” , 1” , 2.5”
250 GPM; 6.9 bar: 12.1 bar
- flow calculation: 500 GPM =
2
Flow
-
class III,I
-
250 GPM GPM 1250 Pump
Flow
.
1500
1250
-
Riser 5 .
X
250 GPM
250 GPM
FF tank
Pump
)32(
"
1250 GPM
1250GPM
"
[email protected]
1000 GPM
750 GPM
500 GPM
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
- Head calculation:
Hp = Hst + Hres + Hf Where: - Hp
pump head
- Hst
static head
bar
–
10
- Hres
residual head bar 6.9 =
- Hf
friction head -
hazen-williams formula
Pl = hf= (4.52 * .) \ (. * . ) Where: -Q
the flow in GPM
-C
friction loss coefficient = 120; from table 22.4.4.7 hazen-williams C values page 67
-D
diameter of the pipe; from table 5-7 pipe schedule page 68 distance of pipe in inch
GPM
D
inch 2.5 class I,III
-
inch 4
,,,,,,,,,,,,,,
_ _
..! )33(
"
"
[email protected]
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Ex:
2.5’’ 250 GPM 250 GPM
4’’, 500 GPM 250 GPM
6’’
FF tank Pump
25 ft 1250 GPM
68
250 GPM
6’’
5’’
4”
25 ft
25 ft
25 ft
1000 GPM
750 GPM
5-7 *
250 GPM
500 GPM
-
sizing
.D
GPM
-
D inch 2.5 class I,III
: "
-
inch 4
-
sections diameter
"
flow 4
Ex:
7
6
2.5’’
5
3
250 GPM
2
250 GPM
4’’, 500 GPM 250 GPM
6’’
FF tank Pump
25 ft 1250 GPM
)34(
"
250 GPM
250 GPM
6’’
5’’
4”
25 ft
25 ft
25 ft
1000 GPM
"
[email protected]
750 GPM
500 GPM
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
: sr 1 2 3 4 5 6 7
section 1-2 2-3 3-4 4-5 5-6 6-7
GPM 1250 1000 750 500 250 250
D 6’’ 6’’ 5’’ 4’’ 4” 2.5”
hf
Lpipe
Leq
Ltotal
Hf
Where: From
Pl = hf= (4.52 * Q ^1.85) \ (C^1.85 * D^4.86)
Lpipe + Leq
hf * Ltotal
Table 6.4.3.1 page 68
Hf
1.1
head
Hp
: …
)35(
"
"
[email protected]
Hf
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
4-2-2 Sprinkler system only:
Steps: 1- Most demand area: " NFPA
"
-
demand
Hazard
Most demand Area
2 , 1500 ft 2 2 2 139 , 1500 ft 232 2 , 2500 ft 2
Light Hazard Ordinary Hazard Extra Hazard
139
,,,,,,,,,,,,,,,,,,,
2- Sprinkler density: NFPA
demand
Sprinkler density GPM\ 2
Hazard Light Hazard Ordinary Hazard Extra Hazard
0.1 0.15: 0.2 0.3 : 0.4 ,,,,,,,,,,,,,,,,,,,
3- K factor; flow & pressure:
Q = K √ 5.65 = KSP
FM UL Factory
-
Under writer laboratories uniform listed
mutual :D
)36(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Ex: Required:
- make a complete design for the fire fighting pump which serves a building; the most demand area is as shown. Note that; the hazard is ordinary hazard. NFPA
)37(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Where:
-
Sp1 , qsp1 , psp1 :
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
:
Pl1
X
-
losses
Most demand area
139
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Steps of the solution: a) Location of most demand area b) c) “ Most remote sprinkler” ,,,,,,,,,,,,,,,,,,,,,,,,,,,
1- most demand area = 1500 2 “ordinary hazard” 2- from NFPA Chart = 0.15 GPM\ 2 3- Discharge of the most remote sprinkler:
1 = 1 * Where:
1
Protection Area Limitations per Sprinkler
Hazard Light Hazard Ordinary Hazard Extra Hazard
Protection Area Limitations per Sprinkler Distance between sprinkler (m) Area ( ) 4.6 200 4.6 130 3.7 100
0.15 =
1 = 130 * 0.15 = 19.5 GPM = 1 )38(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
4- Calculate the pressure @ the most remote sprinkler:
1 = K Where
1 K
sprinkler K factor 5.65
∴
19.5 = 5.65
∴ 1 = 11.9 Note that: - The minimum residual pressure for any sprinkler is 7 psi = 0.5 bar.
5- Calculate the friction losses per unit of pipe from the most remote sprinkler to the adjacent sprinkler by using hazenwilliam formula.
=
4.52 ∗ Q 1.85 C 1.85 ∗ D 4.87 Where:
Frictional losses per unit feet psi\ feet Coefficient of friction for the pipe material = 120 black steel
Diameter on “inch” from table. Flow on “GPM” Apply this formula for )39(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413 . . .
∴
=
∗ . ∗ .
=
6- Multiply friction losses per feet (
pl1
feet )* total length (Pipe length + eq. length)
∴ =
*
=
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 7- Calculate the residual pressure on adjacent sp2
= 1 + 1 = 13.5 psi ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 8- Calculate the discharge @ this adjacent remote sprinkler
2 = k ∴ 2 = 5.65 √ 13.5 = 20.7 psi ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 9- Calculate the discharge in this pipe section
2 = 1 + 2 ∴ 2 = 40.2 GPM ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 10-
3
9 8 7 6 5
:
2 \\ 3 = ( 2 +2 ) \\ 3 \\ 3 )40(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
11-
9 8 7 6 5
4
:
3 \\ 4 = ( 3 +3 ) \\ 4 \\ 4 ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, demand area
-
branch
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
Note that:
Sp5 will be ignored in the calculation as it isn’t included in the most demand area
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
4
12-
=
4.52 ∗ Q 4 1.85 C 1.85 ∗ D 4.87
Multiply friction losses per feet (
)* total length (Pipe length + eq. length)
∴ =
=
*
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, SPK
X
- 13
= 4 + = 4 = 3 + 4 4
)41(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
14-
Calculate K factor for the pipe
K= √ ∴ = ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
5
15-
=
4.52 ∗ Q 4 1.85 C 1.85 ∗ D 4.87
spk
Multiply friction losses per feet (
)* total length (Pipe length + eq. length)
∴ =
*
=
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
py = px + pl5
16-
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 17-
5 = ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
18-
6 = 5 + 4 ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
6
19-
)42(
"
=
4.52 ∗ Q 6 1.85 C 1.85 ∗ D 4.87
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Multiply friction losses per feet (
)* total length (Pipe length + eq. length)
∴ =
*
=
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
pz = py + 6
20-
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 21-
7 = ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
22-
8 = 7 + 6 :
8
)43(
Pump flow ##
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
- Head calculation:
Hp = Hst + Hres + Hf Where: - Hp
pump head
- Hst
static head bar
- Hres
–
10
residual head pz = demand area
- Hf
friction head
Hf
-1
demand area
"
diameter
" section
flow
-2
= 4 in : sr 1 2
section
GPM
D
hf
Lpipe
Leq
Ltotal
Hf
Where: From
Pl = hf= (4.52 * Q ^1.85) \ (C^1.85 * D^4.86)
Lpipe + Leq
hf * Ltotal
Table 6.4.3.1 page 68
Hf
head )44(
"
1.1
Hp "
[email protected]
Hf
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
4-2-3 combined system:
Steps: A) Calculate the flow for cabinet system only. B) Add for this flow : 1- Light hazard
2- Ordinary hazard -
GPM 150
GPM 500
3- Extra hazard -
-
C) Head calculation: - calculate head for cabinet - calculate head for sprinkler *** take the larger cabinet
Riser
= 6 in combined system
.
)45(
head
"
"
[email protected]
% 75
-
-
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
4-3 jockey pump calculation:
Head = + 1 bar stand by elect.
> jockey
Flowjockey = 5:20 GPM
Flowjockey = 1% system flow ,,,,,,,,,,,,,,,,,,,,,
∗ Hp = 3960 ∗ ɳ Horse power
0 .65
)46(
"
"
[email protected]
∴
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
4-4 pumps hock up: 1- Two(2) isolating valve “OS&Y gate valve with tamper switch” ; jockey not need OS&Y 2- Check valve 3- Pressure gage 4- Flow meter 5- Eccentric reducer 6- Automatic air vent “AAV” 7- Two(2) flexible connection to prevent vibration 8- Floating floor “spring cap, rubber pad” 9- Flow switch ; jockey not need it (6)
N
Pump
(1)
(8)
)47(
(7)
"
(3)
(2) (9)
"
[email protected]
(4)
(1)
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
For site engineer 5- Fire fighting fittings
5-1 Material takes off 1- Deign package
2- Construction
Design drawing BOQ “pumps, pipes , spk, co2 or fm200 system, cabinet” Specs “specification”
Cost estimation Requesting order
Pipes “fittings, hangar”
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
5-2 Fittings: 123-
threaded fittings weld fittings grooved fittings
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
)48(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
5-2-3 Grooved fittings: :
-
5-2-3-1 end grooved fittings (Elbow, Tee, Reducer)
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 5-2-3-2 coupling :
a) rigid coupling b) flexible
"
"
rigid
flexible
coupling
% 10 ≅
**
coupling
-
reducer coupling
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
5-2-3-3 mechanical Tee :
a) one branch configuration (grooved or threaded
)
b) cross branch (2grooved or 2threaded or grooved threaded)
)49(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
)50(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Ex: fittings
:
)51(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
: 1- grooved Tee 4” * 2.5” * 4” 2- two(2) rigid coupling 4” 3- one(1) rigid coupling 2.5” 4- grooved elbow 2.5” 5- two(2) rigid coupling (RC) 2.5”
reducer
1- grooved Tee 4” * 3” * 4” 2- reducer 4” * 2.5” 3- one(1) rigid coupling 2.5” 4- one(1) rigid coupling 4” 5- one(1) rigid coupling 3” 6- grooved elbow 3” 7- two(2) rigid coupling (RC) 3” Note that: mechanical Tee NFPA
main )52(
"
mechanical Tee "
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
:
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
RN: riser nipple
10 = ~
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
)53(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting) consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; ; senior Electromechanical Engineer 01226663413
)54(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting) consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; ; senior Electromechanical Engineer 01226663413
Ex:
mechanical Tee fittings
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, Note that:
* Pipe schedule:
"4
4” sch 40 40
**
Schedule
pipe thickness
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, ** groove a) roll groove
b) cut groove ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, *** Diameters:
Pipe diameter
)55(
thickness
"
"
[email protected]
stress
Fire fighting course in QEC (Quality for Engineering consulting) consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; ; senior Electromechanical Engineer 01226663413
∴ Fittings: 1- Threaded 2- Weld 3- Grooved Grooved ( (roll roll groove or groove or cut cut groove) groove) ,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,
From NFPA for fittings we get: 1- Threaded & cut groove
2- Weld & roll groove
Sch40
"8 < D
-
Sch30
"8 > D
-
Sch10 NFPA
"5 ≤ D "5 > D
-
For pipes: 1” , 114 " , 112 " , 2” threaded sch40 For pipes: 212 ” weld roll groove sch10
)56(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-2 Fire extinguishers “fire ext.” 2-2-1 Type of fire ext. “Class of fire” 2-2-2 Location of fire ext. ,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 2-2-1 Type of fire ext. “Class of fire”
Class A
Class B
Surface fire : Wood paper clothes
Class C
Fire in combustible material in liquid material
Class D
Fire in Fire in energized elect combustible Equipment material in solid state
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, 2-2-2 Location of fire ext.
* Travel distance ** Guide location: - escape stair case - escape corridor
)57(
"
"
[email protected]
30 m
Class K Fire in cooking media
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
*
electro galvanized sheet :
Hot deep galvanized
Electro static "
"
,,,,,,,,,,,,,,,,,,,,,,,,,,, ** Type of fire ext. according to its shape:
Portable "
wheeled
automatic “matic”
" )58(
"
"
Matic
[email protected]
Sprinkle
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
How t o U Use a a F F i ir E x t r e E ti i n gui sher It’s easy to remember how to use a fire extinguisher if you remember the acronym PASS:
Pull Aim Squeeze Sweep Aim
‼
)59(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
2-3 Gaseous system: General note: 1- Gaseous system; Special system in case water system no applicable. Such as:
“Electrical room, severe room, IT room”
Banks “document rooms,
“
,,,,,,,,,,,,,,,,,,,,,,,,,,,, 2- Concept:
2
Inert gas “
2 ,,,,,,,,,,,,,,,,,,,,,,,,,,,, 3- design: a) Weight of required gas. “not volume” b) Sequence of operation. ………………………..
A) Weight of required gas. “not volume” It depends on: - Volume of space - Temperature of space - Type of fire
)60(
"
"
[email protected]
, 200
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Steps: 1- Calculate the volume of the space. Volume = length * width * height
2-
W=v*f
Where: W
required gas weight ( kg
V
volume of space
F
or lb )
( 3 or
(
flooding factor
3
3
or
)
3 )
It passed on: - Type of gas - Type of fire - Type of gas
By
table 1
c
, concentration factor
- Type of fire
C By
table 2 Temp. Of space “70 ℉ , 22 ℃
)61(
"
"
[email protected]
F = 0.0341
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
Table 1:
Table 2:
)62(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
b) Sequence of operation:
1- Detectors sends signal to FACP 2- Signal from FACP to motor in solenoid:a) Gives signal to output to alarm (fire strop) ) non manual stopping .b
manual stopping (
non manual stopping
b) Sends signal to close the door holder magnetic door
c) Sends signal to compressor d) Sends signal to solenoid valve to start releasing the gas.
,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, * Standard weight for
2
is 45 kg
** For Fm200 no standard )63(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
weight Plumbing Works Calculations
)64(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
)65(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
)66(
"
"
[email protected]
Fire fighting course in QEC (Quality for Engineering consulting)
Prepared by \ eng.hosam eldin samir
[email protected]
Under supervision of\ eng. Mahmoud Abdelaty ; senior Electromechanical Engineer 01226663413
)67(
"
"
[email protected]