EDVN041518
Split Type Air Conditio Conditioners ners - Heat Pump FTXM-H Series
EDVN041518
Heat Pump
1. 2. 3. 4.
FTXM20HVMV FTXM25HVMV FTXM35HVMV
RXM20HVMV RXM25HVMV RXM35HVMV
Power Power Supply Supply .................. .......................... ................ ................ ................. .................. .................. ................ ............... ..............2 ......2 Functions.. Functions........... .................. ................. ............... ................ .................. ................... ................... ................. ................ ................ .........3 .3 Specificat Specifications ions......... ................. ................ ................ ................. ................. ................ ................ ................ ................. ................4 .......4 Dimensions Dimensions ................. .......................... ................. ................ ................ ................. .................. ................. ................ ................ .........6 .6 4.1 Indoor Indoor Unit............... Unit....................... ............... .............. .............. ............... ............... .............. .............. ............... ............... .............. ........6 .6 4.2 Outdoor Outdoor Unit .............. ..................... .............. ............... ............... .............. ............... ............... .............. ............... ............... .............6 ......6
5. Wiring Wiring Diagrams......... Diagrams................. ................ ................ ................. ................... ................... .................. .................. ................7 .......7 5.1 Indoor Indoor Unit............... Unit....................... ............... .............. .............. ............... ............... .............. .............. ............... ............... .............. ........7 .7 5.2 Outdoor Outdoor Unit .............. ..................... .............. ............... ............... .............. ............... ............... .............. ............... ............... .............7 ......7
6. Piping Piping Diagrams............... Diagrams........................ .................. .................. .................. ................. ................ ................ ................. ...........8 ..8 6.1 Indoor Indoor Unit............... Unit....................... ............... .............. .............. ............... ............... .............. .............. ............... ............... .............. ........8 .8 6.2 Outdoor Outdoor Unit .............. ..................... .............. ............... ............... .............. ............... ............... .............. ............... ............... .............8 ......8
7. Capacity Capacity Tables ................... ........................... ................ ................ ................. .................. ................. ................ ................ .........9 .9 7.1 Heat Heat Pump Pump .............. ..................... .............. .............. .............. .............. .............. .............. ............... ............... .............. ............... ..........9 ..9 7.2 Capacity Capacity correc correction tion factor factor by by the length length of of refrigera refrigerant nt piping piping (Reference) (Reference) ............................................................... .............................. .............................................................. ............................. 12
8. Operation Operation Limit..................... Limit.............................. ................... ................... .................. ................... ................... ..................1 .........13 3 9. Sound Sound Level Level ................ ......................... .................. ................... ................... .................. ................... ................... ..................1 .........14 4 9.1 Measurin Measuring g Location Location...... .............. ............... .............. ............... ............... .............. .............. .............. ............. .............. ..........14 ..14 9.2 Indoor Indoor Unit Unit ............... ...................... ............... ............... .............. ............... ............... .............. .............. ............... ............... .............15 ......15 9.3 Outdoor Outdoor Unit .............. ..................... .............. ............... ............... ............... ............... ............... ............... ............... ................ ..........16 ..16
10.Electric Characteristics..........................................................................17 11.Installation Manual ........................................ .................. ......................................... ....................................... .....................18 .18 12.Operation Manual..................................................................................28 12.1 English...................................................................................... English................................................. ...................................................28 ..............28 12.2 Vietname Vietnamese se ............... ...................... .............. ............... ............... .............. ............... ............... .............. ............... ............... ...........52 ....52
13.Optional Accessories ........................................... ...................... ............................................... .................................76 .......76 13.1 Option Option List ............... ...................... ............... ............... .............. ............... ............... .............. .............. ............... ............... .............76 ......76
Split Type Air Conditioners FTXM-H Series
1
Power Supply
EDVN041518
1. Power Su Supply
Note:
2
Indoor Unit
Outdoor Unit
FTXM20HVMV
RXM20HVMV
FTXM25HVMV
RXM25HVMV
FTXM35HVMV
RXM35HVMV
Power Supply 1 phase, 220 - 230 - 240 V, 50 Hz 1 phase, 220 - 230 V, 60 Hz
Power Supply Intake; Outdoor Unit
Split Type Air Conditioners FTXM-H Series
EDVN041518
Functions
2. Functions
Category
Functions
Basic Function Inverter (with inverter power control)
Compressor
Comfortable Airflow
Comfort Control
Operation
Lifestyle Convenience
Note:
V V M M V V H 5 H 3 / 5 3 5 / 2 / 5 / 0 2 2 0 2 M M X T X F R
Operation limit for cooling (°CDB)
10 ~ 46
Operation limit for heating (°CWB)
1 ~ 20
Category
Functions
Health & Clean Air-purifying filter
V V M M V V H 5 H 3 / 5 3 5 / 2 / 5 / 0 2 2 0 2 M M X T X F R
—
Photocatalytic deodorising filter
—
Air-purifying filter with photocatalytic deodorising function
—
PAM control
Titanium apatite photocatalytic air-purifying filter (option)
Standby electricity saving
—
Air filter (prefilter)
Oval scroll compressor
—
Wipe-clean flat panel
Swing compressor
Washable grille
—
Rotary compressor
—
MOULD PROOF operation
—
Reluctance DC motor
Heating dry operation
—
Power-airflow flap
Good-sleep cooling operation
—
Power-airflow dual flaps
—
WEEKLY TIMER operation
—
Power-airflow diffuser
—
24-hour ON/OFF TIMER
Wide-angle louvres
NIGHT SET mode
Auto-swing (up and down)
Auto-restart (after power failure)
Auto-swing (right and left)
—
Self-diagnosis (R/C, LED)
3-D airflow
—
Wiring error check function
—
COMFORT AIRFLOW operation
Auto fan speed
Anti-corrosion treatment of outdoor heat exchanger
Indoor unit quiet operation
NIGHT QUIET mode (automatic)
—
Flexible power supply correspondence
OUTDOOR UNIT QUIET operation (manual)
—
High ceiling application
—
INTELLIGENT EYE operation
—
Chargeless
2-area INTELLIGENT EYE operation
—
Either side drain (right or left)
Automatic operation
Power selection
—
Programme dry operation
Fan only
Facility setting (cooling at low outdoor temperature)
—
New POWERFUL operation (non-inverter)
—
5-room centralised controller
—
Remote control adaptor (normal open pulse contact)
—
Remote control adaptor (normal open contact)
—
Timer
Worry Free (Reliability & Durability)
Flexibility
Remote Control
Multi-split / split type compatible indoor unit
—
10 m
Inverter POWERFUL operation
Priority-room setting
—
COOL / HEAT mode lock
—
HOME LEAVE operation
—
ECONO operation
DIII-NET compatible (adaptor)
—
Indoor unit ON/OFF button
Wireless LAN connection (option)
—
Signal receiving sign
Wireless
R/C with back light
—
Wired
—
Temperature display
—
Remote Controller
: Available — : Not available
Split Type Air Conditioners FTXM-H Series
3
Specifications
EDVN041518
3. Specifications 50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V Indoor Unit Model
FTXM20HVMV RXM20HVMV
Outdoor Unit
Capacity Rated (Min. ~ Max.) Moisture Removal Running Current (Rated) Power Consumption Rated (Min. ~ Max.) Power Factor (Rated) COP (Rated) Liquid Piping Gas Connections Drain Heat Insulation Max. Interunit Piping Length Max. Interunit Height Difference Chargeless Amount of Additional Charge of Refrigerant Indoor Unit Front Panel Colour H M Airflow Rate L SL Type Fan Motor Output Speed Air Direction Control Air Filter
kW Btu/h kcal/h L/h A
Cooling 2.0 (1.0 ~ 2.6) 6,800 (3,400 ~ 8,850) 1,720 (860 ~ 2,240) 1.2 2.8
Heating 2.0 (1.0 ~ 2.6) 6,800 (3,400 ~ 8,850) 1,720 (860 ~ 2,240) — 2.8
Cooling 2.5 (1.0 ~ 3.4) 8,500 (3,400 ~ 11,600) 2,150 (860 ~ 2,920) 1.2 3.0
Heating 2.5 (1.0 ~ 3.4) 8,500 (3,400 ~ 11,600) 2,150 (860 ~ 2,920) — 3.0
W
454 (225 ~ 645)
454 (225 ~ 645)
610 (225 ~ 1,070)
610 (225 ~ 1,070)
% W/W mm mm mm
73.7 4.40
73.7 4.40
92.4 4.10
92.4 4.10
g/m
20
20
FTXM20HVMV Shiny Pure White
FTXM25HVMV Shiny Pure White
A
Power Consumption (Rated)
W
Power Factor (Rated)
%
Type Motor Output Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) Starting Current Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H Level Drawing No. Fan
Note:
4
φ 9.5
m m m
W Steps
H
φ 6.4
φ 9.5
φ 16.0 Both Liquid and Gas Pipes 15 12 10
Running Current (Rated)
Airflow Rate
φ 6.4 φ 16.0 Both Liquid and Gas Pipes 15 12 10
m³/min (cfm)
Temperature Control Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H / M / L / SL Level Outdoor Unit Casing Colour Type Compressor Model Motor Output Type Refrigerant Oil Charge Type Refrigerant Charge
FTXM25HVMV RXM25HVMV
mm mm kg kg dB(A)
W L kg m³/min (cfm) W A W % A mm mm kg kg dB(A)
9.0 (318) 6.7 (237) 4.4 (155) 3.5 (124)
9.0 (318) 7.6 (268) 6.4 (226) 5.4 (191)
9.0 (318) 6.7 (237) 4.4 (155) 3.5 (124)
Cross Flow Fan 16 5 Steps, Quiet, Auto Right, Left, Horizontal, Downwards Removable, Washable, Mildew Proof 0.19 - 0.18 - 0.17 / 0.19 - 0.18 - 0.17 / 0.19 - 0.18 0.19 - 0.18 39 39 93.3 - 94.2 - 95.6 / 93.3 - 94.2 - 95.6 / 93.3 - 94.2 93.3 - 94.2 Microcomputer Control 283 × 770 × 203 263 × 840 × 344 8 10 39 / 34 / 28 / 25
Cross Flow Fan 16 5 Steps, Quiet, Auto Right, Left, Horizontal, Downwards Removable, Washable, Mildew Proof 0.19 - 0.18 - 0.17 / 0.19 - 0.18 - 0.17 / 0.19 - 0.18 0.19 - 0.18 39 39 93.3 - 94.2 - 95.6 / 93.3 - 94.2 - 95.6 / 93.3 - 94.2 93.3 - 94.2 Microcomputer Control 283 × 770 × 203 263 × 840 × 344 8 10
39 / 34 / 29 / 27
40 / 35 / 29 / 25
RXM20HVMV Ivory White Hermetically Sealed Swing Type 1YC22DXD 395 FW68DA 0.275 R-32 0.75
27.1 (957)
27.1 (957)
Propeller 20
27.1 (957) Propeller 20
2.61 415 72.3
2.81 571 92.4
2.8 550 × 658 × 275 616 × 788 × 359 27 31 48
40 / 35 / 30 / 27
RXM25HVMV Ivory White Hermetically Sealed Swing Type 1YC22DXD 551 FW68DA 0.275 R-32 0.75
27.1 (957)
2.61 415 72.3
9.0 (318) 7.6 (268) 6.4 (226) 5.4 (191)
2.81 571 92.4 3.0 550 × 658 × 275 616 × 788 × 359 27 31
48
48
3D096417
The data are based on the conditions shown in the table below. Cooling Heating Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB
48 3D096418
Piping Length 7.5 m
Conversion Formulae kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35.3
Split Type Air Conditioners FTXM-H Series
EDVN041518
Specifications
50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V Indoor Unit Model
FTXM35HVMV RXM35HVMV
Outdoor Unit
Capacity Rated (Min. ~ Max.) Moisture Removal Running Current (Rated) Power Consumption Rated (Min. ~ Max.) Power Factor (Rated) COP (Rated) Liquid Piping Gas Connections Drain Heat Insulation Max. Interunit Piping Length Max. Interunit Height Difference Chargeless Amount of Additional Charge of Refrigerant Indoor Unit Front Panel Colour H M Airflow Rate L SL Type Fan Motor Output Speed Air Direction Control Air Filter Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) Temperature Control Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H / M / L / SL Level Outdoor Unit Casing Colour Type Compressor Model Motor Output Type Refrigerant Oil Charge Type Refrigerant Charge Airflow Rate
H
Type Motor Output Running Current (Rated) Power Consumption (Rated) Power Factor (Rated) Starting Current Dimensions (H × W × D) Packaged Dimensions (H × W × D) Weight (Mass) Gross Weight (Gross Mass) Sound Pressure H Level Drawing No. Fan
Note:
kW Btu/h kcal/h L/h A
Cooling 3.5 (1.2 ~ 3.8) 11,900 (4,100 ~ 12,950) 3,010 (1,030 ~ 3,270) 1.2 4.6
Heating 3.5 (1.2 ~ 3.8) 11,900 (4,100 ~ 12,950) 3,010 (1,030 ~ 3,270) — 4.6
W
990 (250 ~ 1,320)
990 (250 ~ 1,320)
% W/W mm mm mm
97.8 3.54
97.8 3.54 φ 6.4 φ 9.5
m m m
φ 16.0 Both Liquid and Gas Pipes 15 12 10
g/m
20 FTXM35HVMV Shiny Pure White
m³/min (cfm)
W Steps
A W % mm mm kg kg dB(A)
9.7 (342) 7.1 (251) 4.6 (162) 3.6 (127)
Cross Flow Fan 16 5 Steps, Quiet, Auto Right, Left, Horizontal, Downwards Removable, Washable, Mildew Proof 0.27 - 0.26 - 0.24 / 0.27 - 0.26 0.27 - 0.26 - 0.24 / 0.27 - 0.26 57 57 96.0 - 95.3 - 99.0 / 96.0 - 95.3 96.0 - 95.3 - 99.0 / 96.0 - 95.3 Microcomputer Control 283 × 770 × 203 263 × 840 × 344 8 10 41 / 36 / 30 / 26
L
W A W % A mm mm kg kg dB(A)
41 / 36 / 31 / 28 RXM35HVMV Ivory White Hermetically Sealed Swing Type 1YC22DXD 913 FW68DA 0.275 R-32 0.75
W
kg m³/min (cfm)
9.9 (349) 7.9 (279) 5.9 (208) 4.8 (169)
27.1 (957)
27.1 (957) Propeller 20
4.33 933 96.2
4.33 933 96.2 4.6 550 × 658 × 275 616 × 788 × 359 27 31
48
The data are based on the conditions shown in the table below. Cooling Heating Indoor ; 27°CDB / 19°CWB Indoor ; 20°CDB Outdoor ; 35°CDB / 24°CWB Outdoor ; 7°CDB / 6°CWB
48 3D096419
Split Type Air Conditioners FTXM-H Series
Piping Length 7.5 m
Conversion Formulae kcal/h = kW × 860 Btu/h = kW × 3412 cfm = m³/min × 35.3
5
Dimensions
EDVN041518
4. Dimensions 4.1
Indoor Unit
FTXM20/25/35HVMV AIRFLOW (INDOOR)
THE MARK ( →) SHOWS PIPING DIRECTION REAR
) E C R N A O . F M N E R I M C O 0 A F 3 P R E S ( P
770
LEFT
RIGHT INCLUDING MOUNTING PLATE 205 FRONT PANEL FIXING SCREWS (INSIDE)
3 8 2
TERMINAL BLOCK WITH EARTH TERMINAL (INSIDE)
OPERATION LAMP TIMER LAMP INDOOR UNIT ON/OFF SWITCH
FLAPS
50MIN.
GAS PIPE φ9.5 CuT (THE LENGTH OF PIPE OUTSIDE THE UNIT: ABOUT 350)
ROOM TEMP. THERMISTOR (INSIDE)
DRAIN HOSE (CONNECTING PART I.D. φ14 O.D. φ16 THE HOSE LENGTH OF OUTSIDE THE UNIT IS ABOUT 450)
LIQUID PIPE φ6.4 CuT (THE LENGTH OF PIPE OUTSIDE THE UNIT: ABOUT 400) SIGNAL TRANSMITTER
58
(SPACE FOR MAINTENANCE)
REQUIRED SPACE
MANUFACTURER'S LABEL
SIGNAL RECEIVER
BOTTOM
50MIN. (SPACE FOR MAINTENANCE)
203
770
MODEL NAME PLATE
6 1
549
101
2 7 1
UP/DOWN (AUTOMATIC) HEATING
COOLING 5˚ 3 6 1
5˚
45˚
3 . 1 4
DRY
45˚
45˚
54.5
RIGHT/LEFT (MANUAL)
54
WALL HOLE FOR EMBEDDED PIPING φ65 HOLE
5˚
4.2
3 8 2
5˚
FAN
WIRELESS REMOTE CONTROLLER (ARC433A87)
6
BLADE ANGLE
18
WALL HOLE φ65 HOLE
STANDARD LOCATIONS OF WALL HOLES 4 5 ˚
45˚
3 . 1 4
˚ 4 5
3D093418
Outdoor Unit
RXM20/25/35HVMV DRAIN OUTLET (I.Dφ15.9 HOSE FOR CONNECTION WITH DRAIN JOINT) 470
MINIMUM SPACE FOR AIR PASSAGE 4-HOLES FOR ANCHOR BOLTS (M8 OR M10)
WALL HEIGHT ON AIR OUTLET SIDE = LESS THAN 1200
0 5 1
96 0 0 1
1 1
379
0 5 1
0 4
50
7 9 2
50 50 0 5
BRAND NAME LABEL
HANDLE 275
13.5
12
658
50
MANUFACTURE'S LABEL 8
0 0 3
0 0 1
OUTDOOR AIR THERMISTOR LIQUID STOP VALVE (φ6.4CuT)
WIRING INLET 0 5 5
SERVICE PORT 8 8 6 0 1 1
155 INDICATION LABEL (INDONESIA) FOR INDONESIA MODEL ONLY
IN CASE OF REMOVING STOP VALVE COVER
GAS STOP VALVE (φ9.5CuT)
3D089153C
6
Split Type Air Conditioners FTXM-H Series
EDVN041518
Wiring Diagrams
5. Wiring Diagrams 5.1
Indoor Unit
FTXM20/25/35HVMV
5.2
Outdoor Unit
RXM20/25/35HVMV
Split Type Air Conditioners FTXM-H Series
7
Piping Diagrams
EDVN041518
6. Piping Diagrams 6.1
Indoor Unit
FTXM20/25/35HVMV
INDOOR UNIT 7.0CuT
HEAT EXCHANGER
4.8CuT
T u C 0 . 7
THERMISTOR ON HEAT EXCH.
7.0CuT 7.0CuT
CROSS FLOW FAN
FIELD PIPING
(6.4CuT)
M FAN MOTOR 9.5CuT
FIELD PIPING
(9.5CuT) REFRIGERANT FLOW COOLING HEATING
4D096261
6.2
Outdoor Unit
RXM20/25/35HVMV
OUTDOOR UNIT 7.0CuT T u C 5 . 9
OUTDOOR TEMPERATURE THERMISTOR
HEAT EXCHANGER
7.0CuT R E G N A R H O C T S X I E M T R A E E H H T
6.4CuT
6.4CuT 6.4CuT
M
FAN MOTOR
MOTOR OPERATED VALVE
6.4CuT
MUFFLER WITH FILTER
PROPELLER FAN R E N I A R T S
4-WAY VALVE ON: HEATING
9.5CuT
9.5CuT T u C 8 . 4
6.4CuT
9.5CuT
MUFFLER
DISCHARGE PIPE THERMISTOR
LIQUID STOP VALVE
FIELD PIPING (6.4CuT)
REFRIGERANT FLOW COOLING HEATING
COMPRESSOR
ACCUMULATOR
9.5CuT GAS STOP VALVE
FIELD PIPING (9.5CuT)
3D096247
8
Split Type Air Conditioners FTXM-H Series
EDVN041518
Capacity Tables
7. Capacity Tables 7.1
Heat Pump
FTXM20HVMV + RXM20HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V) Cooling
AFR
9
BF
0.13
INDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB EDB
20
25
30
32
35
40
°C
°C
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
1.97
1.77
0.35
1.88
1.73
0.38
1.79
1.69
0.42
1.83
1.71
0.43
1.77
1.69
0.45
1.68
1.64
0.48
16.0
22
2.05
1.75
0.35
1.97
1.71
0.39
1.88
1.67
0.42
1.92
1.69
0.43
1.86
1.66
0.45
1.77
1.63
0.48
18.0
25
2.14
1.87
0.35
2.05
1.84
0.39
1.96
1.80
0.42
2.01
1.82
0.43
1.95
1.80
0.45
1.86
1.76
0.49
19.0
27
2.19
2.01
0.36
2.10
1.98
0.39
2.01
1.95
0.42
2.06
1.96
0.43
2.00
1.94
0.45
1.91
1.91
0.49
22.0
30
2.32
1.96
0.36
2.23
1.93
0.39
2.14
1.90
0.43
2.19
1.92
0.44
2.14
1.90
0.46
2.05
1.87
0.49
24.0
32
2.41
1.92
0.36
2.32
1.89
0.39
2.23
1.87
0.43
2.29
1.88
0.44
2.23
1.87
0.46
2.14
1.84
0.49
Heating
AFR
9
OUTDOOR TEMPERATURE (°CDB/°CWB)
INDOOR EDB
2/1
7/6
11/10
°C
TC
PI
TC
PI
TC
PI
15.0
1.31
0.36
2.07
0.44
2.25
0.46
20.0
1.26
0.36
2.00
0.45
2.18
0.47
22.0
1.24
0.37
1.97
0.46
2.15
0.47
24.0
1.22
0.37
1.94
0.46
2.13
0.48
25.0
1.21
0.37
1.93
0.46
2.11
0.48
27.0
1.19
0.38
1.90
0.47
2.08
0.48
Symbols:
Notes:
AFR
: Airflow rate
BF
: Bypass factor
(m³/min.)
EWB
: Entering wet bulb temp.
(°C)
EDB
: Entering dry bulb temp.
(°C)
TC
: Total capacity
(kW)
SHC
: Sensible heat capacity
(kW)
PI
: Power input
(kW)
1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5 m Level difference : 0 m
3D096248A
Split Type Air Conditioners FTXM-H Series
9
Capacity Tables
EDVN041518
FTXM25HVMV + RXM25HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V) Cooling
AFR
9
BF
0.13
INDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB EDB
20
25
30
32
35
40
°C
°C
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
2.46
2.00
0.47
2.35
1.95
0.52
2.23
1.90
0.56
2.28
1.92
0.58
2.21
1.89
0.60
2.10
1.83
0.65
16.0
22
2.57
1.97
0.47
2.46
1.92
0.52
2.34
1.87
0.56
2.40
1.89
0.58
2.33
1.86
0.61
2.21
1.81
0.65
18.0
25
2.68
2.09
0.48
2.57
2.04
0.52
2.46
2.00
0.57
2.51
2.02
0.58
2.44
1.99
0.61
2.33
1.94
0.66
19.0
27
2.73
2.23
0.48
2.62
2.18
0.52
2.51
2.14
0.57
2.57
2.16
0.58
2.50
2.13
0.61
2.38
2.09
0.66
22.0
30
2.90
2.16
0.48
2.79
2.12
0.53
2.68
2.08
0.57
2.74
2.10
0.59
2.67
2.08
0.61
2.56
2.04
0.66
24.0
32
3.01
2.11
0.48
2.90
2.07
0.53
2.79
2.04
0.57
2.86
2.06
0.59
2.79
2.04
0.62
2.67
2.00
0.66
Heating
AFR
9
OUTDOOR TEMPERATURE (°CDB/°CWB)
INDOOR EDB
2/1
7/6
11/10
°C
TC
PI
TC
PI
TC
PI
15.0
1.31
0.36
2.59
0.60
2.81
0.62
20.0
1.26
0.36
2.50
0.61
2.73
0.63
22.0
1.24
0.37
2.47
0.62
2.69
0.64
24.0
1.22
0.37
2.43
0.62
2.66
0.64
25.0
1.21
0.37
2.41
0.62
2.64
0.64
27.0
1.19
0.38
2.38
0.63
2.61
0.65
Symbols:
Notes:
AFR
: Airflow rate
(m³/min.)
BF
: Bypass factor
EWB
: Entering wet bulb temp.
(°C)
EDB
: Entering dry bulb temp.
(°C)
TC
: Total capacity
(kW)
SHC
: Sensible heat capacity
(kW)
PI
: Power input
(kW)
1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5 m Level difference : 0 m
3D096249A
10
Split Type Air Conditioners FTXM-H Series
EDVN041518
Capacity Tables
FTXM35HVMV + RXM35HVMV (50 Hz, 220 - 230 - 240 V / 60 Hz, 220 - 230 V) Cooling
AFR
9.7
BF
0.13
INDOOR
OUTDOOR TEMPERATURE (°CDB)
EWB EDB
20
25
30
32
35
40
°C
°C
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
3.30
2.47
0.75
3.28
2.47
0.84
3.13
2.39
0.91
3.19
2.42
0.94
3.10
2.37
0.98
2.93
2.29
1.05
16.0
22
3.60
2.50
0.77
3.44
2.43
0.84
3.28
2.35
0.92
3.36
2.39
0.94
3.26
2.34
0.98
3.10
2.27
1.06
18.0
25
3.75
2.62
0.77
3.59
2.55
0.85
3.44
2.48
0.92
3.52
2.52
0.94
3.42
2.47
0.99
3.26
2.40
1.06
19.0
27
3.83
2.76
0.77
3.67
2.69
0.85
3.51
2.63
0.92
3.60
2.66
0.95
3.50
2.62
0.99
3.34
2.56
1.06
22.0
30
4.06
2.66
0.78
3.90
2.60
0.85
3.75
2.55
0.93
3.84
2.58
0.95
3.74
2.54
1.00
3.58
2.48
1.07
24.0
32
4.21
2.59
0.79
4.06
2.54
0.86
3.90
2.49
0.93
4.00
2.52
0.96
3.90
2.49
1.00
3.74
2.43
1.07
Heating
AFR
9.9
OUTDOOR TEMPERATURE (°CDB/°CWB)
INDOOR EDB
2/1
7/6
11/10
°C
TC
PI
TC
PI
TC
PI
15.0
1.43
0.39
3.62
0.97
3.94
1.00
20.0
1.37
0.40
3.50
0.99
3.82
1.02
22.0
1.35
0.41
3.45
1.00
3.77
1.03
24.0
1.33
0.41
3.40
1.01
3.72
1.04
25.0
1.32
0.41
3.38
1.01
3.70
1.04
27.0
1.30
0.42
3.33
1.02
3.65
1.05
Symbols:
Notes:
AFR
: Airflow rate
(m³/min.)
BF
: Bypass factor
EWB
: Entering wet bulb temp.
(°C)
EDB
: Entering dry bulb temp.
(°C)
TC
: Total capacity
(kW)
SHC
: Sensible heat capacity
(kW)
PI
: Power input
(kW)
1. shows nominal (rated) capacities and power input. 2. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 3. Capacities are based on the following conditions. Corresponding refrigerant piping length : 7.5 m Level difference : 0 m
3D096250B
Split Type Air Conditioners FTXM-H Series
11
Capacity Tables
7.2
EDVN041518
Capacity correction factor by the length of refrigerant piping (Reference) The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length of refrigerant piping — the distance between the indoor unit and the outdoor unit. <— line : cooling capacity> <--- line : heating capacity> (R-32) (%) 100 r o t c a f n o i t c e r r o c y t i c a p a C
90
Range of the refrigerant additional charge
80
5
10
15 (m)
Piping length
Note:
12
The graph shows the factor when additional refrigerant of the proper quantity is charged.
Split Type Air Conditioners FTXM-H Series
EDVN041518
Operation Limit
8. Operation Limit RXM20/25/35HVMV
Cooling
Heating
50 25 46 20
40 n o i t a r e p o s u o u n i t n o C
) B D C 30 ˚ ( . p m e t r o o d t u 20 O
d o i r e p n w o d l l u P
15 ) B W C ˚ ( . p 10 m e t r o o d t u O 5
s u n o o u i n t i t a n r o e p C o
1 0
10
-5 (-5˚CDB)
0 10
14
20
23
28 30
10
Indoor temp. (˚CWB)
30
Indoor temp. (˚CDB) Notes: The graphs are based on the following conditions. • Equivalent piping length • Level difference • Airflow rate
Split Type Air Conditioners FTXM-H Series
20
7.5m 0m High
3D095152A
13
Sound Level
EDVN041518
9. Sound Level 9.1
Measuring Location Indoor Unit
Outdoor Unit 1m
1m
m 8 . 0
MICROPHONE
MICROPHONE
Notes:
1. Operation sound is measured in an anechoic chamber. 2. The data are based on the conditions shown in the table below. Cooling Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB
14
Heating Indoor ; 20°CDB Outdoor ; 7°CDB / 6°CWB
Piping Length 5m
Split Type Air Conditioners FTXM-H Series
EDVN041518
9.2
Sound Level
Indoor Unit
FTXM20HVMV 70 L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T C 20 O
COOLING
70
NC-70
OVER ALL ( dB )
NC-60
50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L) A
39
28
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
STANDARD EXTERNAL STATIC PRESSURE 50/60Hz 220-240/220-230V (H) NC-30
50/60Hz 220-240/220-230V (L)
Cooling APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
HEATING
L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T 20 C O
OVER ALL ( dB )
NC-60
50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L) A
39
29
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
STANDARD EXTERNAL STATIC PRESSURE 50/60Hz 220-240/220-230V (H) NC-30
50/60Hz 220-240/220-230V (L)
Heating APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
8000
NC-70
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
3D096262
8000
FTXM25HVMV 70
COOLING
L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B N d30 A B E V A T C 20 O
70
NC-70
OVER ALL ( dB )
NC-60
50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L) A
40
29
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
STANDARD EXTERNAL STATIC PRESSURE 50/60Hz 220-240/220-230V (H) NC-30
50/60Hz 220-240/220-230V (L)
Cooling APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B N d30 A B E V A T 20 C O
8000
HEATING NC-70
OVER ALL ( dB )
NC-60
50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L) A
40
30
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
STANDARD EXTERNAL STATIC PRESSURE 50/60Hz 220-240/220-230V (H) NC-30
50/60Hz 220-240/220-230V (L)
Heating APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
3D096263A
8000
FTXM35HVMV 70
COOLING
L E 60 V E L E R ) 50 U S r a S b E µ R 2 0 P 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T C 20 O
70
NC-70
OVER ALL ( dB )
NC-60
50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L) A
41
30
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
STANDARD EXTERNAL STATIC PRESSURE 50/60Hz 220-240/220-230V (H) NC-30
50/60Hz 220-240/220-230V (L)
Cooling APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
8000
Split Type Air Conditioners FTXM-H Series
L E 60 V E L E R ) 50 U S r a S b E µ R 2 0 P 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T 20 C O
HEATING NC-70
OVER ALL ( dB )
NC-60
50/60Hz 50/60Hz SCALE 220-240/220-230V 220-240/220-230V (H) (L) A
41
31
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
STANDARD EXTERNAL STATIC PRESSURE 50/60Hz 220-240/220-230V (H) NC-30
50/60Hz 220-240/220-230V (L)
Heating APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
8000
3D096264A
15
Sound Level
9.3
EDVN041518
Outdoor Unit
RXM20HVMV 70
COOLING OVER ALL ( dB )
NC-70
L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T C 20 O
SCALE NC-60
A
50/60Hz 220-240/220-230V (H) 48
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
NC-30
APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
Cooling
70
HEATING OVER ALL ( dB )
NC-70
L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T 20 C O
NC-20
50/60Hz 220-240/220-230V (H)
A
48
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
NC-30
APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
8000
SCALE NC-60
Heating
NC-20
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
3D096257
8000
RXM25HVMV 70
COOLING OVER ALL ( dB )
NC-70
L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B N d30 A B E V A T C 20 O
SCALE NC-60
A
50/60Hz 220-240/220-230V (H) 48
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
NC-30
APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
Cooling
70
HEATING OVER ALL ( dB )
NC-70
L E 60 V E L E R ) 50 U S r a S b E µ R 2 P 0 0 D 0 . 40 N 0 U = B O d S 0 ( D B N d30 A B E V A T 20 C O
NC-20
8000
SCALE
50/60Hz 220-240/220-230V (H)
A
48
NC-60
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
NC-30
APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
Heating
NC-20
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
3D096258
8000
RXM35HVMV 70
COOLING OVER ALL ( dB )
NC-70
L E 60 V E L E R ) 50 U S r a S b E µ R 2 0 P 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T C 20 O
SCALE NC-60
A
48
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
NC-30
APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
16
50/60Hz 220-240/220-230V (H)
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
NC-20
8000
Cooling
70
HEATING OVER ALL ( dB )
NC-70
L E 60 V E L E R ) 50 U S r a S b E µ R 2 0 P 0 D 0 . 40 N 0 U = B O d S 0 ( D B30 N d A B E V A T 20 C O
SCALE
50/60Hz 220-240/220-230V (H)
A
48
NC-60
( B.G.N IS ALREADY RECTIFIED ) NC-50
OPERATING CONDITIONS POWER SOURCE 220-240/220-230V 50/60Hz
JIS STANDARD
NC-40
NC-30
APPROXIMATE THRESHOLD HEARING FOR CONTINUOUS NOISE
63
Heating
NC-20
125 250 500 1000 2000 4000 OCTAVE BAND CENTER FREQUENCY (Hz)
8000
3D096259
Split Type Air Conditioners FTXM-H Series
EDVN041518
Electric Characteristics
10.Electric Characteristics Indoor Unit
Power Supply
Outdoor Unit
Hz - Volts
Voltage Range
Compressor MCA
MFA
RHz
50 Hz - 220 V 50 Hz - 230 V FTXM20HVMV
RXM20HVMV
Max. 50 Hz, 264 V Min. 50 Hz, 198 V
50 Hz - 240 V 60 Hz - 220 V 60 Hz - 230 V
8.0
15
36
Max. 60 Hz, 253 V Min. 60 Hz, 198 V
50 Hz - 220 V 50 Hz - 230 V FTXM25HVMV
RXM25HVMV
Max. 50 Hz, 264 V Min. 50 Hz, 198 V
50 Hz - 240 V 60 Hz - 220 V 60 Hz - 230 V
8.0
15
48
Max. 60 Hz, 253 V Min. 60 Hz, 198 V
50 Hz - 220 V 50 Hz - 230 V FTXM35HVMV
RXM35HVMV
Max. 50 Hz, 264 V Min. 50 Hz, 198 V
50 Hz - 240 V 60 Hz - 220 V 60 Hz - 230 V
8.0 Max. 60 Hz, 253 V Min. 60 Hz, 198 V
15
74
RLA
OFM W
FLA
IFM W
FLA
2.4
0.22
0.19
2.3
0.21
0.18
2.2
20
0.20
16
0.17
2.5
0.22
0.19
2.4
0.21
0.18
2.6
0.22
0.19
2.5
0.21
0.18
2.4
20
0.20
16
0.17
2.7
0.22
0.19
2.6
0.21
0.18
4.2
0.22
0.27
4.0
0.21
0.26
3.8
20
0.20
16
0.24
4.3
0.22
0.27
4.1
0.21
0.26
Symbols:
Notes:
MCA
: Min. circuit amps (A)
MFA
: Max. fuse amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated load amps (A)
OFM
: Outdoor fan motor
IFM
: Indoor fan motor
W
: Fan motor rated output (W)
1. RLA is based on the following conditions. Indoor temp. 27°CDB / 19°CWB Outdoor temp. 35°CDB. 2. Maximum allowable voltage variation between phases is 2%. 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker. 5. Be sure to install an earth leak detector. (This unit uses an inverter, which means that an earth leak detector capable of handling high harmonics must be used in order to prevent malfunctioning of the earth leak detector.)
FLA
: Full load amps (A) 3D096254A
Split Type Air Conditioners FTXM-H Series
17
Installation Manual
EDVN041518
11.Installation Manual
18
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Installation Manual
19
Installation Manual
20
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Installation Manual
21
Installation Manual
22
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Installation Manual
23
Installation Manual
24
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Installation Manual
25
Installation Manual
26
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Installation Manual
3P383016-9A
Split Type Air Conditioners FTXM-H Series
27
Operation Manual
EDVN041518
12.Operation Manual 12.1 English
28
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
29
Operation Manual
30
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
31
Operation Manual
32
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
33
Operation Manual
34
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
35
Operation Manual
36
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
37
Operation Manual
38
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
39
Operation Manual
40
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
41
Operation Manual
42
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
43
Operation Manual
44
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
45
Operation Manual
46
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
47
Operation Manual
48
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
49
Operation Manual
50
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Operation Manual
EN_3P383015-6A
Split Type Air Conditioners FTXM-H Series
51
Operation Manual
EDVN041518
12.2 Vie iettnamese
52
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
53
Operation Manual
54
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
55
Operation Manual
56
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
57
Operation Manual
58
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
59
Operation Manual
60
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
61
Operation Manual
62
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
63
Operation Manual
64
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
65
Operation Manual
66
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
67
Operation Manual
68
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
69
Operation Manual
70
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
71
Operation Manual
72
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Split Type Air Conditioners FTXM-H Series
Operation Manual
73
Operation Manual
74
EDVN041518
Split Type Air Conditioners FTXM-H Series
EDVN041518
Operation Manual
VN_3P383015-6A
Split Type Air Conditioners FTXM-H Series
75
Optional Accessories
EDVN041518
13.Optional Accessories 13.1 Option List 13.1.1 Indoor Unit Option Name
Model Name
1
Titanium apatite photocatalytic air-purifying filter (without frame)
KAF970A46
2
Remote controller loss prevention with chain
KKF917A4
13.1.2 Outdoor Unit Option Name
76
Model Name
1
Air direction adjustment grille
KPW937B4
2
Drain plug
KKP937A4
Split Type Air Conditioners FTXM-H Series