Transformers IS 2705 IEC 60044-1 Voltage Transformers IS 3156 IEC 60044-2
ROUTINE TESTS ON
CT¶S
Accuracy Test Composite Error measurement on Protection core Exciting current measurement Overvoltage interturn test Power frequency dry withstand test on primary windings Power frequency dry withstand test on secondary windings Partial discharge measurement Terminal marking and polarity
ACCURACY TEST
Ratio Error(%) Phase Angle Error(min) Measuring current transformers Standard Accuracy classes are: 0.1,0.2,0.5,1,3 and 5
Protective
Current
Transformers
Standard Accuracy Classes are: 5P,10P and 15P Special Protection Current Transformers Turns Ratio Error (%) Actual turns ratio-Rated turns ratiox100 Rated turns ratio
EXCITING CURRENT MEASUREMENT Knee Point Voltage Auto Transformer
Ammeter
Voltmeter
Test CT
OVERVOLTAGE INTERTURN TEST TO
CHECK
INTERTURN INSULATION
Connection Diagram
Interturn Tester
Test
CT
HIGH
VOLTAGE DRY POWER FREQUENCY WITHSTAND TEST ON PRIMARY
HIGH
VOLTAGE DRY POWER FREQUENCY WITHSTAND TEST ON SECONDARY
TYPE TESTS ON
CT¶S
Short time current tests Temperature rise test Impulse test on primary winding High voltage wet power frequency withstand tests Determination of errors
SPECIAL TESTS Measurement of Dielectric Dissipation factor(Tan) Commissioning tests
ROUTINE TESTS ON VOLTAGE TRANSFORMERS Accuracy Test Induced Over voltage Withstand Test Separate Source Withstand Test High Voltage Power Frequency Withstand Test On Secondary Winding Megger Test Terminal marking and polarity test
ACCURACY TEST Ratio Error(%) Phase Angle Error(min) Measuring VT¶S Standard Accuracy classes are: 0.1,0.2,0.5,1.0 and 3 Protective VT¶S Standard Accuracy classes are: 3P and 6P