SICAM RTUs • AK 1703
SM-25xx/ETA2 Protocol Elements for Ethernet TCP/IP
Protocol element for communication via LAN/WAN SM-2546/ETA
1 x optical ethernet (only for SICAM BC)
SM-25x6 (Symbolfoto)
SM-2556/ETA2
1 x electrical ethernet
SM-2547/ETA2
2 x optical ethernet (only for SICAM BC)
SM-2557/ETA2
2 x electrical ethernet
The protocol element can be attached to master control and communication elements of SICAM RTUs platforms.
SM-25x7 (Symbolfoto)
Copyright Copyri ght © Siemens AG 2013
MC0-047 MC0-047-2.02 -2.02
Table Table of Content s Appl Ap pl ic ation ati on ........... ............... ........ .............. ............... ............... .............. .............. ............... ............... .............. ............... ............... .............. ............... ............... ......... ..3 Overview...............................................................................................................................4 Features and Fun ction ct ion s ................................................................ .................................................................................................. ....................................... .....6 6 Mod es of Operati on ................................................................... ..................................................................................................... .......................................... ........8 Comm uni cati on .............................................................. ............................................................................................... ...................................................... .....................9 Conf igu rati on ...................................................... ........................................................................................ ............................................................... .............................11 11 Technical Specifications ...................................................................................................13 ...................................................................................................13 Bloc Bl ock k Diagrams .................................................. .................................................................................... ................................................................ ..............................15 15 Statu s and Func tio n di spl ay ............................................................... .............................................................................................. ...............................17 17 Pin Ass ig nm ent ................................................................... .................................................................................................... ............................................... ..............19 19 System Components ......................................................................................................... .........................................................................................................21 21 Placement into the Information Landscape ......................................................................23 ...................................................................... 23
Disclaimer of Liability Although we have carefully checked the contents of this publication for conformity with the hardware and software described, we cannot guarantee complete conformity since errors cannot be excluded. The information provided in this manual is checked at regular intervals and any corrections that m ight become necessary are included in the next releases. Any suggestions for improvement are welcome.
Copyright Copyright © Siemens AG 2013 The reproduction, transmission or use of this document or its contents is not permitted without e xpress written authority. Offenders will be liable for damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
Subject to change without prior notice. Document Label: SIC1703-DSSM25XXETA2-ENG_V2.02 Issuing date: 02.09.2013
2
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
App lic ati on
The protocol elements described herein are used in several automation units based on SICAM RTUs platforms.
SICAM AK
SICAM TM
SICAM BC
Protocol elements process speficic communication protocols when SICAM RTUs automation units communicate with each other oder with devices of third-party manufacturers, in the field of telecontrol, automation, and protection. Due to its features, protocol element technology has a successful tradition for many years at SIEMENS. A fundamental characteristic is the separation of protocol-bound communication from application tasks of an automation unit.
Each interface has its own protocol processor
communication has no impact on the application, and vice versa each processor runs one communication protocol varioous different protocols run on one and the same hardware all protocols can be loaded with SICAM TOOLBOX II
You can change the communication protocol, for instance from serial to LAN, without retroactive effect to the application tasks of an automation unit Each automation unit can be equipped with various protocols This allows easy implementation of data nodes and frontends.
Engineering is done using SICAM TOOLBOX II.
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
3
Overview
SM-2546/ETA2
Protocol element based on a Serial Interface Module (SIM) with one LAN interface:
Standard according to IEC 60870-5-104
Fast Ethernet 100Mbit/s, IEEE 802.3, 100Base-Fx, optical TCP/IP time synchronisation via network time protocol (NTP) The SIM can be expanded for one serial interface via SM-0551/PROTOCOL optionally and can be attached to the m aster control element of SICAM BC.
SM-2556/ETA2
Protocol element based on a Serial Interface Module (SIM) with one LAN interface:
Standard according to IEC 60870-5-104
Ethernet / Fast Ethernet 10/100 MBit/s, IEEE 802.3, 10/100Base-TX, electrical TCP/IP time synchronisation via network time protocol (NTP) The SIM can be expanded for one serial interface via SM-0551/PROTOCOL optionally and can be attached to master control and communication elements of SICAM RTUs platforms
4
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
SM-2547/ETA2
Protocol element based on a Serial Interface Module (SIM) with dual LAN interface and integrated switch for ring or star topology:
Standard according to IEC 60870-5-104
Fast Ethernet 100Mbit/s, IEEE 802.3, 100Base-Fx, optical TCP/IP Rapid Spanning Tree Protocol (RSTP) according to IEEE 802.1D, Edition 2004 time synchronisation via network time protocol (NTP) The SIM can be attached to the master control element of SICAM BC.
SM-2557/ETA2
Protocol element based on a Serial Interface Module (SIM) with dual LAN interface and integrated switch for ring or star topology:
Standard according to IEC 60870-5-104
Ethernet / Fast Ethernet 10/100 MBit/s, IEEE 802.3, 10/100Base-TX, electrical TCP/IP Rapid Spanning Tree Protocol (RSTP) according to IEEE 802.1D, Edition 2004 time synchronisation via network time protocol (NTP) The SIM can be attached to master control and communication elements of SICAM RTUs platforms
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
5
Features and Functi ons
LAN/WAN Communi cation over Ethernet TCP/IP - General
10/100MBit (half duplex / full duplex) parameters for TCP/IP optimization
LAN/WAN Communication over Ethernet TCP/IP according to IEC 60870-5-104
controlled station controlling Station max. connections: 100 SICAM RTUs Interoperability IEC 60870-5-101/104 (DC0-013-2) Ax 1703 Interoperability IEC 60870-5-101/104 (DA0-046-2)
Ac qu is it ion of event s (tr ans mis si on of data r eady to be s ent)
General interrogation, outstation interrogation
Clock sy nchroni zation accordi ng to NTP (Network Time Protoc ol) - RFC 1305
NTP server NTP client
Command t ransmission
Supervision of maximum transport delay in control direction Command Transfer Monitoring (Dwell Time Monitoring)
Transmission of int egrated totals
Functions for the support of r edundant communication routes
PSI redundancy (synchronous connections) 104 redundancy according IEC 60870 5 104 Edition 2.0) 104 redundancy „controlling station“ 104 redundancy „controlled station“ with 1 Ethernet interface 104 redundancy „ controlled station“ with 2 Ethernet interfaces 1703 redundancy Deactivation of interface (with PRE control message) Dual LAN interface with integrated switch for ring or star configurations (DNIP) RSTP mode Line Mode switch mode single mode single + service mode
Protocol Element Control and Return Information Protocol Element Control
Interface “Enable/Disable” Send (general) interrogation command Send (general) interrogation command to GI-group Send (general) interrogation command
Protocol Element return information
Station failure protocol-specific return information 0 “Status DATA TRANSFER (BSE)” protocol-specific return information 1 “Status DATA TRANSFER (104)”
TOOLBOX II connection ov er LA N/WAN ("remote connection" )
Remote connection based on integrated terminal server
6
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Web Server
Integrated web server to display connection- statistic- and developer information Access to the web server with standard web browser via HTTP (Hyper Text Transfer Protocol) Password for Web Server Web Server (Enable/Disable) option
Special funct ions
Summer time bit (SU)=0 for all messages in transmit direction (time tag) Day of week (DOW)=0 for all messages in transmit direction (time tag) Originator address=0 for all messages in transmit direction Special functions for project DBAG / PSI Breaker delay in transmit direction () Send originator address with settable value Special functions for project RWE Bit by bit marking of the field Cyclic measured values Address of the return information for selection command 2 NT-Bit, IV-Bit according to RWE requirements
Hint The above mentioned functions are described in detail in the document SICAM RTUs • Ax 1703 Common Functions Protocol Elements, section " LAN Communication (104)"..
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
7
Modes of Operation
Operating mode Optical LAN interface (multimode fibre optic)
SIM
Patch Plug/Modul
SM-2546
CM-5861 b)
Note Fast Ethernet IEEE 802.3 100Base-FX 100Mbps 1300nm signals 50/125µ and 62.5/125µ fibres MT-RJ connector
SM-2547
Ethernet IEC 60870-5-104
Optical LAN interface (fibre optic)
a)
SM-2556/7
CM-2860
SM-2556/7
CM-2860 a)
Ethernet IEC 60870-5-104 Electrical LAN interface (twisted pair) Ethernet IEC 60870-5-104
plus media converter or switch according to SICAM RTUs Platforms Configuration Automation Units and Automation Networks (DC0-021-2)
CM-5860 b)
8
Ethernet / Fast Ethernet IEEE 802.3 10/100Base-TX 10Mbps / 100Mbps RJ45 connector 8-pin according to IEC 603.7
a)
Patch Plug for SICAM AK, SICAM TM; AK 1703, AMC 1703, AM 1703, BC 1703
b)
Patch Module for SICAM BC
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Communication
Communi cation 100Base-FX (opti cal) For the stations to communicate with each other, suitable transmission facilities and/or network components may be needed in addition. Own Station 100Base-FX (opti cal) System
System Element
Protocol Element
SICAM AK
CP-2010/CPC25 CP-2014/CPCX25 CP-2017/PCCX25
SM-2556/ETA2 SM-2557/ETA2
SICAM BC
CP-5014/CPCX55
SM-2546/ETA2 SM-2547/ETA2
SICAM TM
CP-6014/CPCX65
SM-2556/ETA2 SM-2557/ETA2
Note Media converter or switch required
Media converter or switch required
Remo te Station 10/100Base-TX (opti cal) System
System Element
Protocol Element
Note
SICAM AK
CP-2010/CPC25 CP-2014/CPCX25 CP-2017/PCCX25
SM-2556/ET02 SM-2556/ETA2 SM-2557/ETA2 SM-2557/ET02 SM-2558/ETA4
SICAM BC
CP-5014/CPCX55
SM-2546/ET02 SM-2546/ETA2 SM-2547/ETA2 SM-2547/ET02 SM-2558/ETA4
SICAM TM
CP-6014/CPCX65
SM-2556/ET02 SM-2556/ETA2 SM-2558/ETA4
Media converter or switch required
SICAM EMIC
CP-6010/CPC30
ETT0
Media Converter oder Switch erforderlich
SICAM CMIC
CP-8000/CPC80
ET84
Media Converter oder Switch erforderlich
SICAM MIC
CP-6040/CPC60
Third-party system
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
---
Media converter or switch required
10Base-TX ---
IEC 60870-5-104 according SICAM RTUs Interoperabilität IEC 608705-101/104 (DC0-012-2) or Ax 1703 Interoperabilität IEC 60870-5-101/104 (DA0-040-2)
9
Commun icatio n 10/100Base-TX (electrical) For the stations to communicate with each other, suitable transmission facilities and/or network components may be needed in addition. Own Station 100Base-FX (electrical) System
System Element
Protocol Element
SICAM AK
CP-2010/CPC25 CP-2014/CPCX25 CP-2017/PCCX25
SM-2556/ETA2 SM-2557/ETA2
SICAM BC
CP-5014/CPCX55
SM-2556/ETA2 SM-2557/ETA2
SICAM TM
CP-6014/CPCX65
SM-2556/ETA2 SM-2557/ETA2
Note
Remot e Statio n 10/100Base-TX (electr ical ) System
Protocol Element
Note
SICAM AK
CP-2010/CPC25 CP-2017/PCCX25
SM-2556/ET02 SM-2556/ETA2 SM-2557/ET02 SM-2557/ETA2 SM-2558/ETA4
SICAM BC
CP-5014/CPCX55
SM-2556/ET02 SM-2556/ETA2 SM-2557/ET02 SM-2557/ETA2 SM-2558/ETA4
SICAM TM
CP-6014/CPCX65
SM-2556/ET02 SM-2556/ETA2 SM-2557/ET02 SM-2557/ETA2 SM-2558/ETA4
SICAM EMIC
CP-6010/CPC30
ETT0
SICAM CMIC
CP-8000/CPC80
ET84
SICAM MIC
CP-6040/CPC60
AK 1703
CP-2000/CPC00 CP-2002/PCCE00 CP-2002/CE00 CP-2012/CE20
SM-2556/ET02
only IEC 60870-5-104 via Ethernet 10Base-TX
AMC 1703
CP-4000/CPC4x
SM-2556/ET02
only IEC 60870-5-104 via Ethernet 10Base-TX
Third-party system
10
System Element
---
only IEC 60870-5-104 via Ethernet 10Base-TX
10Base-TX
---
IEC 60870-5-104 according SICAM RTUs Interoperabilität IEC 608705-101/104 (DC0-012-2) or Ax 1703 Interoperabilität IEC 60870-5-101/104 (DA0-040-2)
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Configuration
SM-2546 The following table lists supported configurations. In addition to one SM-2546 (SI0/SI1) all parts (carrier module, patch plug, etc.) listed for the choosen configuration are needed: Configuration Carrier Module CP-5000, CP-5014
Interfaces
Patch Module 1)
SI0
one integrated patch module per SIx
1)
2)
SI1
SI2
SI3
1)
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined patch module for each interface
2)
serial interface (V.28) – can be added optionally (SM-0551)
SM-2556 The following table lists supported configurations. In addition to one (SI0/SI1 or SI2/SI3) or two (SI0/SI1 and SI2/SI3) SM-2556, all parts (carrier module, connection board, patch plug, etc.) listed for the choosen configuration are needed: Configuration
Interfaces
Carrier Module
Connection Board 1)
CP-2010, CP-2014
CM-2837
2)
4)
CP-2012, CP-2017
CM-2838
2)
4)
4)
4)
CP-5000, CP-5014 CP-6003,CP-6014
Patch Plug 1)
one integrated patch module per SIx ---
3)
2)
SI0
1)
one connection board for each carrier module, one patch plug for each interface
2)
For patch plugs for standard protocols in standard configurations as supported see modes of operation of the respective protocol element; for patch plugs in other than standard c onfigurations see SICAM RTUs Platforms Configuration Automation Units and Automation Networks (DC0021-2)
3)
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined patch module for each interface
4)
serial interface (V.28) – can be added optionally (SM-0551)
SI1
SI2
4)
SI3
SM-2547 The following table lists supported configurations. In addition to one SM-2546 (SI0/SI1) all parts (carrier module, patch plug, etc.) listed for the choosen configuration are needed: Configuration Carrier Module CP-5000, CP-5014 1)
Interfaces
Patch Module 1) one integrated patch module per SIx
SI0 1)
2)
SI1
SI2
SI3
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined patch module for each interface
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
11
SM-2557 The following table lists supported configurations. In addition to one (SI0/SI1 or SI2/SI3) or two (SI0/SI1 and SI2/SI3) SM-2556, all parts (carrier module, connection board, patch plug, etc.) listed for the choosen configuration are needed: Configuration Carrier Module
Connection Board 1)
Patch Plug 1)
CP-2010, CP-2014
CM-2837
CP-2012, CP-2017
CM-2838
CP-5000, CP-5014 CP-6003, CP-6014
12
Interfaces SI0
SI1
2)
2)
one integrated patch module per SIx ---
3)
2)
1)
one connection board for each carrier module, one patch plug for each interface
2)
For patch plugs f or standard protocols in standard c onfigurations as supported see modes of operation of t he respective protocol element; for patch plugs in other than st andard configurations see SICAM RTUs Platforms Configuration Automation Units and Automation Networks (DC0021-1)
3)
each variant of the SICAM BC (Bay Controller) which can be ordered comes with a determined patch module for each interface
SI2
SI3
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Technical Specifications
SM-2546 Communication Circuits Optical LAN interface (multimode fibre optic)
Fast Ethernet acc. to IEEE 802.3, 100Base-FX Data rate
100 Mbps
Line lengths
50/125 µm
up to 1000 m
62.5/125 µm
up to 1000 m
SM-2546 provides a PECL signal at this int erface. The conversion to an optical signal is done by the patch module which is installed for the interface. 1 serial interface (SM-0551 can be added optionally)
For Technical Specifications, see data sheet SM-x551/PROTOCOL (MC0-003-2)
Power Supply Operating voltage
4.75 .. 5.25 VDC,
typ. 400 mA,
max. 500 mA @5 V (without SM-0551)
4.75 .. 5.25 VDC,
typ. 525 mA,
4.75 .. 5.25 VDC,
typ. 90 mA,
max. 770 mA @5 V (with SM-0551) max. 120 mA @5 V (CM-5861)
The voltage is supplied by the carrier module. Mechanics Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SM-2556 Communication Circuits Electrical LAN interface (twisted pair)
1 serial interface (SM-0551 can be added optionally)
Ethernet / Fast Ethernet acc. to IEEE 802.3, 10/100Base-TX Data rate:
10 Mbps / 100 Mbps
Line lengths
up to 100 m
For Technical Specifications, see SM-x551/PROTOCOL (MC0-003-2)
Power Supply Operating voltage
4.75 .. 5.25 VDC,
typ. 400 mA,
max. 500 mA @5 V (without SM-0551)
4.75 .. 5.25 VDC,
typ. 525 mA,
max. 770 mA @5 V (with SM-0551)
The voltage is supplied by the carrier module. Mechanics Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
13
SM-2547 Communication Circuits Optical LAN interface (multimode fibre optic)
Fast Ethernet acc. to IEEE 802.3, 100Base-FX Data rate
100 Mbps
Line lengths 50/125 µm 62.5/125 µm
up to 1000 m up to 1000 m
SM-2547 provides a TTL signal at this int erface. The conversion to an optical signal is done by the patch m odule which is installed for the interface. Power Supply Operating voltage
4.75 .. 5.25 VDC,
typ. 400 mA,
max. 500 mA @5 V
4.75 .. 5.25 VDC,
typ. 90 mA,
max. 120 mA @5 V (CM-5861)
The voltage is supplied by the carrier m odule. Mechanics Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SM-2557 Communication Circuits Electrical LAN interface (twisted pair)
Ethernet / Fast Ethernet acc. to IEEE 802.3, 10/100Base-TX Data rate:
10 Mbps / 100 Mbps
Line lengths
up to 100 m
4.75 .. 5.25 VDC,
typ. 400 mA,
Power Supply Operating voltage
max. 500 mA @5 V
The voltage is supplied by the carrier m odule. Mechanics
14
Dimensions
227.3 x 63.5 mm
Weight
Approx. 90 g
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Block Diagrams
SM-25x6
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
15
SM-25x7
16
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Status and Function dis play
The protocol elements SM-2546/ETA2, SM-2547/ETA2, SM-2556/ETA2 and SM-2557/ETA2 itself have neither a front panel nor LED displays. They use the LEDs of the master control unit or communication elements. The meaning of these LED displays is described in the manual of the concerning system element. Proto col el ements – Mountin g pl ace and LED display SICAM AK/SICAM TM SIM0
Master control element CP-2014 (symbolic illustration)
LEDs for SIM0
SM-0551 SIM0 SIM1 Communication element CP-2017 (symbolic illustration) LEDs for SIM0
LEDs for SIM1
LEDs for SIM0 and SIM1 SIM0
P C A M 3 0 7 A 1 C I T S M
3 X
6 X
7 X
B T E O S T A H E S L U E P R
2 X
C N
S E R
C 0 1 2 3 Y O R L I S I S I S IS Y K K X P L L T / / C M X K K P P O / / R C x R R E E
4 1 0 6 P C
SIM1
0 / E R P 0 - I M S
1 X E O T S A H E S L U E P R
5 1 X
0 M I S
8 X
) 1 O / T E E R ( P 1 - I M S
9 X
2 ) / B E F R ( P 2 - I M S
0 1 X
3 / E R P 3 - I M S
4 X
B F
1 1 X
2 1 X
5 X
D W
K C O L N U O T H S U P
1
2
3
4
5
6 1 X
4 1 X
R E
6
C D V 0 R 6 W 4 P 2
3 1 X
Master Control Module CP-6014 (symbolic illustration)
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
17
Proto col elements – Mountin g place SICAM BC SIM0
SM-0551
Master control element CP-5014 (symbolic illustration)
Hint SICAM BC has no LED's for status and function display of pr otocol elements.
18
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Pin As signment
SM-2556, SM-2546
The abbreviations have the following meaning:
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
19
SM-2557, SM-2547
The abbreviations have the following meaning:
20
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
System Components
Hardware Designation
Item-Number/MLFB
SM-2546 Ethernet 100FX + 1 SS (optional)
BC2-546 6MF10130CF460AA0
SM-2556 Ethernet 10/100TX + 1 SS (optional)
BC2-556 6MF10130CF560AA0
SM-2547 Network-Interf.Ethernet 2x100FX
BC2-547 6MF10130CF470AA0
SM-2557 Network-Interf.Ethernet 2x100TX
BC2-557 6MF10130CF570AA0
Can be equi pped opti onal on SM-2546 and SM-2556 Designation SM-0551 Serieller Interface Prozessor 1 S S
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Item-Number/MLFB BC0-551 6MF10130AF510AA0
21
Firmware Designation
Item-Number/MLFB
ETA2 Ethernet Interface IEC60870-5-104
SC0-555-1
TU ETA2 TB II-Update
SC0-555-1.XX/53
Acces so ries Designation
22
Item-Number/MLFB
CM-2860 Patch Plug Standard V28,ET,TR
CA2-860 6MF12110CJ600AA0
CM-5860 Patch Modul el. V.28/ET
CC5-860 6MF12130FJ600AA0
CM-5861 Patch Modul optisch ET 100FX mit MTRJ-Stecker (SM-2546)
CC5-861 6MF12130FJ610AA0
CM-5863 Patch Modul optisch ET 100FX LC-Stecker (SM-2547)
CC5-863 6MF12130FJ630AA0
CM-5864 Patch Modul optisch ET 100FX LC-Stecker (SM-2546)
CC5-864 6MF12130FJ640AA0
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
Placement into t he Information L andscape
Document name
Item number
ACP 1703 • Ax 1703 Common Functions Protocol Elements
DC0-023-2
SICAM RTUs Platforms Configuration A utomation Units and Automation Networks
DC0-021-2
SICAM RTUs Interoperability IEC 60870-5-101/104
DC0-013-2
Ax 1703 Interoperability IEC 60870-5-101 bzw. -104
DA0-046-2
SICAM RTUs • AK 1703, SM-25xx/ETA2 MC0-047-2.02, Edition 09.2013
23