Section 8: ‘1+1’ UPS System Control Control
Chapter 1 - "1+1" Configured Systems
1.1 Introduction ........................................ .............................................................. ............................................ ................................ .......... 8-1 1.1.1 “1+1” Power circuit considerations ....................................... ............................................. ...... 8-1 1.1.2 “1+1” Control circuit considerations ........................................ ........................................... ... 8-1 Chapter 2 - Parallel Logic Board – 4520075B
2.1 Chapter Overview. ...................................... ............................................................ ........................................... ........................ ... 8-5 2.2 General Description ...................................... ............................................................. ............................................ ..................... 8-5 2.2.1 Input/Output connections connections ............................................................. ............................................................. 8-5 2.2.2 Circuit board board functions ............................................. .............................................................. ................. 8-10 2.3 General module output control ........................................... ............................................................... .................... 8-12 2.3.1 Inverter ON/OFF request – [OFF_INV> ........................................ ........................................ 8-12 Selective shutdown ........................................... .......................................................... ............... 8-13 2.3.2 Load transfer control .................................................. .................................................................. ................ 8-15 Load-on-inverter request – [C_L_INV> [C_L_INV> .......................... 8-16 Load-on-bypass request – [O_BUS_INV_L> ................. 8-17 2.4 Frequency synchronisation principles .................................................... .................................................... 8-19 2.4.1 Introduction ...................................................... ............................................................................. .......................... ... 8-19 Inverter frequency control – overview ............................. 8-19 Basic GVCO sync principles on module module start-up ............ 8-20 2.4.2 GVCO Detailed description of operation .................................. .................................. 8-23 2.4.3 PLL PLL Phase Comparator (D29) ......................................... ................................................... .......... 8-26 2.4.4 D30 Parallel Control Functions ............................................ ................................................. ..... 8-26 Bypass validation ............................................ ............................................................. ................. 8-27 Sync source selector ......................................... ......................................................... ................ 8-27 Sync bus comparator .......................................... ........................................................ .............. 8-28 VCO-in-loop relay control ............................................... ............................................... 8-28 Internal Sync Logic Logic ........................................ .......................................................... .................. 8-29 2.5 Output current sharing .......................................................... ............................................................................ .................. 8-31 2.5.1 Introduction ...................................................... ............................................................................. .......................... ... 8-31 2.5.2 Current sharing error detection principles ................................. ................................. 8-31 2.5.3 Current-sharing relay control (K3/K4) (K3/K4) ...................................... ...................................... 8-33 2.5.4 Selective shutdown ....................................... .............................................................. ............................. ...... 8-34 Current-sharing error ......................................... ....................................................... .............. 8-34 Reverse Power detector ................................ .................................................... .................... 8-35 Forward Power Power detector ................................................... ................................................... 8-35 2.5.5 On-line On-line module counter .......................................... ............................................................. ................... 8-35 2.6 Parallel rectifier operation ...................................................... ...................................................................... ................ 8-36 2.6.1 Rectifier current-sharing control control ................................................ ................................................ 8-36 2.6.2 Boost Boost charge control control ....................................... .............................................................. ........................... .... 8-37 2.6.3 Battery test control ................................................ ..................................................................... ..................... 8-37
11pm.fm5 - Issue 2 Dated 21/08/9 21/08/97 7
i
SECTION 8 - ‘ 1+1’ UPS Sy s t em Co n t r o l
7200 Ser i es UPS Ser v i c e Man u al
2.7 Other Features and functions ....................................... ............................................................ ........................... ...... 8-38 2.7.1 Ribbon Ribbon cable connection monitor ........................................... .............................................. ... 8-38 2.8 Parallel Logic Board Board circuit operation during start-up ........................... ........................... 8-39 2.8.1 Initialisation/reset .............................................. ..................................................................... ......................... .. 8-39 2.8.2 Inverter run-up run-up and synchronisation synchronisation ......................................... ........................................... 8-39 2.8.3 Connecting Connecting to the parallel control bus ....................................... ....................................... 8-40 2.8.4 Load transfer to inverter ..................................... ........................................................... ........................ .. 8-40 2.8.5 Load Load retransfer back to bypass bypass ........................................... .................................................. ....... 8-42 2.9 Test mode of operation: ..................................................... .......................................................................... ..................... 8-42
ii
11pm.fm5 - Issue 2 Dated 21/08/ 21/08/97 97
Section 8: "1+1" Configured Systems
Chapter 1 - "1+1" Configured Systems
1.1
Introduction A basic description of the principles of a “1+1” configured system is provided in section 1 (see paragraph 1.4 on page 1-7) – the basic block diagram is repeated in Figure 8-1, 8-1, below. Figure 8-1: “1+1” System configuration block diagram
RECTIFIER
INVERTER
Rectifier Control Logic
Inverter Control Logic
INV (SS)
Static Bypass
BYP (SS)
Static Switch Control Logic
Inter-Module Parallel Control Logic
Maint. Bypass
Maint. Bypass Static Switch Control Logic
Inter-Module Parallel Control Logic
1.1. 1.1.1 1
Rectifier Control Logic
Inverter Control Logic
RECTIFIER
INVERTER
Output (LOAD) PowerSupply
Static Bypass
BYP (SS)
INV (SS)
“ 1+1” 1+1” Power circuit consid erations erations As the above diagram shows, in a ‘1+1’ system the power outputs from the two modules are connected to an external common output busbar from where it is routed to the critical load equipment using normal distribution methods. Therefore, from a ‘power’ point of view there are no modifications required to the standard ‘single-module’ UPS.
1.1. 1.1.2 2
“ 1+1” 1+1” Control circuit considerations The extra ‘control’ requirements of a ‘1+1’ system over that of a ‘single-module’ are quite extensive due to the fact that the UPS output power terminals are connected to a common bus. The additional features require an exchange of various control and status signals, both analogue and digital, to pass between the two modules. Such signals are connected via the Parallel Logic Boards which are connected together by cross-connected ribbon cables which form a ‘Parallel Control Bus’ – (See Figure 8-2).
11pm-c1.fm 5 - Issu e 2 Dated 21/08/ 21/08/97 97
8-1
SECTION 8 - " 1+1" Co n f i g u r ed Sy s t em s CHAPTER CHAPTER 1 - " 1+1" 1+1" Confi gur ed Systems
7200 Ser i es UPS Ser v i c e Man u al
Figure 8-2: ‘1+1’ Control Logic
MODULE 1 X3
Parallel Bus
Parallel Logic Board X1 X2
Rect. Logic Bd
X1
X7
MODULE 2 X3
Parallel Logic Board X2 X1
X7
X3
Inv. Logic Bd
Rect. Logic Bd
X3
UPS Logic Board
Static Sw. Drv. Bd
X1
Inv. Logic Bd
UPS Logic Board
Static Sw. Drv. Bd
X5
X5
X2
X2
High Voltage I/F Bd
High Voltage I/F Bd
These inter-module control functions fall into the following broad categories: Balanced output requirements
It is crucial that the modules’ outputs are balanced in order to prevent a circulating current flowing from one module to the other, as such an event could cause significant module damage and invalidate the critical load supply. Balanced conditions are achieved by ensuring that the inverters are always fully synchronised to each other and their output voltages are equal. As with the case of the ‘singlemodule’ it is also necessary to synchronise the inverters to the bypass supply in order facilitate a no-break load transfer when required. Transfer control requirements
Once again due to the paralleled nature of the modules’ outputs, it is crucial that the load transfer control mechanisms in each module are controlled from a common point. That is, to prevent equipment damage due to one module transferring its output to bypass whilst the other is ‘on inverter’. A common control system is therefore used which manages the load transfer according whether the system is configured as redundant or or non-redundant . Redundant vs Non-Redundant configuration
Redundant system. In a ‘redundant’ system, if one module fails the remaining module will remain on-line to maintain the critical load; therefore if a module goes faulty its output contactor is tripped to take it off-line but its static bypass is not activated. The static bypass circuit is only triggered if a fault develops in the second module which requires it also to be taken off-line. In a redundant system system the modules are thus sized such that the potential maximum load can be powered by just one of the two modules. Under normal circumstances both modules are operational and share the load current equally – i.e. under full load conditions both modules operate at 50% of their nominal rating.
8-2
11pm-c1.fm 5 - Issu e 2 Dated 21/08/ 21/08/97 97
7200 Series UPS Service Manual
SECTION 8 - " 1+1" Configured Systems CHAPTER 1 - "1+1" Confi gured Systems
Non-redundant system. In a ‘non-redundant’ configuration, if one module fails then both modules are taken off-line (by opening their output contactors) and the load transferred to the static bypass. The load will not re-transfer to the inverters until both inverters are fully operational and fully synchronised etc. In a non-redundant system each module’s nominal rating must be at least 50% of the potential maximum load. Inter-module power rectifier control
The power rectifier is only affected by the parallel control bus in a “1+1” system if a ‘common battery’ is used – i.e. if both UPS modules are connected to a single battery bank (via separate battery isolators of course). In this type of installation the power rectifiers in each module are effectively connected in parallel and must be controlled such that the battery charge current is shared equally between them. A ‘common battery’ option kit is available. This contains DCCTs (DC Current Transformers) which are fitted to the battery power lines and connected via the parallel control bus to a sharing circuit in the rectifier control block. See the Options section in the relevant system IOM user manual for full details.
11pm-c1.fm 5 - Issu e 2 Dated 21/08/97
8-3
SECTION 8 - " 1+1" Configured Systems CHAPTER 1 - " 1+1" Confi gur ed Systems
8-4
7200 Series UPS Service Manual
11pm-c1.fm 5 - Issu e 2 Dated 21/08/97
Section 8:
Chapter 2 - Parallel Logic Board – 4520075B
2.1
Chapter Overvi ew. This chapter contains a circuit description of the Parallel Logic Board used across the whole 7200 Series UPS model range when configured to operate as a ‘1+1’ system, and should be read in conjunction with circuit diagram SE-4520075-B (4 pages). Signal annotations shown on the circuit diagrams are shown in italics in the following text – e.g. [SYN_INT>.
2.2 2.2.1
General Descri pti on Input/Outpu t con nectio ns Connectors X2 & X3
As mentioned above, connectors X2 & X3 are cross-connected from one module to the other – i.e. X2 on one module is connected to X3 on the other, and viceversa. The signals passing between these connectors are therefore bi-directional. Table 8-1: Pin
Signal
1 2
A_CON / 0V B_CON / 0V
3
4
5
6
7
Signal Function Used to detect that the ribbon cable is connected – (See paragraph 2.7.1)
B_BLK_SW
If a module applies an [O_BLK_SW> signal to X1-43 it is passed to both modules via this l ine, and thereby turns off the inverters in both modules by driving the [OFF_INV> output at D31-19 high. (see page 8-12)
B_MNS_L_SS
If a module applies an [O_MNS_L_SS> signal to X144 it is passed to both modules via this line. This is used by the load transfer control logic when the board is fitted in a multi-module MSS cabinet only, and is overridden in a 1+1 system by jumper X6-4(see page 8-16).
B_MNS_D_SS
If a module applies an [O_MNS_D_SS> signal to X1 pin 45 it inhibits the passage of the mains frequency signal [F-IN> through D31 (See paragraph 2.4.4.1). This signal is coupled to the second module via the parallel bus X2/X3 pin 5 (inhibit = low).
B_PAR_SYN
This is taken high when the VCO-in-loop relay (K1) is closed in either module, and is used to inform the GVCO whether to start in the “master” or “slave” mode during turn-on (See paragraph 2.4.4.4).
B_MNS_SYN_OK
The [O_MNS_SYN_OK> signal to X1-48 informs the Parallel Logic Board when the Inverter Logic Board’s master oscillator is “internally synchronised”. This is applied to the ‘bypass validation’ circuit in both modules (See paragraph 2.4.4.1)
11pm-c2.fm 5 - Issu e 2 Dated 21/08/97
8-5
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
Pin
Signal
8
B_BST_BAT
Used when common battery system is used to force both modules into boost mode if selected in either module (See paragraph 2.6.2).
B_MNS_DIS
This line couples together the [O_MNS_DIS> input to X1-49. When [O_MNS_DIS> is low in both modules the bus line goes high and feeds back a logic high to the UPSLB via X1-37 [MNS_DIS>
B_INV_LOD
This line couples the load-on-bypass request and is logic high (requesting load on inverter) only when neither module is calling for “load on inverter”. This line affects the output on X1-32 (See paragraph 2.3.2.2)
B_FREQ_PAR
This line is connected to the GVCO [FRQ_OSC> output if relay K1 is closed (in either module,) and thereby forms the parallel GVCO sync bus (See paragraph 2.4.1.1).
9
10
11
Signal Function
B_INV_IND
This line, goes low only when the VCO in loop relay (K1) is closed in both modules, and is used to signal the availability of both modules in a non-redundant system.
13
B_TST_BAT
Used when common battery system is used to force both modules into TEST mode if selected in either module (See paragraph 2.6.3).
14
B_SW_BYP
High when Maintenance Bypass Switch is closed in either module (see X1 - 34).
15
B_FREQ_MNS
This line carries the bypass (mains) frequency signal between the modules when it has been accepted by the bypass validation circuit (See paragraph 2.4.4.1).
1618
-
NIU
19 20
-
0V
21
COMM_P
22
I_B_P
12
24
O_N_INV
23 25 26 27 28 29 30
B_IM_0 B_IM_C B_IM_R B_IM_A B_IM_B B_C_0 B_C_P
31 32
8-6
7200 Series UPS Service Manual
These two lines are used to parallel the battery current sense signals when required. Not used for a particular purpose on this board. input via X1 18/19. This line connects the ‘available module counter’ circuits together to allow the number of available modules to be detected (See paragraph 2.5.5).
These lines carry the current sharing sense signals (See paragraph 2.5)
0V
33
-
34
B_GND
NIU Parallel bus ground connection
11pm-c2.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logi c Board
Connector X1
Table 8-2: Pin
Signal
Signal Function
1-4
0V
5-8
+12V
9 - 10
-12V
11
VO_A
12
VO_B
13
VO_C
14
COM
15
IO_A
16
IO_B
17
IO_C
18
I_B_P
19
COMM_P
20
DV_A
21
DV_B
22
DV_C
23
DV_0
Output voltage sense signals derived on the High Voltage Interface Board. Used by the ‘selective shutdown’ circuit (See paragraph 2.5.4). Analogue sense signal common Output current sense signals derived on the High Voltage Interface Board. Used by the current sharing and selective shutdown circuits (See paragraph 2.5). These two inputs are used to parallel the battery current sense signals when required. Not used for a particular purpose on this board but connected directly to second module via parallel bus X2/X3 pins 21/22. These outputs are generated by the current sharing circuit and go to the Inverter Logic Board (via UPSLB) where they perform individual fine adjustment of each output line voltage to balance the line currents between the two paralleled machines. DV-0 is a neutral point for these signals (See paragraph 2.5.2).
IREC_T
Input from rectifier current sense amp on Rectifier Logic Board. This represents the rectifier current taken by this module and is used by the current sharing circuit if a common battery system is used (See paragraph 2.6.1).
25
DB
This output is the result of the rectifier current sharing circuit and passes to the Rectifier Logic Board in the form of a correction signal to ensure balanced input currents to both modules when a common battery system is used (See paragraph 2.6.1).
26
-
24
27-28
NIU 0V
29-30
-
+5V
31
-
NIU
32
I_BUS_INV_L
This is a logic low load-on-bypass request to the control logic on UPSLB. Due to the parallel bus connection (X2/3 - 10) the output is low only when load-onbypass is requested by both modules (See paragraph 2.3.2.2).
33
SW_OUT
This is an input via HVIB which is low when the Output Switch is closed (see page 8-13).
11pm-c2.fm 5 - Issu e 2 Dated 21/08/97
8-7
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
Pin
Signal
Signal Function
34
SW_BYP
This is an input via HVIB which is low when the Maintenance Bypass Switch is closed in either module (see page 8-13).
35
I_BST_BAT
Output to UPSLB which, when high, initiates Battery Boost. Used in common battery system only and is enabled by jumper X6-2.(See paragraph 2.6.2)
36
I_TST_BAT
Output to UPSLB which, when high, initiates Battery Test. Used in common ba ttery system only and is enabled by jumper X6-2. (See paragraph 2.6.3)
MNS_DIS
The input to X1-49 from the UPSLB goes high. This input is coupled together via the parallel control bus (X2/3 - 9), and when [O_MNS_DIS> is low in both modules a logic high is fed back to the UPSLB via X1-37 [MNS_DIS>
38
BLK_SEL
Output to the UPSLB which is high when the ‘selective shutdown’ circuit is active (led H1 illuminated) (See paragraph 2.3.1.1).
39
OFF_INV
Output to inverter ON/OFF control logic on UPSLB. Turns OFF inverter if high. (See paragraph 2.3.1)
40
C_L_INV
Output to load-on-inverter control logic on UPSLB. Requests load on inverter selection if high (See paragraph 2.3.2.1).
41
RES_EXT
Input from the reset circuit on the UPSLB which, when high, resets several functions within the Parallel Logic Board ASIC devices.
42
V_AUX
Input from the UPSLB reset generator chip which resets various latches within D39 and D31on powerup. The signal is a 1 second logic high pulse.
O_BLK_SW
Input from the UPSLB software-controlled inverter off signal [O_BLK_SW>. The signal is also coupled to the second module via X2/X3 pin 3 which enables the inverters in both modules to be turned off if a [O_BLK_SW> signal is generated in either module (See paragraph 2.3.1)
O_MNS_L_SS
This input is used by the load transfer control logic when the board is fitted in a multi-module MSS cabinet, it is not functional in a 1+1 system due to configuration jumper X6-4. (see page 8-16).
45
O_MNS_D_SS
Input from the UPSLB processor system. When high, it inhibits the passage of the mains frequency signal [F-IN> through the bypass validation circuit. This signal is coupled to the second module via the parallel bus X2/X3 pin 5 (See paragraph 2.4.4.1).
46
O_TST_BAT
Input from the UPSLB processor system which goes high when it calls for a battery test sequence (See paragraph 2.6.3).
47
O_BST_BAT
Input from UPSLB which, when high, requests Battery Boost (See paragraph 2.6.2).
37
43
44
8-8
7200 Series UPS Service Manual
11pm-c2.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logi c Board
Pin
Signal
Signal Function
48
O_MNS_SYN_OK
Input from UPSLB which is low when the Inverter Logic Board’s master oscillator has achieved internal synchronisation (See paragraph 2.4.4.1).
O_MNS_DIS
The input to X1-49 from the UPSLB goes high. This input is coupled together via the parallel control bus (X2/3 - 9), and when [O_MNS_DIS> is low in both modules a logic high is fed back to the UPSLB via X1-37 [MNS_DIS>.
BLK_INV
This input is driven by the fault output on the Inverter Logic Board and provides an input to the ‘sync source selector’ circuit (See paragraph 2.4.4.2)
PAR_REC
Input from the UPS Logic Board Processor system which is high when it is programmed with parallel rectifier operation (See paragraph 2.6).
INV_L
This input from the UPS Logic Board goes high when the load is “on-inverter” and is used to validate the ‘selective shutdown’ circuit (See paragraph 2.3.1.1).
53
FRQ_SYN
This is connected to the GVCO output [FRQ_OSC> and thereby represents the reference frequency to which the UPS inverter synchronises (See Figure 85).
54
FRQ_PAR
This output passes the parallel sync bus frequency to the UPS Logic Board (See Figure 8-5).
55
F_IN
This input is a squarewave at the incoming mains Rphase frequency, used as the bypass reference frequency is accepted by the ‘bypass validation’ circuit (See paragraph 2.4.4.1).
56
-
49
50
51
52
57
58
59
60
NIU
INV_OK
This input is high when the UPS Logic Board determines that the inverter is operating normally and is used by the synchronisation control logic within D30 during start-up (See paragraph 2.4.4).
CON_SEL
This input is generated on the UPS Logic Board and is logic high when the battery is low or the bus voltage is 150% of nominal charge voltage. This is used by the ‘selective shutdown’ circuit (See paragraph 2.3.1.1)
I_SW_BYP
This output goes low when the [SWBYP> input to X134 is low in either module (i.e. when Maintenance Bypass Switch is closed in either module) (see page 8-13).
N_AUX_CONT
This input is generated by the UPS Logic Board and is low, to disable the “load on bypass” request, if the inverter output contactor is closed (See paragraph 2.3.2.2).
11pm-c2.fm 5 - Issu e 2 Dated 21/08/97
8-9
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
2.2.2
7200 Series UPS Service Manual
Circuit board functio ns Figure 8-2 illustrates the position of the Parallel Logic Board in a ‘1+1 configured’ module. The inter-module control signals pass from one module to the other by means of the ribbon-cables fitted to the boards’ X2 and X3 connectors, which are cross-coupled – i.e. X2 on one Parallel Logic Board is connected to X3 on the other. Due to their function, the ribbon cables connecting the two boards together are referred to in this manual as the “parallel control bus”. The parallel control functions will be maintained if one of the two cables is disconnected but for safety reasons both cables should normally be connected – led H2 illuminates if one cable becomes disconnected, but the system is not otherwise affected. The third connector (X1) on the Parallel Logic Board is connected to the UPS Logic Board from where it has access to the remaining module control boards. This topology allows any control board in one module to communicate with any control board in the second module, a s required by the control regime. In addition to its role in providing a paralle l control bus, the Parallel Logic Board contains a number of active circuits whose functions are summarised below. Note: each of the following categories are assigned major section headings in the remainder of this chapter: General module output control
The Parallel Logic Board generates control logic signals which: •
provides an Inverter Start/Stop command signal which is connected as an input to the Inverter Start/Stop control logic on the UPS Logic Board.
•
provides the ‘static switch control section’ of the UPS Logic Board with load transfer control signals which determine whether the load is connected to the inverter (output contactor closed) or static bypass supply.
•
monitors the number of available modules and shuts-down the inverter (via the UPS Logic Board) if the system redundancy is exceeded.
Module frequency control and synchronisation control
Although each UPS module ultimately operates at a frequency determined by its Inverter Logic Board’s master oscillator, in a 1+1 sys tem the Parallel Logic Board provides a complex synchronisation function which operates between the two modules and also between the modules and the bypass supply. This ensures that the two modules are frequency-locked together at all times when the inverters are operating in parallel, and also locked to the bypass supply provided it remains healthy. Output current control
When both modules are on-line and feeding a common load, their power inverter sections are effectively operating in parallel and should share the load current equally. It is especially important that circulating currents are not allowed to appear in the UPS output stages, whereby one module attempts to reverse-feed the other. The Parallel Logic Board contains analogue circuits which:
8-10
•
provide an output current-sharing function by using fine control of the Inverter Logic Board voltage regulation circuit in such a manner as to ensure that both UPS modules produce an equal output current.
•
provide protection against current sharing failure and trip the module off-
11pm-c2.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logi c Board
line if it detects that one module is feeding reverse current into the other. This function is called “Selective Shutdown” in this manual. Common battery control
In installations where a common battery is used by both modules, the Parallel Logic Board provides a rectifier current-sharing function whereby is finely ad justs the rectifier voltage to obtain balanced rectifier input currents. If both modules produce the same output current and take the same input current this implies that they are also (within limits) providing the same amount of battery charge current. When a common battery is used, the Parallel Logic Board also controls the rectifier float/boost charge mode selection in both modules to ensure they operate in the same mode at all times. Miscellaneous functions
In addition to the ‘easily categorised’ functions mentioned above, the Parallel Logic Board also provides other minor functions which are mainly associated with its role of providing the parallel control bus.
The digital control element of the above functions are carried out by two ASIC circuits shown on page 1 of the circuit diagram – D30 and D31. The internal logic of these devices is not described in detail in this chapter; however an appreciation of their input/output conditional relationships is essential t o understand the wider functionality of the circuits which they control, therefore internal block diagrams of these devices are used to aid explanation where necessary.
11pm-c2.fm 5 - Issu e 2 Dated 21/08/97
8-11
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
7200 Series UPS Service Manual
Section 8:
2.3
General modu le out put cont rol The signals described in this sub-section are concerned with turning ON/OFF the inverter in the local module and controlling the load transfer between the inverter and bypass supplies – these signals are developed by D31, as described below.
2.3.1
Invert er ON/OFF requ est – [OFF_INV> Figure 8-3: Inverter ON/OFF & Selective Shutdown X1
D31
19
[OFF_INV>
X7
39
39
X3
5
D88
33
1=OFF
[ON_INV>
X4
36
39
1=ON
Parallel Logic Board
13
D11
UPS Logic Board
7
[BLK> 1=OFF
Inverter Logic Board
D31 Internal Block Diagram
[RIT_INV_L> [C_N_INV> [CON_SEL>
31 27 11
Selective Shutdoown Logic
37
[BLK_SEL>
43 [TEST> [BLK_SW> (mm only)
[I_SW_BYP> [SW_OUT> [CONN_A> [CONN_B>
26
6 14 17
Inverter ON/OFF Logic
19
[OFF_INV>
18
An ‘inverter ON/OFF’ control signal [OFF_INV> is produced by D31 pin 19 and applied to the ‘inverter inhibit logic’ on the Inverter Logic Board (D11) via the path shown above in Figure 8-3. The [OFF_INV> signal at D31-19 goes high to ‘inhibit’ the inverter and low to ‘enable’ it. Note that the signal does not pass straight through D88 on the UPS Logic Board, but is combined with several other inverter inhibit logic signals at that point. It is therefore quite possible for the signal at D31-19 to call for the inverter to be enabled ( [OFF_INV> = low) but for some other input to D88 to override this request on the UPS Logic Board ( [ON_INV> = stays low). Similarly, there are other inputs to D11 on the Inverter Logic Board which can override an [ON_INV> request. The [OFF_INV> signal logic state at D31-19 depends upon a complex combination of the inputs to D31, as described below, and it is driven high (turning off the inverter) if any of the following conditions are true : Selective shutdown. (D31 pin 37 high)
The ‘selective shutdown’ function is concerned with a current sharing problem. The error detection circuit, which is explained in paragraph 2.5.4, is part of the current sharing control description; however the effects of the ‘selective shutdown’ error signal within D31 is described below in paragraph 2.3.1.1. In summary, if the selective shutdown logic within D31 becomes active D31-37 ( [BLK_SEL>) will switch high (illuminating H1) in addition to driving D31-19 ( [OFF_INV>) high.
8-12
11pm-c3.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
Software block. (D31 pin 26 high)
Note: in a 1+1 configured system this input is overridden internally due to jumper X6-4 being made (pulling D31-1 permanently low). Therefore, the described affects of this signal on the Inverter ON/OFF control signal apply only when the board is fitted in a multi-module inverter system.
A logic high signal applied to X1-43 from the UPS Logic Board ([O_BLK_SW>) is inverted by a section of D23 from where it is connected to the parallel control bus (X2/3 pin 3). The signal at this point ( [B_BLK_SW>) is also reinverted at D26 pin 6 to provide the high [BLK_SW> signal to D31-26 which turns off the inverter. This means that in a multi-module system all the modules are affected by the software block signal if it is generated in any module. Maintenance bypass interlock. (D31 pin 6 high and pin 14 low)
If the Maintenance Bypass Switch is closed (D31-6 is high) at the same time as the module’s Output Switch (D31-14 is low) it will drive D31-19 high, turning off the inverter to prevent damage occurring due to reverse power flow from the mains into the inverter. Note: the Maintenance Bypass switch contacts are sensed by both modules via the parallel control bus X2/3 pin 14. Thus, the inverter is shut down in both modules if the maintenance bypass switch is closed in either module. Output switch interlock. (D31 pin 43 high)
When operating in a 1+1 configuration, it is required that the inverter is allowed to operate only if the UPS output switch is closed. This ensures that the parallel current-sharing and frequency control systems are enabled. There is however a TEST facility which is invoked by jumper X6-8 on the Parallel Logic Board which, when closed, overrides this interlock to allow the inverter to be run-up for test purposes with the output switch open. When the module is not operating in the TEST mode – i.e jumper X6-8 is open (D31-43 high) – the inverter will be turned off by the input to D31 pin 14 which is driven high when the output switch is open. Test mode interlock. (D31 pin 43 low)
When the UPS is running in the TEST mode, jumper X6-8 is fitted (D31-43 is low), the inverter will be turned OFF if the module’s Output Switch is c losed (D31-14 is low). Open circuit parallel control bus. (D31 pins 17 and 18 high)
If both ribbon cables that form the parallel control bus (to connectors X2 and X3) are improperly connected (D31-17 & D31-18 both high) the inverter will be shut down for safety reasons due to the loss of the parallel control bus. Note: led H2 will illuminate when either one of these cables are disconnected, driven by a logic high output on D31-32. 2.3.1.1
Selective shu tdo wn
This paragraph considers the actions of the ‘selective shutdown’ circuit within D31 (See Figure 8-3), and its effects on the [OFF_INV> inverter ON/OFF command at D31-19.
11pm-c3.fm 5 - Issu e 2 Dated 21/08/97
8-13
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
7200 Series UPS Service Manual
The ‘Selective Shutdown’ circuit detects various forms of current sharing faults and is shown on page 3 of the circuit diagram (see paragraph 2.5.4 on page 8-34). The detector’s output signal [IN_SEL> goes high in a current-related fault event and is inverted to a low at D31 pin 4 which: •
Turns off the inverter (drives D31-19 [OFF_INV> high).
•
Sends a [BLK_SEL> status signal to the UPS Logic Board (from D31-37 and X1-38) to inform that board of the current conditions.
•
Illuminates H1.
•
Drives the output on D31-13 high. This output is debounced and inverted, and fed back to D31-9 as a logic low signal which latches the above signals in their fault state. Once activated, the latch must be reset by pressing the RESET push-button on the UPS Logic Board, which applies a logic high [RES_EXT> input to D31-8 via X1-41. Note that when the module is first started the power-supply monitor on the UPS Logic Board applies a 1 second logic high [V_AUX> reset pulse to D31-5 which initially holds off the ‘selective shutdown’ latch (connected via X1-42).
In order for the [IN_SEL> ‘selective shutdown’ signal to produce the above outputs from D31, the following conditions have to be satisfied on other D31 inputs. If any of these conditions are not satisfied the ‘selective shutdown’ signal [IN_SEL> is ignored by D31 internally. Load on inverter (D31 pin 31 low).
The UPS Logic Board must be commanding ‘load on-inverter’. This is validated as a logic low on D31 pin 31. UPS Not in ‘Test’ mode (D31 in 43 high).
The UPS must not be operating in the ‘Test’ mode. Jumper X6-8 must therefore be open, providing a logic high at D31 pin 43. Two modules on line (D31 in 27 high).
In a ‘non-redundant’ system the [C_N_INV> input to D31 pin 27, generated by the module counter circuit (see paragraph 2.5.5 on page 8-35), is logic high when both modules are on line, which is a requirement for the selective shutdown circuit output to be valid. In a ‘redundant module’ system it is permissible for one module to operate alone, and where this is the case the ‘selective shutdown’ circuit is irrelevant. The [C_N_INV> input to D31 pin 27 is overridden in this case by making jumper X6-3. DC Bus above Vmin & Load below 150% nominal (D31 pin 11 high).
These two conditions are detected by the UPS Logic Board and a single signal ([CON_SEL>) is connected to D31 pin 11 which is high when both conditions are satisfactory.
8-14
11pm-c3.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
2.3.2
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
Load transfer cont rol Figure 8-4: Load Transfer control logic X1
18 [O_BUS_INV_L>
32
[I_BUS_INV_L>
X7
X5
[INV_DIS>
32
7
38
[MNS_L>
X3
17
[MNS_L>
17
1=turn on static bypass
1=load on bypass
0=enable load on byp D31
D88
12
40
[C_L_INV>
40
[C_L_INV>
6
0=enable load on inv
36
1=turn close inv output contactor [INV_L>
15
15
[INV_L>
1=load on inv
Parallel Logic Board
Static Switch Driver Board
UPS Logic Board
D31 Internal Block Diagram
[O_PAR_SYN>
[TEST>
[PAR_INV> [MNS_L_SS> (mm only) [C_N_INV> [N_AUX_CON> [INV_L> Jumper X6-4 (made) Jumper X6-1 (made = non-redundant) [INV_IND>
24
VCO-in-loop Control
21
[RIP> To Relay K1/K2
43
7
18
28
[O_BUS_INV_L>
27 34 25 1
Load Transfer logic
12
[C_L_INV>
44
44
20
[O_INV_IND>
Load transfer control is based on several complex circuits which are interlocked in such a way as to avoid the bypass static switch being activated while the inverter output contactor is closed, and vice versa, to prevent back-feeding the UPS inverter from the mains supply. In a ‘single-module’ installation this function is performed by the UPS Logic Board’s micro-controller system in conjunction with other status signals applied to D88. However, when the module is connected in a 1+1 configuration it requires additional circuitry to cater for the parallel control elements of the load transfer operation – i.e. to ensure that both modules transfer the load between inverter and bypass simultaneously, and also to manage the t ransfer-to-bypass requirements in a redundant-module situation. These ‘additional’ parallel control functions are provided by the Parallel Logic Board, based on the logic operation within D31. As illustrated in Figure 8-4, D31 on the Parallel Logic Board produces two si gnals associated with load transfer control. The [C_L_INV> output from D31-12 informs the UPS Logic Board that it is safe (from a paralleling point of view) to transfer the load to the inverter; and the [O_BUS_INV_L> output from D31-18, which is interlocked with [C_L_INV> within D31, informs the UPS Logic Board whether or not it is safe to transfer the load to the bypass supply. Both these signals are described in more detail below. Note: A detailed description of the load transfer control operation during module start-up is provided in paragraph 2.8.
11pm-c3.fm 5 - Issu e 2 Dated 21/08/97
8-15
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
2.3.2.1
7200 Series UPS Service Manual
Load-on -invert er reques t – [C_L_INV>
The [C_L_INV> output from D31 pin 12 goes low when the logic within D31 deems it safe to transfer the load to the inverter, and can be viewed as a ‘load on inverter’ request . This is applied to D88 on the UPS Logic Board and, provided other inputs to D88 are valid, produces a logic high [INV_L> output at D88 pin 36. This is connected to the Static Switch Driver Board where it activates the i nverter ‘output contactor close’ circuit; thereby connecting the load to the inverter. To drive [C_L_INV> low (to request ‘load-on-inverter’) all the conditions described immediately below must be valid. Module synchronisation validation (D31 pin 7 low)
D30-14 applies a logic high [O_PAR_SYN> signal to D31 pin 24 when it detects that the module synchronisation conditions are valid. This drives D31-21 low ([RIP>) which is debounced and inverted at D28-4 to appear as a logic high [PAR_INV> input to D31-7. Note 1: the [RIP> signal also energises the ‘VCO-in-loop’ relays (K1/K2) which connect the module’s synchronisation control circuits to the parallel frequency control bus (See paragraph 2.4). Note 2: the [PAR_INV> signal is also used by the ‘available module counter’ circuit (See paragraph 2.5.5) and ‘current-sharing’ relay control circuit (K3/ K4) (See paragraph 2.5.3).
When the TEST mode jumper X6-8 is made (D31-43=low) the [O_PAR_SYN> signal has no affect on D31, and D31-21 [RIP> is held permanently high. Valid ‘Available module counter’ output (D31 pin 27 high)
In a ‘non-redundant’ system the ‘available module’ counter is configured to produce a logic high [C_N_INV> signal only when both modules are available. In a ‘redundant’ module system [C_N_INV> goes high when the local module is available irrespective of the state of the second module. No “load-on-bypass” request from system (D31 pin 28 low)
This input is overridden in a 1+1 module due to jumper X6-4 being fitted; the following description thus applies only when the board is fitted to a module forming part of a multi-module system. In a multi-module system, the decision whether to connect the load to the inverter or bypass supply rests with the UPS Logic Board’s micro-controller system. When it decides to connect the load to the bypass supply, the UPS Logic Board sends a logic high [O_MNS_L_SS> signal to the Parallel Logic Board X1 pin 44. This is inverted to a logic low at D23 pin 11 ([B_MNS_L_SS>) and connected to the parallel control bus via X2/3 pin 4, and also reinverted at D26 pin 8 to provide a logic high [MNS_L_SS> input to D31 pin 28 – i.e. when the UPS Logic Board is calling for ‘load-on-bypass’, the logic high [MNS_L_SS> input to D31 pin 28 forces D31-12 high to prevent it from signalling a ‘load-on-inverter’ request. Note: due to the fact that the ‘load-on-bypass’ request from the UPS Logic Board is connected to the parallel control bus X2/3 pin 4 ( [B_MNS_L_SS> ), it affects all modules when either of them is calling for load-on-bypass.
8-16
11pm-c3.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
‘Non-redundant’ module conditional logic (D31 pin 29 low)
In a ‘non-redundant’ system the load must not be transferred to the inverters unless both inverters are fully operational and connected to the parallel control ‘sync’ and ‘current-sharing’ busses. Therefore a circuit is required which prevents [C_L_INV> requesting ‘load-on-inverter’ until these conditions are satisfied. The circuit which performs this task is again w ithin D31, and acts in response to the [PAR_INV> signal applied to D31-7 (which is high when the module is connected to the parallel control bus), and the [C_N_INV> signal from the ‘available module counter’ circuit applied to D31-28 (which is high when both modules are running. When both these conditions are satisfied, the [O_INV_IND> output from D3120 is driven low. This is inverted to a high at D24 pin 17 and connected to the parallel control bus (X2/X3-12), and then reinverted to a low at D26 pin 12 ([INV_IND>) and applied to D31 pin 29. D31-29 must be low to enable the [C_L_INV> output from D31 pin 12 to go low and request load-on-inverter. Note that the parallel control bus action means that these conditions must be valid in both modules before either module is allowed to request ‘load-oninverter’. In a ‘redundant-module’ system the [INV_IND> input to D31-29 is overridden by the removal of the configuration jumper X6-1 and the input to D31-29 has no effect. (X6-1 must be fitted to obtain non-redundant operation.) TEST mode of operation
When the TEST mode is selected (jumper X6-8 made) the [C_L_INV> output at D31-12 is forced low irrespective of the state of the other conditions described above. This allows the inverter output contactor operation to be tested while the load is isolated from the inverter through opening the output power switch. 2.3.2.2
Load-on -bypass requ est – [O_BUS_INV_L>
The [O_BUS_INV_L> output from D31 pin 18 goes low when t he logic within D31 deems it unsafe to power the load from the inverter. It can therefore be viewed as a ‘load on bypass’ request as, under normal conditions, the UPS system should always attempt to transfer the load to the bypass supply whenever the inverter supply becomes invalid (See Figure 8-4). When requesting ‘load-on-bypass’, the low [O_BUS_INV_L> output is inverted to a high [B_INV_LOAD> at D24-18 from where it is connected to the second module via the parallel control bus X2/X3 pin 10. It is then re-inverted to a low [I_BUS_INV_L> at D26-10 from where it is connected to D88 on the UPS Logic Board. The parallel control bus thus couples together this signal between the two modules in such a way that both modules will detect the ‘load on bypass’ request when it is generated by either module. This is crucial to avoid a potentially catastrophic situation if one module only were to transfer to bypass while the other remained ‘on inverter’. On the UPS Logic Board, D88 produces a logic high [MNS_L> output at pin 38 provided other inputs to D88 are valid. This is then connected to the Static Switch Driver Board where it activates the static bypass SCR driver circuit.
11pm-c3.fm 5 - Issu e 2 Dated 21/08/97
8-17
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
7200 Series UPS Service Manual
D31 pin 18 [O_BUS_INV_L> is driven low (to request ‘load-on-bypass’) if any of the four conditions described immediately below are valid: “Load-on-bypass” request from system (D31 pin 28 high.)
As described above, this input is overridden in a 1+1 module due to jumper X6-4 being fitted; the following description thus applies only when the board is fitted to a module forming part of a multi-module system. The decision whether to connect the load to the inverter or bypass supplies rests with the UPS Logic Board’s micro-controller system. When it decides to connect the load to the bypass supply, the UPS Logic Board sends a logic high [O_MNS_L_SS> signal to the Parallel Logic Board X1 pin 44. This is inverted to a logic low at D23 pin 11 ( [B_MNS_L_SS>) from where it is connected to the parallel control bus via X2/X3 pin 4, and also reinverted at D26 pin 8 to provide a logic high [MNS_L_SS> input to D31 pin 28. Note 1: the [O_MNS_L_SS> signal also inhibits the ‘load on inverter’ request from within D31 as described earlier. Note 2: due to the fact that the ‘load-on-bypass’ command from the UPS Logic Board is connected to the parallel control bus ( [B_MNS_L_SS>), it affects both modules when either one of them is calling for load-on-bypass. UPS Logic Board not commanding ‘load on inverter’ (D31 pin 25 low.)
D31 pin 25 input is connected to the [INV_L> signal applied to X1 pin 52 and is logic low when the UPS Logic Board is not commanding the Static Switch Driver Board to close the output contactor – i.e. not commanding ‘load-oninverter’. Module synchronisation invalid (D31 pin 7 low.)
This input is driven low when the [RIP> output from D31 pin 21 is high, which occurs when there is a sync error between the modules or bypass sup ply. Also used by the ‘load on inverter’ request signal [C_L_INV> described above (See paragraph 2.3.2.1). In practice this input is normally effective only while the module is being started, and is unlikely to appear once the modules have achieved initial synchronisation. When the TEST mode jumper X6-8 is made (D31-43=low) D31-21 is held permanently high, which allows the load transfer circuit to be tested while the module is isolated from the load by means of opening the output switch. Output contactor auxiliary (D31 pin 34 high).
The [N_AUX_CONT> input to D31-34 is controlled by the UPS Logic Board processor system and is driven high when the output contactor auxiliary contacts are open.
8-18
11pm-c3.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
Section 8:
2.4
Frequency synchroni sation princi ples
2.4.1
Introduction When two UPS modules are operating with their outputs connected in parallel, such as in the case of a ‘1+1’ system, it is of paramount importance that their out puts are synchronised in both phase and frequency to prevent large, damaging, circulating currents appearing. Not only must the two modules be synchronised to each other, but they must also be synchronised to the bypass supply in order to allow a no-break transfer to take place between the UPS and bypass supplies when called for. The system synchronisation control circuitry is therefore necessarily complex. This section begins by providing a f airly detailed overview of the frequency control and synchronisation principles and continues with a full description of the major signals and components employed by this function
2.4.1.1
Inverter frequency contr ol – overview
Figure 8-5: Frequency control block diagram X7
X2/ X3
Parallel Logic Board
X1
K1/K2 54
54
53
53
-
[FRQ_SYN>
6
33 3 14
45
48 m e t s y S r e l l o r t n o C o r c i M
55
45
48
55
[O_MNS _D_SS>
25
[O_MNS _SYN_OK>
8
[F_IN>
[FRQ_REF>
D30 ASIC
D29 (PLL)
FRQ_PAR>
-
[FRQ_OSC>
31
13 [PH_COM_2>
5 GVCO [SYN_INT>
[FRQ_ MNS>
-
11
[FRQ_PAR>
P a r a l l e l S y n c B u s
X2 [F_IN>
15
(Bypass Frequency Single module) X7
X1 [BACK>
34
34
[INV_F>
32
32
Select 50/60Hz Base Frequency
[SYNC>
UPS Logic Board
[BACK>
[INV_F> Master Oscillator
40
40
[SYNC>
44
27
D1 (Divider)
Osc O/P
Reference Sinewave Generator
Clk 14
D6 (PLL)
3
Inverter Logic Board
In each module the inverter frequency is controlled directly by the ‘master oscillator’ section of the Inverter Logic Board. As shown in Figure 8-5, the ‘master oscillator’ comprises a phase-locked-loop (PLL) integrated circuit (D6) and a frequency divider (D1), both of which are controlled by the UPS Logic Board micro-control system. The nominal 50/60 Hz oscillator output from D1 pin 27 controls the reference sinewave generator circuits and thus controls the inverter operating frequency.
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
8-19
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
In practice, the VCO section of D6 clocks D1 which divides the clock pulses by a factor determined by the [INV_F> signal to D1 pin 44. This input thus determines whether the master oscillator operates at a base frequency of 50Hz or 60 Hz, as programmed into the UPS Logic Board micro controller system. The phase comparator section of the P LL (D6) compares the oscillator output (pin 3) with a frequency reference signal ([SYNC> pin 14) which is again supplied by the UPS Logic Board micro controller s ystem. Any detected phase error between these two signals will amend the VCO output to the frequency divider which has the effect of correcting the oscillator output frequency and make it track the [SYNC> reference frequency. Thus the [SYNC> signal indirectly determines the inverter frequency through its effect on the ‘master oscillator’. Note that the UPS Logic Board also monitors the ‘master oscillator’ frequency via the [BACK> signal connected via X1 in 34. Sync operation in a ‘single-module’ system’
As explained in the Inverter Logic Board detailed description, in the case of a single-module system the [SYNC> reference signal is made to track a bypass frequency signal [F_IN> which is derived from the bypass R-phase supply via X2 pin 15. Such tracking is performed in software by comparing [F_IN> with [BACK> and adjusting the [SYNC> reference frequency accordingly. Thus in the simple ‘singlemodule’ the ‘master oscillator’ effectively functions within two nested phaselocked loops; the outer one being software controlled and the other being part of the ‘master oscillator’ itself. Sync operation in a ‘1+1’ system’
In a ‘1+1’ system, the Inverter Logic Board’s ‘master oscillator’ functions in the same manner as for a ‘single-module’ system; however, due to the complex parallel-operating requirements, the [SYNC> reference signal is made to track the [FRQ_SYN> output of the ‘Governing Voltage Controlled Oscillator’ (GVCO) on the Parallel Logic Board, rather than the bypass frequency directly. The reason for adding this extra layer of complexity to the s ynchronisation regime is that it allows the GVCO outputs from both modules to be directly coupled together via the parallel control bus and thereby ensure that the [SYNC> reference signals are locked together in both modules. 2.4.1.2
Basic GVCO sync princip les on module start-up
As shown in Figure 8-5, the GVCO is synchronised to the [FRQ_REF> signal produced at D30 pin 31 via a phase-locked-loop (PLL) circuit (D29). The phase detector section of the PLL detects any phase difference between the [FRQ_REF> signal (D29-14) and the GVCO [FRQ_SYN> output (D29-3), and produces a frequency correction signal ( [PH_COM_2>) which makes the GVCO track the [FRQ_REF> signal frequency. The [FRQ_REF> signal itself can be derived from one of two sources – i.e. to the ‘bypass frequency’ [F_IN> or the ‘parallel sync bus frequency’ [FRQ_PAR>, as determined by the ‘sync-source selector’ circuit within D30. Alternatively, if neither of these signals are present, the PLL can be disabled and the GVCO made to operate at its base frequency (i.e. 50/60Hz). The ‘selected’ sync source depends on whether or not the bypass supply is available and the sequence in which the modules are started. A brief description of the various options is given below:
8-20
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
Bypass supply present & first module to be started
When the first module is started, the ‘sync source selector’ circuit within D30 connects the bypass frequency signal [F_IN> present at D30 pin 5 through to D30 pin 31 ( [FRQ_REF>). Thus, due to the action of the PLL described above, in this situation the GVCO synchronises the bypass mains frequency. When the UPS Logic Board micro controller system detects that the Inverter Logic Board has gained internal synchronism (i.e. the Inverter Logic Board’s ‘master oscillator’ PLL is phase-locked) its sends a logic high [O_MNS_SYN_OK> signal to D30 pin 18 which energises the VCO-in-loop relay (K1/K2). Note; for reasons of clarity the relay energising circuit is not shown in Figure 8-5. This relay has several contacts, which are described in detail later: however, the primary contact, shown in the block diagram, connects the GVCO [FRQ_PAR> output to the parallel ‘sync bus’. This in effect connects the GVCO output of the first module to be started to the corresponding point (X2/X3 pin 11) in the second module (which is not yet running). To summarize the circuit action; at the end of the start-up sequence of the first module: • •
•
its GVCO is synchronised to the bypass supply. its Inverter Logic Board master oscillator is synchronised to the GVCO output (therefore the inverter is also indirectly synchronised to the bypass supply). the VCO-in-loop relay is energised and the GVCO output is placed onto the parallel sync bus.
Bypass supply present & second module to be started
When the second module is started, its ‘sync s ource selector’ within D30 initially connects its [FRQ_REF> output (D30-31) to the ‘parallel sync bus’ frequency reference signal [FRQ_PAR> (D30-6). Thus the action of the PLL phase comparator effectively synchronises the GVCO of the second module to track the parallel sync bus frequency (which is in fact derived from the GVCO output from the first module). This condition can be looked upon at as being a ‘master/sla ve’ situation; whereby the GVCO of the on-coming module is slaved to that of the module already running. A ‘sync bus comparator’ circuit within D30 compares the local GVCO’s [FRQ_SYN> output with the ‘parallel sync bus’ signal ( [FRQ_PAR> from the first module), and detects when the local (slave) GVCO is fully synchronised to the ‘parallel sync bus’ (master). Notice that this comparator actually monitors the frequency at either side of the ‘VCO-in-loop’ relay contact – which is still open in the second module at this time. When the ‘sync bus comparator’ detects that the local GVCO is properly synchronised and UPS Logic Board micro controller system detects that the Inverter Logic Board has achieved ‘internal sync’ (i.e. a logic high [O_MNS_SYN_OK> signal to D30 pin 8), D30 will energise the ‘VCO-in-loop relay’ (K1/K2) in the second module. This has two major affects: 1. It connects the second module’s GVCO output to the sync bus in parallel with the existing GVCO signal from the first module; thus ensuring that both GVCOs remain fully synchronised from this point onwards.
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
8-21
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
2. It makes the ‘sync source selector logic’ within D30 now select the bypass frequency [F_IN> as the sync reference source ( [FRQ_REF>) instead of the ‘parallel sync bus’ [FRQ_PAR> signal. This means that the local GVCO now tracks the bypass supply frequency directly and is no longer seen as being ‘slaved’ to the first module but is in fact acting as a ‘master GCVO’ in its own right. To summarize the circuit action; at the end of the start-up sequence of the second module: • •
the GVCO of the first module is synchronised to the bypass frequency. the GVCO of the second module is also synchronised to the bypass frequency. • the VCO-in-loop relay is energised in both modules, connecting the out puts from both GVCOs together via the parallel sync bus. Starting a module while the bypass supply is missing
On start-up, if the bypass supply is missing, D30 produces an ‘internal sync’ command signal ([SYN_INT>) which inhibits the GVCO synchronisation circuit, and forces it to operate at its ‘base frequency’ (i.e. 50/60Hz). In the first module to be started, the ‘VCO-in-loop’ relay (K1/K2) will be energised when the UPS Logic Board micro controller system detects that the Inverter Logic Board has achieved ‘internal sync’ (i.e. a logic high [O_MNS_SYN_OK> signal to D30 pin 8). This then places the GVCO output (still operating at its base frequency) onto the ‘parallel sync bus’ in the same way as described on the previous pages. When the second module is started it operates in its ‘slave’ mode, as before, and initially synchronises to the ‘parallel sync bus’ (which is at the base frequency of the first module’s GVCO). However, once the ‘sync bus comparator’ within D30 detects synchronism between the local GVCO and t he parallel sync bus, it will energise the ‘VCO-in-loop’ relay whereupon the module changes over from ‘slave’ to ‘master’ mode. This situation now presents a problem which must be overcome. That is, both modules are now operating independently at their base frequency yet connected together via the parallel sync bus; and no matter how closely the two GVCOs are matched, their base frequencies are certain to drift apart and thus cause a non-synchronous condition. This potential problem is overcome by a s econd parallel sync bus line, (not shown in Figure 8-5), which connects together the integrator sections of both GVCOs via a second contact of the ‘VCO-in-loop’ relay. This absolutely locks together the GVCOs and ensures they both operate at exactly the same frequency – i.e. act as one. This is explained in more detail in the GVCO functional description below. Note: in practice they will adopt the frequency of the fastest running oscillator. If either module detects that the bypass supply becomes available, the ‘sync source selector’ within D30 will remove the GVCO inhibit and connect the bypass [F_IN> signal through to both modules. Under these circumstances both GVCOs, acting as one, remain fully synchronised together while they seek and then track the bypass frequency.
8-22
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
2.4.2
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
GVCO Detailed descrip tio n of operation Figure 8-6: Governing VCO Block Diagram Sync Inhibit from D30
[FRQ_SYN> [SYN_INT>
[PH_COM_2>
[FRQ_PAR>
Angle Regulator
Integrator
Comparator (Schmitt)
[FRQ_OSC>
-
K1
X2/ X3 11
From PLL K2 [C_P>
Frequency correction signal
Reference Voltage
30
P a r a l l e l S y n c B u s
VCO-in-loop relays
R18/ R20
Figure 8-6 illustrates a detailed block diagram of the GVCO block shown in Figure 8-5 complete with its major input/output signal annotations. The complete circuit is shown on page 2 of the circuit diagram. The above diagram shows that the GCVO comprises four functional sub-blocks; namely, the ‘angle regulator’, ‘reference voltage’, ‘integrator’ and ‘comparator’. Overview description
Basically, the oscillator function is satisfied by the integrator and comparator blocks – i.e. the integrator provides the comparator with an ramp signal which causes the comparator output ( [FRQ_OSC>) to switch logic states when the ramp reaches the comparator threshold. This is then fed back to the integrator ([FRQ_SYN> ) making the integrator ramp in the opposite direction. Once again when the ramp reaches the comparator’s threshold the comparator output ([FRQ_OSC>) switches back to its original state and the integrator ramp is made to reverse once more. This sequence of events is regenerative and leads to a square waveform at [FRQ_OSC> and a triangular waveform at the integrator out put. The oscillator frequency is determined by the integrator’s ramp-rate – i.e. if the ramp rate is increased, it takes less time for the comparator to reach its switching threshold which results in an increased frequency. The ramp rate is voltage-controlled by the output of the ‘reference voltage’ block which, in the a bsence of any synchronising signal, is set by R18/R20 to produce an oscillator output of 50/ 60Hz – this is described as the GVCO “base frequency”. When the GVCO is synchronised to a reference frequency (e.g. bypass supply) an additional ‘correction’ voltage is superimposed upon the reference voltage which modifies the GVCO frequency and makes it track the desired frequency reference. The ‘angle regulator’ circuit provides signal conditioning to the correction voltage ([PH_COMP_2>), which is produced by the phase comparator section of PLL D29 (See Figure 8-5), to control its slew-rate etc. Each of the sub-blocks mentioned are described in more detail below.
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
8-23
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
Reference voltage
The ‘reference voltage’ circuit comprises a three-terminal regulator (N12) and four sections of N8. N12 provides a stable +2.5V at its cathode. This is connected to N8a/b via varia ble resistor R18, and to N8c/d via R20. Considering N8c/d; N8c inverts the +2.5V stabilised voltage such that a negative reference voltage appears at D22 pin 3, and this is again inverted by N8d (unity gain) which provides a positive voltage at D22 pin 5. R20 should be adjusted for -4V at D22-3 and +4V at D22-5. N8a/b operate in a similar manner to provide positive and negative reference voltages to D22 pins 1 and 2 respectively – calibration of R18 is described later. Integrator & Comparator
These two sub-blocks are so inter-dependant that their operation is best described together. The integrator comprises N7a-c and the comparator N7d The circuits’ operation is best understood by considering one cycle of its operating sequence, beginning with the analogue switches in their states shown in the diagram – as follows: 1. The negative reference voltage on IC22 pin 2 passes through IC29 and is inverted to a positive voltage at N7a pin 1, which charges C76 via R119. The output from N7b follows the capacitor voltage and therefore ramps in a positive direction. 2. N7d compares the positive-ramping signal from N7b pin 7 with the positive threshold present on IC22 pin 4 (set by R20). 3. When the positive-going ramp on N7d pin 12 rises above the positive threshold on pin 13 (which is set by R20 and applied through D22 pins 5-4), its out put pin 14 ( [FRQ_OSC>) switches from logic low to high, with the following effects: a) It drives D23-14 low (sheet 4) which is connected to the parallel sync bus via X2/X3 pin 11 ( [B_FRQ_PAR>) provided the VCO-in-loop relay K1 is closed. If K1 is closed the [B_FRQ_PAR> signal is also inverted to a high at D26-2 ( [F_PAR>) and fed to D30 pin 6 (sheet 1) from where it is connected to the internal ‘sync bus comparator’. Note: [F_PAR> is also fed to the UPS Logic Board micro controller system via X1-54 (sheet 4). b) The low from D23-14 is inverted to a high at D25-12 ( [FRQ_SYN>) which is fed back to the UPS Logic Board micro controller system (X7-53) as the frequency reference pulse to which the Inverter Logic Board’s master oscillator is ultimately synchronised. c) The high [FRQ_SYN> at D25-12 is also fed to D30 pin 33 from where it is connected to the internal ‘sync bus comparator’. d) Finally, the high [FRQ_SYN> at D25-12 is connected to the control gate of solid-state switches D22 pins 9 & 10, which makes the switches changeover from their state shown on the diagram. 4. With solid state switches D22 in their new positions, N7a pin 1 now switches low and discharges C76 through R119. 5. The output from N7b pin 7 follows the capacitor discharge and thus now ramps in a negative direction.
8-24
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
6. When the negative-going ramp on IC16 pin 12 falls below the negative threshold now applied to pin 13 (which is once again set by R20 but now applied through D22 pins 3-4) the [FRQ_OSC> output at N7d pin 14 switches from a logic high to logic low. 7. This reverses the signals described in 3a to 3d above, which now revert to their original logic state. This includes the control gate signals to D22 pins 9 & 10, which now open and cause the above sequence to be repeated.
Frequency calibration. The above sequence shows that the circuit is self oscillating at a rate determined by the voltages set by R18 and R20 as these affect the ramp rate of the integrator and the comparator’s switching threshold. Calibrate R18 and R20 should be calibrated to obtain the GVCO base frequency as follows: 1. Ensure there are no external sync sources (turn off bypass supply). 2. Adjust R20 to obtain 4.0Vdc at test point X8 pin 3. 3. If necessary adjust R18 to obtain 50Hz (60Hz) at test point X8 pin 2. Note: jumper X7 shunts R108, which is in R18’s resistor chin, and should be positioned 2-3 (open) when operating at 50Hz and 1-2 (closed) at 60Hz.
Integrator phase locking. In the overview description of the frequency synchronisation principles it was stated that the GVCO will operate at its ‘base frequency’ if the bypass supply is unavailable. It also explained that under these circumstances the GVCO integrator sections were locked together between the two modules to ensure that both GVCOs adopt a common frequency and phase. In practice, this is achieved by a set of the VCO-in-loop relay contacts (K2) which directly connect the integrator outputs together on both modules when the re lays are energised. With reference to the circuit diagram, the points in question are annotated and on page 2, which are connected to the parallel control bus X2/X3 pins 29 & 30 when K2 is closed (see sheet 4). The effectively connects together the top of the integrator capacitors (C76) in both modules which e nsures that the integrators in both modules change direction simultaneously – thereby locking the oscillators together absolutely once the VCO -in-loop relay has closed. Angle Regulator
The ‘angle regulator’ circuit integrates the [PH_COM_2> frequency error signal produced by the PLL D29, to provide the GVCO with a suitable frequency correction signal to keep it synchronised to the selected sync source. The frequency correction signal is applied to N8a, via R104, where it is added to the reference voltage set by R18. In this way the correction signal is able to modify the integrator ramp-rate, and thereby modify the GVCO output frequency in order to synchronise the GVCO to the bypass (or parallel sync bus) frequency. The correction signal takes the form of an analogue voltage which goes positive to increase the GVCO frequency and vice-versa. Relating this to the diagram (sheet 1), the [PH_COM_2> error signal produced at D29 pin 13 takes the form of a series of positive or negative going pulses of varying width – depending on the polarity and magnitude of the detected phase e rror. These pulses are converted to an analogue voltage by a complex 4-pole filter (sheet 2) comprising N9a, D22 (normally made 12 to 14), N10a, IN10b, N10c, and N10d. N8a ultimately sums the correction signal (via R104) with the reference voltage set by R18.
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
8-25
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
The correction signal is inhibited when the bypass supply is unavailable. This is achieved by the [SYN_INT> output from D30 pin 29 which goes high if the bypass is missing (or out of limits). This energises D22 control gate (pin 11) which disconnects the [PH_COM_2> from the filter input and replaces it with a 0V level referenced through R84. Under these conditions the correction signal emerging from N10d pin 14 ramps back to 0V which therefore applies zero frequency correction to the GVCO which allows it to operate at its ‘base frequency’ – as set by R18.
2.4.3
PLL Phase Comp arator (D29) This circuit is based on the phase-comparator section of a type 4046 phase locked loop integrated circuit which monitors the GVCO output waveform [FRQ_SYN> at pin 3 and the selected sync source waveform [FRQ_REF> at pin 14. If these waveforms are unsynchronised the [PH_COM_2> output at pin 13 exhibits either a positive or negative going pulse of a width proportional to the detected phase difference. A positive pulse is produced if [FRQ_SYN> leads [FRQ_REF> (i.e. the GVCO frequency is the greater) and vice versa. The [PH_COM_2> output pulses are integrated by the ‘angle regulator’ circuit and then applied to the GVCO as an analogue error correction signal which modifies the GVCO operating frequency. Thus if the PLL phase comparator detects an error it ultimately modifies the GVCO frequency to make it track the [FRQ_REF> reference frequency.
2.4.4
D30 Parallel Contro l Functi ons Figure 8-7: D30 Internal Block Diagram
[MNS_SYN_OK>
[38] [T> [37] [SYN_PAR_KO> [PAR_SYN> (Reset) [V-AUX> [BLK_INV> [INV_OK> [SYN_PAR> [FRQ_SYN>
[FRQ_PAR>
18
Internal Sync Logic
41 40
29
14 VCO-in-loop Relay Control
20
38
[O_MNS_SYN_OK> [F_IN> [MNS_D_SS>
[O_PAR_SYN>
[CON_PAR> [41]
4 34 39 27 33
6
Sync Bus Comparator
37
31
[11] [I_FRQ_MNS>
[SYN_INT>
28
Sync Source Selector
27
[PH_COM> [40]
[FRQ_REF>
[SYN_PAR>
8 5 25
Bypass Validation
11
[O_FRQ_MNS> [28]
D30 is an ASIC device containing numerous static logic gates which serve several functions associated with the frequency synchronisation control; most of which have been mentioned earlier. For reasons of clarity these are shown in block diagram form in Figure 8-7, although in reality many of these blocks are to some extent interactive, and share some of the input signals shown.
8-26
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
2.4.4.1
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
Byp ass valid ation
This block validates the bypass frequency signal [F_IN> to determine if it is suita ble for use by the sync source selector circuit. The bypass frequency sense signal [F_IN> is connected to D30-5 and is allowed through D30, to appear at D30-11 as [O_FRQ_MNS> provided both the following conditions are satisfied: 1. The Inverter Logic Board’s master oscillator is phase-locked. Sensed by a logic low [O_MNS_SYN_OK> input to D30-8. 2. The UPS Logic Board micro controller system has determined that the bypass supply is within the programmed voltage and frequency limitation. Sensed by a logic high [MNS_D_SS> input to D30-25. Note: in each case, these input signals are coupled to both modules via the parallel control bus via X2/3 pins 7 & 5 respectively; therefore the frequency validation function of D30 will be affected in both modules if an invalid condition is present in either module.
Provided the above conditions are satisfactory, the [O_FRQ_MNS> bypass frequency signal output at D30-11 is inverted by D23-13 and reinverted by D26-4 and then reapplied to D30-28 as [I_FRQ_MNS> from where it is internally connected to the sync source selector circuit. The reason for this double-inversion is to allow the signal at D23-13 to be coupled to the second module via the parallel control bus via X2/X3 in 15. Thus, once again the [I_FRQ_MNS> input to D30-28 is applied to both modules even if the bypass frequency is being sensed by one module only. 2.4.4.2
Sync sou rce selecto r
This circuit determines whether the bypass frequency signal [I_FRQ_MNS> (pin 28) or parallel sync bus signal [FRQ_PAR> (pin 6) is allowed through D30 to appear at pin 31 as the frequency reference signal [FRQ_REF>. Whichever is the case, the [FRQ_REF> signal produced at D30-31 provides the ma in frequency reference signal to the PLL phase comparator and therefore dictates the GVCO operating frequency. Under normal circumstances the circuit selects the bypass frequency reference signal [I_FRQ_MNS> except for the case where the module is the s econd to be started, whereupon it momentarily selects the parallel sync bus signal [FRQ_PAR> until it becomes fully synchronised – i.e. during the period of “slave” operation (See paragraph 2.4.1.2). A second output from the sync source selector, at D30-27, goes high when the ‘parallel sync bus’ is the selected frequency reference and illuminates led H3. Under normal circumstances, LED H3 should therefore illuminate briefly when the second module is started and then remain extinguished while the module is synchronised to the bypass supply. The external conditions necessary to select the parallel sync bus as the reference signal, and illuminate H3, are as follows ( all conditions must be valid ): 1. External reset signal is not applied (D30-4 = low). 2. VCO-in-loop relay K1 is closed in the first module (D30-4 = low). 3. VCO-in-loop relay K1 is open in the local module (D30-14 = low). 4. [BLK_INV> signal to D30-34 = high (no inverter problem).
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
8-27
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
5. [INV_OK> signal to D30-39 = high (no inverter problem). Note: once the VCO in loop relay becomes energised in the local module, the [PAR_INV> signal from D28-4 to D30-26 goes high and overrides the effects of the [INV_OK> signal within D30. 2.4.4.3
Sync bus com parato r
The sync bus comparator circuit monitors the frequency of the local GVCO output ([FRQ_SYN> applied to D30-33) and the parallel sync bus ( [FRQ_PAR> ap plied to D30-6) and drives the [PH_COMP> output at D30 pin 37 low when the two monitored signals are in-phase. This output is inverted and debounced by D27 and its associated R-C components, and then fed back to D30 pin 40 as a logic high [SYN_PAR_KO> signal – which is then internally connected to the VCO-in-loop relay control circuit. In practice the two monitored signals are taken from either side of the VCO-inloop relay contacts and therefore indicate when it is safe to close the relay (K1/ K2) from a parallelling viewpoint. 2.4.4.4
VCO-in-lo op relay con tro l
This circuit determines when it is safe to close the VCO-in-loop relay (K1/K2), by driving [O_PAR_SYN> (D30-14) high, and thus connect the GVCO output to the parallel sync bus. The circuit’s internal logic is affected by the following signals: • • • •
External reset [V_AUX> at D30-4. [PAR_SYN> at D30-20. [BLK_INV> at D30-34 [INV_OK> at D30-39 Note: once the VCO in loop relay becomes energised in the local module, the [PAR_INV> signal from D28-4 to D30-26 goes high and overrides the effects of the [INV_OK> signal within D30. • [SYN_PAR_KO> at D30-40 The logic state (and sequence) of these signals required to energise K1 depends on whether the module in question is the first or second module to be started, as described below: First module to be started
1. As there is no module yet connected to the parallel sync bus, the [PAR_SYN> input to pin 20 is high. 2. Provided there is no problem with the inverter control, the [INV_OK> and [SYN_PAR_KO> status signals to pins 34 and 39 are both high once the inverter has run-up. 3. The above conditions drives the [CON_PAR> output on pin 38 high, which is then inverted, debounced and delayed by R151/C107/D27, and applied to pin 41 as a logic low ( [T1>). 4. Provided there is no reset applied to pin 4 (low) and the inverter status signals to pins 34 and 39 are still both valid (high), the logic low [T1> input to pin 41 will drive pin 14 high and energise the VCO-in-loop relay (K1/K2) via [O_PAR_SYN> and one section of D24 (test point X12-1 = low). 5. When the VCO-in-loop relay energises:
8-28
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
a) It connects the GVCO (and integrator) output to the parallel sync bus. b) A further contact closes and places a logic low signal to D30 pin 20 in both modules (via the parallel control bus). This has no effect on the current module, but will inform the second module (when it is started) that the first module is already running. 6. In addition to energising the VCO-in-loop relays (K1/K2), the [O_PAR_SYN> output from D30-14 also signals the “parallel” status to D31-24 which drives D31-21 low (provide not in test mode). (See paragraph 2.3.2.1). One effect of this is that D31 applies a logic high [PAR_INV> signal to D30 pin 26 which overrides the [INV_OK> signal. 7. The [O_PAR_SYN> output at pin 14 will remain high, holding-on relay K1/K2 unless one of the following conditions occur: a) The reset signal is applied to D30 pin 4 (high). b) The [BLK_INV> signal to pin 39 goes to an invalid state (low). c) Both the [INV_OK> signal to pin 34 and the [PAR_INV> signal to pin 26 go simultaneously low d) The sync bus comparator detects a problem – [SYN_BUS_KO> to pin 40 goes low. This is unlikely to occur in the first module unless K1 is faulty, or the is a printed circuit board fault. Second module to be started
1. As the first module is already running and its VCO-in-loop relay is closed, connecting its GVCO output to the parallel sync bus, the [PAR_SYN> input to pin 20 is low. 2. Provided there is no problem with the inverter control, the [INV_OK> and [SYN_PAR_KO> status signals to pins 34 and 39 are both high. 3. When the sync bus comparator detects that the local GVCO and the parallel synch bus are in-phase, the [SYN_PAR_KO> input to pin 40 will go high. 4. The above conditions drives the [CON_PAR> output on pin 38 high, which is then inverted, debounced and delayed by R151/C107/D27, and applied to pin 41 as a logic low ( [T1>). 5. Provided there is no reset applied to pin 4 (low) and the inverter status signals to pins 34 and 39 are still both valid (high), the logic low [T1> input to pin 41 will drive pin 14 high and energise the VCO-in-loop relay (K1/K2) via [O_PAR_SYN> and one section of D24 (test point X12-1 = low). 6. When the VCO-in-loop relay energises, the GVCO output is connected to the parallel sync bus via one contact of K1. A second K1 contact closes which reinforces the logic low signal to D30 pin 20 i n both modules (via the parallel control bus). 7. The [O_PAR_SYN> output at pin 14 will remain high to hold on relay K1/K2 unless the conditions described above with respect to the first module occur. 2.4.4.5
Internal Sync Log ic
This logic block is responsible for detecting when it is unsafe to synchronise the GCVO to the [FRQ_REF> signal, but instead make it operate at its ‘base’ frequency (See paragraph 2.4.2).
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
8-29
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
The [SYN_INT> output at pin 29 goes high to invoke the GVCO base-frequency operation (also described as “internal sync”), and can be brought about by any one of the following four logic combinations: Reset
1. If an external reset [V_AUX> signal (high) is applied to pin 4. Note that this is sourced from the software reset circuit on the UPS Logic Board. Inverter problem
2. If either of the inverter status signals to D30 pins 34 and 39 are invalid (low), while the local module is not connected to the parallel sync bus (pin 14 low) but the second module is connected to the parallel sync bus (pin 20 low). Note: if such an inverter problem occurs at D30-34 it will trip the local module’s VCO-in-loop relay, as described above, therefore driving pin 14 low automatically. Inverter Logic Board loses internal sync
3. If the Inverter Logic Board master oscillator loses sync ([MNS_SYN_OK> pin 18 high) when either module is connected to the parallel sync bus ([PAR_SYN> pin 20 low OR [O_PAR_SYN> pin 14 high). Note that if such a situation occurs it should affect both modules in an identical manner as both are connected via the parallel control bus via X2/X3 pin 7 (low).
8-30
11pm-c4.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
Section 8:
2.5
Output curr ent sharin g
2.5.1
Introduction Figure 8-8: Simplified current-sharing circuit (R-phase) R1
X1 CT Neutral 14 LOCAL 15 R-ph current
R1 R1
2 N1a
R42 R30
1
R36
9
3
X1 Current
N1c
R48
8
10
DV-A
R21 X2/3 Current sharing 27 RL-K3/4 bus
3 2
N4a
1
R11
5 6
R11
D21
N1b
12 7
R1
R31 13
14
sharing error signal 20 [ DV-A > To Inverter Logic Board
To Selective shutdown circuit
(via UPS Logic Board)
11 “0”
ABIL_RIP
The current sharing circuit is shown on sheet 3 of the circuit diagram. In a ‘1+1’system the inverters should share the load current equally when both modules are connected to the critical bus. The current sharing circuit shown above controls this function by comparing the two modules’ currents via a current sharing line of the parallel control bus and generating an error signal if a difference is de tected. The error signal is passed to the Inverter Logic Board where it modifies the local inverter’s output voltage, by up to ±5%, in order to restore a balanced current sharing condition. This action is undertaken on an individual phase basis and an error signal is thus produced for each of the three inverter phases. The following text describes the operation of the R phase current sharing circuit in detail – the other two phases work in an identical manner. Figure 8-8 shows a simplified diagram of the R-phase circuit used in the description.
2.5.2
Current sharin g error detectio n prin cip les The local module’s R phase output current sense signal ( [IO_A>) enters X1 pins 15 (signal) and 14 (neutral) and is buffered by N1a. The ac signal at N1 pin 1 is thus proportional to the current being drawn from the local module, and connected to N1c pin 9, via R30/R36, and also to N4a pin 3, via R21/R24. RL-K3 energises when the [PAR_INV> signal from IC31 pin 7 goes high, which occurs just after the VCO-in-loop relay is energised. RL-K3 contacts connect the local current sense signal passing through R21 onto the parallel control bus at X2/ 3 pin 27. Notice that due to the parallel bus connection, X2/3 pin 27 is connected directly to the corresponding point on the Parallel Logic Board in the second module. Circuit operation when one module only is running
When a module is shut-down (off-line) its RL-K3 is de-energised and solid state switch D21 is open (contacts as shown) – because [ABIL_RIP> is low due to the fact that the inverter output contactor is open. These c onditions force the current sharing error signal [Dv-R> to zero volts, as the current sense signal from N1a is fed to
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
8-31
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
N1c pins 9 and 10 in anti-phase and are self cancelling. Note: R10 and R11 are of equal value (3k9). In a ‘redundant-module’ configured ‘1+1’ system it is permissible to operate on one module only (i.e. with the second module shut down). Under these conditions D21’s contacts change over when the inverter output contactor is closed ([ABIL_RIP> = 1) and the current sense signal at N1a pin 1 is now buffered by N4a and N1b and connected to N1c pin 10 via R31, D21 and R37. However, R31 is of equal value to R30 (6K8), and once again the anti-phase signals applied to IC1c pins 9 and 10 will be of equal magnitude and keep the error signal at 0V. Put simply, under these conditions the lone module attempts to current-share ‘with itself’ and is therefore never in error. Note: In this scenario RL-K3 energises, and connects the current sense signal to the current sharing bus line once the module is synchronised, but this has no affect on the current sharing circuit’s operation at this time as RL-K3 remains open in the second (shut-down) module. Current sharing operating under balanced conditions
When the second module is started, its current sense signal is applied to the current sharing parallel control bus X2/3 pin 27 (via its RL-K3). Assuming that both modules are supplying exactly the same amount of load current, the current sense signal produced by N1a will be of the same amplitude and phase in both modules; therefore there will be no net current flow through R21 in either module and thus no net voltage dropped across it. Figure 8-9: Module 1 X1
Sense Amp
15
N1a
8 Error Amp
1Vac
1 X2/X3
R21 9
N1a
1Vac
1
N1c Dv-R 20
Module 2
RL-K3
10 Unbalanced current
27
X2/X3 1Vac
15
N1c
R21 RL-K3
27
CN1
Sense Amp
9 10
8
20 Dv-R
Error Amp
This is illustrated in Figure 8-9, where a current sense signal of 1Vac is assumed in both modules. Under these conditions the input signals to the error amplifier (N1c) are equal and produce zero [Dv-R> ‘error’ signals to the Inverter Logic Board –these conditions are the same in both modules.
8-32
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
Current sharing operating under unbalanced conditions
Figure 8-10: Module 1 X1
Sense Amp
15
N1a
8 Error Amp
N1a 1
N1c Dv-R 20
Module 2
X2/X3
R21 9
1Vac
2Vac
RL-K3
27
X2/X3 1.5Vac
10 Unbalanced current
15
N1c
R21 RL-K3
27
1
CN1
Sense Amp
9 10
8
20 Dv-R
Error Amp
If the two modules supply different amounts of load current their current sense signals at N1a will be different and there wi ll be a net current flow along the current sharing parallel control bus, resulting in a voltage drop across R21 in each module proportional to the degree of current imbalance. This is depicted in Figure 8-10, which shows the situation where Module 1 is sup plying more current than module 2. In this case the current sharing control bus voltage (1.5Vac) is less than the current sense signal (2Vac) in module 1 but greater than the current sense signal (1Vac) in module 2. In Module 1 the voltage dropped across R1 produces a greater voltage at N1c inverting input with respect to its non-inverting input and the [Dv-R> error signal (X1-20) will be a sinusoidal signal in anti-phase with the current sense signal. In Module 2 however these conditions are reversed, w ith the greater voltage being applied to the non-inverting input of N1c, resulting in a [Dv-R> error signal which is in-phase with the current sense signal. The respective [Dv-R> error signals are applied to each module’s Inverter Logic Board; and in this case the signal to Module 1 will cause a reduction of the output voltage and that to Module 2 will cause a corresponding increase – thus restoring a balanced load current condition. Note: the above action is dynamic in operation and in practice the circuit effectively maintains a balanced state, with zero current flowing along the current s haring bus, at all times.
2.5.3
Current-sharin g relay cont rol (K3/K4) Under normal circumstances, relays K3 and K4 are energised and de-energised at the same time as the VCO-in-loop relays (K1/K2); in fact all four relay share a common control signal – i.e. the [O_PAR_SYN> output from D30 pin 14 (see paragraph 2.4.4.4 on page 8-28). The only control difference between these two relay groups is that in the case of the current-sharing relays the [O_PAR_SYN> signal is gated with the TEST mode logic within D31 and the ultimate relay control signal ( [PAR_INV>) is produced at D31 pin 7. [PAR_INV> is driven to a logic high to energise K3/K4 – this is inverted to a logic low at the relay driver D24 pin 13. When the Parallel Logic Board is placed in its TEST mode (D31 in 43 taken low) the [PAR_INV> control signal at D31 pin 7 is forced to a permanent low logic s tate to prevent the current sharing relays being energised. This is required in a redun-
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
8-33
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
dant module system to allow an off-line module to be tested without affecting the current-sharing function of the second (on-line) module.
2.5.4
Selectiv e shut dow n The Selective Shutdown circuit, which is shown on sheet 3 of the circuit diagrams, monitors the current-sharing circuit output signals together with output phase voltage sense signals and detects three types of current-related fault conditions: 1. It detects when the current sharing is in error and calling for the local module to provide an excessive amount of current in comparison to the other module. 2. It detects an excess ‘reverse power’ condition whereby a fault in the local module is causing it to draw current into its output terminals from the other module. 3. It detects an excess ‘forward power’ condition whereby a fault in the local module is causing it to feed current into the output terminals of the other module. Considering the R phase circuit: the current error signal produced at N1c pin 8 ([Dv-A>), described on the previous pages, is fed to N1d pin 13 via R48 where it is summed with a sense signal proportional to the module’s output R-phase voltage ([VO_A>). The ‘VA-proportional’ output from N1d pin 14 is connected to a three-phase full-wave rectifier, along with the corresponding S and T phase signals (V1-V6), which then produces a single VA-related signal across R61 which is proportional to the module’s three phase output. Under balanced conditions the current error signal [Dv-A> is negligible; and the output from N1 pin 14 is directly proportional to the voltage sense signal. Under such circumstances the bridge rectifier produces approximately 4.1V at N5 pin 1.
2.5.4.1
Curren t-shari ng error
If the current sharing function fails to operate correctly and calls for this module to produce an excessive amount of current in comparison to the second module, the [DV-R> [DV-S> [DV-T> signal(s) add to the voltage-related signals and result in an increased output from IC5a pin 1. This is monitored by N5d whose output goes high if N5a pin 1 rises above 5.0V (equivalent to 30% of nominal current sharing imbalance) – i.e. if the module is being asked to produce 30% of nominal load capacity more than the second module. The resulting logic high [IN_SEL> signal flags D31 pin 4 which turns off the inverter and trips the output contactor (see paragraph 2.3.1.1 on page 8-13). Calibration
N5d’s switching threshold is determined by a reference voltage generator (N11) whose output voltage is calibrated by R19. This resistor should be adjusted according to the module’s working voltage to obtain the following dc voltage at the top of R68 (junction with R72): 380V = 5.0 Vdc 400V = 5.26 Vdc 415V = 5.46 Vdc
8-34
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
2.5.4.2
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
Reverse Power detecto r
If the local module’s output voltage suddenly decreases due to an internal fault condition it will begin to take reverse current from the second module. Under these circumstances the current sense signals will be out of phase with, and therefore subtract from, the voltage sense signals. The VA signal at N5a pin 1 will therefore reduce and ultimately fall below the operating threshold of N5c, whose output will in turn go high and invoke the [IN_SEL> shutdown signal with the same results as the current error situation described above. Due to the current imbalance, the current-sharing circuit in the second module will call for it to reduce its output voltage, and the falling voltage sense signals will cancel out the increasing forward current signals. Thus the [IN_SEL> signal is not triggered in the second module and the healthy module will not be tripped offline in a ‘redundant module’ system. However, in a ‘non-redundant’ system the second module will trip of line automatically along with the faulty local module. Calibration
This function shares the same calibration features as the current-sharing error circuit described previously. 2.5.4.3
Forward Power detect or
If the local module’s output voltage suddenly increases due to an internal fault condition it will attempt to supply all the load current and also feed a reverse current into the second module. Under these circumstances, in the local module, the summation of the VA signals at N5 pin 1 triggers the upper level detector N5d and the [IN_SEL> signal is activated in the same manner as described for a ‘currentsharing’ fault. Due to the current imbalance, the current sharing circuit in the second module will call for it to increase its output voltage and the rising voltage sense signals will cancel out the decreasing reverse current signals. Thus the [IN_SEL> signal is not triggered in the second module and the healthy module is not tripped off-line in a ‘redundant module’ system. In a non-redundant system the second module will trip of line automatically along with the faulty local module. However, in a ‘non-redundant’ system the second module will trip of line automatically along with the faulty local module.
2.5.5
On-line mod ule coun ter This circuit, shown on sheet 2 of the circuit diagrams, detects the number of online modules and is used in a ‘redundant system’ to inhibit the selective shutdown circuit within D31 when only one module is on-line – i.e. if only one module is running, and by definition providing all the load current, there is no valid reason to allow its current sharing circuit to produce a selective shutdown and trip the module off-line (see paragraph 2.3.1.1 on page 8-13). When a module is brought on-line, the signal used to energise the VCO-in-loop relays (K1/K2) is also fed to the module counter circuit as [PAR_INV>. This signal goes high when the module is on-line, whereupon it turns on V43 and V42 which provides a current source whatever resistance value is selected by jumpers X5. In a standard configuration X5 jumpers 1/2/3 are made. This in turn causes a voltage rise to the non-inverting input of comparator N9b (pin 5) via R130. is connected to the parallel control bus via X2/3 pin 24, therefore
when both modules are on-line the c urrent passing through the selected resistance doubles, with a corresponding increase to the voltage offered to the comparator.
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
8-35
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
The comparator’s operating threshold is determined by the resistance selected by X4. In a standard 1+1 configuration X4 jumper 1 only is fitted, w hich sets the circuit operation such that [C_N_INV> switches high only when both modules are on line, and is low at all other times. Note: the reason for the additional jumper positions on X4 and X5 is to allow this board to be used in a multi-module system, where up to six modules can co connected in a parallel-operating configuration. Where such a system is used, X4 and X5 permit the minimum number of on-line modules necessary to retain system integrity to be programmed.
2.6
Parallel rectif ier operatio n
2.6.1
Rectifier current -sharing cont rol If a single stand-by battery bank is used by both modules the installation is described as having a ‘common battery’, and in this situation steps are taken to ensure that both modules contribute an equal amount of battery charge current. A current sharing circuit, similar to that used to c ontrol the output current sharing, is employed to ensure that both modules’ rectifiers take an equal amount of input current. Consequently, if the modules’ input currents are equal and their output currents are equal this implies that they are properly sharing the battery charge current. The local module’s input current sense signal ( [I_RECT_T>) enters X1 pin 24 and is buffered by N6a. The signal at N6a pin 1, is then connected to N6b pin 6 and also to N6c pin 10 via R66. If the local module is the only module on-line, as part of a redundant module system, the inputs to N6b pins 5 and 6 wil l cancel each other as they are both obtained from the same source – e.g. pin 6 monitors the current sense signal from N6 pin 1 and pin 5 monitors the same signal via a second buffer (N6c). Under such circumstances the output from N6b pin 7 is zero, which then produces a zero error signal output ( [DB>) at X1 pin 25. X1 pin 25 is connected to the voltage regulation control circuit on the Rectifier Logic Board, via a through connection on the UP S Logic Board, and trims the rectifier voltage as necessary to adjust its input current. Rectifier current sharing is enabled by energising relay K5. This removes the ground inhibit from N6d non-inverting input and also connects the local current sense signal () passing through R66 to the current sharing bus connected to X2/3 pin 26. When the second module is started, its input current sense signal is applied to the parallel control bus X2/3 pin 26 in the same manner as described for the local module. Assuming that both modules are drawing exactly the same amount of input current, there will be no net current flow through R55 in either module, resulting in zero output from IC8b pin 7. If the modules draw different amounts of input current their current sense si gnals differ and there will be a net current flow along the parallel control bus resulting in a volts drop across R66 proportional to the current imbalance in each module. This will be detected by N6c, whose output will increase [DB> in the module drawing less current and decrease [DB> in the other. This processes is continuous and results in close input current sharing between the two modules at all times under normal conditions.
8-36
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Config uration Control Princi ples
Relay K5 control
As mentioned above, relay K5 must be energised in order to activate the rectifier current sharing function; this is achieved by the [O_PAR_REC> output from D30 pin 17 going high. D30 pin 17 is itself controlled by the [PAR_REC> input to D30 pin 32 which is derived from the UPS Logic Board micro controller system and goes high to select parallel rectifier operation – i.e. when the UPS Logic Board is programmed to invoke rectifier current sharing (common battery) it sends a logic high [PAR_REC> signal to D30 pin 32 whose [O_PAR_REC> output then switches high to energise relay K5. This can be overridden by jumper X6-2 which, when made, clamps [O_PAR_REC> to a logic low. X6-2 is used to select ‘parallel’ or ‘non-parallel’ rectifier operation (open for non-parallel operation) and also affects the boost charge and battery test functions as described below.
2.6.2
Boo st charge con trol In a common battery system it is not permissible to have one module operating in the boost charge mode while the other is in float charge, otherwise they will be unable to share the battery charge current. ‘Boost’ charge is requested by the UPS Logic Board’s micro controller system which applies a logic high [O_BST_BAT> input to X1 pin 47. This is connected to the parallel control bus via X2/3 pin 8 ( [B_BST_BAT>), and also to D30 pin 24 ([BST_BAT>). Sending the signal through the parallel control bus thus drives the [BST_BAT> signal high in both modules if either module requests boost charge. When [BST_BAT> goes high it drives D30 pin 16 high, which is then connected back to the UPS Logic Board via X1 pin 35 ( [I_BST_BAT>) to inform the UPS Logic Board that the request has been acknowledged. The UPS Logic Board will then initiate the boost charge mode via appropriate signalling to the Rectifier Logic Board. Therefore, in a parallel rectifier configured system both rectifiers are triggered into the boost mode. If parallel rectifier operation is not required then jumper X6-2, when fitted, will override the boost charge request logic within D30 and clamp the output on D30 pin 16 at logic low. In this situation the signal passed along the parallel control bus will have no effect in either module and the boost mode will be independently controlled for each rectifier.
2.6.3
Battery test con trol In a common battery system it is not permissible to have one module operating in the battery mode without the other, otherwise they will be unable to share the battery charge current. A control mechanism similar to the boost charge circuit described immediately above is therefore used to prevent this from happening. ‘Battery Test’ is requested by the UPS Logic Board’s micro controller system which applies a logic high [O_TST_BAT> input to X1 pin 46. This is connected to the parallel control bus via X2/3 pin 13 ( [B_TST_BAT>), and also to D30 pin 21 ([TST_BAT>). Sending the signal through the parallel control bus thus drives the [TST_BAT> signal high in both modules if either module requests a Battery Test. When [TST_BAT> goes high it drives D30 pin 19 high, which is then connected back to the UPS Logic Board via X1 pin 36 ( [I_TST_BAT>) to inform the UPS Logic Board that the request has been acknowledged. The UPS Logic Board will then initiate the Battery Test via appropriate signalling to the Rectifier Logic Board. Therefore, in a parallel rectifier configured system both rectifiers are triggered into the Test mode.
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
8-37
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - " 1+1" Configu ration Control Princip les
7200 Series UPS Service Manual
If parallel rectifier operation is not required then jumper X6-2, when fitted, will override the Battery Test request logic within D30 and clamp the output on D30 pin 19 at logic low. In this situation the signal passed along the parallel control bus will have no effect in either module and the Battery Test mode will be inde pendently controlled for each rectifier.
2.7
Other Features and fun cti ons
2.7.1
Ribbon cable connection monito r As mentioned on page 8-13, the Parallel Logic Board senses the parallel control bus integrity by monitoring the continuity of the two ribbon cables fitted X2 and X3, which are cross connected between the two modules. The modules’ parallel operation can be maintained if one of these cables becomes disconnected (in which event Led H2 illuminates), but if both cables become disconnected then the Parallel Logic Board demands that the module inverters are shut-down and the load transferred to bypass. Monitoring the cables’ continuity is made possible due to the way that the cables are cross-connected between the two modules; the error detection signals are annotated [A_CON> and [B_CON> (see page 4 of the circuit diagrams). For example, the [A_CON> signal at X2 pin 1 is held at 0V due to the fact that pin 1 of X3 in the second module is grounded – the same principle applies to the [B_CON> signal at X3 pin 2. Thus, the Parallel Logic Board can detect if a ribbon cable is disconnected at either end.
8-38
11pm-c5.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
Section 8:
2.8
Parallel Logic Board circuit operation during start-up When the UPS system is started, there are distinct phases that the module goes through before the load is connected to the inverter(s). These can broadly be described as: •
Initialisation/reset
•
Run-up & inverter synchronisation
•
Connecting to the parallel control bus
•
Load transfer procedure (depending on system redundancy)
These phases are described in detail below and aims to give a full understanding of the system start-up process to facilitate system troubleshooting.
2.8.1
Initialisation/reset When a module is first started, its UPS Logic Board micro-system goes through a power-up reset and initialisation routine which applies a 1-second logic high pulse to X1-42 ([V_AUX>). The effects of this are: 1. D31-5 goes high to reset the ‘selective shutdown’ circuit latch (D31-37 set low and led H1 = off) (See paragraph 2.3.1.1) 2. D30-4 goes high which: a) drives D30-29 ([SYN_INT>) high which forces the GVCO to its ‘internal sync’ mode – (See paragraph 2.4.4.5). b) drives D30-38 & D30-14 low to reset the VCO-in-loop control logic and ensure the VCO-in-loop relays (K1/K2) are de-energised ( [O_PAR_SYN> = low) – (See paragraph 2.4.4.4). 3. D30-14 ([O_PAR_SYN> ) going low is connected to D31-24 where it drives D31-21 ([RIP>) high which is inverted to a logic low [PAR_INV> at D28-4 which then: a) de-energises the current-sharing relays (K3/K4). b) informs the ‘available modules counter’ circuit that the module is off-line. c) places a logic low input to D31-7 which enables the ‘load-on-bypass’ request from D31-18 (low) and disables the ‘load-on-inverter’ request from D31-12 (high) (See paragraph 2.3.2). d) feeds a logic low input to D30-26 which enables the [INV_OK> signal applied to D31-39 within D31.
2.8.2
Inverter run -up and synch ron isatio n 1. Provided the UPS power switches and parallel bus cables are positioned correctly, at the culmination of the reset action D31-19 ( [OFF_INV>) should go low, requesting the inverter to run (See paragraph 2.3.1) 2. If other parameter on the UPS Logic Board are satisfactory, the inverter should now start and its voltage should begin to rise to nominal value; during which time the following events occur: a) [O_MNS_SYN> to D30 pins 8 and 18 go low when the Inverter Logic Board’s master oscillator gains internal sync. The input to pin 8 is associ-
11pm-c6.fm 5 - Issu e 2 Dated 21/08/97
8-39
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
7200 Series UPS Service Manual
ated with the bypass frequency validation circuit (See paragraph 2.4.4.1) and the input to pin 18 with the GVCO ‘internal sync’ logic – although [SYN_INT> is still high, requesting “internal sync” at this time due to the still logic low [INV_OK> input to D30 pin 34 (See paragraph 2.4.4.5). b) The [BLK_INV> input to D30 pin 34 is high, indicating that there is no fault detected on the Inverter Logic Board – once again this has no effect on D31 internal operation due to the logic low [INV_OK> input to D30 pin 34.
2.8.3
Connectin g to the parallel cont rol bus When the inverter output voltage rises to its nominal value the [INV_OK> input to D30 pin 39 will go high, and initiate the following sequence of events: 1. The [SYN_INT> output from D30-29 will go low to enable the GVCO’s ‘angle regulator’ circuit, allowing the GVCO to synchronise to the selected [FRQ_REF> signal (See paragraph 2.4.4.5). 2. Provided the synchronisation functions are satisfied, the VCO-in-loop relays (K1/K2) will be energised by D30-14 ( [O_PAR_SYN>) going high. The synchronisation functions vary according to whether the module is the “first” or “second” module to be started and is described in details in paragraph 2.4.4.4. If K1/K2 fail to energise at this stage it is recommended that you read and thoroughly understand paragraph 2.4.4.4 before going further. 3. D30-14 ([O_PAR_SYN>) going high is connected to D31-24 where it drives D31-21 ([RIP>) low which is inverted to a logic high [PAR_INV> at D28-4 which then: a) energises the current-sharing relays (K3/K4). b) feeds a logic high input to D30-26 which disables the effects of the [INV_OK> input to D31-39 within D31. c) informs the ‘available modules counter’ circuit that the module is connected to the parallel control bus and available for use. d) places a logic high [PAR_INV> input to D31-7 which disables the ‘load-on bypass’ request from D31-18 (now switches high) and enables the ‘loadon-inverter’ request from D31-12 (although D31-12 is not driven low due to this signal at this point – see below).
2.8.4
Load transfer to inverter The point at which the load is transferred to the inverter depends on whether the Parallel Logic Board is configured for a ‘redundant’ or ‘non-redundant’ system operation – i.e. jumper X6-3 closed = ‘redundant’ configuration and X6-1 closed = ‘non-redundant’. The difference between these configuration is that in a ‘redundant’ system the load can be allowed to transfer to inverter when only one module is running, but in a ‘non-redundant’ system both modules have to be running before the load is allowed to transfer. The effects of the configuration on the transfer circuit operation are described below. ‘Redundant’ system transfer operation
1. In a ‘redundant module’ configuration the ‘available module counter’ circuit is configured such that its [C_N_INV> output switches high when only one module is connected to the parallel control bus. Thus, in such a system this
8-40
11pm-c6.fm 5 - Issu e 2 Dated 21/08/97
7200 Series UPS Service Manual
SECTION 8 - "1+1" Configured UPS System Control CHAPTER 2 - Parallel Logic Bo ard
occurs at this point in the start-up sequence. 2. The effects of the logic high [C_N_INV> input to D31-27, coupled with the logic high [PAR_INV> input to D31-7 now make D31-12 ( [C_L_INV>) switch low, sending a ‘load-on-inverter’ request to the UPS Logic Board. 3. If the UPS Logic Board conditions are normal it should now send a ‘transfer to inverter’ command to the Static Switch Driver Board which will closed the inverter output contactor and turn off the static bypass SCRs. ‘Non-redundant’ system transfer operation
4. In a ‘non-redundant’ system two sets of signals, each of which detects the availability of both modules on the parallel control bus, are required by the transfer control logic before the load is allowed to transfer to the inverter. a) In a ‘non-redundant module’ configuration the ‘available module counter’ circuit is configured such that its [C_N_INV> output switches high only when both modules are connected to the parallel control bus b) The logic high [PAR_INV> input to D31-7 is inverted to a logic low [O_INV_IND> at D31-8. This is inverted to a high at D24-17 from where it is connected to the parallel control bus via X2/X3 pin 12. Due to the parallel control bus, the [INV_IND> input to D31-29 is thus logic low only if both modules are available (i.e. if [O_INV_IND> is low in both modules). 5. The effects of the logic high [C_N_INV> input to D31-27, coupled with the logic high [PAR_INV> input to D31-7 and low [INV_IND> input to D31-29, now make D31-12 ( [C_L_INV>) switch low, sending a ‘load-on-inverter’ request to the UPS Logic Board. 6. If the UPS Logic Board conditions are normal it should now send a ‘transfer to inverter’ command to the Static Switch Driver Board which will closed the inverter output contactor and turn off the static bypass SCRs. Applicable to both system configurations
7. Once the load has transferred to the inverter two key signals are sent back from the UPS Logic Board to the Parallel Logic Board: a) First, a lockout signal slaved to the inverter output contactor auxiliary contacts applies a logic high [N_AUX_CONT> input to D31-34 which prevents the ‘load on bypass’ request from being generated at D31-18 while the contactor is closed. b) Second, a logic high ‘inverter on load’ status signal ( [INV_L>) is fed back to X1-52 which is connected to: – D31-31 (low) to enable the ‘selective shutdown’ circuit within D31. – D31-25 (high) to provide a second lockout to the ‘load on bypass’ request circuit within D31 in the same manner as [N_AUX_CONT> described above. – via a debounce circuit, [INV_L> produces a logic high [ABIL_RIP> signal which energises the current-sharing circuit solid-state switches to activate the current-sharing facility (See paragraph 2.5.2). 8. The UPS Module is now running and on-line, and its synchronisation and load-sharing signals are connected to the second module via the parallel control bus.
11pm-c6.fm 5 - Issu e 2 Dated 21/08/97
8-41