To Find
Amperes when Horsepower is known Amperes when Kilowatts is known
Direct Current
Single gle-Phase
Two-Pha -Phasse* Four Wire
Three-Phase
H.P x 746
H.P x 746
H.P x 746
H.P x 746
E x % EFF
E x % EFF x P.F
2 x E x % EFF x P.F
1.73 x E x %EFF x P.F
K.W x 1000
K.W x 1000
K.W x 1000
K.W x 1000
E x P.F
2 x E x P.F
1.73 x E x P.F
K.V.A x 1000
K.V.A x 1000
K.V.A x 1000
E
2xE
1.73 x E
IxE
I x E x P.F
I x E x 2 x P.F
I x E x 1.73 x P.F
1000
1000
1000
1000
IxE
IxEx2
I x E x 1.73
1000
1000
1000
K.V.A
Horse-power (output)
ALTERNATING CURRENT
E
Amperes when K.V.A is Known Kilowatts
Fax: 0117 961 0960
IxEx% EFF
I x E x % EFF x P.F
746
746
I x E x 2 x % EFF x I x E x 1.73 x % EFF P.F x P.F 746
746
I = Amperes · E = Volts · % EFF = per cent efficiency · P.F = Power Factor .8 · K.W = Kilowatts K.V.A = Kilo-Volt-Amperes · H.P = Horse Power * For three wire, two phase circuits the current in the common conductor is 1.41 times that in either of he other two conductors.
SOLUTIONS Electrical (Distribution) Ltd Tel: 0117 961 0948
Fax: 0117 961 0960
SYMBOLS: V = VOLTAGE IN VOLTS I = CURRENT IN AMPERES R = RESISTANCE IN OHMS P = POWER IN WATTS
Motor kW
.55
.75
1.1
1.5
Motor kW
18.5
22
30
37
Ratings HP
.75
1
1.5
2
Ratings HP
25
30
40
50
To BS775 FLA 1.45 1.85 2.35
3.3
To BS775 FLA
35
40
55
66
Fuses BS88 D.O.L.
6
6
10
15
Fuses BS88 D.O.L.
80
80 125 125
Assisted
2
4
4
6
Assisted
40
50
60
Motor kW
2.2
3
4
5.5
Motor kW
45
55
75
90 110
Ratings HP
3
4
5.5
7.5
Ratings HP
60
75 100 125 150
To BS775 FLA
4.9
6.4
7.5
11
To BS775 FLA
80
96 126 156 188
Fuses BS88 D.O.L.
15
20
20
30
Fuses BS88 D.O.L. 150 200 200 250 350
Assisted
10
15
15
20
Assisted 100 100 150 200 250
Motor kW
7.5
10
11
15
Motor kW 132 160 200 220 250
10 13.5
15
20
Ratings HP 175 220 270 300 350
Ratings HP
80
To BS775 FLA
14
18 21.5
28
To BS775 FLA 216 275 340 375 437
Fuses BS88 D.O.L.
35
40
50
60
Fuses BS88 D.O.L. 350 400 450 500 500
Assisted
20
25
25
35
Assisted 250 350 400 450 500
SOLUTIONS Electrical (Distribution) Ltd Tel: 0117 961 0948
Fax: 0117 961 0960
Inches to millimetres (mm)
25.4
Millimetres to inches
0.03937
Feet to metres (m)
0.3048
Metres to feet (ft)
3.280
Yards to metres
0.9144
Metres to yards (yd)
1.0936
Miles to kilometres (km)
1.6093
Kilometres to miles
0.6214
Square inches to square millimetres (mm²)
645.16
Square millimetres to square inches (inch²)
0.00155
Square yards to square metres (m²)
16.387
Square metres to square yards (yd²)
1.196
Cubic inches to cubic centimetres (cm³)
16.387
Cubic centimetres to cubic inches (inch³)
0.06102
Pounds to kilograms (kg)
0.4536
Kilograms to pounds (lb)
2.2046
Tons (2,240 lb) to kilograms (kg)
1,016.05
Kilograms to tons (2,240 lb)
0.0009842
Ounces (avoirdupois) to grams
28.3495
Grams to ounces (avoirdupois)
0.0353
Gallons to litres (l)
4.561
Litres to gallons
0.220
Force N (Newtons) to lbft
0.225
1N = 1 kg (mass) accelerated at 1 metre/sec. 1 NM = 1 J (Joule) to calorie
0.239
Horse power to kilowatts (kW)
0.7458
Kilowatts to horse power (h.p)
1.3408
1W (watt) = 1 J/S Atmospheres to lb per square inch (lb/inch²) 1 bar = 1 kg/cm² = 735.6mm Hg = 14.2lb/inch²
14.68
SOLUTIONS Electrical (Distribution) Ltd Tel: 0117 961 0948
Fax: 0117 961 0960
SOLUTIONS Electrical (Distribution) Ltd Tel: 0117 961 0948
Fax: 0117 961 0960
Motor Rating
230V
kw
Cosϕ η %
Rated Motor Current A
Fuse Y/ Δ starting A D.O.L A
Rated Motor Current A
0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 250 315 400 450 500 560 630
0.7 0.7 0.7 0.7 0.7 0.72 0.75 0.79 0.81 0.81 0.81 0.82 0.82 0.82 0.82 0.84 0.84 0.84 0.84 0.85 0.86 0.86 0.86 0.86 0.86 0.86 0.87 0.87 0.87 0.87 0.87 0.88 0.88 0.88 0.88 0.88
0.37 0.54 0.72 0.75 1.4 2 2.7 3.2 4.6 6.3 8.7 11.5 14.8 19.6 26.4 38 51 63 71 96 117 141 173 233 279 342 401 486 607 -
2 2 4 4 4 6 10 10 10 16 20 25 32 32 50 80 100 125 125 200 200 250 250 315 400 500 630 630 800 -
0.21 0.31 0.41 0.6 0.8 1.1 1.5 1.9 2.6 3.6 5 6.6 8.5 11.3 15.2 21.7 29.3 36 41 55 68 81 99 134 161 196 231 279 349 437 544 683 769 -
58 60 60 62 62 66 69 74 74 74 78 80 83 86 87 87 88 88 92 92 92 93 93 94 94 94 95 95 95 95 96 96 96 97 97 97
400V
2 2 2 4 4 4 6 10 10 16 16 25 32 40 63 80 80 100 125 160 200 250 315 400 500 630 630 -
415V
500V
Fuse Y/ Δ starting A D.O.L A
Rated Motor Current A
Fuse Y/ Δ starting A D.O.L BS A BS
Rated Motor Current A
Fuse Y/ Δ starting A D.O.L A
Rated Motor Current A
Fuse Y/ Δ starting A D.O.L A
2 2 2 2 4 4 4 6 6 6 10 16 20 25 32 40 63 63 80 100 125 160 200 200 250 315 400 400 500 630 800 1000 1000 -
0.21 0.30 0.40 0.58 0.8 1.1 1.5 1.8 2.6 3.5 4.8 6.4 8.2 10.9 14.6 20.9 28.2 35 40 53 65 78 96 129 155 189 222 269 337 421 525 -
2 2 2 2 4 4 6 6 10 16 16 20 20 25 35 50 80 80 80 100 125 125 160 250 250 315 355 355 450 500 630 -
0.17 0.25 0.33 0.48 0.7 0.9 1.2 1.5 2.1 2.9 4 5.3 6.8 9 12.1 17.4 23.4 28.9 33 44 54 65 79 107 129 157 184 224 279 349 436 547 615 -
2 2 2 2 2 2 4 4 6 6 10 16 16 20 25 32 50 50 63 80 100 125 160 200 200 250 250 315 400 500 630 800 800 -
0.12 0.18 0.24 0.35 0.5 0.7 0.9 1.1 1.5 2.1 2.9 3.8 4.9 6.5 8.8 12.6 17 20.9 23.8 32 39 47 58 78 93 114 134 162 202 253 316 396 446 491 550 618
2 2 2 2 2 2 4 4 4 6 10 10 16 16 20 25 32 32 50 63 80 80 100 160 160 200 250 250 315 400 500 630 630 630 800 800
2 2 2 4 4 4 6 10 10 16 16 25 32 40 50 63 80 100 125 160 200 200 250 315 400 500 630 800 800 -
2 2 2 2 2 2 4 4 6 10 10 16 16 20 25 32 40 50 50 80 80 80 100 160 160 200 250 315 355 450 560 -
690V
2 2 2 4 4 4 6 10 16 16 20 25 32 32 50 63 80 80 125 160 160 200 250 315 400 500 630 630 -
2 2 2 4 4 4 6 10 10 16 20 25 25 32 50 63 63 100 100 125 160 200 250 315 400 400 630 630 630 630
(Approximate figures for squirrel-cage motors). Minimum fuse size for short-circuit protection of 3-phase motors. The maximum size is determined by the requirements of the switchgear or overload relay The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-cooled motors. D.O.L. starting : maximum starting current 6 x rated motor current. Maximum starting time : 5 s. Y/ Δ starting : maximum starting current 2 x rated motor current. Maximum starting time : 15 s. set overload relay in the phase lead to 0.58 x rated motor current. Rated fuse currents for Y/ Δ starting are also valid for 3-phase motors with slip-ring rotors. For higher rated currents, starting currents / longer starting times, larger fuses will be required. Table is valid for 'slow' / 'gL' fuses (DIN VDE 0636) For NH fuses with aM characteristic, fuses = rated current selected.
SOLUTIONS Electrical (Distribution) Ltd Tel: 0117 961 0948
Fax: 0117 961 0960
AC hp KLOCKNER ABB
ALLEN
-3
BRADLEY HAMMER
MOELLER
CUTLER
CLIPSAL AGUT
SIEMENS SPRECHER+ STROMBERG TELESCHUH MECANIQUE
kW 4
5
DIL EM
B6
MCIA-3 3FT2
CA4-9
4
5
DIL 00 M
B9
100-A09N
HR09100-N 6C9/10
CL00
CA3-9
OK00W10
LC1-D910
5.5 7.5 DIL 00 AM
B12
100-A12N
HR1310-N
6C12/10
CL01A3 3TF-31
CA3-12
OK0W10
LC1-DI210
7.5 10 DIL0M
B16
100-A18N
HR1710
6C16/10
CL02A3 3TF-32
CA3-16
OK01W10
LC1-D1810
11
15 DIL0AM
B25
100-A24N
HR2510-N
6C25
CL25A3 3TF-33
CA3-23
OK1W10
LC1-D2510
15
20 DIL 1M
B30
100-A30-N HR3300-N
6C35
CL04A3 3TF-34
CA3-30
OK1.5W10
LC1-D3210
100-A38N
HR 4000-N 6C38
CL05A3 3TF-35
CA3-37N-11
OK02W10
100-A45N
HR 4600-N
CL06A3 3TF-46
CA3-43N-11
OKYM45
LC1-D4011
100-A60N
HR5500-N
6C50
CL07A3 3TF-47
CA3-60N-11
OKYM63
LC1-D5011
100-A75N
CE15KN
6C65
CL08A3 3TF-48
CA3-72N-11
18.5 25 DIL 1AM
3TF-30
LC1-K0910
22
30 DIL 2M
30
40 DIL 2AM
37
50 DIL 3M
B63
45
60 DIL3AM
EH80
6C80
CL09A3 3TF-49
CA6-85-11
OKYM75
LC1-D8011
55
80 DIL4M
EH100 100-B110N CE15MIN
6C95
CL10A3 3TF-50
CA6-105-11
OKYM90
LC1F115
75
100 DIL 4AM
EH145
CE15NN
6C115
3TF-51
CA6-140-E-11 OKYM150
LC1-F150
90
120 DIL6M
EH150 100-B180N CE15PN
6C150
CK08BA 3TF-52
CA6-170-E-11 OKYM175
LC1-F185
EH160
6C180
3TF-53
CA6-210
LC1-F225
6C250
CK09BA 3TF-54
CA6-210
OKYM200
LC1-F265
3TF-55
CA6-300
OKYM315
LC1-F330
CK10BA 3TF-56
CA6-420
OKYM400
LC1-F400
CK11BA 3TF-57
CA6-420
OKYM500
LC1-F500
110 145 DIL 6AM
B50
6M9/10
132 175 DIL8M
100-B250N
160 215 DIL8AM
EH250 100-B300N CE15SN
200 265 DIL10M
EH370 100-B400N
250 355 DIL 10 AM
6C400 C10GYAN3
LC1-D6511
335 450 DIL12AM
EH550 100-B600N C10GYBN3 6C500
CK12BA 3TF-68
CA5-550
OKYM630
LC1F630
450 600 DIL 14AM
EH800
CK13BA 3TF-69
CA5-850
OKYM800
LC1-F780
C10KN3
NOTE: This serves as a guide only. Technical specifications should be checked against the relevant manufacturers brochures.