Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Lecture-18
Shear Walls and Coupling beams By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar
[email protected]
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
1
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Topics Addressed Shear Wall Introduction Behavior ACI Recommendations Design Examples
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
2
1
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Topics Addressed Coupling Beam Introduction Behavior ACI Recommendations Design Examples
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
3
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
SHEAR WALLS
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
4
2
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Shear Walls
The term “shear wall” is used to describe a wall that resists lateral (wind or earthquake) loads acting parallel to the plane of the wall in addition to the gravity loads from the floors and roof adjacent to the wall.
Such walls are also referred to as “structural walls”.
Non structural walls and partitions, whether directly considered or not also add to the total lateral stiffness of the structure.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
5
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Difference between Wall and Column
The differentiation between columns and walls in the code is based on the principal use rather than on arbitrary relationships of height and crosssectional dimensions, ACI 318-02, Chapter 2 Definitions.
While a wall always encloses or separates spaces, it may also be used to resist horizontal or vertical forces or bending.
A column is normally used as a main vertical member carrying axial loads combined with bending and shear. It may, however, form a small part of an enclosure or separation.
The code permits walls to be designed using the principles stated for column design .
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
6
3
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Difference between Wall, Column and Pier
For the sake of terminology, however, following difference is recognized by the code.
Column: Member with a ratio of height-to-least lateral dimension exceeding 3 used primarily to support axial compressive load.
Wall: Though not specifically mentioned in the code, members of heightto-least lateral dimension NOT exceeding 3 are considered as WALLS.
Pier: This is a wall segment and refers to a part of a wall bounded by openings or by an opening and an edge.
Traditionally, a vertical wall segment bounded by two window openings has been referred to as a pier, ACI 318 -02, R21.7.4.2
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
7
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction
Other Definitions
DIAPHRAGM is a horizontal or nearly horizontal system acting to transmit lateral forces to the vertical-resisting elements. The term “diaphragm” includes horizontal bracing systems.
DIAPHRAGM or SHEAR WALL CHORD is the boundary element of a diaphragm or shear wall that is assumed to take axial stresses analogous to the flanges of a beam.
BOUNDARY ELEMENT is an element at edges of openings or at perimeters of shear walls or diaphragms.
COLLECTOR is a member or element provided to transfer lateral forces from a portion of a structure to vertical elements of the lateral-forceresisting system.
STRUCTURAL DIAPHRAGMS are structural members, such as floor and roof slabs, which transmit inertial forces to lateral- force-resisting members.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
8
4
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Other Definitions
1629.6.4 Moment-resisting frame system. A structural system with an essentially complete space frame providing support for gravity loads. Moment-resisting frames provide resistance to lateral load primarily by flexural action of members.
1629.6.5 Dual system. A structural system with the following features:
1. An essentially complete space frame that provides support
for gravity loads.
2. Resistance to lateral load is provided by shear walls or braced frames and moment-resisting frames (SMRF, IMRF, MMRWF or steel OMRF). The moment-resisting frames shall be designed to independently resist at least 25 percent of the design base shear.
3. The two systems shall be designed to resist the total design base shear in proportion to their relative rigidities considering the interaction of the dual system at all levels.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
9
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Types of Shear Walls Shape Length to height ratio Seismic demand
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
10
5
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Importance of Shear Walls
Shear walls are extremely important in high-rise buildings. If unaided by walls, high rise frames could not be efficiently designed to satisfy strength requirements or to be within acceptable lateral drift limits.
Since frame buildings depend primarily on the rigidity of connections for their resistance to lateral loads, they tend to be uneconomical beyond a certain height range.
11 to 14 stories, in regions of high to moderate seismicity
15 to 20 stories, elsewhere.
Many times, however, shear walls are also provided in low rise (1 to 5) or medium rise frame buildings (6 to 10) in order to reduce sizes of columns.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
11
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Locations of Shear Walls
It should be located such that the center of mass and center of rigidity of the structure coincide.
If there is eccentricity as illustrated in the fig, the building will undergo torsional distortions. Though the structure can be designed for such effects, it would be relatively uneconomical.
Center of mass
Center of resistance
Shear wall
Eccentricity Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
12
6
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Locations of Shear Walls
Most multi-story buildings are constructed with a central core area.
The core usually contains, among other things, elevator, plumbing and HVAC shafts etc.
Walls provided for such core can be used as Shear Walls.
Additional walls can be provided at other appropriate locations.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
13
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Frame-Wall Interaction
In a RC frame structure, the floor systems (RC slabs) distribute the lateral loads to the vertical framing elements in proportion to their rigidities.
Though the actual distribution of lateral loads will depend on the relative rigidities of walls and columns, the structural walls usually being substantially stiffer than the columns attract major portion of the lateral loads, leaving only small portion for the frame members.
With adequate wall bracing, the frame can be considered as non-sway for column design.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
14
7
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Frame-Wall Interaction
The analysis and design of the structural system for a building frame of moderate height can be simplified if the structural walls are sized to carry the entire lateral load.
Members of the frame (columns and beams or slabs) can be proportioned to resist the gravity loads only.
Neglecting frame-wall interaction for buildings of moderate size and height will result in reasonable member sizes and overall costs.
When the walls stiffness is much higher than the stiffness of the columns in a given direction within a story, the frame takes only a small portion of the lateral loads.
Thus, for low-rise buildings, neglecting the contribution of frame action in resisting lateral loads and assigning the total lateral load resistance to walls is an entirely reasonable assumption.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
15
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Introduction Frame-Wall Interaction
In contrast, frame-wall interaction must be considered for high-rise structures where the walls have a significant effect on the frame: in the upper stories, the frame must resist more than 100 % of the story shears caused by the wind loads.
Thus, neglecting frame-wall interaction would not be conservative at these levels. Clearly, a more economical high-rise structure will be obtained when frame-wall interaction is considered.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
16
8
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Behavior of Shear Walls A typical shear wall, which is part of a lateral
load
resisting
system,
is
subjected to following actions.
In-plane
shear
and
bending
moment
(along major axis)
Out-of-plane shear and bending moment (along minor axis)
Axial Load
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
17
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Behavior of Shear Walls In-plane
shear
and
bending
moment (along major axis) In-plane shear
A variable shear, which reaches a maximum at the base.
Both
horizontal
and
vertical
reinforcement are provided for shear.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
18
9
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Behavior of Shear Walls In-plane shear and bending moment (along major axis) In-plane bending moment
A variable bending moment which reaches a maximum at the base and tends to cause vertical tension near the loaded edge and compression at the far edge.
Vertical distributed reinforcement (fig a) or reinforcement at the edges in boundary zones (fig b) will be required against this action
Fig a
Fig b Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
19
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Behavior of Shear Walls Out-of-plane shear and bending moment (along minor axis) Out-of-plane bending moment
Depending on a number of parameters, the wall may bend in an out-of-plane mode either
as a whole from top to bottom called global bending or
as Individual wall segments in a story called local bending
In both cases vertical reinforcement distributed all along the length of the wall shall be provided.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
20
10
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Behavior of Shear Walls Out-of-plane shear and bending moment (along minor axis) Out-of-plane shear
Out-of-plane shear is not usually a problem in shear walls.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
21
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Types of Walls according to Seismic Hazard (Definitions, Chapter 21)
Walls located in regions of low to moderate seismic hazard (zones 1, 2a and 2b UBC 97), shall comply with the requirements of ordinary reinforced concrete structural walls of the chapter 14 of ACI 318-02.
There are no special requirements for structural walls located in regions of low to moderate seismic hazard, except for the connection requirements.
Walls located in regions of high seismic hazard (zones 3 and 4 of UBC 97), shall comply with the requirements of Special reinforced concrete structural wall of chapter 21 of the ACI 318-02,, in addition to the requirements for ordinary reinforced concrete structural walls.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
22
11
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Types of Walls according to Seismic Hazard (Definitions, Chapter 21) The provisions for the design of Ordinary reinforced concrete structural wall from chapter 14 will be presented first. Special provisions for Special reinforced concrete structural wall from chapter 21 will be presented next.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
23
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
According to section 14.2.3, walls subjected to shear forces shall be designed in accordance with the provisions of chapter 11, section 11.10 on provisions of shear reinforcement for structural walls.
According to section 14.4, Walls subjected to flexure load, axial load or combined flexure and axial load shall be designed in accordance with the provisions for flexure and axial loads of chapter 10. (like column design)
Walls shall be properly anchored into all intersecting elements, such as floors, columns, other walls, and footings.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
24
12
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Wall sizing
A minimum of 6 in thickness will be required for a wall with a single layer of reinforcement and 10 in for a wall with double layer.(ACI 14.3.4)
Moreover, according to (ACI 318-89) the shear wall must have a total stiffness of at least six times the sum of stiffness of all columns in a given direction within the story I(walls) > 6I(columns)
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
25
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Shear: (Section 11.10, ACI 318-02)
Shear Wall Capacity contributed by concrete alone is given as
ФVc =0.75 x 2 x √fc′ x h x d
where d = 0.8 lw
(ACI 11.10.4) ( ACI 11.10.4)
Vu
hw
lw Prof. Dr. Qaisar Ali
CE 5115
h
Advance Design of Reinforced Concrete Structures
26
13
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Shear: (Section 11.10, ACI 318-02) Minimum reinforcement for shear
Both horizontal and vertical shear reinforcement shall be provided as per following criterion.
Conditions
Horizontal Shear Reinforcement
Vertical Shear Reinforcement
Vu ≤ ФVc /2 (11.10.8)
ρh = 0.0020 for #5 and smaller ρh = 0.0025 for other bars (14.3)
ρn = 0.0012 for #5 and smaller with fy>60ksi ρn= 0.0015 for other bars (14.3)
ФVc/2 ≤ Vu ≤ ФVc (11.10.8)
ρh = 0.0025
ρn = 0.0025 (11.10.9.4)
Vu > ФVc (11.10.8)
s =0.75 x Av x fy x d / (Vu – ФVc)
(11.10.9.2)
ρn = 0.0025 +0.5(2.5-hw / lw )(ρh - 0.0025) (11.10.9.4)
ρh = ratio of horizontal shear reinforcement area to gross concrete area of vertical section ρn = ratio of vertical shear reinforcement area to gross concrete area of horizontal section
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
27
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Shear: (Section 11.10, ACI 318-02)
Maximum Spacing of Shear reinforcement
Horizontal Shear reinforcement
Spacing of horizontal shear reinforcement shall not exceed
Vertical Shear reinforcement
Spacing of vertical shear reinforcement shall not exceed
Prof. Dr. Qaisar Ali
Iw/5 , 3h nor 18 inch, (whichever is less)
CE 5115
Iw/3 , 3h nor 18 inch, (whichever is less )
Advance Design of Reinforced Concrete Structures
28
14
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Shear: (Section 11.10, ACI 318-02)
The ACI code additionally requires that
Vu < Ф 10√f c h(0.8lw ) ( ACI 318-02,11.10.3)
Increase thickness of wall, if this happens
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
29
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Flexure (14.2, 14.3)
Walls must be designed as compression members by the strength design provisions in Chapter 10 for flexure and axial loads.
Vertical reinforcement, however, need not be enclosed by lateral ties if vertical reinforcement area is not greater than 0.01 times gross concrete area.
Minimum ratio of vertical reinforcement area to gross concrete area shall be
(a) 0.0012 for deformed bars not larger than No. 5 with a specified yield strength not less than 60,000 psi; or
Prof. Dr. Qaisar Ali
(b) 0.0015 for other deformed bars
CE 5115
Advance Design of Reinforced Concrete Structures
30
15
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Placement of Reinforcement (14.3.4)
Walls more than 10 in. thick, except basement walls, shall have reinforcement for each direction placed in two layers parallel with faces of wall in accordance with the following:
(a) One layer consisting of not less than one-half and not more than twothirds of total reinforcement required for each direction shall be placed not less than 2 in. nor more than one-third the thickness of wall from the exterior surface;
(b) The other layer, consisting of the balance of required reinforcement in that direction, shall be placed not less than 3/4 in. nor more than one-third the thickness of wall from the interior surface.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
31
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Code Recommendations Ordinary reinforced concrete structural wall (Chapter 14)
Reinforcement around openings (14.3.7)
In addition to the minimum reinforcement, not less than two No. 5 bars shall be provided around all window and door openings. Such bars shall be extended to develop the bar beyond the corners of the openings but not less than 24 in.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
32
16
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall General
In the case of low-rise walls, shear requirements usually govern, so a preliminary thickness can be determined based on shear.
In high-rise structures, a preliminary wall thickness is not as obvious. In such structures, the wall thickness can vary a number of times over the height of the structure, and a thickness is usually determined from experience.
While fire resistance requirements will seldom govern wall thickness, the governing building code requirements should not be overlooked.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
33
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall General
The size of openings required for stairwells and elevators will usually dictate minimum wall plan layouts. Thus, the lengths of walls are usually dictated by architectural considerations.
Therefore, the first step in the design procedure is to determine a preliminary thickness of the wall.
From a practical standpoint, a minimum thickness of 6 inches will be required for a wall with a single layer of reinforcement, and 10 inches for a wall with a double layer.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
34
17
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall General
In low-rise walls,
which are typically governed by shear
requirements, it is common practice to determine the amount of vertical and horizontal reinforcement based on the shear provisions of Section 11.10.
The flexural and axial force requirements of the appropriate design method are then checked based on the reinforcement for shear.
It is not uncommon for low-rise walls to have minimum amounts of reinforcement over their entire height.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
35
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall General
In the case of high-rise walls, wall sections at the base of the structure will usually, but not always, be governed by the requirements for flexure and axial load. Once the required amount of reinforcement is established for those requirements, the shear requirements of Section 11.10 are checked.
The amounts of reinforcement are typically varied over the height of high-rise walls.
In no case shall the provided areas of reinforcement be less than the minimum values prescribed in the code.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
36
18
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Shear
ФVn = ФVc + ФVs
ФVs =Vu – ФVc = 0.75 x Av x fy x d/ s
Therefore s = 0.75 x Av x fy x d /(Vu – ФVc)
“s” is center to center to center spacing of horizontal reinforcement in inches
Av is single bar area for one curtain and two times bar area for two curtains of reinforcement. Vu hw
h
lw Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
37
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Shear
Horizontal and vertical shear reinforcement Ash & Asv from minimum reinforcement ratio “ρ” can be calculated as follows
Ash or Asv = (inch2 per foot ) = ρ x 12 x h ; h is thickness of wall
Spacing “s” (inch c/c) = (Av /Ash ) x 12
s = Av /(ρ x 12 x h ) x 12 (substituting Ash )
s = Av /(ρ x h )
ρ = Av /(s x h )
hw
h h lw
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
38
19
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
In general, when designing a wall as a compression member, an interaction diagram needs to be constructed for sections subjected to combined flexure and axial load, and the applied factored moments must be magnified to account for slenderness effects.
Details on how to construct such a diagram have been discussed earlier.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
39
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Approximate procedure for design of In-plane bending
For buildings of moderate height, walls with uniform cross-sections and uniformly distributed vertical and horizontal reinforcement are usually the most economical.
Concentration of the reinforcement at the extreme ends of a wall or small segment (boundary zones) is usually not required except in high and moderate seismic zones (special walls).
Uniform distribution of the vertical wall reinforcement required for shear wall usually provides adequate moment strength as well.
Minimum amounts of reinforcement will usually be sufficient for both shear and moment requirements.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
40
20
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Approximate procedure for design of In-plane bending
In general, walls that are subjected to axial load or combined axial and flexure load need to be designed as compression members according to the provisions given in ACI Chapter 10.
For rectangular shear walls containing uniformly distributed vertical reinforcement and subjected to an axial load smaller than that producing balance failure, the following approximate equation can be used to determine the nominal moment capacity of the wall. ( Cardens A.E et. al, Design Provisions for Shear walls,” Journal of the ACI, Vol 70, No. 3 March 1973, pp 221-230)
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
41
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
•
•
Approximate procedure for design of In-plane bending
Where
0.5
1
1
= total area of vertical reinforcement, in.2 = horizontal length of wall, in. = factored axial compressive load, kips = yield strength of reinforcement = 60 ksi
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
42
21
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Approximate procedure for design of In-plane bending
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
43
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Prof. Dr. Qaisar Ali
Approximate procedure for design of In-plane bending
CE 5115
Advance Design of Reinforced Concrete Structures
44
22
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Approximate procedure for design of In-plane bending
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
45
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Prof. Dr. Qaisar Ali
Approximate procedure for design of In-plane bending
CE 5115
Advance Design of Reinforced Concrete Structures
46
23
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Approximate procedure for design of In-plane bending
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
47
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Out-of-plane bending
As wall is mostly slender along its minor axis, moment magnification shall be done before wall is designed for out-of-plane bending
Once moment is magnified, wall shall be designed for this moment either using interaction diagram or approximate procedure.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
48
24
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Out-of-plane bending
Moment Magnification
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
49
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Out-of-plane bending
Moment Magnification
Cracked moment of inertia, Icr
Es Icr =
Prof. Dr. Qaisar Ali
Ec
CE 5115
As +
Pu fy
(d –
c)2
+
w c3 3
Advance Design of Reinforced Concrete Structures
50
25
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Ordinary Reinforced Concrete Structural Wall Flexure
Out-of-plane bending
out-of-plan deflection requirements
s =
5Mc2 48EcIe
1–
CE 5115
c 150
Msa
M=
Prof. Dr. Qaisar Ali
5Psc2 48EcIe
Advance Design of Reinforced Concrete Structures
51
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Provisions for Special reinforced concrete structural walls
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
52
26
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Provisions for Special reinforced concrete structural walls
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
ACI Provisions for Special reinforced concrete structural walls
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
27
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Provisions for Special Boundary Elements
The minimum reinforcement ratio for both the longitudinal and transverse reinforcement is 0.0025, unless the design shear force does not exceed Acv fc , where Acv is the net area of concrete bounded by the web thickness and the length of the wall in the direction of analysis; in this case, the minimum reinforcement must not be less than that given in 14.3. The reinforcement provided for shear strength must be continuous and distributed uniformly across the shear plane with a maximum spacing of 18 in. At least two curtains of reinforcement are required if the in-plane factored shear force assigned to the wall exceeds Acv fc
n = ratio of area of distributed reinforcement parallel to the plane of Acv to gross concrete area perpendicular to that reinforcement.(horizontal, denoted by h in chapter 14)
v = ratio of area of distributed reinforcement perpendicular to the plane of Acv to gross concrete area Acv.(vertical, denoted by n in chapter 14)
Acp = area of concrete section, resisting shear, of an individual pier or horizontal wall segment, in.2
Acv = gross area of concrete section bounded by web thickness and length of section in the direction of shear force considered, in.2
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
28
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Provisions for Special Boundary Elements 21.7.2.1:1. ordinary
If Vu ≤ Acv
′, provide minimum reinforcement as given for
reinforced structural walls, where Acv is the net area of concrete
bounded by the web thickness and the length of the wall in the direction of analysis Acv = h × lw
h
h
lw
’
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Provisions for Special Boundary Elements 21.7.2.2: 2. If Vu> Acv ′ , both the longitudinal (v)and transverse reinforcement (n ) must not be less than 0.0025 21.7.2.2: 3. If Vu>2 Acv both directions.
′ ,
Two curtains of reinforcement are required in
21.7.2.3:4. Anchoring or splicing of reinforcement as per 21.5.4 21.7.4: Shear Strength. Vn = Acv (c
′ + n fy)
c = 3 (for hw/lw ≤ 1.5) &c= 2 (for hw/lw ≥ 2.0) & varies linearly for other values.
(c = 2.0 conservatively)
21.7.4.3: Walls shall have distributed reinforcement providing resistance in two orthogonal directions in the plane of the wall. If the ratio hw/lw does not exceed 2.0 then reinforcement v shall not be less than n Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
29
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Provisions for Special Boundary Elements R 21.7.4: The ratio hw/lw may refer to overall dimensions of a wall, or of a segment of the wall bounded by two openings or an opening and an edge. To restrain the inclined cracks effectively, reinforcement included in n and v should be appropriately distributed along the length and height of the wall. Chord reinforcement provided near wall edges in concentrated amounts for resisting bending moments is not to be included in determining n and V. 21.7.5:
Design of flexure and axial loads.
21.7.5.1: 21.7.5.2:
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.6 Boundary Elements of Special Reinforced Concrete Structural Walls 21.6.3. Compression zones shall includes special boundary elements where the maximum extreme fiber stress corresponding to the factored forces, including earthquake effects, exceeds 0.2 fc’ (see Fig. 29-21).
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
30
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.6 Boundary Elements of Special Reinforced Concrete Structural Walls
Fig 29-21: Special Boundary Element Requirements per 21.7.6.3
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.6 Boundary Elements of Special Reinforced Concrete Structural Walls When special boundary elements are required, they must extend horizontally from the extreme compression fiber a distance not less than the larger of c – 0.1 lw and c/2 (21.7.6.4(a); see Fig. 29-20). In the vertical direction, the special boundary elements must extend from the critical section a distance greater than or equal to the larger of lw or Mu/4Vu (21.7.6.2). This distance is based on upper bound estimates of plastic hinge lengths, and is beyond the zero over which concrete spalling is likely to occur. From earlier codes, it is 0.15 to 0.25 lw See chapter 6 simplifired approach.
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
31
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.6 Boundary Elements of Special Reinforced Concrete Structural Walls
Fig 29-20: Special Boundary Element Requirements per 21.7.6.2
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.6 Boundary Elements of Special Reinforced Concrete Structural Walls Section 21.7.6.4 contains the details of he reinforcement when special boundary elements are required by 21.7.6.2 or 21.7.6.3. The transverse reinforcement must satisfy the same requirements as per special moment frame members subjected to bending and axial load (21.4.4.1 through 21.4.4.3), excluding Eq. (21-3) (21.7.6.4(c); see Fig. 29-22). Also, the transverse reinforcement shall extend in the support a distance not less than the development length of the largest longitudinal bar in the special boundary element; for footing or mats, the transverse reinforcement shall extend at least 12 in. into the footing or mat (21.7.6.4(d)). Horizontal reinforcement in the wall web shall be anchored within the confined core of the boundary element within the confined core of the boundary element to develop its specified yield strength (21.7.6.4(c)). To achieve this anchorage, 90-deg hooks or mechanical anchorages are recommended. Mechanical splices and welded splices of the longitudinal reinforcement in the boundary elements shall conform to 21.2.6 and 21.2.7, respectively (21.7.6.4(d) )
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
32
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.6 Boundary Elements of Special Reinforced Concrete Structural Walls when special boundary elements are not required, the provisions of 21.7.6.5must be satisfied. For the cases when the longitudinal reinforcement ratio at the wall boundary is greater than 400/fy, transverse reinforcement, spaced not more than 8 in. on center, shall be provided that satisfies 21.4.4.1(c), 21.4.4.3, and 21.7.6.4(c)(21.7.6.5(a)). This requirement helps in preventing bucking of the longitudinal reinforcement that can be caused by cyclic load reversals. The longitudinal reinforcement ratio to be used includes only the reinforcement at the end of the wall as indicated in Fig. R21.7.6.5. Horizontal reinforcement terminating at the edges of structural walls must be properly anchored per 21.7.6.5(b)in order for the reinforcement to be effective in resisting shear and to help in preventing buckling of the vertical edge reinforcement. The provisions of 21.7.6.5(b)are not required to be satisfied when the factored shear force Vu ′ is less than Acv
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.6 Boundary Elements of Special Reinforced Concrete Structural Walls
Fig 29-22: Reinforcement Details for Special Boundary Elements
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
33
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.7 Coupling Beams When adequately proportioned and detailed, coupling beams between structural wall can provide an efficient means of energy dissipation under seismic forces, and can provide a higher degree of overall stiffness to the structure. Due to their relatively large depth to clear span ratio, ends of coupling beams are usually subjected to large inelastic rotations. Adequate detailing and shear reinforcement are necessary to prevent shear failure and to ensure ductility and energy dissipation. coupling beams with ln/h ≥ 4 shall satisfy the requirement of 21.3for flexure members of special moment frames, excluding 21.3.1.3and 21.3.1.4(a)if it can be shown that the beam has adequate lateral stability (21.7.7.1). When ln/h < 4, coupling beams with two intersecting groups of diagonally-placed bars symmetrical about the midspan is permitted (21.7.7.2). The diagonal bars are required for deep coupling beams (ln/h < 2) with a factored shear force Vu greater than 4 ′ Acp, unless it can be shown otherwise that safety and stability are not compromised (21.7.7.3). Experiments have shown that diagonally oriented reinforcement is effective only if the bars can be placed at large inclination. Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.7 Coupling Beams Note that in 2002 code, h replaces d in the definition of the aspect ratio (clear span/depth) and Acp replaces bwd in the shear equations. The first change simplifies the code requirements, since d is not always readily known for beams with multiple layers of reinforcement. The second change removes an inconsistency between 21.6.4.5 and 21.6.7.4 of the 1999 code; Acp is now consistently used in 21.7.4.5and 21.7.7.4. Section 21.7.7.4 contains the reinforcement details for the two intersecting groups of diagonally placed bars. Figure 29-23 provides a summary of these requirements. The requirement on side dimensions of the cage and its core is to provide adequate toughness and stability when the bars are stressed beyond yielding. The nominal shear strength of a coupling beam is computed from the following (21.7.7.4(b)): Vn = 2Avdfysin ≤ 10
Prof. Dr. Qaisar Ali
′ AcpEq. (21-9)
CE 5115
Advance Design of Reinforced Concrete Structures
34
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
21.7.7 Coupling Beams The additional reinforcement specified in 21.7.7.4(f) is used to confine the concrete outside of the diagonal cores.
Fig 29-23: Coupling Beam with Diagonally Oriented Reinforcement
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
References ACI 318-02 Design of Concrete Structures (13th Ed.) by Nilson, Darwin and Dolan PCA Notes on ACI 318-02
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
70
35
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
The End
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
71
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Design of Shear Wall Ordinary reinforced concrete structural wall
Flexure
Wall design is further complicated by the fact that slenderness is a consideration in practically all cases of out-of-plane bending.
The approximate evaluation of slenderness effects prescribed in Section 10.11 may be used
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
72
36
Department of Civil Engineering, University of Engineering and Technology Peshawar, Pakistan
Ash Asv
Prof. Dr. Qaisar Ali
CE 5115
Advance Design of Reinforced Concrete Structures
73
37