Flexi Power Module (FPMA) and submodules (FPAA and FPBA) description
6 6.1 6. 1
Flexi Pow Flexi Power er Mod Module ule (FP (FPMA) MA) and submodules (FPAA and FPBA) description Fle lexi xi Pow ower er Mo Mod dul ule e (F (FP PMA MA)) an and d su subb-mo modu dule les s (FPAA and FPBA) operation Flexi Power Module (FPMA) is an optional module. It comprises FPMA mechanics and AC and DC interfaces. The actual power sub-modules are the following: .
Flexi Power AC/DC sub-module 200-240 V AC (FPAA)
.
Flexi Power Battery sub-module (FPBA)
The maximum number of sub-modules in an FPMA is four. For installation instructions, see section section Installing Flexi Power Module (FPMA) in (FPMA) in the Installing the Installing Flexi EDGE BTS Optional Items document. Items document. The FPMA is presented in the following figures.
DN70178394 Issue 3-0 en 19/06/2008
# Nokia Siemens Networks
29 (128)
Optional Items Description
Type label
DN70230045
Figure 9.
Power Module (FPMA)
DN7084386
Figure 10.
30 (128)
FPMA: full configuration with two FPAAs and two FPBAs
# Nokia Siemens Networks
DN70178394 Issue 3-0 en 19/06/2008
Flexi Power Module (FPMA) and submodules (FPAA and FPBA) description
For examples of how many FPMAs are required for common configurations, see section Common stack, wall and pole configurations in Creating Stack, Wall and Pole Configurations , Common cabinet configurations in Creating FCIA Configurations or Creating FCOA Configurations or Common sector configurations in Creating Stack, Wall and Pole Configurations , Creating FCIA Configurations or Creating FCOA Configurations .
6.1.1
Operation The FPMA can support 1-phase and 3-phase AC input. The nominal input voltage is 200-240 V AC (the operating voltage range is 180 - 276 V AC). The maximum output power from the FPMA is 4kW (with 4 FPAAs). Flexi Power AC-DC sub-module (FPAA) The main function of the FPAA is to provide the BTS with nominal 48 V DC power from an AC supply. Maximum DC output power of one FPAA module is 1000 W. A nominal 48 V DC supply is intended for BTS internal use only (a nominal 48 V DC supply is not intended for 3rd party equipment because they may require lower conducted emission level than EN55022 Class A). It should be especially noted that an external lead acid battery for longer backup times cannot be connected to nominal 48 V DC supply. (This is because the temperature compensation of charging voltage is not supported). The FPAA includes its own integrated selfcontrolled fan. In case the fan fails, an alarm is generated and the FPAA has to be replaced (the fan alone cannot be replaced). The FPAA unit remembers the main control switch position. If the FPAA power is switched to Standby, the power remains OFF after input voltage interrupt. The stand-by switch is used for switching the FPAA unit ON/Stand-by when AC input voltage has been connected to the FPAA unit. Flexi Power Battery sub-module (FPBA) The Flexi Power Battery Sub-Module (FPBA) is a separate optional submodule used together with the FPAA. The FPBA provides short-term battery backup time when the AC power mains is down on a Flexi BTS site. The FPBA is a lithium ion battery. The maximum DC output power from one FPBA module is 1000 W. The input power for the BTS cannot exceed the maximum output power of the installed batteries. Otherwise the batteries do not provide the BTS with the needed power during power failure.
DN70178394 Issue 3-0 en 19/06/2008
# Nokia Siemens Networks
31 (128)
Optional Items Description
The power switch of the FPBA unit controls input power. Batteries can be drained by the BTS if the power switch is set to OFF position. The stand-by switch is used for switching the FPBA unit ON/Stand-by when AC input voltage has been connected to the FPBA unit. Lightning protection requirements .
.
.
6.2
+/- 2 kV, 1.2/50 µs pulse, Rs=(2 Ω + 10 +/- 1 kV, 1.2/50 µs pulse, Rs=2
Ω (line
Ω)
(line to ground, common)
to line, differential)
+/- 6 kV, 1.2/50 µs pulse, Rs=2 Ω (each phase conductor to greenwire ground or neutral conductor, neutral conductor and green-wire ground)
Flexi Power Module (FPMA) and sub-module (FPAA and FPBA) interfaces FPMA front panel connectors The connectors on the FPMA front panel, their types and purposes are listed in the table below.
Table 11.
FPMA front panel connectors, types and purposes
Connector
Type
Purpose
Power supply in
Terminal block
AC main power supply in
Power supply out
2-wire DC cable 4 x multibeam
DC feed to the BTS
Grounding
2 x M5
Module grounding
FPAA front panel connectors There is a stand-by switch on the front panel of the FPAA. The stand-by switch is used for switching the FPAA unit ON/stand-by. The connectors on the FPAA front panel, their types and purposes are listed in the table below.
32 (128)
# Nokia Siemens Networks
DN70178394 Issue 3-0 en 19/06/2008
Flexi Power Module (FPMA) and submodules (FPAA and FPBA) description
Table 12.
FPAA front panel connectors, types and purposes
Connector
Type
Purpose
AC cable connector
Mate-N-Lock
AC input
DC connector
Multi-beam power supply connector
DC output
Alarm connector
2 x RJ-45*
Alarms**
Operational state visual indication
tri-colour LED
FPAA state or alarm indication
*for chaining **Alarm 1 (AL01): AC input failure (alarm is sent when AC input voltage is missing or it is out of range). **Alarm 2 (AL02): maintenance needed (possible reasons are unit failure, cooling fan failure, output power is low or over temperature shut down is ON). FPBA front panel connectors There is a stand-by switch on the front panel of the FPBA. The connectors on the FPBA front panel, their types and purposes are listed in the table below.
Table 13.
FPBA front panel connectors, types and purposes
Connector
Type
Purpose
DC input/output connector
Multi-beam power supply connector
DC input and output
Alarm connector
2 x RJ-45*
Alarms**
Operational state visual indication
tri-colour LED
FPBA state or alarm indication
*for chaining
DN70178394 Issue 3-0 en 19/06/2008
# Nokia Siemens Networks
33 (128)
Optional Items Description
**Alarm 2 (AL02): maintenance needed (possible reasons are unit failure, output power is low or unit has reached end of it's life). **Unit has an input for Alarm 1 (AL01) from FPAA unit (Alarm 1 is a trigger for battery discharging).
6.3
Flexi Power Module (FPMA) dimensions and weight The following table lists the dimensions and weight for the Power Module.
Table 14.
Dimensions and weight of the Power Module
Property
FPMA
Height
133 mm/3 U (5.2 in.)
Width
447 mm (17.6 in.)
Depth without covers
422 mm (16.6 in.)
Depth with covers
560 mm (22.1 in.)
Weight (empty)
< 11 kg (< 24.3 lbs)
6.4
Weight
28 kg
(fully equipped with one AC/DC power module and batteries)
(61.9 lbs)
Flexi power sub-module (FPAA and FPBA) LED indications FPAA LED indications The FPAA LED indications are explained in the table below. Read the information on LED indications thoroughly. A blinking red LED does not always require removing the module.
34 (128)
# Nokia Siemens Networks
DN70178394 Issue 3-0 en 19/06/2008
Flexi Power Module (FPMA) and submodules (FPAA and FPBA) description
Table 15.
FPAA LED indications
Colour
Explanation
Yellow
Stand-by (AC connected)
Green
Normal operation
Red
Alarm or fault
Red, blinking
Unit operating with abnormal input voltage
See the following figure for the location of the FPAA LED.
LED
DN70350654
Figure 11.
FPAA LED
FPBA LED indications The FPBA LED indications are explained in the table below.
Table 16.
DN70178394 Issue 3-0 en 19/06/2008
FPBA LED indications
Colour
Explanation
Yellow
Stand-by (DC connected from FPAA)
Ggreen
Normal operation, battery OK
Green, blinking slowly
Charging
Green, blinking fast
Discharging
Blinking fast between green and yellow
Forced discharge mode
Red, blinking fast
Minor alarm
Red
Major alarm or fault
# Nokia Siemens Networks
35 (128)
Optional Items Description
The LED's slow blinking frequency is 1 Hz (1 sec) and fast blinking frequency 2 Hz (0.5 sec). See the following figure for the location of the FPBA LED.
LED
DN70350678
Figure 12.
36 (128)
FPBA LED
# Nokia Siemens Networks
DN70178394 Issue 3-0 en 19/06/2008