Catalogue/Engineering Data
Fan Coil Unit (DDW) Horizontal Unit Model: Air Flow:
Vertical Unit Model: Air Flow:
DDW020H-DDW450H 2,000m3/h-45,000m3/h
DDW040V-DDW450V 4,000m3/h-45,000m3/h
PCUA14-10
Double Skin Fan Coil unit DDW Literature No.: PCUA14-10 Supersedes: ED-DDW-201311B
Contents Nomenclature....................................................................................................................... 2 Features................................................................................................................................ 3 Specifications....................................................................................................................... 4 Dimensions......................................................................................................................... 10 Fan Discharge Type............................................................................................................ 16 Selection Software............................................................................................................. 17 Special Notes...................................................................................................................... 18 Wiring Diagrams................................................................................................................. 19 Installation........................................................................................................................... 20 Servicing And Maintenance .............................................................................................. 22 Common Failures............................................................................................................... 24
Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. Caution: Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them. Warning: Moving machinery and electrical power hazard may cause severe personal injury or death. Disconnect and lock off power before servicing equipment.
1
DDW
Double Skin Fan Coil unit
Nomenclature D D W 080 H R 08 -4 L- F F B E Export Design ID Discharge Type F - Horizontal Discharge Type T - Top Discharge Type Power Supply: F - 380-415V/3N~/50Hz R - 380V/3N~/60Hz P - 208-230V/3N~/60Hz Q - 460V/3N~/60Hz Pipe Connection: R - Left Hand L - Right Hand (Facing Air Discharge) Coil Rows: 4 - 4 Rows 6 - 6 Rows External Total Pressure 08 - 80 Pa; 15 - 150Pa 22 - 220Pa; 30 - 300Pa Air Conditioning R - Return Air F - Fresh Air Structure Type H - Horizontal V - Vertical Air Flow 080 - 8000m3/h DDW - Double-Skin FCU
2
Double Skin Fan Coil unit DDW
Features General Information DAIKIN DDW air handling units are designed to meet the needs of the terminal air conditioning market. DDW units are full featured handlers that are applicable for the central air-conditioning systems installed in hotels, supermarkets, hospitals and office buildings.
Without Frame Type DDW units are equipped with no frame structure patent of DAIKIN and prevent air leakage angle design,to ensure no cold bridge and low leakage rate.
Casing DDW Casing units is of double-skin panels and assembled with self supporting modular panel elements with an integrated base frame made of galvanized steel. assembled 25mm polyurethane foam offer ideal heat/sound insulation.
Filter Washable nylon primary air filter, removable and easy installation. Bag filter is optional.
Coil Selection All the computing results and the products built on these results have passed strict test. This ensures their safe, reliable and effcient operation.
Sirocco Fan High efficient and quiet titled multi-blade double-intake fans.
Motor V-belt driving,Class F,IP55 provide different amounts of air flow and ETP to meet different needs.
3
DDW
Double Skin Fan Coil unit
Specifications DDW-H (Horizontal) Model
DDW020H
DDW030H
DDW040H
DDW050H
DDW060H
DDW080H
2000 80 150
3000 80 150
4000 80 150
5000 150
6000 150
8000 150
220
220
220
220
220
220
--
-
-
300
300
300
4 Rows (Return air)
12
17
24
30
37
49
4 Rows (Fresh air)
28
41
56
66
80
111
6 Rows (Return air)
15
23
32
38
46
61
6 Rows (Fresh air)
34
52
67
86
103
136
4 Rows (Return air)
19
29
40
49
60
81
4 Rows (Fresh air)
32
48
65
80
97
130
6 Rows (Return air) 6 Rows (Fresh air)
23 37
35 56
47 75
59 93
71 112
94 149
Nominal Air Flow (m3/h) I(5) Internal+External II(5) Static pressure III(5) (Pa) IV(5) Nominal cooling capacity (kW)
Nominal heating capacity (kW)
Coil
Fan
Motor
Filter Casing Unit weight (kg)
Unit dimension
Packing dimension
Type
Corrugated aluminum fin mechanically bonded with copper tube
FPI Working pressure (MPa) Entering/Leaving water pipe Condensing water pipe Copper pipie diameter (mm) Type/Material
12 1.6 R1-1/2
R1-1/2
R2
R2
R2
R1-1/4 12.7 High Efficient Centrifugal Multi-blades Fan/Galavnize Steel
Drive type Fan disdcharge orientation Power supply
Lower horizontal discharge/Top discharge
Motor type
3-Phase Asynchronous Motor,Class F, no less than IP54
Motor output power (kW)
R2
V-belt
380V/3N~/50Hz I(5)
0.37(0.37)(6)
0.55(0.55)
0.55(0.75)
-
-
-
II(5)
0.37(0.55)
0.55(0.75)
0.75(1.1)
1.1(1.1)
1.1(1.5)
1.5(2.2)
III(5) IV(5)
0.55(0.55) -
0.75(0.75) -
1.1(1.1) -
1.1(1.5) 1.5(1.5)
1.5(1.5) 1.5(2.2)
2.2(2.2) 2.2(2.2)
Type/Material Thickness (mm) Type 4 Rows 6 Rows
Nylon 21 25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel 132 155 172 196 215 253 142 161 184 203 227 278
Height (mm)
600
650
730
730
800
800
Width (mm)
900
1050
1080
1250
1320
1680
Length (mm)
960
1000
1100
1060
1150
1150
Height (mm)
800
850
930
930
1000
1000
Width (mm)
1150
1300
1330
1500
1570
1930
Length (mm)
1170
1210
1310
1270
1360
1360
NOTES: 1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY. 2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB; STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB; STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER; STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER; 3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW SELECTION SOFTWARE. 4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL. 5) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION. 6) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.
4
Double Skin Fan Coil unit DDW
DDW-H (Horizontal) Model Nominal Air Flow (m /h)
DDW100H
DDW120H
DDW150H
DDW180H
DDW200H
DDW250H 25000
10000
12000
15000
18000
20000
I(5)
-
-
-
-
-
-
II(5)
150
150
150
150
150
150
III(5)
220
220
220
220
220
220
IV(5)
300
300
300
300
300
300
Nominal cooling capacity (kW)
4 Rows (Return air)
62
73
95
108
121
152
4 Rows (Fresh air)
139
166
194
233
266
333
6 Rows (Return air)
76
91
118
144
151
190
6 Rows (Fresh air)
170
204
263
316
346
430
Nominal heating capacity (kW)
4 Rows (Return air)
101
120
152
182
200
250
4 Rows (Fresh air)
159
193
242
291
325
404
6 Rows (Return air) 6 Rows (Fresh air)
118 186
141 223
179 283
213 335
237 373
297 467
3
External total
pressure (Pa)
Coil
Fan
Type
Corrugated aluminum fin mechanically bonded with copper tube
FPI
12
Working pressure (MPa)
1.6
Entering/Leaving water pipe
R2
R2
R2-1/2
R2-1/2
R2-1/2
Condensing water pipe
R1-1/4
Copper pipie diameter (mm)
12.7
Type/Material
High Efficient Centrifugal Multi-blades Fan/Galavnize Steel
Drive type
V-belt
Fan disdcharge orientation
Lower horizontal discharge/Top discharge
Power source
380V/3N~/50Hz
Motor type Motor Motor output power (kW)
R3
3-Phase Asynchronous Motor,Class F, no less than IP54 I(5)
-
-
-
-
-
-
II(5)
2.2(2.2)(6)
2.2(3.0)
3.0(4.0)
4.0(4.0)
4.0(4.0)
5.5(5.5)
III(5) IV(5)
2.2(2.2) 2.2(3.0)
3.0(3.0) 3.0(3.0)
4.0(4.0) 4.0(4.0)
4.0(5.5) 5.5(5.5)
4.0(5.5) 5.5(5.5)
5.5(7.5) 7.5(7.5)
Type/Material
Nylon
Thickness (mm)
21
Casing
Type
25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel
Unit weight (kg)
4 Rows
313
325
347
444
479
6 Rows
335
354
415
497
535
600
Height (mm)
930
1050
1180
1240
1240
1430
Filter
Unit dimension Packing dimension
557
Width (mm)
1690
1690
1940
2120
2300
2400
Length (mm)
1170
1170
1170
1310
1310
1310
Height (mm)
1130
1250
1380
1440
1440
1630
Width (mm)
1940
1940
2190
2370
2550
2650
Length (mm)
1380
1380
1380
1520
1520
1520
NOTES: 1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY. 2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB; STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB; STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER; STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER; 3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW SELECTION SOFTWARE. 4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL. 5) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION. 6) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.
5
DDW
Double Skin Fan Coil unit
DDW-H (Horizontal) Model Nominal Air Flow (m3/h) External total pressure (Pa)
Nominal cooling capacity (kW)
Nominal heating capacity (kW)
Coil
Fan
DDW300H 30000
DDW350H 35000
DDW400H 40000
DDW450H 45000
I(5)
300
300
300
300
II(5)
400
400
400
400
(5)
III
500
500
500
500
IV(5)
600
600
600
600
4 Rows (Return air)
178
205
238
266
4 Rows (Fresh air)
390
448
520
577
6 Rows (Return air)
222
256
296
329
6 Rows (Fresh air)
490
556
639
703
4 Rows (Return air)
295
337
391
437
4 Rows (Fresh air)
472
534
604
670
6 Rows (Return air) 6 Rows (Fresh air)
371 544
398 629
450 719
500 802
Type FPI
Corrugated aluminum fin mechanically bonded with copper tube 12
Working pressure (MPa)
1.6
Entering/Leaving water pipe Condensing water pipe Copper pipie diameter (mm) Type/Material
R3
R2-1/2
12.7 High Efficient Centrifugal Multi-blades Fan/Galavnize Steel
Drive type Fan disdcharge orientation Power source
Motor output power (kW)
R2-1/2 R1-1/4
V-belt Horizontal discharge /Top discharge 380V/3N~/50Hz
Motor type Motor
R2-1/2
3-Phase Asynchronous Motor,Class F, no less than IP54 I(5)
7.5(11)(6)
11(11)
11(15)
15(15)
II(5)
11(11)
11(15)
15(15)
15(18.5)
III(5)
11(11)
15(15)
15(15)
18.5(18.5)
IV(5)
15(15)
15(15)
18.5(18.5)
18.5(18.5) Nylon 21 25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel
Casing
Type/Material Thickness (mm) Type Height (mm)
1549
1709
1869
2029
Unit dimension
Length (mm)
1646
1646
1806
1806
Width (mm) Height (mm) Width (mm) Length (mm)
2766 1566 1846 2966
2766 1726 1846 2966
2926 1886 2006 3126
2926 2046 2006 3126
Filter
Packing dimension
NOTES: 1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY. 2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB; STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB; STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER; STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER; 3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW SELECTION SOFTWARE. 4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL. 5) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION. 6) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.
6
Double Skin Fan Coil unit DDW
DDW-V (Vertical) Model Nominal Air Flow (m3/h) External total pressure (Pa) Nominal cooling capacity (kW) Nominal heating capacity (kW)
DDW040V 4000
Fan
DDW080V 8000
DDW100V 10000
DDW120V 12000
DDW150V 15000
-
-
-
-
-
-
-
II(6)
150
150
150
150
150
150
150
III(6)
220
220
220
220
220
220
220
IV(6)
300
300
300
300
300
300
300
4 Rows (Return air)
23
29
36
49
62
72
90
4 Rows (Fresh air)
54
69
78
106
135
164
194
6 Rows (Return air)
31
39
54
61
76
94
118
6 Rows (Fresh air)
69
85
102
132
164
202
259
4 Rows (Return air)
39
49
59
80
100
120
152
4 Rows (Fresh air)
64
80
96
128
161
193
241
6 Rows (Return air) 6 Rows (Fresh air)
47 75
59 93
71 112
95 149
119 187
141 223
176 279
R2
R2-1/2
Corrugated aluminum fin mechanically bonded with copper tube
FPI
12
Working pressure (MPa)
1.6
Entering/Leaving water pipe Condensing water pipe
R2
R2
R2
R2
R2
R1-1/4
Copper pipie diameter (mm)
12.7
Type/Material
High Efficient Centrifugal Multi-blades Fan/Galavnize Steel
Drive type
V-belt
Fan disdcharge orientation
Top discharge
Power source
380V/3N~/50Hz
Motor type Motor
DDW060V 6000
I(6)
Type
Coil
DDW050V 5000
Motor output power (kW)
I(6) II(6)
0.75(1.1)(7)
III(6) IV(6)
1.1(1.1) 1.1(1.5)
3-Phase Asynchronous Motor,Class F, no less than IP54 1.1(1.1) 1.5(1.5) 1.5(2.2) 2.2(2.2) 2.2(3.0)
3.0(4.0)
1.1(1.5) 1.5(1.5)
4.0(4.0) 4.0(5.0)
Type/Material
2.2(2.2) 2.2(2.2) Nylon
Thickness (mm)
21
Casing
Type
25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel
Unit weight (kg)
4 Rows
199
225
246
274
345
369
432
6 Rows
208
237
259
305
367
399
474
Height (mm)
1283
1343
1403
1613
1853
1923
1673
Length (mm)
980
1140
1210
1320
1390
1530
2090
Width (mm)
650
650
650
810
900
900
900
Height (mm)
1470
1530
1590
1800
2040
2110
1860
Width (mm)
860
860
860
1020
1110
1110
1110
Length (mm)
1160
1320
1390
1500
1570
1710
2270
Filter
Unit dimension Packing dimension
1.5(2.2) 2.2(2.2)
2.2(2.2) 2.2(3.0)
3.0(3.0) 3.0(3.0)
NOTES: 1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY. 2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB; STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB; STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER; STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER; 3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW SELECTION SOFTWARE. 4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL. 5) MODEL DDW040~250V ARE WITHOUT FRAME; DDW300~450V ARE WITH FRAME TYPE. 6) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION. 7) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.
7
DDW
Double Skin Fan Coil unit
DDW-V (Vertical) Model
DDW180V
DDW200V
DDW250V
DDW300V
DDW350V
DDW400V
DDW450V
Nominal Air Flow (m3/h)
18000
20000
25000
30000
35000
40000
45000
I(6)
-
-
-
300
300
300
300
II(6)
150
150
150
400
400
400
400
III(6)
220
220
220
500
500
500
500
300 109 239
300 121 266
300 154 342
600 178 390
600 205 448
600 238 520
600 266 577 329
External total pressure (Pa) Nominal cooling capacity (kW) Nominal heating capacity (kW)
Coil
Fan
IV(6) 4 Rows (Return air) 4 Rows (Fresh air) 6 Rows (Return air)
135
152
193
222
256
296
6 Rows (Fresh air)
313
347
427
490
556
639
703
4 Rows (Return air)
183
200
250
295
337
391
437
4 Rows (Fresh air)
292
325
393
472
534
604
670
6 Rows (Return air) 6 Rows (Fresh air)
214 336
237 373
297 469
371 544
398 629
450 719
500 802
Type
Corrugated aluminum fin mechanically bonded with copper tube
FPI
12
Working pressure (MPa)
1.6
Entering/Leaving water pipe
R2-1/2
R2-1/2
R3
R3
R2-1/2
R2-1/2
Condensing water pipe
R1-1/4
Copper pipie diameter (mm)
12.7
Type/Material
High Efficient Centrifugal Multi-blades Fan/Galavnize Steel
Drive type
V-belt
Fan disdcharge orientation
Top discharge
Power source
380V/3N~/50Hz
Motor type
3-Phase Asynchronous Motor,Class F, no less than IP54 I
Motor Motor output power (kW)
R2-1/2
(6)
-
-
-
7.5(11)
11(11)
11(15)
15(15)
II(6)
4.0(4.0)(7)
4.0(4.0)
5.5(5.5)
11(11)
11(15)
15(15)
15(18.5)
III(6) IV(6)
4.0(5.5) 5.5(5.5)
4.0(5.5) 5.5(5.5)
5.5(7.5) 7.5(7.5)
11(11) 15(15)
15(15) 15(15)
15(15) 18.5(18.5)
18.5(18.5) 18.5(18.5)
Type/Material
Nylon
Thickness (mm)
21
Casing
Type
25mm Double skin,outer plate material is color coated steel,inner plate material is EG steel
Unit weight (kg)
4 Rows
485
538
622
-
-
-
-
6 Rows
536
595
664
-
-
-
-
Filter
Unit dimension Packing dimension
Height (mm)
1923
1983
2043
2555
2715
3035
3195
Length (mm)
2240
2320
2670
2766
2766
2926
2926
Width (mm)
900
900
900
1006
1006
1166
1166
Height (mm)
2110
2170
2230
2572
2732
3052
3212
Width (mm)
1110
1110
1110
1206
1206
1366
1366
Length (mm)
2420
2500
2850
2966
2966
3126
3126
NOTES: 1) THE ABOVE PARAMETERS ARE FOR STANDARD PRODUCTS ONLY. 2) STANDARD RETURN AIR COOLING CONDITIONS: 27ºC DB/19.5ºC WB; STANDARD FRESH AIR COOLING CONDITIONS: 34ºC DB/28ºC WB; STANDARD RETURN AIR HEATING CONDITION: 21ºC DB; STANDARD FRESH AIR HEATING CONDITION: 0ºC WB STANDARD CHILLED WATER ENTERING/LEAVING CONDITIONS: 7ºC FOR ENTERING WATER; 12ºC FOR LEAVING WATER; STANDARD HOT WATER ENTERING/LEAVING CONDITIONS: 60ºC FOR ENTERING WATER; 50ºC FOR LEAVING WATER; 3) THE UNIT SUPPORTS HIGHER ESP AS REQUIRED BY CUSTOMERS. FOR DESIRED CONFIGURATIONS, PLEASE USE DAIKIN DDW SELECTION SOFTWARE. 4) WATER INLET/OUTLET NPT CONNECTION IS OPTIONAL. 5) MODEL DDW040~250V ARE WITHOUT FRAME; DDW300~450V ARE WITH FRAME TYPE. 6) THE I, II, III, IV INDI CADES THE PARAMETERS CNDER DEFINED TOTAL PRESSURE CONDITION. 7) THE MOTOR OUTPUT POWER IS TESTED UNDER THE CORRESPONDING EXTERNAL TOTAL PRESSURE I, II, III, IV INDI CATES AND THE UALNE IN THE BARCFET IS THE MOTOR OUTPUT POWER OF CODWS UNITS THE OTHER VAIUE IS THE 4 ROWS UNITS.
8
Double Skin Fan Coil unit DDW
External static presure check list DDW-H Unit model
DDW020H DDW030H DDW040H DDW050H DDW060H DDW080H DDW100H DDW120H DDW150H DDW180H DDW200H
Nominal air flow (m3/h)
ETP (Pa)
ESP (Pa)
2000
3000
4000
5000
6000
8000
10000
12000
15000
18000
20000
I
80
80
80
-
-
-
-
-
-
-
-
II
150
150
150
150
150
150
150
150
150
150
150
III
220
220
220
220
220
220
220
220
220
220
220
IV
-
-
-
300
300
300
300
300
300
300
300
I
50
34
39
-
-
-
-
-
-
-
-
II
120
104
109
86
104
68
99
77
35
61
85
III
190
174
179
156
174
138
169
147
105
131
155
IV
-
-
-
236
254
218
249
227
185
211
235
DDW-V Unit model
DDW040V
DDW050V
DDW060V
DDW080V
DDW100V
DDW120V
DDW150V
DDW180V
DDW200V
Norminal air flow (m3/h)
4000
5000
6000
8000
10000
12000
15000
18000
20000
I
-
-
-
-
-
-
-
-
-
II
150
150
150
150
150
150
150
150
150
III
220
220
220
220
220
220
220
220
220
IV
300
300
300
300
300
300
300
300
300
I
-
-
-
-
-
-
-
-
-
II
69
86
58
68
85
56
78
61
85
III
139
156
128
138
155
126
148
131
155
IV
219
236
208
218
235
206
228
211
235
ETP (Pa)
ESP (Pa)
DDW-H/V Unit model Norminal air flow (m3/h)
ETP (Pa)
ESP (Pa)
DDW250H DDW300H DDW350H DDW400H DDW450H DDW250V DDW300V DDW350V DDW400V DDW450V 25000
30000
35000
40000
45000
25000
30000
35000
40000
45000
I
-
300
300
300
300
-
300
300
300
300
II
150
400
400
400
400
150
400
400
400
400
III
220
500
500
500
500
220
500
500
500
500
IV
300
600
600
600
600
300
600
600
600
600
I
-
201
165
188
159
-
201
165
188
159
II
48
301
265
288
259
48
301
265
288
259
III
118
401
365
388
359
118
401
365
388
359
IV
198
501
465
488
459
198
501
465
488
459
NOTES: THE DATA IS FOR STANDARD UNIT.ESP VALUE IS BASED ON ETP VALUE.FOR EXAMPLE,THE ESP VALUE IS 50PA WHEN ETP IS 80PA FOR DDW020H UNIT.
9
DDW
Double Skin Fan Coil unit
Dimensions DDW-H (Horizontal)
Hanging holes 4- 15
Manual air vent Leaving water pipe D Entering water pipe D Condensation water drain pipe C
DDW-H Horizontal Discharge
Hanging holes 4- 15
Leaving water pipe D
Entering water pipe D Condensation water drain pipe C
DDW-H Top Discharge Unit: mm
Dimension
Width
Length Height
Return air
Supply air B
Connection pipe Entering Condensation dimension water pipe water drain pipe
Hanging holes
MODEL
W
L
H
F
G
A
D
C
DDW020H
900
960
600
810
460
298
262 1080 1020 910 150 201 191 85
K
M
158 276
R 1-1/2
R 1-1/4
DDW030H
1050
1000
650
960
510
331
289 1230 1170 950 150 207 280 85
158 339
R 1-1/2
R 1-1/4
DDW040H
1080
1100
730
990
590
395
341 1260 1200 1050 150 177 234 85
164 454
R2
R 1-1/4
DDW050H
1250
1060
730
1160
625
395
341 1430 1370 1010 150 216 317 85
164 454
R2
R 1-1/4
DDW060H DDW080H
1320 1680
1150 1150
800 800
1230 1590
660 660
471 471
404 1500 1440 1100 150 243 324 85 404 1860 1800 1100 150 243 529 85
164 518 164 518
R2 R2
R 1-1/4 R 1-1/4
10
N
J
S
E
P
Q
R
Double Skin Fan Coil unit DDW
DDW-H (Horizontal)
L N
F
28.5
Hanging holes 4- 15
40
T
A
W M K
Manual air vent Leaving water pipe D
R
G
90
H
A
E
50 P
95
J
Q
B
Enteringentering water pipe D pipe D Chilled water Condensation water drain pipe C
DDW-H Horizontal Discharge
L N
F
28.5
Hanging holes 4- 15 W M K
Leaving water pipe D S
E
A
A
G
R H
T
40
B
90
50 P
95
Q
Enteringentering water pipe D pipe D Chilled water Condensation water drain pipe C
DDW-H Top Discharge
Unit: mm
Dimension
Width
Length Height Return air Supply air F
G
Condensation Connection pipe Entering water water drain dimension pipe pipe
Hanging holes
MODEL
W
L
H
A
B
K
M
N
J
Q
R
D
C
DDW100H
1690
1170
930
1600 790
373
404
1870
1810
1120
150
194 102 85
164
645
R2
R 1-1/4
DDW120H
1690
1170
1050
1600 910
373
404
1870
1810
1120
150
194 102 85
164
772
R2
R 1-1/4
DDW150H
1940
1170
1180
1850 1040 373
404
2120
2060
1120
150
194 237 85
172
883
R 2-1/2
R 1-1/4
DDW180H
2120
1310
1240
2030 1100 430
478
2300
2240
1260
150
295 197 85
172
946
R 2-1/2
R 1-1/4
DDW200H DDW250H
2300 2400
1310 1310
1240 1430
2210 1100 557 2310 1290 557
478 478
2480 2580
2420 2520
1260 1260
165 165
295 135 85 295 107 85
172 178
946 R 2-1/2 1124 R3
R 1-1/4 R 1-1/4
11
S
E
P
DDW
Double Skin Fan Coil unit
DDW-H (Horizontal)
L
F
T
40
A
W
A Manual air vent
90
Leaving water pipe D Entering water pipe D
H
G
Leaving water pipe D
B
Entering water pipe D
63
J
125
P
Condensation water drain pipe C
DDW-H Horizontal Discharge
L
F
Unit: mm
W Width
MODEL
W
L
H
DDW300H
2766
1646
1549
DDW350H
2766
1646
DDW400H
2926
1806
DDW450H
2926
1806
A Supply air
G
A
Length Height Return air
Hanging holes J
S
Manual air vent Entering Condensation waterEntering pipe water drain pipe
water pipe D
E
T
P
DEentering
2670 1390 569 569
273
450
352 200
98
1709
2670 1550 569 569
284
450
352 203
98
R 2-1/2
1869
2830 1710 638 638
266
500
352 213
98
water pipe D R 2-1/2 R 1-1/4
2029
2830 1870 638 638
266
500
352 213
98
R 2-1/2 Entering
DDW-H Top Discharge
12
C
water pipe R D 1-1/4 R3 Leaving
R 1-1/4 R 1-1/4
water pipe D
P
B
Connection pipe dimension
A
125
F
T
H
Dimension
E
40
S
63
B
G
90
Condensation water drain pipe C
Double Skin Fan Coil unit DDW
DDW-V (Vertical)
F
S
A
E
40
B
Manual air vent
R
G
H
Leaving water pipe D
Condensation water drain pipe C
N L
90
P
Q
63
Entering water pipe D
M W
DDW-V Top Discharge
Unit: mm
Dimension
Width
MODEL DDW040V DDW050V DDW060V DDW080V DDW100V DDW120V
W 980 1140 1210 1320 1390 1530
Length Height L 650 650 650 810 900 900
H 1283 1343 1403 1613 1853 1923
Return air
Supply air
F 890 1050 1120 1230 1300 1440
A 331 395 395 471 557 557
G 655 687 740 842 1014 1070
B 289 341 341 404 478 478
Connection pipe dimension
Hanging holes M 960 1120 1190 1300 1370 1510
N 630 630 630 790 880 880
13
S 71 84 84 98 98 102
E 444 480 480 517 574 639
P 85 85 85 85 85 85
Q 164 164 164 164 164 164
R 518 518 581 708 835 899
Entering Condensation water water drain pipe pipe D R2 R2 R2 R2 R2 R2
C R 1-1/4 R 1-1/4 R 1-1/4 R 1-1/4 R 1-1/4 R 1-1/4
DDW
Double Skin Fan Coil unit
DDW-V (Vertical) F
A
40
S
20
B
A
T
E
Leaving water pipe D
G
R
H
Entering water pipe D
90
P
63
Q
Condensation water drain pipe C
N
M
L
W
DDW-V Top Discharge
Unit: mm
Dimension
Width
Length
Height
MODEL DDW150V DDW180V DDW200V DDW250V
W 2090 2240 2320 2670
L 900 900 900 900
H 1673 1923 1983 2043
Return air F 2000 2150 2230 2580
G 923 1035 1109 1155
Supply air A 471 430 557 557
B 404 478 478 478
Connection pipe dimension
Hanging holes M 2070 2220 2300 2650
14
N 880 880 880 880
S 144 100 98 100
E 167 440 156 156
P 85 85 85 85
Q 172 172 172 178
R 756 883 946 997
Entering Condensation water water drain pipe pipe D R 2-1/2 R 2-1/2 R 2-1/2 R3
C R 1-1/4 R 1-1/4 R 1-1/4 R 1-1/4
Double Skin Fan Coil unit DDW
DDW-V (Vertical)
B
E
A
T
A Leaving water pipe D
40
S
40
F
Entering water pipe D
H
Lveaing water pipe D
63
G
Entering water pipe D
L
P 63
M W
Condensation water drain pipe C
DDW-V Top Discharge
MDW-V Top Discharge Dimension Width
Length Height
Return air
Supply air
Unit: mm
Hanging holes
Connection Condensation Entering water pipe water drain pipe dimension pipe P D C
MODEL
W
L
H
F
G
A
B
E
T
S
DDW300V
2766
1006
2555
2670
1390
569
569
284
450
305
98
R3
R 1-1/4
DDW350V
2766
1006
2715
2670
1550
569
569
273
450
305
98
R 2-1/2
R 1-1/4
DDW400V
2926
1166
3035
2830
1710
638
638
276
500
357
98
R 2-1/2
R 1-1/4
DDW450V
2926
1166
3195
2830
1870
638
638
267
500
357
98
R 2-1/2
R 1-1/4
15
DDW
Double Skin Fan Coil unit
Fan Discharge Type Horizontal Air Discharge For DDW-H Horizontal Type
Top Air Discharge For DDW-H Horizontal Type
Horizontal air discharge of DDW-H fans
Top air discharge for DDW-H fans
Top Air Discharge For DDW-V Vertical Type
Top Topair airdischarge dischargeofofDDW-V MDW-Vfans fans
16
Double Skin Fan Coil unit DDW
Selection Software DAIKIN Smart Tools provide customers with more convenient and reliable services Professional model selection software for air handling units Convenient graphical user interface Providing most economic and reasonable combination solutions Provide different configuration options according to the requirements of the customer Output the performance table of the unit according to the customer’s requirements Figuring out the component list and automatically calculate the price of the entire unit Output units arrangement drawing, development drawing and technical specifications
17
DDW
Double Skin Fan Coil unit
Special Notes Facing air discharge, if the chilled hot water inlet/outlet is on your left, the unit is L connection. Otherwise,
the unit is R connection. For vertical type unit,refer to the below chart to judge the connection. Please provide unit model, quantity and operating condition when purchasing. Please contact us if any other specifications required.
Right connection
Leaving air
Entering air
Left connection
Figure 1 (Horizontal unit)
Right connection
Entering air
Left connection
Figure 2 (Vertical unit)
18
Double Skin Fan Coil unit DDW
Wiring Diagrams Motor power input < 11kW
U
V
Motor power input ≥ 11kW
W
U1
M ~
V1
W1 U2
V2
M ~
NOTE: TO CONNECT ELECTRIC CONTROL DEVICES, PLEASE USE OVER-CURRENT, SHORT CIRCUIT AND OVERHEAT PROTECTORS.
19
W2
DDW
Double Skin Fan Coil unit
Installation Installing DDW Important Notice Installation and maintenance are to be performed only by technicians who are familiar with local rules and regulations, and experienced with this type of equipment. Make sure that the rated voltage of the power supply conforms to the voltage stated on the unit nameplate. Cut off all power supplies before mounting or maintaining the unit. Electric connections must conform to local laws and regulations. The voltage should fluctuate within the range of ± 10% of the rated voltage. The unit must be well earthed to prevent insulation failures. All the wires must be securely connected. The design of water pipes and ducts must conform to the Specifications of Heating, Ventilation and Air Conditioning (GBJ19-87). DDW Mounting Location Make sure it is convenient to connect wires and pipes in the selected mounting location. The minimum space reserved around DDW horizontal units is shown in Figure 1; DDW vertical units are shown in Figure 2. Unit: mm
50
0 50
0
0
50
0
50
00
10
00
10
Figure 1
Figure 2
20
Double Skin Fan Coil unit DDW
Suspending Installation During the installation, please handle the unit or packing case with care, to avoid damage to any part. Before leaving the factory, the unit or its packing case already has forklift handling holes or hoisting holes. During the hoisting, the lifting poles should be strong enough to bear the unit weight. Please handle the DDW unit as shown in Figure 3.
4
4
3
2
3
2
1
1
Figure 3
Storage When a unit is placed protect it from dirt, rain, snow and even animals. Be sure not to damage the protective film on its surface.
Base Setup Adjust the base levelness The base, if not put on a level surface, may result in water leakage or break the dynamic balance of the fan due to poor drainage of condensing water or cause the bearing to fail or vibrate. The base height should match the U-shaped pipe blend. The drain pipe should be connected with the Ushaped water seal, as shown in Figure 4. Need suitable water seal when installing in order to condensation water drain smoothly.
H
Drain pipe
P = Negative pressure value (Pa) inside the unit H ≥P/10+20(mm)
NOT MORE THAN 1/2H Drain bend
Figure 4 21
DDW
Double Skin Fan Coil unit
Servicing And Maintenance Notices Responsibilities And Obligations This product comes to you with the DAIKIN service warranty. Only DAIKIN technicians or experienced technicians authorized by DAIKIN are allowed to install, test or maintain these products.
Using The Unit After installing the piping system, please first wash the pipes. To do so, be sure to shut off the valve connected to the unit, to prevent unwanted things in the pipes from entering the coils or blocking the loop. After the installation, please check there is anything unwanted inside the fan. Turn the blades by hand. If no unusual noise is heard, turn on the fan, to see if it is running properly. Before turning on the water flow, please open the exhaust valve to let the air out of the pipe till water flows out from the pipe. When the unit stops running, fill the coil with water or otherwise keep the pipe from erosion. When the environment temperature falls below 0°C in the winter, drain the pipe to prevent it from freezing. Clean the coils at regular intervals, to remove the dust from the coils. Clean the scale inside the coils every 2 or 3 years. If possible, use soft water to supply hot/cold water to the coils. Check the unit filter for dust regularly; if possible, please use a pressure difference detector. Once the resistance reaches the limit, wash or replace the filter media in time. After the unit runs for a week, please readjust the V-belt. Afterwards, check the belt every three months.
Servicing And Maintenance A sound maintenance schedule helps reduce operational failures. A dirty filter may worsen the performance and air flow of the unit. Thus, replace or wash the filter in time. Be sure to check the filter every month to see if it is clean enough. Wash the coils with compressed air or water. Brush the coil surface gently with a soft brush or use a vacuum cleaner to clean the dust. Do the following on a regular basis: Clean up the fans every 6 months, to keep them in good balance. Check and clean the water coils. Check the drain pipe in case dust or unwanted things block the pipes. Check if the bearing comes loose. If so, fix the fastening screw tightly to the bearing. Clean the dirt in the coils at regular intervals. Check that the side front of the fan V-belt is flush with the side front of the motor V-belt, to make sure the pulleys are placed on a flat plane. Usually, check using the four-point method (see Figure 5). Use V-belts of the same brand and model. Never mix old V-belts with new ones. Make sure that the V-belts match the pulley grooves. Use a tensiometer to check the V-belts, and tighten them properly (see Figure 6).
22
Double Skin Fan Coil unit DDW
Check and adjust the levelness of the V-belt using the four-point method, as shown in Figure 5. Ruler A
B
C
D
Figure 5
Check the tightness of the V-belt, as shown in Figure 6. C sp ente ac r to ing c e
nte
r
The belt tension indicator acts on the midpoint of center-to-center spacing
Torture 16mm every meter
Figure 6
23
DDW
Double Skin Fan Coil unit
Common Failures DDW Common Failures
Locations
1. Blower
Possible Causes
Solutions
Blower out off center
Contact the seller
Loose bearings due to large gap
Contact the seller
Blower is loose
Contact the seller
Loose connection between bearings
Contact the seller
Blower is damaged
Contact the seller
The fan fastening screw is loose
Fasten the screw
There are unwanted things inside fans.
Remove unwanted things
Belt pulley is not fastened on the axis. Fasten the V-shaped belt V-shaped belt is loose. Adjust after it runs for 48 hours for the Adjust the V-shaped belt first time. V-shaped belt is too tight Adjust the V-shaped belt 2. Drive
The V-shaped belt model is not right V belts are of different length
Replace the V-shaped belt Replace V-shaped belts with those of the same length
The V-shaped belt pulley of the fan does not align with that of Align the belt pulleys the motor V-shaped belt is damaged Replace the V-shaped belt
3. Bearing
Abnormal sound 4. Fan house
The screw fixing the motor to the motor base is loose
Fasten the screw
Bearing failure
Replace bearings
Lack of lubricant oil
Add lubricant oil
The bearing housing is loose
Fasten the bearing housing
The bearing is not mounted flush
Re-mount the bearing
There are unwanted things inside bearings
Remove unwanted things
Bearings are damaged
Replace bearings
Bearings are rusty
De-rust or replace bearings
There are unwanted things inside houses
Remove the unwanted things
House is loose
Contact the seller
Air intake house is damaged
Contact the seller
Incoming line is loose
Fasten the incoming line
5. Electric appliances Motor gives AC hum
6. Axis
7. Air speed is too high
Contact the seller.
Phase lack
Supply 3-phase power
Bent or distorted
Replace axis
Balance weight is loose
Fasten the balance weight
Axis is loose
Fasten axis
Duct is too small
Re-design the duct Change the V-shaped belt pulley to reduce Static pressure has not reached the set static pressure value the fan speed The duct is too small Re-design the duct
8. Periodical vibration System is unstable
Adjust the system
Duct vibrates as the fan pulsates
Adjust the fan speed
9. Noise caused by hispeed wind passing Duct leaks the aperture & holes
Seal it with glue
Duct turns too sharply
Re-design the duct
Duct expands sharply 10. When blocked, the high-speed air Duct shrinks sharply rattles or howls Air speed is too high inside the duct
Re-design the duct Re-design the duct Re-design the duct
Damping connector is too tight
Re-adjust the damping connector
24
Double Skin Fan Coil unit DDW
Common failures
Locations
Possible causes
Solutions
Blower is mounted incorrectly
Contact the seller
Fan rotates in the opposite direction
Regulate the power phase sequence
Actual resistance in the duct exceeds set resistance.
Re-design the system
Duct is poorly sealed
Seal with glue
Fireproof valve is shut off
Shut on the fireproof valve
3. Filter
Too dirty or even blocked
Clean or replace filter
The fan is 4. Coil functioning but the air 5. Blocked air supply supply is insufficient 6. Fan air inlet is blocked
Too dirty or even blocked
Clean coil
1. Fan
2. Duct system
The air inlet and the air outlet are not properly isolated. Thus, Add air deflector the air runs directly to the air inlet through the separator Elbow at the return air inlet and fan outlet are too close to the Move the fan unit wallboard The fan outlet is blocked
Remove the obstructions
A length of straight tube is mounted at the fan outlet during 7. No collimator tube at fan testing. Without straight tube, the fan performance might the fan outlet be worsened. Thus, the fan may run faster to offset the resistance. (Check the fan speed) 8. There’re unwanted The fan outlet is blocked things inside fan There is an elbow at the fan outlet system
The fan is functioning 1. System but the air supply is too large 2. Duct
Mount collimator tube Remove the obstructions Re-design duct
Improper duct size
Remove the obstructions
The access door is open
Close the access door
The system is not well balanced and the actual resistance is lower than the set resistance
Re-design the system
No air valve or air valve blade
Mount wind valve or wind valve blower
Filter falls off
Re-mount the filter
Return duct leaks
Seal it with glue
25
Warning
● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation. ● Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. ● Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. ● Read the User’s Manual carefully before using this product. The User’s Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer.
The air conditioners manufactured by Daikin Industries have received ISO 9001 series certification for quality assurance.
The airconditioning factories of Daikin Industries have received environmental management system standard ISO 14001 certification.
Certificate Number. 9601019
Certificate Number. EMS80362
Cautions on product corrosion 1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the unit close to the sea shore, contact your local distributor.
Dealer Head Office: Umeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan http://www.daikin.com/global_ac/ © All rights reserved
Literature No.: PCUA14-10 Supersedes: ED-DDW-201311B