DESIGN OF FOUNDATION FOR COLUMN OF COMPOUND WALL (CITY PLOT)
C/L of footing C/L OF FOOTING
810
2200
290
2200
Axial Load form staad =71 kN Moment
= 41kNm
footing at depth of 1.4m below NGL
C/C dist b/w column center line & footing center line = 0.29m Weight of soil above Foundation =2.2x2.2x1x18 (1m depth of soil above foundation) = 87.12 kN Weight of Foundation = 2.2x2.2x.4x25=48.4kN Total Axial load =71+87.12+48.4
= 206.62 KN
Additional moment due to Eccentricity
= 71X0.29=21kNm
Total moment = 41+21=61 kNm Eccentricity of loading (e) =
Check for one way shear Base pressure at dist of d from face of column=8.92+(0.805x67.58/2.2)=33.65kN/m2 Shear force at a dist d form face of column 810
225
352
805
233
Max S.F =33.65 x0.805+0.5x(76.5-33.65)x0.805=44.4kN TV=
44 .4 X 10 3 =0.13x1.5=0.19 1000 X 340
Ast provided =
Pt =
3.14 1000 =565.2mm² x122 x 4 200
565.2 x100 =0.16% 1000x340
Tc= 0.29; TV< Tc hence safe Check for 2 – way shear Ast a dist d/2 form face of column 790
Axial load from staad = 70 kN ( Excluding soil weight and weight of footing) 70 KN will act at centre of column Weight of soil =2.2x2.2x1x18 =87.12 kN will out at centre of footing Weight of footing =2.2x2.2x25 = 121 kN will out at centre of footing Total dead weight = 121+87.12+70 =278.12 = 279 kN Normal due to wind load from staad =41kNm Normal due to Earth Pressure =8.316x1.4x0.5x⅓x(1.4) =2.45kNm
ᵤ(coeff of friction)=0.45 considered for coarse grained soil with silt
kNm
Design of 230 thk brick wall for wind load Clear Height of Brick wall = 1.84m Clear Length of Brick wall = 4.9-0.3=4.6m Check for slenderness
Safe as for table 7 IS 1905 K₁ =1.0; considering as permanent structure with design life 50 years K₂= considering class A & category 2=1 K₃ =Topography factor taken as 1 Design wind speed =50x1x1x1=50m/s P₂=0.6x50²=1.5KN/M² Force co-eff as per table 24-IS-875-part 3 for b/h=
=2.5 &one edge on ground is 1.2
Panel load on wall =1.5x1.2x1.84x4.6=15.2 kN U.D.L due to self weight =0.23x1.84x18=7.61 kN/m Compressive strength =
=0.033
Bending moment for H/L =0.4=
as per table 14 IS 1905 -1987
M =Section modulus(Parallel to bed joint) ZH=
kNm
=16.22x10⁶ mm3
Bending strength due to wind (Parallel to bed joint) =
=0.079
=40.55x10⁶ mm3
Section modulus(Perpendicular to bed joint) ZL=
Bending strength due to wind (Perpendicular to bed joint) =
=0.0318
Now, Max comp stress (Parallel to bed joint)
=0.079+0.033 =0.112 N/mm²
For M1 grade Masonry with C.M Proportion 1:5 (corresponding to masonry strength of 5 N/mm²) Max Comp stress as per table 8 is 0.5 N/mm² 0.112<0.5 N/mm² (safe) Max tensile stress (Parallel to bed joint)
=0.079-0.033 =0.046<0.14(safe) As per cl 5.4.2 IS 1905