in this paper comparison is made on the basis of soil strata. Various responses are taken for the comparison. STAAD PRO software is used for analysis. PEB structure is used for analysis in staad pro software. Prof. G. S. Patil | Dr. Prof. M. B. Choug
Descrição completa
Full description
Descrição completa
Dryer Design
172.16.6.215
Design Calculations For Compressed For Compressed Air Piping Pipe Line Diameter
D
=
(1.6*10^3*V^1.85*L/(10^10*$p*
V
=
0.2831684
cum/sec
L
=
30
m
$p
=
0.0075842
bar
Presure drop in bar
Pmax
=
6.894757
bar
Operating Pressure
D
=
volume of air Equivalent Length of
0.097683 m 97.68294 mm 100 mm
Recommen
Pressure Drop Calculations $p
=
1.6*10^3*V^1.85*L/(10^10*D^5
V
=
0.2831684
cum/sec
L
=
274.6
m
Equivalent Length of
D
=
0.1
m
Diameter of the pipe
Pmax
=
6.894757
bar
$p
=
volume of air
Operating Pressure 1.6*10^3*V^1.85*L/(10^10*D^5 0.0090 0.009001 01 Bar Bar
Available Pressure At the end Point
6.885756 Bar
Total Length of Pipe Actual Accessori Total Length(M) es (M) Length(M) 20 0
7 4 .6
274.6
Values Of 'C' Cast Iron
100
Mild Steel 120 Galvanise 120 Equivalent Length of Fittings a t Fittings & Valves