U
PID A/D
RAM F
GLOBAL SUPPLIERS OF TURBINE
ID
AND COMPRESSOR CONTROL SYSTEMS
UM3300/H
Series 3++ Hardware Referencemanual
# Hardware Reference Installation, Maintenance and General Operation Publication UM3300/H (1.1.0) Product Version: #61-001 August 2007
Documentation Feedback Form 4725 121st Street Des Moines, Iowa 50323, U.S.A. Phone: (515) 270-0857 Fax: (515) 270-1331 Web: www.cccglobal.com
For a list of certifications, see the Agency Certifications for Series 3++ Controllers technical note [TN41] at the back of this manual. For environmental and safety recommendations, see page 14
© 1987-2007, Compressor Controls Corporation. All rights reserved. This manual is for the use of Compressor Controls Corporation and is not to be reproduced without written permission. Air Miser, Guardian, Recycle Trip, Reliant, Safety On, SureLink, TTC, Total Train Control, TrainTools, TrainView, TrainWare, Vanguard, Vantage, WOIS, and the TTC and impeller logos are registered trademarks; and COMMAND, TrainPanel, and the Series 3++ and Series 5 logos are trademarks of Compressor Controls Corporation. Other company and product names used in this manual are trademarks or registered trademarks of their respective holders. The control methods and products discussed in this manual may be covered by one or more of the following patents, which have been granted to Compressor Controls Corporation by the United States Patent and Trademark Office: 4,949,276 5,622,042 5,879,133 6,116,258 6,494,672
5,347,467 5,699,267 5,908,462 6,217,288 6,503,048
5,508,943 5,743,715 5,951,240 6,317,655
5,609,465 5,752,378 5,967,742 6,332,336
Many of these methods have also been patented in other countries, and additional patent applications are pending. The purpose of this manual is only to describe the configuration and use of the described products. It is not sufficiently detailed to enable outside parties to duplicate or simulate their operation. The completeness and accuracy of this document is not guaranteed, and nothing herein should be construed as a warranty or guarantee, expressed or implied, regarding the use or applicability of the described products. CCC reserves the right to alter the designs or specifications of its products at any time and without notice.
Series 3++ Hardware Reference
3
Document Scope This manual provides the information you will need to physically install and maintain Series 3++ Controllers. However, it does not tell how to configure or tune them, nor how to program a host computer or DCS to utilize their Modbus communication interface (see the Series 3++ Modbus Reference manual [UM3300/M]). Chapter 1
describes the components of and provides safety and environmental recommendations for Series 3++ Controllers.
Chapter 2
describes the parameter memory and tells how to view or alter parameter values or run tests from the engineering panel.
Chapter 3
tells how to mount Series 3++ Controllers and connect their field I/O and communication cables.
Chapter 4
describes the general operation of the controller and tells how to configure the field I/O circuits.
Chapter 5
tells how to set up and operate redundant controllers.
Chapter 6
discusses controller maintenance and troubleshooting.
Appendix A
describes each configuration or tuning parameter discussed in the body of this manual.
Appendix B
describes the controller test procedures that can be executed from the engineering panel of a Series 3++ Controller.
The following supporting documents are included at the back of this manual: DS3300/P
lists the replaceable components of the Series 3++ Controller.
DS3300/C
specifies the physical and electrical characteristics of Series 3++ Compressor Controllers.
DS3300/T
specifies the physical and electrical characteristics of Series 3++ Turbine Controllers.
DS3300/N
describes the built-in Modbus TCP to RTU converter options.
DS3300/R
describes the Series 3++ Redundant Control Selector
DS3301/V
documents controller hardware revisions.
TN41
lists the agency certifications for Series 3++ Controllers.
The configuration and operation of each turbomachinery control application is described in its user manual:
August 2007
UM3301
Series 3++ Antisurge Controller
UM3302
Series 3++ Performance Controller
UM3303
Series 3++ Dual-Loop A/P Controller
UM3307
Series 3++ Speed Controller
UM3308
Series 3++ Extraction Controller UM3300/H (1.1.0)
4
Contents
Document Conventions The document title appears in the header of each odd-numbered page, while the chapter or appendix title appears in the header of even-numbered pages. Odd-page footers list the document number and revision level [UM3300/H (1.1.0)], while even-page footers provide the publication date (August 2007). Acronyms are defined in the sections of this manual that discuss the corresponding subjects, by placing them in parentheses following the spelled-out terms they represent. As an example, a three-letter acronym (TLA) is a way to represent a three-word subject by combining and capitalizing the initial letters of those three words. Most are also listed under Symbols and Acronyms on page 10. Cross-references to other documents specify a section and chapter, while cross-references between chapters of this document specify a page number. References that do not specify a location are internal to the chapter in which they appear. In computerized versions of this manual, all such references are hot-linked to their target locations and appear in green. Entries in the tables of contents, illustration and table lists, and index are also hot-linked but are not green. Attention may be drawn to information of special importance by using this text styling or one of the following structures:
Note:
Notes contain important information that needs to be emphasized.
Caution:
Cautions contain instructions that, if not followed, could lead to irreversible damage to equipment or loss of data.
Warning!
Warnings contain instructions that, if not followed, could lead to personal injury. The appearance of this electrical hazard warning symbol on CCC equipment or the word Warning appearing in this manual indicates dangerously-high voltages are present inside its enclosure. To reduce the risk of fire or electrical shock, do not open the enclosure or attempt to access areas where you are not instructed to do so. Refer all servicing to qualified service personnel. The appearance of this user caution symbol on CCC equipment or the word Caution appearing in this manual indicates damage to the equipment or injury to the operator could occur if operational procedures are not followed. To reduce such risks, follow all procedures or steps as instructed.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
5
Table of Contents Document Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Document Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Table of Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 List of Figures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 List of Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Symbols and Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
Hardware Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental and Safety Considerations . . . . . . . . . . . . . . . . . . . . . Components and Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . Component Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Input Channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Discrete Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Discrete Output Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . Serial Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary PCB Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Discrete Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . High-Current Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Frequency Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Position Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Front Panel Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Engineering Panel Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Back Panel Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Termination Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . Power Supply Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2
Engineering Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Support Software Packages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameter Memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Alternate Parameter Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data Groups and Pages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameter Checksum. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuration Forms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Engineering Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Key Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Viewing and Changing Parameter Values . . . . . . . . . . . . . . . . . . . Key Sequence Illustrations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Key Sequence Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Enabling Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . List Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Label Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Numeric Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameter Memory Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . .
August 2007
13 14 15 16 17 18 18 18 18 18 19 19 20 20 20 21 22 23 24 26 27 28 28 29 30 30 30 31 32 34 34 34 37 39 40 43
UM3300/H (1.1.0)
6
Contents Diagnostic Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 Bad CRC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 Com# POF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 CS= XXXX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 Error! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 No Store. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Chapter 3
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46 Internal Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47 Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47 CPU/IO Control Relay Switches . . . . . . . . . . . . . . . . . . . . . . . . . . .48 Analog Input Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 Analog Output Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 Auxiliary PCB Jumper Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Fault Relay Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Inductive Load Jumper. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Maximum Output Jumpers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Daughter Board Jumper. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52 Back-Panel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53 Discrete I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53 Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 Speed Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56 FTA Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 FIM 24Vdc Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 FIM Discrete Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58 FIM Analog Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59 FIM Speed Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 FIM Position Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 FOM 24Vdc Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62 FOM Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62 FOM Control Relay Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63 Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64 Serial Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64 Cable Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64 Surge Suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64 Termination Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64 Ports 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 Port 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 Port 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 Ports 3 and 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66 Port 3 and 4 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66 RS-232 Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Chapter 4
Configuration and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU/IO Board Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Machine Control Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reloading the Control Program . . . . . . . . . . . . . . . . . . . . . . . . . Serial Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Configuring Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . Discrete I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Speed Board Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Speed Board Discrete I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Position Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Speed Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Speed Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPU Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High-Current Analog Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bipolar Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Circuit Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Loopback Circuit Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Loopback Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Engineering and Front Panel Operation. . . . . . . . . . . . . . . . . . . . . . . Status Screen and Menu System Buttons . . . . . . . . . . . . . . . . . . . User Preferences and LED Tests. . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5
69 70 70 71 72 73 74 75 76 77 78 78 79 79 80 81 82 83 85 87 88 89 90 90
Redundant Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switching Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tracking Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Output Switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Redundant Control Selector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault Relay Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tracking Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RCS Power Failure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Unswitched Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Discrete Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Analog Input Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Serial Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ethernet Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 6
7
91 92 92 92 94 94 95 95 96 96 97 97 97 97 98 98
Maintenance and Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Monitoring Controller Health . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100 Internal Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
August 2007
UM3300/H (1.1.0)
8
Contents Field I/O Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101 Compressor Controller I/O Signals . . . . . . . . . . . . . . . . . . . . . .101 Turbine Controller I/O Signals . . . . . . . . . . . . . . . . . . . . . . . . . .102 Analog In Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103 Problem Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104 Fault Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104 Fault LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105 CPU/IO Fault Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105 Speed Board Fault Relay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105 Alarm System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106 External Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108 General Failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108 Relay Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108 Modbus/OPC Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109 Engineering Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .110 Tracking Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .110 Shutdown Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112 Power Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113 Front and Test Panel Problems . . . . . . . . . . . . . . . . . . . . . . . . . . .114 Communication Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115 CPU/IO Board Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .117 Analog Input Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118 Analog Output Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118 Discrete Input Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119 Discrete Output Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120 Speed Board Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121 Speed Input Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121 Positioning Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122 Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123 Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123 Return Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123 Component Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124 Controller Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125 Front Panel Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125 Programming and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . .126
Appendix A
Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
Appendix B
Controller Test Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137 Glossary/Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
9
List of Figures Figure 1-1 Figure 1-2 Figure 1-3 Figure 1-4 Figure 1-5 Figure 1-6 Figure 1-7 Figure 1-8 Figure 1-9 Figure 1-10 Figure 1-11 Figure 1-12 Figure 2-1 Figure 2-2
Series 3++ Compressor and Steam Turbine Controllers . . . . . . . . . . Major Components of Series 3++ Controller . . . . . . . . . . . . . . . . . . . . Series 3++ Panel-Mounting Case . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary PCB Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Antisurge and Performance Controller Front Panels . . . . . . . . . . . . . The Engineering Panel Mounts Behind the Front Panel . . . . . . . . . . Compressor Controller Back Panels . . . . . . . . . . . . . . . . . . . . . . . . . Turbine Controller Back Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Input Module (FIM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Field Output Module (FOM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AC Power Supply Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13 15 16 17 19 21 22 23 24 25 25 26
Alternate Parameter Set Memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Series 3++ Engineering Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 3-1 Figure 3-2 Figure 3-3 Figure 3-4 Figure 3-5 Figure 3-6 Figure 3-7 Figure 3-8 Figure 3-9 Figure 3-10 Figure 3-11 Figure 3-12 Figure 3-13 Figure 3-14 Figure 3-15 Figure 3-16 Figure 3-17 Figure 3-18 Figure 3-19 Figure 3-20 Figure 3-21 Figure 3-22 Figure 3-23 Figure 3-24
Mounting a Series 3++ Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU/IO PCB Configuration Switches. . . . . . . . . . . . . . . . . . . . . . . . . CPU/IO PCB Control Relay Switches . . . . . . . . . . . . . . . . . . . . . . . . Analog Input Resistors and Mode Switches. . . . . . . . . . . . . . . . . . . . Analog Output Switches and Jumpers . . . . . . . . . . . . . . . . . . . . . . . . Jumper Locations on the Auxiliary PCB. . . . . . . . . . . . . . . . . . . . . . . Back-Panel Discrete I/O Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . Back-Panel Discrete Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . Back-Panel Control Relay Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . Back-Panel Analog I/O Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . Back-Panel Analog I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . Back-Panel Speed Input Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . FIM Discrete Input Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FIM Analog Input Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FIM Speed and Position Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FOM Analog Output Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FOM Control Relay Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Port Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring Diagrams for Ports 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting to an RS-422/485 Host Port . . . . . . . . . . . . . . . . . . . . . . Connecting to an RS-232 Host Port. . . . . . . . . . . . . . . . . . . . . . . . . . Ethernet Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Cable Connector Configurations. . . . . . . . . . . . . . . . . . . . . . .
46 47 48 49 50 51 53 54 54 55 56 56 58 59 61 62 63 64 65 66 66 67 68 68
Figure 4-1 Figure 4-2 Figure 4-3 Figure 4-4 Figure 4-5 Figure 4-6
Position of Loader Switch on Front of CPU/IO PCB . . . . . . . . . . . . . Analog Input Signal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MPU Signal Varies With Speed, Shaft Ratio, and Tooth Count. . . . . High-Current Output Functional Diagram. . . . . . . . . . . . . . . . . . . . . . Operation of Bipolar Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Layout of Series 3++ Front Panel . . . . . . . . . . . . . . . . . . . . .
71 75 80 82 83 89
August 2007
UM3300/H (1.1.0)
10
Contents Figure 5-1 Figure 5-2 Figure 5-3 Figure 5-4
Redundant Controller Data Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 Typical Redundant Switching Circuitry . . . . . . . . . . . . . . . . . . . . . . . .93 Typical Redundant Control Selector Connections. . . . . . . . . . . . . . . .95 Connecting Current-Loop Outputs to an RCS . . . . . . . . . . . . . . . . . . .96
Figure 6-1 Figure 6-2
Controller Status Screen and Menu Buttons . . . . . . . . . . . . . . . . . . .100 Front-Panel Status LEDs and Alarm Menu . . . . . . . . . . . . . . . . . . . .104
List of Tables Table 2-1
Data Groups and Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Table 4-1 Table 4-2
Expected Output Readings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84 Expected Output Readings for Common Actuators. . . . . . . . . . . . . . .84
Table 6-1
Acceptable Voltages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Symbols and Acronyms Ω
ohm (electrical resistance measurement)
%
percent (parts or divisions per hundred)
# AC
Alternating Current
AD
Analog-to-Digital variable
ADC
Analog-to-Digital Converter
C#
Capacitor (for example, C9)
CCC CFTA CH COND
Compressor Controls Corporation Communications Field Termination Assembly analog input CHannel signal CONDitioning
CPC
Circular Plastic Connector
CPU
Central Processing Unit
CPU/IO CRC
PCB providing the main CPU and Input/Output Circuitry Cyclic Redundancy Checksum
CR
Control Relay (discrete/digital output)
D or DI
Discrete/Digital Input signal or circuit
DAC DC DCS August 2007
generic symbol for any number or numeric key
Digital-to-Analog Converter Direct Current Distributed Control System UM3300/H (1.1.0)
Series 3++ Hardware Reference DEV
Dual Inline Package
EIA
Electronic Industries Alliance
F# FIM FOM
Electrically-Erasable Programmable Read-Only Memory Fuse (for example, F1) Field Input Module Field Output Module
FPGA
Field Programmable Gate Array
FREQ
Frequency (speed) input
FTA G or GRD H HDIC HMI
Field Termination Assembly electrical ground terminal electrical hot terminal High-Density Interconnect Cable Human-Machine Interface
Hz
Hertz (frequency in cycles per second)
I/H
Current-to-Hydraulic signal converter
I/O
Input and Output (circuits or signals)
I/P
Current-to-Pneumatic signal converter
IRG
Instrument Reference Ground
IVP
Intended Valve Position
J#
Jumper (for example, J3)
JB#
Jumper Block (for example, JB10)
LCD
Liquid Crystal Display
LED
Light Emitting Diode
LVDT mA MPU N NEMA NO/NC OUT PC PCB August 2007
antisurge control DEViation
DIP EEPROM
11
Linear Variable Differential Transformer (position input) milli-Ampere Magnetic PickUp electrical neutral terminal also speed (Number of revolutions per minute) National Equipment Manufacturer’s Association Normally-Open or Normally-Closed OUTput (IBM-PC compatible) Personal Computer Printed Circuit Board UM3300/H (1.1.0)
12
Contents PI PID
Proportional-Integral-Derivative control
PLC
Programmable Logic Controller
PSA
Power Supply Assembly
PV
Process Variable readout
R#
Resistor (for example, R33)
RAM
Random Access Memory
RCS
Redundant Control Selector
RMA
Returned Material Authorization
RTU
(Modbus) Remote Terminal Unit
RVDT RX S SCADA SP SPEC
Rotary Variable Differential Transformer (position input) serial port reception terminals (for example, RX3) Solenoid Supervisory Control And Data Acquisition Set Point readout SPECial response
SV
Signal Variable
TB
Terminal Block
TCP
Transmission Control Protocol
TTC
Total Train Control®
TX V
serial port transmission terminals (for example, TX3) Voltage
Vac
alternating-current Voltage
Vdc
direct-current Voltage
W Xmtr
August 2007
Proportional-Integral control
Watt (electrical power measurement) transmitter
UM3300/H (1.1.0)
Series 3++ Hardware Reference
13
Series 3++ Hardware Referencemanual
UM3300/H
Chapter 1
Hardware Description
This chapter describes the components of and provides safety and environmental recommendations for Series 3++ Controllers.
DEV SP
ALT
LIMIT 2
LIMIT 3
PV OUT
SP
Antisurge Controller
ALT
LIMIT 2
PV
LIMIT 3
OUT
SP
Performance Controller
AS/PF
ALT
RPM OUT
LIMIT
SP
Dual-Loop A/P Controller
CASC
LIMIT
POWER
OUT
PV SP
Speed Controller
Fault
Fault
Fault
Fault
Fault
Alarm
Alarm
Alarm
Alarm
Alarm
ACK
MENU
AUTO
TEST
A
SCROLL
ACK
MENU
SCROLL
SURGE RESET
AUTO
MAN
∆
REMT SP
LOCAL SP
∆
∇
TEST
ENTER
#
A
MAN
ENTER
Figure 1-1
Introduction
ACK
MENU
SCROLL
ACK
MENU
ALT
LIMIT 2
LIMIT 3
OUT
Extraction Controller
SCROLL
ACK
MENU
SCROLL
PERF AUTO
A/S AUTO
SURGE RESET
AUTO
MAN
ESD RESET
AUTO
MAN
ESD
PERF MAN
A/S MAN
∆
OP MODE
SP MODE
∆
OP MODE
SP MODE
∆
∇
TEST
ENTER
∇
TEST
ENTER
∇
TEST
ENTER
∇
#
A
#
A
#
A
#
Series 3++ Compressor and Steam Turbine Controllers Series 3++ Controllers are traditional, single- or dual-loop devices that are optimized and factory-programmed to regulate and protect turbocompressors and steam turbines. Each can be configured to a specific application and operated without using an engineering or operator workstation, although Modbus communication is built in and an OPC server and client software is an available option. This manual describes the general operation of and tells how to install and maintain Series 3++ Controllers: • For environmental and safety recommendations and descriptions of the controller components, read the rest of this chapter. • If you want to know how controllers are adapted to particular applications, see Chapter 2. • If you want to know how to mount controllers and connect their field I/O circuits, see Chapter 3. • If you want to understand the operation of such controllers and know how to configure their field I/O features, see Chapter 4. • If you want to know how to set up and operate controllers in redundant pairs, see Chapter 5. • If you want to know how to maintain, troubleshoot and repair such controllers, see Chapter 6.
August 2007
UM3300/H (1.1.0)
14
Chapter 1: Hardware Description
Environmental and Safety Considerations
Caution:
Series 3++ Controllers are intended to be permanently mounted in a dry environment that minimizes static electrical discharges and conforms to the temperature and humidity restrictions stated on the Series 3++ Compressor Controllers Hardware Specifications sheet [DS3300/C] and the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]. Conformal coating is available as an added-cost option for corrosion resistance. Never disassemble a controller or handle its components without protecting them from static discharge and excessive moisture. To prevent damage, all circuit boards should be stored and transported in static-resistant, water-resistant pouches. Conformance with the safety requirements of various government agencies and industry groups is tabulated in the Agency Certifications for Series 3++ Controllers technical note [TN41]. All wiring and maintenance must be performed by qualified personnel in conformance with all applicable safety codes.
Warning!
Disconnect the power cable before disassembling the controller or disconnecting any internal component.
Caution:
Most test and maintenance procedures should be performed only while the process is shut down or under another means of control. The ground pin of the power connector must be connected to an earth ground. However, that connector is not designed to assure its ground is the first connection made and the last broken. If that is a concern, an alternate means of disconnection should be provided.
Warning!
Because the power connector is not designed to assure its ground is the first connection made and last broken, there is a slight risk of electric shock while connecting or disconnecting that cable to the controller. These devices should only be configured and operated by personnel familiar with all applicable instructions and documentation. Due to the nature of industrial processes and controllers, they can offer no protection against settings and actions that might be ineffective or even hazardous in one application but appropriate in another.
Caution: Warning! August 2007
If a controller’s Fault relay de-energizes, its final control element should be immediately transferred to an alternate control device. Failing to comply with the installation and use instructions in this or any other Series 3++ Controller manual might create unforeseen safety hazards. UM3300/H (1.1.0)
Series 3++ Hardware Reference Front Panel Assembly Engineering Panel Assembly
CPU/IO PCB Assembly
Figure 1-2
Components and Configurations
15
Back Panel Assembly Power Supply Assembly
Auxiliary PCB Assembly (optional)
Major Components of Series 3++ Controller All Series 3++ Controllers use a common hardware platform that consists of the following major components: • The CPU/IO PCB Assembly provides the controller’s primary computational, serial communication, and I/O capabilities. • The Auxiliary PCB Assembly provides the added I/O and computational capabilities needed for turbine control applications. • The Front Panel Assembly provides the controller’s operator display and input functions. • The Engineering Panel Assembly provides the controller’s configuration and tuning functions. • The Power Supply Assembly generates regulated 24 Vdc power for the internal and I/O circuits from either an AC or DC source. • The Back Panel Assemblies and optional Field Termination Assemblies (FTAs) provide wiring terminals for the controller’s field I/O circuits and communication ports. With the exception of the optional, externally-mounted FTAs, all of these components are usually housed in an extruded aluminum case for mounting in a control panel cutout (see Figure 1-3): • The optional auxiliary PCB assembly plugs into a connector on the face of (and is bolted to) the CPU/IO PCB. • The CPU/IO PCB plugs into a 120-pin connector along the front edge of the power supply assembly. • The power supply assembly plugs into a 120-pin connector on the inside of the back panel. • The engineering panel plugs into a 20-pin connector along the front edge of the CPU/IO PCB. • The front panel plugs in and attaches to the engineering panel.
August 2007
UM3300/H (1.1.0)
16
Chapter 1: Hardware Description Case
Figure 1-3
Mounting Slide
Slide Adjuster
Series 3++ Panel-Mounting Case All but the back panel can be replaced from the front of the case without removing it from the panel, and the entire controller can be replaced without disturbing any of its field wiring. The back panel and internal components can also be attached to a plate that can be mounted in a control panel, while the engineering and attached front panel are mounted on the control panel door and connected to the CPU/IO PCB using a cable. Such “plate-mounted” configurations are especially useful when the back of the control panel/rack is inaccessible.
Component Configuration
Series 3++ Controllers can be divided into two basic hardware configurations, depending on whether or not they are equipped with an auxiliary PCB assembly: • Because that board is needed for some (but not all) turbine control applications, controllers that do include it are referred to as Turbine Controllers (see the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]). • Because it is rarely (if ever) required for compressor control applications, controllers that do not include it are referred to as Compressor Controllers (see the Series 3++ Compressor Controllers Hardware Specifications sheet [DS3300/C]). Several different Back Panel Assemblies (see page 23) are available for each of these basic configurations, depending on whether the controller is equipped for AC or a DC power, and back-panel or FTA field wiring terminals.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
17
Power Supply Connector
CPU
Engineering Panel Connector
Figure 1-4
CPU/IO PCB Assembly
Auxiliary PCB Connector
CPU/IO PCB Assembly The CPU/IO PCB provides the controller’s central processor, memory, serial communication, and field I/O capabilities. The major components of this assembly (see Figure 1-4) are: • the central processing unit (CPU) with built-in discrete I/O and serial communication circuits; • a random access memory (RAM) chip with a backup battery, real-time clock, and watchdog timer; • two electrically-erasable programmable read-only memory chips (EEPROM) that store the control program and parameters; • direct current 24 to 1.2, 3.3, 5.0 and ±15 Vdc power converters; • eight electro-mechanical relays triggered by the CPU’s discrete outputs, with NO/NC configuration switches; • two isolated analog output circuits, with switches that configure each for voltage or current-loop operation; • eight field analog input circuits, with switches that configure each for voltage or current-loop operation; • eight internal analog input circuits for voltage, temperature, and analog output monitoring; and • a speaker for audible feedback. Storing configuration parameters in EEPROMs protects them from being lost or corrupted during power failures (see page 28), while still allowing them to be easily changed from either the Engineering Panel keyboard or via Modbus communication from a computer workstation running WOIS or TrainTools field engineering programs. Similarly, storing the control program in the EEPROMs means it can also be updated from such a computer.
August 2007
UM3300/H (1.1.0)
18
Chapter 1: Hardware Description Analog Input Channels
The CPU/IO board’s analog input circuits are referred to as channels (CH) 1 through 8: • Turbine controllers with terminal-block Back Panel Assemblies (see page 23) support only four of these circuits (CH1 to CH4). • All other controller configurations support all eight. Each of these channels can be switch-configured for either currentloop or voltage operation and internally measures its own value.
Analog Outputs
Each of the CPU/IO board’s isolated analog output circuits can be switch-configured for either current-loop or voltage operation: • For compressor controllers, the CPU/IO board’s analog outputs are referred to as OUT 1 and 2. • For turbine controllers, output 1 is the high-current output of the Auxiliary PCB Assembly (see page 19). The CPU/IO PCB’s analog outputs are then referred to as OUT 2 and 3.
Discrete Inputs
The CPU/IO board’s boolean inputs are referred to as discrete inputs (DI) 1 through 8: • Compressor controllers have terminals for and thus support only seven of these inputs (labeled D1 through D7). • Turbine controllers support all eight, plus one (D9) or all eight of those provided by the Auxiliary PCB Assembly (see page 19).
Discrete Output Control Relays
The CPU/IO board’s boolean outputs are referred to as control relays (CR) 1 through 8: • All compressor controllers have terminals for and thus support only the first five of these circuits (CR1 through CR5). • Turbine controllers with terminal-block Back Panel Assemblies (see page 23) support seven of these circuits (CR1 through CR7), plus the auxiliary PCB’s fault relay (CR9). Those with FTAs support all output relays provided by both boards. CR1 is of particular interest, because it is normally energized and thus fails off. This provides an automatic indication of hardware failure or power loss. CR2 can be switch-configured to do the same.
Serial Ports
The CPU/IO board’s four serial communication circuits (Ports 1 to 4) are compatible with the EIA RS-485 standard: • Ports 1 and 2 are used for communications with Series 3++ and other CCC controllers. • Ports 3 and 4 are used for Modbus RTU communication with host computers or control systems.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
19
CPU
Daughter Board
Figure 1-5
Auxiliary PCB Assembly
CPU/IO PCB Connection
Auxiliary PCB Assembly The auxiliary PCB (speed board) provides the added computational and I/O capacity needed for speed control and valve positioning. Its major components (see Figure 1-5) are: • the Motorola 68332 central processing unit (CPU); • two random access memory (RAM) chips, in which the results of internal calculations are stored (the board’s working memory); • the EPROM chip (erasable programmable read-only memory) that stores the control program for this board; • a super-capacitor that powers the RAM when the controller is unplugged and during power outages; • a universal asynchronous transmitter and receiver (UART) chip that provides eight additional discrete inputs; • one electro-mechanical relay and a jumper to configure it as a normally-open or closed indicator of auxiliary PCB malfunctions; • an analog output that can provide a bipolar current-modulated signal of up to 200 mA, and the jumpers to configure it; and • a daughter board that provides six frequency (rotational speed) input circuit, and one LVDT and one current-loop position input.
Discrete Inputs and Outputs
The auxiliary PCB provides eight boolean input circuits (in addition to the eight provided by the CPU/IO PCB) that are referred to as discrete inputs 9 through 16: • Turbine controllers with terminal-block Back Panels support only one of these inputs (labeled D9). • Those with FTAs support all eight. It also provides a single control relay (CR9) that signals auxiliary board faults.
August 2007
UM3300/H (1.1.0)
20
Chapter 1: Hardware Description High-Current Output
The auxiliary PCB includes an analog output circuit that can provide virtually any current-modulated signal from –200 to +200 mA. Because this greatly exceeds the usual 4 to 20 mA range, this circuit is usually called the high-current output. It includes: • a digital-to-analog converter (DAC) that generates an intermediate 0 to 5 Vdc signal, • circuitry that converts that voltage into a current signal with a jumper-selectable maximum magnitude of 20, 60, or 200 mA, • a phase inverter that can be turned on by the auxiliary PCB’s CPU when reverse current flow is needed, and • an analog-to-digital converter (ADC) that measures the loopback value of this signal. • circuitry that measures the frequency of any transducer feedback signal modulated onto this output signal.
Frequency Inputs
The daughter board provides six inputs for reading the rotational speed signals from a turbine’s magnetic pickups (MPUs): • Turbine controllers with terminal-block Back Panels support only three of these inputs (FREQ 1 to 3). • Those with FTAs have terminals for all six. Each such input can read the frequency signals from either active or passive magnetic pickups: • If active pickups are used, the controller can read any speed that produces at least a 5 Hz signal. The corresponding minimum speed depends on the number of teeth on the exciter and shaft ratio. For example, a 60-tooth gear mounted on the main shaft would generate a 5 Hertz signal at 5 rpm. • If passive pickups are used, the minimum detectable speed is that at which the voltage of the MPU signal meets the minimum listed on the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]. This can be determined from the electrical specifications for your MPUs.
Position Inputs
August 2007
The daughter board provides one five-wire linear variable differential transformer (LVDT) and one bipolar 20 mA analog input, either of which can be used to measure the position of a control element. They are available only through the Field Input Module, and referred to as LVDT 1 and the Auxiliary Input (see the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]).
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Control Loop Readouts and Buttons
.000 SP
DEV
9.3 ALT
LIMIT 2
LIMIT 3
OUT
SP
Antisurge Controller
Status LEDs, Screen and Buttons
Fault Alarm
MENU
ALT
PV
50.4
LIMIT 2
LIMIT 3
OUT
Performance Controller
Mode RUN TotlB=10.3 SrgCnt=001 ACK
9.01 9.00
21
Mode
RUN
Fault Alarm
SCROLL
ACK
MENU
SCROLL
Remote RT
AUTO
MAN
SURGE RESET
Local
AUTO
MAN
REMT SP
LOCAL SP
∆
TEST
ENTER
∇
Alt PV
Control LEDs and Keys
∆
POC Tracking Limit Balance Fallback
TEST
Stop
A
Figure 1-6
Front Panel Assembly
ENTER
∇
#
Tracking Limit CV Open Fallback Stop
A
#
Antisurge and Performance Controller Front Panels The front panel assembly provides the primary operator interface for the Series 3++ Controller. It is attached to the engineering panel by a swing-out hinge and a ribbon cable. Regardless of which model you purchase, the general features of this panel are always the same. As shown in Figure 1-6, each has: • The upper section has a three-digit control response readout, two five-digit controlled variable and set point readouts, and three buttons that select the displayed loop. • The middle section has a four-by-ten character LCD status screen, three buttons for its menu system, and the Fault and Alarm LEDs; • The lower section has eight control keys and twelve LEDs, three of which are embedded in associated keys, plus a TEST key that activates front panel test features. The keys, buttons, and Alarm, Fault, and key status LEDs are all built into the front panel overlay, which is unique to each model. That overlay also identifies the type of controller you have and labels its readouts and LEDs. Detailed information about each controller’s front-panel operation can be found in its operator interface data sheet [DS330#/O].
August 2007
UM3300/H (1.1.0)
22
Chapter 1: Hardware Description
Figure 1-7
Engineering Panel Assembly
The Engineering Panel Mounts Behind the Front Panel The chief feature of the engineering panel is the engineering keyboard (see Figure 2-2), which can be used to: • enter and change the configuration and tuning parameters that adapt each controller to its specific application, and • display diagnostic information. In Series 3++ Controllers, the engineering panel is equipped with an embedded microprocessor that controls not only its readout and keyboard, but also the front panel. Off-loading these functions from the main CPU allows the controller to run more demanding control algorithms while still providing a responsive user interface. The engineering panel is mounted on the front of the controller, immediately behind the front panel (see Figure 1-7). It is accessed by loosening the screw at the bottom of the front panel, pulling its right side (your left) forward about an inch, and then swinging the entire assembly forward and to your left.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Modbus RTU
Modbus TCP
FTA-Connector
CH 1 + –
CH 2 + –
CH 3 + –
CH 4 + –
OUT 1 +
OUT 2 +
CH 1 + –
CH 2 + –
CH 3 + –
CH 4 + –
OUT 1 +
OUT 2 +
CH 5 + –
CH 6 + –
CH 7 + –
CH 8 + –
CR1 1 2
CR2 1 2
CH 5 + –
CH 6 + –
CH 7 + –
CH 8 + –
CR1 1 2
CR2 1 2
CR3 1 2
CR4 1 2
CR5 1 2
DISCRETE IN D1 D2 D D3 D4 D5
CR3 1 2
CR4 1 2
CR5 1 2
DISCRETE IN D1 D2 D D3 D4 D5
MADE IN USA
1
4
INPUTS/ OUTPUTS (J1) 60
PORT 2 TX2 RX2 + – 2 + –
PORT 1 TX/RX 1 + –
NOT USED
PORT 1 1 TX/RX – +
PORT 2 TX2 RX2 + – 2 + –
63
24VDC DISCRETE +
–
D6 D7
PORT 4 TX4 RX4 4 + – + – PORT 3
PORT 3 TX3 RX3 3 + – + –
24VDC DISCRETE + – D6 D7
23
PORT 5
RX5 + –
96-264 VAC 21-32 VDC
96-264 VAC 21-32 VDC 21-32 VDC PORT 4
TX5 + –
N
G
H
96-264 VAC
MADE IN USA
N GRD H 35 W max
Figure 1-8
Back Panel Assemblies
MADE IN USA
N GRD H 35 W max
35 W max
Compressor Controller Back Panels All I/O wiring and the input power cable connect to the controller’s back panel assembly. Each controller is equipped with one of five basic versions of this panel: • New compressor controllers use either Modbus RTU or TCP back panels, which have serial port terminal blocks or RJ-45 ethernet connectors, respectively. Series 3++ circuit boards can also be used to upgrade Series 3 Plus Controllers that use the discontinued field input / output module (FIOM) and its single FTA-connector back panel (see Figure 1-8). • Turbine controllers use either the FTA-Connector or TerminalBlock Back Panel (see Figure 1-9): • Those equipped with the FTA back panel connect to external Field Termination Assemblies (see page 24) via high-density interconnect cables (HDICs). Because they provide terminals for all CPU/IO and auxiliary PCB I/O circuits, they are referred to as extended I/O turbine controllers. • Those with back-panel terminal blocks, which support fewer I/O circuits, are called standard turbine controllers.
August 2007
UM3300/H (1.1.0)
24
Chapter 1: Hardware Description
Terminal-Block +
CH 1 –
CH 2
+
–
CH 3
+
–
CH 4
+
–
OUT 1
+
FTA-Connector OUT 2 +
MADE IN USA
1 OUT 3 +
CR1 1 2
CR2 1 2
CR6 1 2
CR7 1 2
CR9 1 2
PORT 1 1 TX/RX – +
CR3 1 2
CR4 1 2
4
CR5 1 2
INPUTS (J1) 60
63
1
4
DISCRETE IN D1 D2 D D3 D4 D5
PORT 2 TX2 RX2 + – 2 + –
24VDC DISCRETE +
–
D6 D7
OUTPUTS (J2)
DISCRETE PORT 4 PORT 3 D8 D9 TX3 RX3 TX4 RX4 3 4 + – + – + – + – 60
FREQ1 + –
FREQ2 + –
FREQ3 + –
63
96-264 VAC 21-32 VDC 21-32 VDC
N
G
H
96-264 VAC
MADE IN USA
Figure 1-9
N GRD H 35 W max
35 W max
Turbine Controller Back Panels For panel-mounted controllers, the back panel is bolted to the case and the power supply plugs into it. For plate-mounted applications, the power supply is bolted to the plate and the back panel plugs into it using a right-angle connector. In order to facilitate controller replacement, the non-FTA versions feature two-part terminal blocks, the removable halves of which can be unplugged and reconnected to a replacement controller without disturbing the field wiring.
Field Termination Assemblies
Because there is not enough room on the back panel to provide terminals for all I/O circuits provided by the CPU/IO and auxiliary PCBs, turbine controllers are usually equipped with two external field termination assemblies (FTAs): • The field input module (or FIM, see Figure 1-10) has terminals for all input signals. • The field output module (or FOM, see Figure 1-11) handles all output and serial communication connections. The specifications for these modules are provided by the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T].
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Discrete Input Fuses and 24 Vdc Fuses Config. Blocks and Config. Block
Terminals for Discrete Inputs
CPC Connector for Controller Data Cable
Terminal Block for Valve Position Inputs
Figure 1-10
Analog Input Fuses and Config. Blocks
Terminals for Frequency Inputs
Terminal Blocks for Analog Inputs
Field Input Module (FIM)
CPC Connector for Controller Data Cable
Terminal Blocks for Serial Ports 1 to 4
Figure 1-11
25
Discrete Output Fuses and Config. Blocks
Terminal Block for Analog Outputs Terminal Block for 24 Vdc
Terminal Blocks for Discrete & Misc. Outputs
Field Output Module (FOM) In addition to supporting additional I/O circuits, the use of FTAs can reduce panel design and wiring costs. They also include fusing and dropping resistor options that would otherwise be quite difficult to install. Other FTA design features facilitate connecting the controller’s I/O signals to a DCS or other supervisory control system. Because the FTAs have no active components, they should never fail or need replacement. In the remote event one does, the terminal blocks can be disconnected and reinstalled on a replacement FTA without disturbing the field wiring.
August 2007
UM3300/H (1.1.0)
26
Chapter 1: Hardware Description
Back Panel Connector
CPU/IO PCB Connector
Power Supply 2
Power Supply 1
Figure 1-12
Power Supply Assembly
AC Power Supply Assembly Each controller has either a DC or an AC power supply assembly (PSA) with dual 24 Vdc power circuits: • the DC assembly’s soldered-on voltage regulation circuits accept a wide range of direct current inputs (nominally 24 Vdc). • the AC assembly’s voltage conversion daughter boards accept a range of alternating current inputs (nominally 110 to 240 Vac). The two power circuits share a single power cord and back-panel power connector: • one provides 24 Vdc power directly to the CPU/IO PCB’s 1.2, 3.3, 5.0 and ±15 Vdc power converters, while • the other powers the analog outputs and external transmitter power terminals. This design prevents faulty field devices from affecting the controller’s internal voltages. The AC and DC back panels connect the power supply to different pins of their power connectors (see Figure 3-24), and are clearly labeled to indicate their required supply voltages.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference UM3300/H
Chapter 2
27
Series 3++ Hardware Referencemanual
Engineering Procedures
Each Series 3++ Controller is adapted to its specific application by setting the configuration and tuning parameters that govern its operation. These can be viewed or changed from the engineering panel or from a computer running our Series 3 Plus Configurator program. Each controller model also offers diagnostic tests that are run from the engineering panel. This chapter describes the parameter memory and tells how to view or alter parameter values or run tests from the engineering panel. Detailed test procedure descriptions can be found in Appendix B.
Support Software Packages
Series 3++ Controllers can be configured and updated from a PC running the Series 3 Plus Configurator program, which can read, edit, and replace a controller’s configuration parameter set and update or change its control program via either of its Modbus communication ports. It is included in the following software packages: • The TrainTools Software Packages are collections of programs developed for the 32-bit Windows 2000 and XP Professional operating systems. The Platform Engineering Utilities package includes the Series 3 Plus Configurator program, which then communicates with controllers via the TrainTools Series 3 OPC Server program. The Series 3 Engineering Utilities user manual [UM5513] tells how to use it in that fashion. • The Workstation Operator Interface Software (WOIS) is an older group of Series 4 and 3 Plus software packages developed for 16-bit Windows 95/98/ME operating systems. Using the Configurator program to modify a controller’s parameter set or update its control program will not change the parameters that govern the communication between them. On the other hand, using it to convert one type of controller to another (see Programming and Configuration on page 126) can change the serial port settings, which could then be restored only from the engineering panel.
August 2007
UM3300/H (1.1.0)
28
Chapter 2: Engineering Procedures Stored In RAM
Stored in EEPROM Store 3 Store 2 Store 1
Download
Present Set
Keyboard
Figure 2-1
Parameter Memory
automatic
Long-Term Alternate Set Set 1
Alternate Set 2
Alternate Set 3
Recall 1 Recall 2 Recall 3
Alternate Parameter Set Memory All Series 3++ Controllers store two copies of their configuration parameter values. The long-term set is stored in an electrically erasable programmable read only memory (EEPROM) that retains them even if the controller is powered down for years. The present set is stored in a battery-backed up random access memory (RAM) that would retain them even if the controller was powered down for a year or more. The controller usually keeps both parameter sets identical by continuously comparing the values in the present set to their long-term counterparts, and correcting any that differ. Changes can be made only by disabling that mechanism: • When making changes from a PC, the Configurator program automatically disables and re-enables that mechanism. • When using the engineering panel, it is disabled and re-enabled by special Parameter Memory Procedures (see page 43). Any changes, however entered, are made to both the present and long-term parameter sets.
Alternate Parameter Sets
Most Series 3++ Controllers allow you to define three alternate parameter sets, which are also stored in the EEPROM. Special Parameter Memory Procedures (see page 43) are provided for defining these parameter sets, determining which one (if any) is in use, and switching to a different one. Some controllers also allow you to select an alternate parameter set by clearing or asserting a discrete input.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Data Groups and Pages
29
Each controller’s parameters are divided into data groups and pages to facilitate their entry from the engineering panel. As shown in Table 2-1, each data group has an associated key and key color, and each group/page combination has a unique abbreviation (the last character of which indicates the data page). For example, the abbreviation for PID parameters on the device page is PID:D. In all Series 3++ documents, the key sequence used to view or enter a parameter or execute a test begins with the abbreviation for its data group and page (for example, Transmitter Status Test [MODE:D ANIN –]). Procedures that are not assigned to a specific data page indicate only the data group key (for example, Reset Controller [MODE COMM]).
Table 2-1
Data Groups and Pages Data Group Key
Color
Data Pages
Abbreviation
Blue
Antisurge Cascade Device Extraction Gas Turbine Performance Speed
PID:A PID:C PID:D PID:E PID:G PID:P PID:S
Red
Antisurge Cascade Device Extraction Gas Turbine Performance Speed
MODE:A MODE:C MODE:D MODE:E MODE:G MODE:P MODE:S
CONDitioning
Green
Antisurge Cascade Device Extraction Gas Turbine Performance Speed
COND:A COND:C COND:D COND:E COND:G COND:P COND:S
SPECial RESPonse
Yellow
Antisurge Gas Turbine Speed
SPEC:A SPEC:G SPEC:S
PID
MODE
August 2007
UM3300/H (1.1.0)
30
Chapter 2: Engineering Procedures
Parameter Checksum
Each parameter set has an associated cyclic redundancy checksum (CRC) that is calculated by applying a standard algebraic function to all of its parameter values. Changing any parameter will produce a new checksum. You can tell if two parameter sets are identical by comparing their checksums. Both the engineering panel and Configurator program provide easy ways to determine these checksums.
Note: Configuration Forms
Parameter checksums are displayed as hexadecimal numbers (for example, F10C), in which each digit can have any one of sixteen values. Those greater than nine are represented by the letters A (10) through F (15). Two forms are available for planning and recording the configuration of each controller. Configuration Worksheets [FM33##/C] group the parameters by Data Groups and Pages, while the Configuration Planners [FM33##/L] list them according to the associated feature. If you permanently change any parameters from the engineering panel, you should record the new values and the resulting checksum on one of these worksheets. Determining whether or not the controller’s configuration has been changed then becomes a simple matter of comparing the current checksum to that on the worksheet.
Engineering Panel
The engineering panel not only allows you to display or change parameter values but also provides the only method of executing the process and controller test procedures described in Appendix B. It consists of three main sections: • an eight-character alphanumeric readout across the top, • four data group keys across the bottom, • and sixteen data keys in the middle. The controller beeps and displays a confirming message as each key is pressed. If you do not complete a key sequence, the controller will beep and clear this display after 45 seconds of keyboard inactivity. Certain Diagnostic Messages (see page 44) may also be displayed by this panel’s readout. To expose this panel, loosen the screw at the bottom of the front panel and swing the bezel out and to the left. This allows simultaneous access to both the operator and configuration interfaces.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
31
ENGINEERING PANEL
∞∞∞∞∞∞∞∞ PB – fA Q
Td 2 SS GAIN
Tf 3 MOR BIAS
fD β
K 5 REV ALARM
b 6 LOCK DISPLAY
TL LOW fE IN
RT 7 MVAR LVL
SO 8 TEST OUT
C 9 RA SP
CLEAR
d • AN IN f (X)
A 0 COMM X
ENTER
PID
SPEC RESP
MODE
COND
G HIGH fC M
Figure 2-2
Key Descriptions
Kr 1 fB CONST r
4
Series 3++ Engineering Panel The data group keys are used only to initiate a new key sequence, at which point one of them is pressed one or more times to select the desired data page and group. Pressing a data group key at any other point in a sequence causes an error that aborts the procedure. The two gray data keys are used primarily to end key sequences: • Pressing CLEAR either aborts a sequence without entering any changes or, when entering a numeric value, clears the digits you have entered so you can start over. • Pressing ENTER at the end of a parameter entry sequence records the new value. Although pressing it at any other point usually causes an error, some multi-parameter sequences allow you to press ENTER to display the value of the second parameter without first defining a new value for the first. The other fourteen multi-colored data keys are divided into four sections. One is gray, each of the others is the same color as a data group key. The function of each such key depends on when it is pressed in a key sequence. If pressed immediately after a data group key, it has the value labeled in the matching-colored area. Otherwise, it enters the value shown in the gray area.
August 2007
UM3300/H (1.1.0)
32
Chapter 2: Engineering Procedures For example, consider the key in the upper right hand corner: • Pressing the blue PID key defines this as the Tf key: PID Tf
PID: Tf
• Pressing the red MODE key defines it as the MOR key: MODE
MOR
MODE: MOR
• Pressing the green COND key defines it as the BIAS key: COND
COND: BIAS
BIAS
• If pressed at any other point in a sequence, it is the three key: COND
COND: OUT
OUT 3
Viewing and Changing Parameter Values
OT3
The parameter listings in the appendix of each instruction manual include each parameter’s engineering panel key sequence and confirming display. Pressing the indicated keys will elicit the listed display, which consists of a prompt followed by the current value: • Enabling parameters can have the value Off and one or more others such as On, High, Low, or single digits. These ranges are indicated as “OFF/ON”, “OFF/HIGH/LOW”, or “Off/#”. • List parameters have a limited number of possible values that are generically indicated as “Value” or “Valu”. • Numeric parameters can have any value within the listed range, the precision of which is indicated by the number of “#” symbols used to represent its digits. The position of any decimal point is fixed. The space before a negative value is replaced by a “–”. A hexadecimal ten leading digit shows as “A” (A0.0 is 100.0).
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
33
For parameter arrays, the prompt also includes a digit corresponding to the element index and represented by the character “#”.
Note:
You may examine the value of any configuration parameter while the controller is on line without affecting the controller output or your process, and without entering the configuration password. If you attempt to change a parameter without enabling reconfiguration, the No Store diagnostic message will be displayed and the new value will be discarded. After a parameter’s current value or status has been displayed, you can terminate the procedure and clear the display by pressing the gray CLEAR key. Or, if you have entered the Enable Reconfiguration [MODE LOCK 5 1] procedural key sequence, you can enter a new value. The required procedure depends on the parameter type: • Enabling parameters are changed by pressing the corresponding key (0 for Off, 1 for On, HIGH, LOW, or a digit) followed by the ENTER key. Until you do press ENTER, you can change your mind and press as many of the allowed value keys as you need. • List parameters are changed by pressing the decimal key until the desired value is displayed and then pressing ENTER. • Numeric parameters are changed by pressing the indicated number of numeric keys, including any leading or trailing zeroes, then ENTER. Any decimal point is placed automatically. A negative value is defined by pressing the minus (–) key before the first digit. A hexadecimal ten leading digit is defined by pressing the HIGH key (100.0 is entered as HIGH 0 0). If you make a mistake prior to pressing ENTER, you can press CLEAR to start over. For any parameter, pressing ENTER to finalize a value change also clears the confirming display.
Caution:
August 2007
To prevent process upsets, parameters should only be changed with the controller in manual or off-line.
UM3300/H (1.1.0)
34
Chapter 2: Engineering Procedures
Key Sequence Illustrations
Although a confirming message is displayed as each key is pressed, key sequence illustrations (such as those shown in Appendix B) usually show only the most important of these messages (to save space). For clarity’s sake, they also show only the effective value of the data keys at each point in the sequence. Thus, the initial steps of a sequence that might require you to press the data group key more than once (for example, the Transmitter Status Test [MODE:D ANIN –]) would be shown as: repeat
MODE
until you see –
MODE:
D
AN1 GOOD
AN IN
In contrast, the initial steps of a sequence that is not assigned to a specific page (for example, the Signal Values Test [MODE TEST 4]) would be shown as: 4 MODE
TEST
Inputs
Key Sequence Examples
The following examples illustrate the procedures for viewing and changing the various types of parameters. When possible, they are device page parameters that are common to most if not all models of the controller.
Enabling Parameters
Most enabling parameters are assigned to the MODE data groups and simply enable or disable a controller feature. A good example is Modbus Write Inhibit, which determines whether or not Modbus hosts can change coils and holding registers (Off allows changes, On prevents them). The listing for this parameter gives its sequence as MODE:D LOCK 2 and its display as “LOC2 OFF/ON”. Thus, pressing those keys displays the current status of that option as follows: repeat
MODE
until you see 2
LOCK
or
August 2007
MODE:
D
LOC2 OFF LOC2 ON
UM3300/H (1.1.0)
Series 3++ Hardware Reference
35
You can then press CLEAR to retain that status, enter 0 to disable that feature, or enter 1 to enable it: 0
LOC2 OFF
1
LOC2 ON
or ENTER
Other enabling parameters either disable the associated feature (Off) or select one of two possible modes of operation (High or Low). An example would be the Speed Controller’s Alternate MW Input (Off) disables the redundant MW input, High configures the controller to use the highest of the two inputs, Low selects the lowest). The listing for this parameter gives its sequence as MODE:S SS 3 and its display as “SS3 OFF/HIGH/LOW”. Thus, pressing those keys displays the current status of this option as follows: repeat
MODE
until you see 3
SS
MODE:
S
SS3 HIGH
or
SS3 LOW
or
SS3 OFF
You can then press CLEAR to leave it unchanged, or enter HIGH, LOW, or 0 to select the desired new configuration: HIGH
LOW
or 0
or
SS3 HIGH SS3 LOW SS3 OFF
ENTER
August 2007
UM3300/H (1.1.0)
36
Chapter 2: Engineering Procedures A few enabling parameters allow you to select from options that are intuitively numeric by pressing the corresponding decimal key. They usually either disable a feature or select the companion controller or analog input from which a given signal is to be obtained. An example is the Performance Controller’s Mass Flow Input, which selects the input for its mass flow rate calculation (Off disables that calculation, any digit from 1 to 8 configures it to use that analog input). The listing for this parameter gives its sequence as MODE:D fD 1 and its display as “fD1 OFF/#”. Thus, pressing those keys displays the current status of this option as follows: repeat
MODE
until you see 1
fD
or
MODE:
D
fD1
OFF
fD1
#
You can then press CLEAR to leave this feature unchanged, enter 0 to disable it, or enter the desired input number: 0
#
or
fD1
OFF
fD1
#
ENTER
where the digit key used to enter the new value is represented as #. Parameters that define the decimal point positions for front panel display variables are a variant of this type of parameter. An example is the Measured Variable Decimal parameter arrays, of which each element defines the position of the decimal point in the corresponding measured variable display (Off means no decimal). The listings for these parameters gives their sequence as COND:D DISPLAY 0 # • and their display as “0#. 4321 (selected digit is replaced by •)”. Thus, pressing those keys displays the current decimal position (in this example, it follows the second digit): repeat
COND 0
until you see #
•
COND:
D
0#. 43.1
DISPLAY
where the fourth key you press is the digit corresponding to the analog input, as is the number (#) in the resulting display. August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
37
You can then press CLEAR to leave that variable’s decimal position unchanged, or change it by pressing the numeric key (0 to 4) corresponding to the desired decimal position: 0
0#. 4321
1
0#. 432.
or 2
0#. 43.1
or 3
0#. 4.21
or 4
0#. .321
or
You can continue pressing numeric keys in any order until the desired decimal point position is displayed. Finally, press CLEAR to exit the procedure without changing the parameter, or press ENTER to accept the displayed position: ENTER
List Parameters
Like enabling parameters, list parameters are usually assigned to the MODE data groups and also have a limited number of values. However, few if any of those values intuitively correspond to data keys, so they are selected by repeatedly pressing the decimal (•) key until the desired value is displayed. A universal example is the Port 2 Baud Rate, which defines the data transmission rate for serial Port 2 (2400, 4800, or 9600 bits per second, which appear to be numeric values but are in fact selected from a list). The listing for this parameter gives its sequence as MODE:D COMM 2 and its display as “PT2 Valu”. Thus, pressing those keys displays the current value (2400 baud in this example): repeat
MODE
until you see 2
COMM
August 2007
MODE:
D
PT2 2400
UM3300/H (1.1.0)
38
Chapter 2: Engineering Procedures You can then press CLEAR to leave this baud rate unchanged, or press the decimal key (•) until the desired new rate is displayed and then press ENTER: •
PT2 4800
•
PT2 9600
•
PT2 2400
ENTER
Some list parameters have both a sign (+ or –) and a list value. An example is the Relay Assigned Function parameter array, each element of which sets the conditions under which the corresponding discrete output is triggered (if the assigned function is positive, the relay will be energized when the associated condition exists; if the value is negative, the relay will de-energize). The listing for these parameters gives their sequence as MODE:D RA # and their display as “RA#±Valu (press HIGH or LOW to select sign, then press • to select function)”. Thus, pressing those keys displays the current value as follows: repeat
MODE
until you see #
RA
MODE:
D
RA#±AAAA
where the third key you press is the digit corresponding to the discrete output number, as is the digit (RA#) in the resulting display. To change the normally energized/de-energized circuit configuration, press HIGH or LOW: HIGH
LOW
or
RA#+AAAA RA#-AAAA
Pressing the decimal key will advance the display to the next available function (BBBB): •
August 2007
RA#±BBBB
UM3300/H (1.1.0)
Series 3++ Hardware Reference
39
You can press any of these keys as many times as necessary to display the desired configuration. Pressing ENTER accepts the displayed relay configuration: ENTER
Label Parameters
Label parameters are entered as a series of characters individually selected from a list. An example are the Measured Variable Name and Units parameters, each of which defines the name displayed above and units displayed after a measured variable’s value when it is viewed via the status screen’s Analog In menu. The listing for these parameters gives their sequence as COND:D DISPLAY 0 # – and their display as “AAAAAAAA then EU:AAAAA”, followed by the instruction “selected symbol (A) flashes, press • to select, then ENTER for each”. Thus, pressing those keys displays the current value as follows: repeat
COND 0
until you see #
–
COND:
D
AAAAAAAA
DISPLAY
where the fourth key you press is the digit corresponding to the variable’s analog input and the first character (shown in blue above) would be flashing. You can then press CLEAR to leave the name and units unchanged, or change the flashing character by pressing the decimal (•) key to advance it to the next possible symbol or the minus (–) key to back up to the previous possible symbol:
AAAAAAAA •
–
BAAAAAAA AAAAAAAA
You can also hold either key down to scroll rapidly through the available symbols. When the desired symbol appears (P in this example), press ENTER to accept it and edit the next: •
ENTER
August 2007
PAAAAAAA PAAAAAAA UM3300/H (1.1.0)
40
Chapter 2: Engineering Procedures Repeat this procedure to edit each succeeding character. Once you have accepted a character, you cannot return to it without entering the rest of the label and starting over. For this parameter, entering the eighth character accepts the name and displays the units:
Psuction EU:AAAAA
ENTER
Press clear to leave the engineering units unchanged, or edit each displayed symbol as described above. Entering the fifth character accepts the new units: •
EU: psig
ENTER
Numeric Parameters
Because numeric parameters have virtually continuous ranges, their desired values must be defined by pressing the corresponding digit keys. A good example is the Dual-Loop Controller’s Transmitter Failure Limit, which defines the minimum valid value (00.0 to 99.9 percent) for any offset zero inputs. The listing for this parameter gives its sequence as MODE:D ANIN LOW and its display as “ANL ##.#”. Thus, pressing those keys displays the current value as follows: repeat
MODE
until you see LOW
AN IN
MODE:
D
ANL ##.#
You can then press CLEAR to leave that value unchanged, or enter the desired new value: #
#
#
ANL # . ANL ##. ANL ##.#
ENTER
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
41
where each key used to define the new value is represented as # and the decimal point is placed automatically. The precision of such a parameter is indicated by the number of “#” symbols in its listed display. When changing its value, you must press that many digit keys, even if they correspond to leading or trailing zeroes. A hexadecimal ten leading digit is entered by pressing the HIGH key and is displayed as “A” (100.0 is entered as HIGH 0 0 and displays as “A0.0”). A negative value is defined by pressing the minus (–) key before the first digit key. If you make a mistake prior to pressing ENTER, you can press CLEAR to start over.
Note:
Most numeric parameters can range from zero to some power of ten. When the routines for entering them from the keyboard do not permit you to enter a hexadecimal leading ten by pressing HIGH, the parameter listing will show the maximum value as .999, 9.99, or 99.9. However, such parameters can be given a maximum value of one, ten, or one hundred (1.000, 10.00, or 100.0) from a computer workstation and the engineering panel will consequently display them as such (.A00, A.00, or A0.0). Characterizing functions are arrays that define the values of one variable that correspond to ten specific values of another: • For some functions, the independent variable (X) values are predefined in even steps from zero to one, ten, or one hundred (for example, 00.0, 11.1, 22.2, ..., 88.8, 100.0). • For others, only the first and last X values are fixed (0 and 1.000, 10.00, or 100.0). The eight intermediate steps (which must have increasing values) are defined by an array entered using a COND X # # key sequence (the first digit is the function number, the second is the element index). In either case, however, the values of the dependent variable (Y) are defined by the corresponding elements of an array entered using a MODE f(X) # # sequence. An example is the Antisurge Controller’s Reported Flow Characterizer, which defines how it calculates the flow rate it reports to its companion controllers from the flow rate used in its own proximityto-surge calculation. The listing for this parameter gives its sequences as COND:A f(X) 2 # and X 2 # and its displays as “X2# #.##” and “Y2# #.##”. Thus, you must define both arrays for this particular characterizer.
August 2007
UM3300/H (1.1.0)
42
Chapter 2: Engineering Procedures Press these keys to view point N’s argument (X2,N = #.##): repeat
COND 2
until you see #
COND:
A
X2# #.##
X
where the fourth key you press is the digit corresponding to the characterizer point, as is the first digit (X2#) in the resulting display. Press CLEAR to leave it unchanged, or enter the desired new value: #
#
#
X2# #.##
ENTER
where each numeric key used to enter the new value is represented as # and the decimal point is positioned automatically. Press these keys to view point N’s result (Y2,N = #.##): repeat
COND 2
until you see #
COND:
A
Y2# #.##
f(X)
where the fourth key you press is the digit corresponding to the characterizer point, as is the first digit (Y2#) in the resulting display. Press CLEAR to leave it unchanged, or enter the desired new value: #
#
#
Y2# #.##
ENTER
again, each numeric key used to enter the new value is represented as # and the decimal point is positioned automatically.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Parameter Memory Procedures
43
Because the present parameter values stored in the controller’s working memory (RAM) are subject to random (albeit extremely rare) changes, the controller continuously compares them to their long-term counterparts and corrects any errors. Before you can change any parameters from the engineering panel, this feature must be disabled by entering the Enable Reconfiguration [MODE LOCK 5 1] key sequence. Otherwise, any attempt to enter a new parameter value will only elicit a No Store message on the panel’s alphanumeric readout. While reconfiguration is enabled, the controller will not automatically correct any errors that might develop in its present parameter set. To restore this protection, you should enter the Disable Reconfiguration [MODE LOCK 5 0] sequence when you finish configuring the controller. If you do not, the controller will automatically disable reconfiguration after 30 minutes of keyboard inactivity. The Parameter Checksum [MODE LOCK 4] procedure displays the checksum values of the controller’s various parameter sets. You can also determine which of these parameter sets (if any) agree with those recorded on your configuration forms by comparing these checksums to those recorded on those worksheets. For controllers with Alternate Parameter Sets (see page 28), the following procedures can be used to define these parameter sets, determine which one (if any) is in use, or switch to a different one: • Each alternate set is defined by assigning the desired values to the present and long-term parameters and using the Store Alternate Parameters [MODE LOCK 3 •] procedure to copy them to an Alternate Set. • You can switch to one of the alternate sets by using the Recall Alternate Parameters [MODE LOCK 3 • •] procedure to copy it back to the present and long-term sets. • You can determine which (if any) of the alternate sets is in use by using the Parameter Checksum [MODE LOCK 4] procedure to compare their Parameter Checksums with that for the present and long-term sets. You can also determine if any of these sets agree with those recorded on your configuration forms by comparing these checksums to those on those worksheets.
August 2007
UM3300/H (1.1.0)
44
Chapter 2: Engineering Procedures
Diagnostic Messages Bad CRC Com# POF
Note: CS= XXXX
Error!
The following paragraphs explain the various messages that can appear on the engineering panel’s eight-character display. This message indicates the controller has found and corrected a difference between the present and long-term Parameter Memory. This message indicates a low-level serial communication error (see Communication Problems on page 115). If a communication error occurs while you are entering parameter values, the controller will only beep. This message indicates an unreasonable parameter setting was detected and changed during a CPU Reset (see page 77), which in turn changed the parameter checksum to the indicated new value (XXXX). It usually appears only after installing a new EEPROM, downloading a new control program, or using the Configurator program to change parameter values. If the controller repetitively beeps and flashes this message, the parameter memory is probably damaged (see CPU/IO Board Problems on page 117). This message indicates you have entered an unrecognized key sequence. This is typically caused by: • pressing a parameter (multi-colored) key without first pressing the correct data group (solid-colored) key, • failing to press the data group key enough times to access the correct data page, • pressing the wrong number of data keys, • pressing the decimal key in sequences that automatically place the decimal point, or • entering an out-of-range value for a numeric parameter. If the controller repetitively beeps and flashes this message, one of the engineering panel keys is probably stuck down (see Front and Test Panel Problems on page 114).
August 2007
No Store
This message indicates you tried to change a parameter without first entering the Enable Reconfiguration [MODE LOCK 5 1] sequence.
Reset
This message indicates a CPU Reset (see page 77), which can be manually triggered by changing critical parameters, recalling an alternate parameter set, or invoking the Reset Controller [MODE COMM] procedure. Repetitive beeping and flashing of this message indicates the control program is restarting but failing to reset the watchdog timer (see CPU/IO Board Problems on page 117).
UM3300/H (1.1.0)
Series 3++ Hardware Reference UM3300/H
Chapter 3
45
Series 3++ Hardware Referencemanual
Installation
This chapter tells how to mount Series 3++ Controllers and connect their field I/O and communication cables.
Overview
The installation of a panel-mounted Series 3++ Controller entails the following general procedures: Step 1: Mount the controller in a properly-sized panel cutout (see Mounting on page 46). Step 2: Remove the internal PCBs, set their switches and jumpers, then reinstall them (see Internal Settings on page 47). Step 3: Connect your field elements to the appropriate back-panel terminals (see Back-Panel Connections on page 53), or Mount the field termination assemblies (FTAs), connect them to the controller back panel, and connect your field wiring to the appropriate terminals (see FTA Connections on page 57). Step 4: Connect your communication cables to the back-panel or field output module (see Communication Ports on page 64). Step 5: Configure and connect the power cable to the controller and an appropriate power supply (see page 68). Refer to page 110 if the controller starts beeping repeatedly. Additional considerations apply when installing Redundant Controllers (see Chapter 5). Refer to Chapter 2 and Appendix B for more information on the remaining steps: Step 6: Use the Program Version [MODE TEST 2] procedure to identify the installed control program. If needed, use the Series 3 Plus Configurator to load the correct one (see page 71). Step 7: If the controller was not preconfigured, use the Configurator utility or engineering panel to enter appropriate values for all configuration and tuning parameters, which are described in its user manual. Be sure to keep a record of these values and the resulting parameter checksum. If your controller was preconfigured, use the Configurator utility or Parameter Checksum [MODE LOCK 4] procedure to verify that the current and recorded parameter checksums match. If not, reload the supplied parameter set or identify and correct any changed parameters using either the Configurator program or the engineering panel. Step 8: Use the Set Clock [MODE TEST 9] key sequence to set the internal date and time (Speed Controllers only).
August 2007
UM3300/H (1.1.0)
46
Chapter 3: Installation
Mounting Slide
Slide Clamp
Pressure Screw
1 2
Figure 3-1
Mounting
Note:
3
Mounting a Series 3++ Controller Refer to Figure 3-1 for an illustration of the slide clamps (located on the top and bottom of the case) and to the Series 3++ Compressor Controllers Hardware Specifications sheet [DS3300/C] or the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T] for panel cutout dimensions. DS3300/T also discusses the dimensions and mounting options for turbine controller FTAs. Panel cutouts must have specified dimensions after painting. Use the following procedure to mount a Series 3++ Controller in a properly-sized panel cutout: Step 1: Loosen the slide clamp pressure screws, then remove the clamps from the case. Step 2: Remove the mounting slides from the case by sliding them off the back. Step 3: Slide the controller case back into the panel cutout until the flanges contact the panel. Step 4: Reinstall the slides and slide clamps from behind the panel. Step 5: Tighten the pressure screws until the slides are tight against the panel.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
47
Control Relays Analog Outputs
CPU
Analog Inputs
Figure 3-2
CPU/IO PCB Configuration Switches
Internal Settings
The CPU/IO PCB, auxiliary PCB, and some back panel assemblies have configuration switches and/or jumpers whose settings might need to be changed for a specified application. To do so, you must remove the internal components from the controller case, verify or change the appropriate settings, and reassemble the controller.
Warning!
Disconnect the power cable before disassembling the controller or disconnecting any internal component.
Caution:
Never disassemble a controller or handle its components without taking steps to prevent static discharge.
Disassembly
Use the following procedure to access the internal components of a newly-mounted Series 3++ Controller: Step 1: Make sure the power cable is not connected to the rear of the controller. Step 2: Loosen the screw at the bottom of the front panel, pull its left side forward about an inch, then swing it out and to the left. Step 3: Remove the engineering panel assembly from the case by removing the four screws at its corners and pulling the entire assembly forward to disengage it from the CPU/IO PCB. Step 4: Pull the internal components from the case (considerable force may be required). Step 5: Separate the auxiliary PCB (if present) by removing the four screws that attach it to the CPU/IO PCB, then disengage the pins on its rear side from their CPU/IO PCB connector.
August 2007
UM3300/H (1.1.0)
48
Chapter 3: Installation DO2 Mode Switch NORM
NO
CR6
DO2 FAULT
NO
CR1
DO6 NC
NC
NO
CR7 CR8
DO7
DO1
NO
CR4
DO4
NO
CR2
DO2
NC
NC
NC
NO
NO
NO
DO8 NC
CR5
DO5
CR3
NC
DO3 NC
Normal Position Switches
Figure 3-3
CPU/IO Control Relay Switches
CPU/IO PCB Control Relay Switches CR1 is normally-energized for use as a fault relay, while CR3 to CR8 must be energized by the control program (see Discrete I/O on page 74). The operation of CR2 is set by its mode switch, which is located to the left of CR6 on the CPU/IO PCB: • If it is set to its upper NORM position, CR2 will be a normally de-energized relay that is programmatically or parametrically set to indicate some process or internal condition. • If it is set to its lower FAULT position, CR2 will be a second fault relay that only de-energizes when CR1 does. In addition, each relay must be configured for normally-open (NO) or normally-closed (NC) operation by setting the normal position switch (DO#) located to its right: • Setting that switch to the lower NC position connects that relay’s field terminals to its normally-closed contacts. • Setting that switch to the upper NO position connects them to the normally-open contacts.
Note:
August 2007
A relay’s NO contacts are open and its NC contacts are closed when it is de-energized. The NO contacts of normally-energized fault relay are usually selected, so the external circuit will be complete when no fault exists.
UM3300/H (1.1.0)
Series 3++ Hardware Reference
V
AIN1 1
AIN2 1
AIN3 1
AIN4 1
AIN5 1
AIN6 1
AIN7 1
49
AIN8 1
AIN I
Figure 3-4
Analog Input Switches
2 SW11
2 SW12
2 SW13
2 SW14
2 SW15
2 SW16
2 SW17
2 SW18
Analog Input Resistors and Mode Switches The eight analog inputs are individually configured to accept either current-loop (20 mA) or voltage (5 Vdc) signals by setting switches SW11/AIN1 through SW18/AIN8, which are mounted halfway up on the right side of the CPU/IO PCB (see Figure 3-4): • Setting a switch to the upper (1/V) position configures its circuit as a voltage input. • Setting a switch to the lower (2/I) position configures its circuit as a current-loop input. The appropriate settings for FTA-equipped turbine controllers are discussed on page 59. The scaling and testing of these inputs is discussed on page 75.
Note:
August 2007
Unlike Series 3 Plus Controllers, which had to be equipped with all 5 Vdc or all 20 mA analog inputs, Series 3++ Controllers can be set up for any desired combination of voltage and current-loop inputs. It is also not necessary to install resistors across unused voltage inputs.
UM3300/H (1.1.0)
50
Chapter 3: Installation On CPU/IO PCB V
Inside Back Panel
1
AO1
V
V2 I2
2 SW21
I
V1 I1
1
AO2 I
2
SW22
V2 I2
Figure 3-5
Analog Output Switches
V1 I1
Analog Output Switches and Jumpers The CPU/IO PCB analog outputs are individually configured to provide either current-loop (20 mA) or voltage (5 Vdc) signals by setting switches SW21/AO1 and SW22/A02, which are mounted near the top of the auxiliary PCB connector on the upper-right side of the CPU/IO PCB (see Figure 3-5): • Setting a switch to the lower (1/I) position configures its circuit as a current-loop output. • Setting a switch to the upper (2/V) position configures its circuit as a voltage output. Terminal-block back panel assemblies have jumpers on the inner side of their circuit boards that can be set to either an I (current loop) or V (voltage) position. For Series 3++ Controllers, either position connects the back-panel terminals to the switch-selected signal, so you never need to change them when installing Series 3++ boards into a case that formerly housed a Series 3 Plus Controller (but the jumper positions would indicate how the switches should be set). The turbine controller FOM provides two sets of terminals for each of these outputs. Because these are connected in parallel to the switch-selected signal, both can be used only if voltage operation is selected (although the second set of terminals could be connected to a high-impedance voltmeter even if the circuit was configured for current-loop operation.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference JP5
JP6
Figure 3-6
JP3
JP4
51
JP1
Daughter Card JP1
Jumper Locations on the Auxiliary PCB
Auxiliary PCB Jumper Settings
When installing a turbine controller or replacing its auxiliary PCB, you must verify the correct setting of several jumpers on that board. (jumper JP6 is not used).
Fault Relay Jumper
Jumper JP1 configures the auxiliary PCB fault relay (CR9). Connect the center and right pins for normally-open (NO) operation, or short the center and left pins for normally-closed (NC) operation.
Inductive Load Jumper
The auxiliary PCB includes special circuitry to deal with inductive loads on the high-current output. If that output is connected to an electronic I/P transducer, you might need to bypass this circuitry by removing jumper JP3.
Maximum Output Jumpers
The high-current output’s maximum current is set to any of three values by setting jumpers JP4 and JP5: • to select a 200 mA maximum output, short the two top pins of both jumpers (labeled 200 mA), • to select a 60 mA maximum output, short the two center pins of both jumpers (labeled 60 mA), or • to select a 20 mA maximum output, short the two bottom pins of both jumpers (labeled 20 mA). The selected range can be further restricted by setting the high-current output and loopback calibration parameters (see page 82).
Daughter Board Jumper
August 2007
In order to use the LVDT position input, you must connect the center and left pins of jumper JP1 on the auxiliary PCB daughter board.
UM3300/H (1.1.0)
52
Chapter 3: Installation
Reassembly
To reassemble a Series 3++ Controller, you basically reverse the Disassembly procedure: Step 1: To reinstall the auxiliary PCB, align the pins on its rear side with the corresponding connectors on the CPU/IO PCB, then press them together. Reinstall the four machine screws that attach the auxiliary PCB to the CPU/IO board. Step 2: Slide the resulting assembly into the case as a unit. The CPU/IO PCB and PSA fit into the left-most set of grooves in the top and bottom of the case. Press fairly hard until you feel the PSA “pop” back into its connector on the front of the back panel. Step 3: Align the tabs on the sides of the engineering panel’s mounting brackets with the grooves in the sides of the case, then slide it back until the front of those brackets is flush with the front of the mounting flange (thus engaging it into the connector on the front edge of the CPU/IO PCB). Secure this assembly by reinstalling the four screws at its corners. Step 4: Swing the front panel back and to the right until it contacts the front of the case. Pull its left edge forward about an inch, until you can engage the tab on its right rear side into the slot in the right side of the case. Push the left side back until the panel is parallel to the front of the case, then secure it by tightening the retaining screw at the bottom of the panel. Step 5: Reconnect the power cable and FTA data cables or backpanel terminal strips.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Compressor Controllers
CR1 1 2
CR3 1 2
CR4 1 2
CR5 1 2
Turbine Controllers
CR2 1 2
DISCRETE IN D1 D2 D D3 D4 D5
53
CR6 1 2
CR1 1 2
CR2 1 2
CR7 1 2
CR9 1 2
CR3 1 2
CR4 1 2
CR5 1 2
DISCRETE IN D1 D2 D D3 D4 D5
DISCRETE
DISCRETE
D6 D7
D6 D7
D8 D9
Figure 3-7
Back-Panel Connections Discrete I/O
Back-Panel Discrete I/O Terminals This section tells how to connect field devices to a controller’s backpanel field input and output terminals.
Every Series 3++ Controller’s CPU/IO PCB provides eight discrete inputs and eight control relays. • Compressor controllers provide back-panel terminals for seven of those inputs (D1 through D7) and five relays (CR1 to CR5). • Turbine controllers without FTAs provide terminals for all eight of those inputs (D1 to D8) and seven relays (CR1 to CR7), as well as the fault relay (CR9) and one discrete input (D9) from the auxiliary PCB. The locations of those terminals are shown in Figure 3-7. All discrete inputs are optically isolated from the connected signals and share a common return terminal labeled by a D in a triangle. The discrete outputs are dry contacts that are galvanically isolated from all other controller circuits. The controller’s 24 Vdc transmitter power output could be included in their external circuitry but usually does not provide enough power for all of them.
August 2007
UM3300/H (1.1.0)
54
Chapter 3: Installation Internally Powered
Externally Powered
DISCRETE IN D1 D2 D D3 D4 D5
DISCRETE IN D1 D2 D D3 D4 D5
30 Vdc (max.)
24VDC DISCRETE
24VDC DISCRETE
+
Figure 3-8
+
– D6 D7
– D6 D7
Back-Panel Discrete Input Wiring Figure 3-8 shows how to connect the discrete inputs to external devices: • The left panel shows how to include external power sources. • The right panel shows how to incorporate the controller’s 24 Vdc transmitter power output.
CR1 1 2
CR3 1 2
Figure 3-9
CR4 1 2
CR2 1 2
CR5 1 2
30 Vdc, 1.0 A. max.
Load
Back-Panel Control Relay Wiring Figure 3-9 shows how to connect field devices to a controller’s drycontact, non-directional, back-panel control relay terminals.
Caution:
August 2007
The controller’s transmitter power output does not have sufficient capacity to drive the control relay circuits.
UM3300/H (1.1.0)
Series 3++ Hardware Reference Compressor Controllers CH 1 + –
CH 2 + –
CH 3 + –
CH 4 + –
CH 5 + –
CH 6 + –
CH 7 + –
CH 8 + –
OUT 1 +
Turbine Controllers OUT 2 +
Analog I/O
+
CH 1 –
CH 2
+
–
CH 3
+
–
CH 4
+
–
OUT 1
+
OUT 2
+
OUT 3
+
24VDC + –
Figure 3-10
55
24VDC + –
Back-Panel Analog I/O Terminals Every Series 3++ Controller’s CPU/IO PCB provides eight analog inputs and two analog outputs: • Compressor controllers have terminals for both of these outputs (OUT1 and OUT2) and all of these inputs (CH1 to CH8). • Turbine controllers without FTAs have terminals for both of these outputs (OUT2 and OUT3) but only four of these inputs (CH1 to CH4). OUT1 is provided by the auxiliary PCB. The terminals for these circuits (see Figure 3-10) are usually connected to an intermediate terminal block, with the cable shields tied to an earth ground at that point. Back-panel current-loop outputs are connected in series with their control elements (and any other load) as if they were batteries, as shown for OUT1 in the left panel of Figure 3-11. Thus, the positive (+) output terminal should be connected to the positive terminal of the first load. The negative terminal of the first should be connected to the positive of the second, and so on. The negative terminal of the last load should be connected to the negative (–) output terminal. Voltage outputs are wired in parallel with all connected devices, as shown on the right side of Figure 3-11. Current-loop inputs are wired in series with all connected devices, as shown for CH1 in the left panel of Figure 3-11. Voltage inputs are wired in parallel with all connected devices, as shown in the right panel of Figure 3-11.
August 2007
UM3300/H (1.1.0)
56
Chapter 3: Installation Current Loops
Voltage Circuits
FT
FY
G
OUT 1 +
CH 1 + –
FY
FT +5
CH 1 + –
OUT 1 +
24VDC + –
Figure 3-11
Speed Inputs
Back-Panel Analog I/O Connections Turbine controllers without FTAs provide terminals for three of the auxiliary PCB’s speed inputs (FREQ1 through FREQ3), located to the left of the power connector at the bottom of the back panel. These terminals (see Figure 3-12) should be connected to MPUs using twisted-pair cables whose shields are tied to an earth ground. By convention, the black lead of each magnetic pickup (MPU) is connected to the positive terminal and its white lead is connected to the negative terminal. However, the inputs are non-polar and will function correctly even if you do not follow this convention.
Note:
Twisted-pair cables are recommended for speed input signals. FREQ1 FREQ2 FREQ3 +
–
+
–
+
–
TB6
Figure 3-12 August 2007
Back-Panel Speed Input Terminals UM3300/H (1.1.0)
Series 3++ Hardware Reference
FTA Connections
57
In order to use all of the input and output circuits provided by the CPU/IO and auxiliary PCB assemblies, a turbine controller must be equipped with the optional field input and output modules (FIM and FOM), which are collectively called field termination assemblies (FTAs). Specifications and terminal lists for those modules can be found in the back of the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]. Snap each FTA onto a DIN mounting rail and connect it to the controller back panel using a high-density interconnect cable (HDIC): • Connect the field input module to the back-panel J1 connector and the field output module to the J2 connector. • If the FTAs are located in the same cabinet as the controller, ground both of each HDIC’s shield pigtails. Otherwise, only the controller ends of the HDICs should be grounded (grounding both ends can create an electric shock hazard if the ground potentials differ). In order to safely comply with CE electromagnetic requirements, connect both ends of each HDIC to equal-potential grounds.
Warning!
Independently grounding both ends of a long HDIC can create a hazardous ground loop.
FIM 24Vdc Bus
The FIM includes a 24 Vdc bus that can be used to power discrete and analog input circuits. It can be configured to draw that power from either the controller’s transmitter power supply or any source connected to terminals 1 and 2. Although this choice could be made by selectively installing diodes and jumpers in the 24 Vdc jumper block, it is simpler to install the diodes and jumpers for both sources and either leave terminals 1 and 2 disconnected or remove the fuse for the internal power circuit: 24 VDC
24 VDC
(to I/O circuits)
(to I/O circuits)
A C E G
B D F H
A
C
E
G
A
C
B
D
F
H
B
D
1.0 Amp
August 2007
G
F
H
1.0 Amp 1
(in controller)
E
2
1
2
(in controller)
UM3300/H (1.1.0)
58
Chapter 3: Installation
Discrete Input Fuses and Configuration Blocks DI1/DI3 DI5/DI7 DI9/DI11 DI13/DI15
DI1 to DI6
Figure 3-13
FIM Discrete Input Circuits
DI7 to DI13
1.0 Amp
DI10/DI12 DI14/DI16
1.0 Amp
DI6/DI8
14 16
DI2/DI4
DI14 to DI16
FIM Discrete Input Features Each of the FIM’s discrete input circuits has a jumper block that can configure it to draw power from the FIM 24Vdc Bus: • To configure one of these circuits to use the onboard 24 Vdc, install jumpers between pins A and D, B and E, and C and F, and install a dry contact device across the field terminals: A B C DI
A
D
B
E
C
F
24 Vdc 50 mA
D E F
• If a circuit is externally powered, configure it to bypass the onboard bus by installing jumpers between pins A and E and pins B and F (note that this reverses the polarity of the terminals from that listed by DS3300/T): A B C DI
A
D
B
E
C
F
24 Vdc
D E F
August 2007
50 mA
UM3300/H (1.1.0)
Series 3++ Hardware Reference
59
Fuses and Configuration Blocks AI-1
AI-3
AI-5
AI-7
AI-2
AI-4
AI-6
AI-8
Analog Inputs 1, 2, and 3
Analog Inputs 7 and 8
Figure 3-14
FIM Analog Input Circuits
Analog Inputs 4, 5, and 6
FIM Analog Input Features Each of the FIM’s analog inputs has an jumper block and five wiring terminals (B, C, D, H, and S). Terminals B, C, D, and H are directly connected to the corresponding pins of the configuration block, the S (shield) terminal is connected to the FIM’s earth ground. The CPU/IO PCB is switch configured (see page 49) to read the voltage drop across or current flowing between terminals C and D. The simplest application is to connect a 5 Vdc transmitter to the C and D terminals (62 and 63, for example) and set the CPU/IO PCB switch for 5 Vdc operation: B
A C E G
61 E
C 50 mA
24 Vdc
A
G
B D F H
62
+
Xmtr
CH F
63
D
–
64
H
65
Shield
When a 4-to-20 mA transmitter is used in a simplex application, the preferred configuration is to connect it to the C and D terminals and set the CPU/IO PCB switch for 20 mA operation (this uses the CPU/IO PCB’s precision dropping resistor): B
A C E G
66 E
C 50 mA
24 Vdc
A
H
F
D
68
+
–
+
69 70
August 2007
Xmtr –
CH G
B D F H
67
Shield
UM3300/H (1.1.0)
60
Chapter 3: Installation Alternately, a 250 ohm dropping resistor can be installed between the C and D terminals and the CPU/IO PCB switch can be set for 5 Vdc operation (however, this would provide less-precise, uncalibrated measurements unless a precision potentiometer was installed and precisely adjusted): B
A C E G
66 E
C 50 mA
24 Vdc
A
+
CH G
B D F H
67
Xmtr –
F
68
D
–
+
69
H
70
Shield
To use the FIM 24Vdc Bus to power a 4-to-20 mA transmitter, jumper pin A to B and G to F, then connect the transmitter across the B and C terminals: B
A C E G
E
C 50 mA
24 Vdc
A
81
CH G
B D F H
82
F
+
Xmtr –
83
D
84
H
85
Shield
To include a DCS current-loop input in a 4-to-20 mA circuit, jumper pin G to H and connect the DCS input across the D and H terminals: B
A C E G
E
C 50 mA
24 Vdc
A
81
CH G
B D F H
82
H
F
D
83 84 85
August 2007
+
Xmtr – +
DCS –
Shield
UM3300/H (1.1.0)
Series 3++ Hardware Reference
61
MPU 1 to 3
Auxiliary Input MPU 4, 5, 6+
LVDT1
Figure 3-15
FIM Speed Inputs
FIM Speed and Position Inputs Turbine controllers with FTAs provide terminals for all six of the auxiliary PCB’s speed inputs (frequency inputs 1 through 6). with the exception of the negative terminal for the rarely used sixth MPU, all of them are located on the FIM. By convention, the black lead of each magnetic pickup (MPU) is connected to the input’s positive terminal and its white lead is connected to the negative terminal. However, the inputs are non-polar and will function correctly even if you do not follow this convention. These terminals (see Figure 3-12) should be connected to MPUs using twisted-pair cables. to prevent ground loops, connect the cable shield to the FIM shield terminal and leave it ungrounded at the pickup end.
Note:
Twisted-pair cables are recommended for speed input signals. The speed input circuits are capacitively isolated from the MPUs within the controller.
FIM Position Inputs
The FIM also provides terminals for the auxiliary PCB’s LVDT and analog position inputs: • LVDT leads have five-conductors that should be connected to the corresponding FIM terminals — two for the excitation coil (51 & 52), two for the return coil (53 & 55), plus a common (74). Connect the shield to any convenient shield terminal and make sure the left and center pins of the Daughter Board Jumper (see page 51) are connected. • If your controller uses the bipolar 20 mA position input, connect it to the auxiliary input terminals (71, 72) and any convenient shield terminal.
August 2007
UM3300/H (1.1.0)
62
Chapter 3: Installation
OUT:
Figure 3-16
FOM 24Vdc Bus
FOM Analog Outputs
3
1
2
3
FOM Analog Output Terminals If any relay circuits are configured to use the onboard power bus, a 24 Vdc source must be connected to terminals 29 and 30: 24 VDC
24 VDC
(from controller)
(to I/O circuits)
26
Caution:
2
27
28
29
30
The controller’s transmitter power output does not have sufficient capacity to drive the control relay circuits and thus should not be connected to FOM terminals 29 and 30. Current-loop OUT1, which is configured as described on page 51, should be connected in series with all loads. Its positive terminal should be connected to the positive terminal of its first load. If there is more than one load, the negative terminal of the first should be connected to the positive of the second, and so on. The negative output terminal should be connected to the negative terminal of the last (or only) load. OUT2 and 3, which can be independently set for either current-loop or voltage operation (see page 50), have two sets of terminals each: • If 20 mAdc operation is selected, connect all loads in series to one set of terminals. The second set should be connected (if at all) only to a high-impedance voltmeter. • If 5 Vdc operation is selected, connect all loads in parallel using either or both sets of terminals.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
63
Fuses and Configuration Blocks CR1 CR2 CR4 CR6 CR8 CR3
24 Vdc In
Figure 3-17
FOM Control Relay Circuits
CR5
CR7
CR9
CR8 and CR9
CR1 to CR7
FOM Control Relay Features Each of the FOM’s control relay circuits has a jumper block that can configure it to draw power from the FOM 24Vdc Bus (which draws power from terminals 29 and 30) and include the provided fuse: • To configure a relay circuit to use the FTA’s onboard 24 Vdc, install jumpers between pins C and D and pins G and H: A C E G
B
A 1.0 A
CR
C
H
D
G
B D F H
Field Element – 24 Vdc
• For circuits using external 24 Vdc power sources, bypass the onboard source by installing a jumper between pins C and H: A C E G
B
A 1.0 A
CR
Field Element
C
H
D
G
B D F H
– 24 Vdc
• Each circuit includes an onboard fuse that can be bypassed by installing a jumper between pins A and B of the jumper block: A C E G
B
A 1.0 A
CR
B D F H
August 2007
Field Element
C
H
D
G 24 Vdc
UM3300/H (1.1.0)
64
Chapter 3: Installation PORT 1 1 TX/RX + –
PORT 2 TX2 RX2 + – 2 + –
PORT 3 TX3 RX3 3 + – + –
PORT 4 TX4 RX4 4 + – + –
Port 1
Port 2
Port 3
TB6
Port 4
Figure 3-18
Communication Ports
Communication Port Terminals The CPU chip provides four EIA RS-485 serial ports (Ports 1 to 4). The controller back panel or field output module (FOM) provides compression terminals for all of them (see Figure 3-18), which in either case are galvanically isolated from the instrument ground, each other, and all other I/O circuits. The connection of those ports to other controllers or computers is discussed below. For compressor controllers, the back-panel terminals for Ports 3 and 4 can be replaced by built-in Modbus RTU-to-TCP converters (see page 23). The connection of those ethernet ports to other controllers or computers is discussed on page 67. In either case, Ports 2, 3 and 4 must be configured as discussed under Serial Communication on page 72.
Serial Connections Cable Length
Note: Surge Suppression
Termination Resistors August 2007
Because each serial port supports communication among several devices connected to a single cable, certain RS-485 networking considerations apply. Unless RS-485 repeaters are installed, the total length of the cables in each network can be no more than 4000 feet (1200 meters). Always use shielded, twisted-pair serial communication cables. All Series 3++ I/O circuits, including the serial ports, are designed to withstand electrical surges of 4000 volts or more, so external surge suppression devices are usually not needed. The serial port transceivers used in Series 3++ Controllers do not require termination resistors at any of the available baud rates. UM3300/H (1.1.0)
Series 3++ Hardware Reference
Port 1
Master
Tx/Rx+
Tx/Rx+
Tx/Rx+
Tx/Rx–
Tx/Rx–
Tx/Rx–
Ground
Ground
Ground
Figure 3-19
100 Ω
Port 2
65
Slaves
Rx –
Tx +
Tx +
Rx +
Tx –
Tx –
Gnd
Gnd
Gnd
Tx –
Rx +
Rx +
Tx +
Rx –
Rx –
100 Ω
Wiring Diagrams for Ports 1 and 2
Ports 1 and 2
Ports 1 and 2 are used to communicate with other Series 3++ Controllers using proprietary protocols. Figure 3-19 shows how to wire such networks, whose ground terminals should be interconnected using the cable shields and collectively grounded through a single small resistor (100 ohms generally works well). They should not be grounded at any other point.
Port 1
Serial Port 1 communication is used to coordinate the actions of Series 3++ Controllers regulating a single turbomachinery train. In installations where several trains are operated in parallel, there will usually be a separate Port 1 network for each train. Under the Port 1 protocol, each device transmits in turn to all of the others. Thus, these ports are connected in parallel by a single pair of wires (all positive terminals together in one group, and all negative terminals in a second).
Port 2
Port 2 is used primarily for load-sharing and performance override control. The protocol it uses designates a single primary controller (the master) that can either broadcast to the other controllers on the network or query a single secondary controller for specific information. The secondary controllers transmit only in response to such queries. Only one secondary controller can transmit at any given time, and then only to the master. Port 2 networks are installed as shown in the right panel of Figure 3-19. The secondary controllers’ receivers are wired in parallel with the master’s transmitter and the secondary controllers’ transmitters are similarly wired in parallel to the master’s receiver.
August 2007
UM3300/H (1.1.0)
Chapter 3: Installation
66
Host
Host
Controllers
Controllers
Tx/Rx +
Tx +
Tx +
Rx +
Tx +
Tx +
Tx/Rx –
Tx –
Tx –
Rx –
Tx –
Tx –
Ground
Gnd
Gnd
Ground
Gnd
Gnd
Rx +
Rx +
Tx +
Rx +
Rx +
Rx –
Rx –
Tx –
Rx –
Rx –
Figure 3-20
Ports 3 and 4
Connecting to an RS-422/485 Host Port Ports 3 and 4 are used to communicate with external devices using the Modbus RTU protocol, such as a DCS or a PC running one of our Support Software Packages (see page 27). That protocol allows a single master device and multiple slaves to be connected to each network (Series 3++ Controllers are always slaves). These ports can be directly connected to a host’s RS-422 or RS-485 serial port using either a two-wire or four-wire connection (as shown in Figure 3-20). You should use Belden 8723 twisted-pair cable (or its equivalent), and ground the shield at one end only.
Note: Port 3 and 4 Grounding
9 25 pin pin
Host
2 3 4 5 6 7 8 20
TxD RxD RTS CTS DSR GND DCD DTR
3 2 7 8 6 5 1 4
The ground pins of interconnected Modbus serial ports must not be connected and grounded unless none of them are grounded at any other point. Although Ports 3 and 4 are isolated from all grounds, we generally advise against grounding their networks (as indicated by the lack of ground pin connections in Figure 3-20).
Converter 2 3 4 5 6 7 8 20
Figure 3-21
August 2007
Using a two-wire connection will increase the communication load on each controller, as it would then “hear” the responses of its peers to requests the master directs to them.
Controller + – + – G
Rx + Rx – Tx + Tx – Gnd
9 25 pin pin
Host
Controller
2 3 4 5 6 7 8 20
TxD RxD RTS CTS DSR GND DCD DTR
Rx + Rx – Tx + Tx – Gnd
3 2 7 8 6 5 1 4
Connecting to an RS-232 Host Port
UM3300/H (1.1.0)
Series 3++ Hardware Reference RS-232 Converter
67
If your host is equipped with serial ports conforming to the more common RS-232C standard, you should connect them to the controllers using an RS-485/232 converter with isolated grounds (for example, the AEG OIC-422). Because Series 3++ Controllers do not support handshaking signals (such as request-to-send/clear-to-send), you might need to crossconnect those of the host. A typical wiring diagram for this application is shown in the left panel of Figure 3-21. In an emergency (say your converter fails and you can not wait for a replacement), you can directly connect a controller’s RS-485 port to a computer’s RS-232 port as shown in the right panel of Figure 3-21. However, you can not connect very many controllers at a time, nor use very long cables. PORT 2 TX2 RX2 + – 2 + –
24VDC DISCRETE +
–
D6 D7
PORT 3
PORT 1 1 TX/RX – +
PORT 4
96-264 VAC 21-32 VDC
MADE IN USA
Figure 3-22
Ethernet Connections
N GRD H 35 W max
Ethernet Communication Ports Compressor controllers can be equipped with Modbus TCP back panel assemblies that feature built-in Modbus RTU/TCP converters for serial Ports 3 and 4 (see Figure 3-22). Their RJ-45 jacks can be connected to the same or separate ethernet switches or hubs using standard category 5 patch cables. One or more Modbus TCP clients can then communicate with each of those ports via the associated TCP/IP networks. Alternately, a single client can be connected to each jack using an ethernet cross-over cable. When a converter port is connected using the appropriate cable, its lower, yellow LED will light. Its upper, green LED will flash when it is sending or receiving ethernet packets Although the converters are built into the back panel, the controller can communicate with them only as a Modbus slave that cannot send configuration instructions. So, they must be configured from a PC connected to their ethernet jacks, as described in Chapter 4 of the Series 3++ Modbus Reference manual [UM3300/M] or Appendix B of the Series 3 OPC Server user manual [UM5503].
August 2007
UM3300/H (1.1.0)
68
Chapter 3: Installation
M630
Figure 3-23
Power Cable
Power Cable As shown in Figure 3-23, each pair of panel-mounted controllers is supplied with a 14-foot (4.3 meter) power cable, both ends of which have connectors that plug into the back-panel power receptacle. This cable can be cut at any point to provide maximum flexibility in choosing the length of the two resulting cables. The configuration of the power cable connectors depends on which power supply (AC or DC) is installed, as shown in Figure 3-24.
Warning!
Because the power cable connector is not designed to assure the ground conductor is the first connection made and the last broken, there is a risk of electric shock while connecting or disconnecting the cable to the controller. AC Cable Cable
Controller
DC Cable – (Black) Ground (White)
Line (Black)
+ (Red)
Ground (Green)
Cable
Neutral (White)
Figure 3-24
Controller
Power Cable Connector Configurations The ground conductor of the power cable should be connected to a suitable earth ground. This grounds the case (for electrical safety), provides the reference potential for internal power supply voltages and analog outputs, and serves as a sink for any transient voltages and high-frequency components of the analog input signals.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference UM3300/H
Chapter 4
69
Series 3++ Hardware Referencemanual
Configuration and Operation
This chapter describes the general operation of the controller and tells how to configure the field I/O circuits. Chapter 6 describes the general operation and maintenance uses of the front panel.
Overview
The operation of a compressor controller is orchestrated by two microprocessors (one each on the CPU/IO and engineering panel PCBs), which communicate via an internal parallel port. Turbine controllers have a third microprocessor (on the auxiliary PCB, which communicates with the CPU via another parallel link. External I/O and serial communication signals pass between the back panel and CPU/IO PCB via the power supply PCB, where they are either read/written or connected to the appropriate auxiliary PCB circuits (which are read and set by its CPU). When the controller is first powered up, each processor loads its own firmware, initializes its associated components, then initiates normal operation and communication with the others. Each controller can be operated from any combination of: • its front panel readouts, LEDs, buttons, and keys; • readouts, potentiometers, indicators, and switches connected to its analog and discrete I/O channels; and/or • operator workstations connected to its Modbus serial ports, either directly or via a Series 3 OPC server.
August 2007
UM3300/H (1.1.0)
70
Chapter 4: Configuration and Operation
CPU/IO Board Operation
The microprocessor on the CPU/IO PCB is a field programmable gate array (FPGA) that has been programmed to duplicate the computational, I/O logic, and serial communication features of the Series 3 Plus Controller’s CPU and analog PCB assemblies. Thus, the only changes required to run the field-proven Series 3 Plus control programs on these controllers were adaptations to the new internal PCB and front panel features. When the FPGA powers up, it loads the stored programming and interconnections for its internal logic units from an associated flash memory chip. This has two implications: • powering down and restarting a controller can potentially correct some CPU malfunctions, and • the operation of the FPGA can potentially be improved by downloading a new program to the flash memory chip. The FPGA program configures some of its circuits to emulate: • a microprocessor that runs the machine control program stored in the EEPROM chips; • the parallel ports used to communicate with the front panel and optional auxiliary PCB assembly; • the analog and discrete I/O interface; and • the four serial communication ports. To identify the installed FPGA firmware, enter the Program Version [MODE TEST 2] engineering keyboard sequence and then press the decimal key until the FPGA display appears.
Machine Control Program
The actions of the main CPU (within the FPGA) are specified by a machine control program stored in the EEPROM chips, which can be updated by the Configurator program via serial Port 4 (see page 71). Each such program (for example, version 761-001 of the antisurge control program) defines: • a startup sequence (see page 77); • a main loop that runs repeatedly (subject to various interrupts), which primarily handles communication tasks and checks for differences between the present and long-term parameter sets (see page 28); • an input/output scan (see page 75) triggered by a clocked five millisecond interrupt; and • a process control scan initiated by every eighth I/O scan (in other words, every 40 milliseconds). To identify the installed control program, enter the Program Version [MODE TEST 2] engineering keyboard sequence.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
71
FORCE
NORM
Loader Switch
Figure 4-1
Position of Loader Switch on Front of CPU/IO PCB
Reloading the Control Program
The machine control program can be updated via serial Port 4 from a PC running the Series 3 Plus Configurator program (see Chapter 2 of the Series 3 Engineering Utilities user manual [UM5513]).
Note:
Port 4 must be set for 19,200 baud and odd parity in order to replace the machine control program. A controller is usually prepared for that process simply by initiating manual operation, as discussed in the user manual for its currentlyloaded control program. However, a Series 3++ Controller can be forced into its program loader mode using the following procedure: Step 1: Power down the controller. Step 2: Loosen the screw at the bottom of the front panel, pull its left side forward about an inch, then swing it out and to the left. Step 3: Remove the engineering panel assembly from the case by removing the four screws at its corners and pulling the entire assembly forward to disengage it from the CPU/IO PCB. Step 4: Move the loader switch at the front of the CPU/IO PCB (see Figure 4-1) to its FORCE (down) position. Step 5: Align the tabs on the sides of the engineering panel’s mounting brackets with the grooves in the sides of the case, then slide it back until the front of those brackets is flush with the front of the mounting flange (thus engaging it into the connector on the front edge of the CPU/IO PCB). Temporarily reinstall one of the four screws that normally secure that assembly. Step 6: Power up the controller. The SP readout will indicate “Addr.” and the OUT readout will display the controller’s computer ID. Step 7: Connect the controller to a PC running the Series 3 Plus Configurator program.
August 2007
UM3300/H (1.1.0)
72
Chapter 4: Configuration and Operation Step 8: Start that program and invoke its Download command. Step 9: Click the Load BHF File button and select the desired control program (.bhf) file from the resulting dialog. Step 10: Click the Select From Port and Controller Number option, then select the PC port the controller is connected to from the Port Number menu and the computer ID displayed in the OUT readout from the Controller Number menu. Step 11: Click the Start button to download the new program. The thirteen progress bars along the left side of the dialog will indicate the progress of the program download. Step 12: When the download is finished, power down the controller, remove the engineering panel, move the loader switch back to the NORM (up) position, and replace the engineering panel. Step 13: Reconnect the power cable, then use the Program Version [MODE TEST 2] engineering keyboard procedure to verify that the controller is now running the desired control program. Step 14: Secure the engineering panel by reinstalling the four screws at its corners, then close and secure the front panel. This procedure is normally used only after a failed or interrupted program download has left a controller otherwise inoperable. If that happened with a Series 3 Plus Controller, controller operation could be restored only by installing pre-programmed EEPROM chips.
Serial Communication
The FPGA provides four EIA RS-485 serial ports: • Ports 1 and 2 are used for communications with Series 3++ and other CCC Controllers. • Ports 3 and 4 are used for Modbus RTU communication with host computers or control systems, using two-byte registers with a configurable significant range (as discussed in the Series 3++ Modbus Reference manual [UM3300/M]). All four are protected against transients by the power supply PCB, and optically-isolated (from the instrument ground and each other) by the CPU/IO PCB. There are no internal termination resistors, which are not usually needed at the supported baud rates. The occurrence of low-level (parity, framing, and overrun) errors is indicated by beeping and displaying a “Com# POF” message on the Engineering Panel (see page 110). Unless frequent or continuous, such errors are not generally serious. If a controller is not receiving expected Port 1 or 2 transmissions, however, it will light the Alarm LED. The problematic port can then be identified by displaying the status screen alarms menu. The corresponding Modbus bit and possibly a control relay will also be set.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Configuring Communications
73
In order for two devices to successfully communicate, both must be set up to send and receive information at the same speed and in the same basic format (for example, number of bits per character): • There are no parameters for Port 1, which operates at 38.4k baud with even parity, 1 start, 8 data, and 2 stop bits. • The Port 2 Baud Rate [MODE:D COMM 2] can be 2400, 4800, or 9600. It is normally set to 9600. If you wish to mix Series 3 and Series 3++ Controllers, however, you must set the Port 2 baud rate to the 2400 bps rate used by the older controllers. This port also uses even parity, 1 start, 8 data, and 2 stop bits. • The Port 3 Baud Rate [MODE:D COMM 3] can be 4800, 9600, 19.2k, or 38.4k baud, while the Port 3 Parity can be odd, even, or none. The same options are available for the Port 4 Baud Rate [MODE:D COMM 4] and the Port 4 Parity. Both of these ports use one start bit, eight data bits, and one stop bit. The key sequences that set these ports’ baud rates and parities also allow you to select the Port 3 Scaling and Port 4 Scaling. Each of those parameters specifies the Modbus register value that port would report for most real variables when they equal their normal maximum values (generally 100 percent): • The 4000 setting reports 100% as 0x0FA0. • The 4095 setting reports 100% as 0x0FFF. • The 64k setting reports 100% as 0xFA00. In addition, multidropped ports require a unique identifying number for each controller. The Port 1 protocol uses the Controller ID Number [MODE:D COMM 0], while the Port 2 protocol and Modbus use the Computer ID Number [MODE:D COMM 0 •]. When a Modbus RTU-to-TCP converter is connected (internally or externally) to Port 3 or 4, that port must be configured to use the same baud rate and parity as the converter’s serial port. By default, the built-in converters available for compressor controllers are set for 19.2 kbaud and odd parity. Finally, a controller can be configured to prevent Modbus hosts from setting coil and holding register values by setting the Modbus Write Inhibit [MODE:D LOCK 2] parameter to On. The Enable Reconfiguration [MODE LOCK 5 1] key sequence must be entered before changing settings from the engineering panel.
Note:
August 2007
To alter a controller’s operation from a PC workstation, you must clear the Modbus Write Inhibit [MODE:D LOCK 2] parameter. However, its control program can be updated when that parameter is set.
UM3300/H (1.1.0)
74
Chapter 4: Configuration and Operation
Discrete I/O
The D1 through D8 input signals are routed directly to the FPGA and read by each process control scan: • Compressor control programs associate each of those signals with a predefined controller feature. • For turbine control programs, those associations are set by the Discrete Input Assigned Function [COND:D IN ##] parameters. Conversely, each scan sets or clears the FPGA’s discrete outputs to indicate whether or not the conditions assigned by the corresponding Relay Assigned Function [MODE:D RA #] parameters exist. Those signals are routed to a clocked-latching chip, whose outputs in turn energize or de-energize the coils of the corresponding control relays (thus, those outputs will freeze rather than clear if the CPU faults or restarts): • CR3 through CR8 energize and de-energize as their assigned functions set and clear the corresponding discrete outputs. • CR1 is a normally-energized fault relay (see Fault Indicators on page 104). • CR2 can be switch-configured (see page 48) to be energized by its own assigned function or to de-energize when CR1 does (in which case it should usually be assigned the same function as CR1 so its state indicators will echo those for CR1). Compressor controllers have back-panel terminals only for CR1 through CR5. Turbine controllers have terminals for all eight, and provide another fault relay and eight more discrete inputs that are connected to the auxiliary PCB. The monitored discrete input and intended discrete output states can be displayed by the front-panel status screen.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference AN IN OFF
AN IN ON
(e.g., 0 to 10 V)
(e.g., 4 to 20 mA)
CH (V)
CH (mA)
Sampling Hardware Failed if: < AN IN LOW or > AN IN HIGH
AD (%)
Sampling Hardware Failed if: < AN IN LOW or > AN IN HIGH
SV (%)
MV = Min + (Span · SV)
MV
Figure 4-2
Analog Inputs
AD (%)
SV = 1.25 • (AD - 20%)
SV = AD
MODE TEST 4
75
MODE TEST 4
SV (%)
MV = Min + (Span · SV)
MV
Analog Input Signal Processing The CPU/IO PCB provides eight analog field input circuits (CH1 to CH8), whose signals are protected against transients by the power supply PCB, and filtered and isolated (from the instrument ground and each other) by the CPU/IO PCB. The Analog Input Switches (see page 49) route each such signal to a multiplexed 14-bit analog-to-digital converter (ADC) either: • directly (if it is connected to voltage transmitter), or • via a precision dropping resistor (if it is connected to a currentloop transmitter). In either case, there is no need and no provision for calibrating any such circuit, either before shipment or in the field. Each five millisecond input scan retrieves the digital values of these signals, then triggers a logic circuit that sequences the reading of new values for the next I/O scan. Each process control scan then: • averages the last eight values of each signal; • compares the result to the 21.0 mA smart-transmitter fail level specified by the Namur NE 43 recommendation and a configurable testing range set by that input’s Analog Input Low Alarm Limit [MODE:D ANIN # LOW] and Analog Input High Alarm Limit [MODE:D ANIN # HIGH] or the Dual-Loop A/P Controller’s common Transmitter Failure Limit [MODE:D ANIN LOW];
August 2007
UM3300/H (1.1.0)
76
Chapter 4: Configuration and Operation • calculates its signal variable value by scaling it to between 00.0 and 100.0 percent of the span selected by that input’s Offset Zero Input [MODE:D ANIN #] parameter; and • calculates its measured variable engineering units value by linearly scaling that signal variable within the range defined by its Measured Variable Maximum [COND:D DISPLAY 0 # HIGH], Measured Variable Minimum [COND:D DISPLAY 0 # LOW], Measured Variable Decimal [COND:D DISPLAY 0 # •], and Measured Variable Name and Units [COND:D DISPLAY 0 # –]. If its Measured Variable Display [COND:D DISPLAY 0 #] is enabled, an input’s measured variable value and alarm limits status can be displayed by the front panel status screen. The Transmitter Status Test [MODE:D ANIN –] and the Signal Values Test [MODE TEST 4] can be used to view any input’s alarm limits status and signal variable value from the engineering panel. The 16-channel ADC also reads eight internal analog inputs, which are used to monitor the analog output signals, the five componentpower voltages, and the internal temperature. The front panel status screen can also display all of these variables (see Monitoring Controller Health on page 100).
Analog Outputs
The CPU/IO PCB provides two analog outputs that are powered by the isolated 24 Vdc field power circuit and internally protected against electrostatic discharge and other voltage transients. Compressor controllers label these circuits OUT1 and OUT2, while turbine controllers label them OUT2 and OUT3 (OUT1 is the speed board’s High-Current Analog Output). Each process control scan specifies a new normalized value for each of these outputs, which usually can be clamped and/or nonlinearly scaled as appropriate for the connected field device. It then triggers a logic circuit that sequences the conversion of those values to voltage signals by the 16-bit digital-to-analog converter (DAC). The intended values are latched, so the generated voltages freeze if the CPU faults or restarts. These output circuits are calibrated prior to shipment and cannot be adjusted in the field. The generated voltages are monitored by internal analog inputs, and the intended and measured value of each can be displayed by the front-panel status screen. Because PID control algorithms automatically adjust to inaccurately calibrated output circuits, any discrepancy between the actual and intended values is not considered a fault. However, an output failure alarm would be indicated and any output failure relays would be set.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
CPU Reset
77
When a controller is first powered up, the FPGA loads the stored programming and interconnections for its internal logic units. It then resets the emulated CPU, which: 1. 2. 3. 4. 5.
Initializes the I/O circuitry and serial ports. Sends a restart instruction to the engineering panel. Resets its serial ports and analog input circuitry. Writes the “Reset” message to the engineering panel readout. Assigns default values to any configuration parameters that have unreasonable values, and instructs the engineering panel to display the resulting parameter checksum (“CS=####”). 6. Initiates a new scan of the machine control program. A CPU reset is also initiated when the watchdog timer triggers the CPU/IO Fault Relay (see page 105), critical parameters are changed or an alternate parameter set is recalled, the controller is reconfigured from a workstation, or the Reset Controller [MODE COMM] key sequence is entered from the engineering panel. Note that the battery-backed RAM, which stores the most recent values of all control program internal variables, is not initialized. Thus, those programs can and generally do resume control of the process from its last known state. Most controllers always execute a soft reset, which does not change the operating state or analog output. However, the Speed Controller will execute a hard reset (which initiates an emergency shutdown) when it is powered up or detects a fault.
August 2007
UM3300/H (1.1.0)
78
Chapter 4: Configuration and Operation
Speed Board Operation
The Auxiliary PCB and its daughter board provide: • eight additional discrete input circuits and its own fault relay (see below), • linear variable displacement transformer (LVDT) and bipolar 20 mA current-loop valve Position Inputs (see page 79), • six Speed Inputs (see page 79) for magnetic pickup frequency signals, and • a configurably bipolar High-Current Analog Output (see page 82) that includes loopback circuitry for measuring its own value. It also provides a high-speed valve positioning loop that varies the high-current output in response to deviations of the LVDT input from an intended position received from the main CPU. However, that loop is supported only by the speed controller and is used primarily for upgraded Series 3 Plus systems that implemented it prior to the development of our external Digital Positioning Module (see the Valve Positioning section in Chapter 3 of UM3307). To identify the installed auxiliary PCB firmware, enter the Program Version [MODE TEST 2] engineering keyboard sequence and then press the decimal key until the SPBD display appears. In addition, the Auxiliary PCB Error Count [MODE TEST HIGH] key sequence will dynamically display the number of times this board’s CPU has failed to respond to the main CPU since this count was last zeroed. An Extraction Controller that does not use any of its speed board’s I/O signals can be configured to ignore or operate without it by enabling the Auxiliary PCB Lockout [MODE:E LOCK 6] parameter.
Speed Board Discrete I/O
The auxiliary PCB provides discrete inputs D9 through D16. All of them are supported by controllers equipped with FTAs, while those with terminal-block back panels can use only D9: • Their states are read by the speed board microprocessor and then communicated to the main CPU. • The associated controller features are set by the corresponding Discrete Input Assigned Function [COND:D IN ##] parameters. The speed board provides no additional discrete outputs other than its normally-energized fault relay (CR9), which is controlled by that board’s watchdog timer (see Speed Board Fault Relay on page 105 and cannot be assigned any additional function.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Position Inputs
79
This assembly provides two inputs for valve position measurements. LVDT1 is for linear variable differential transformer measurements, while the Auxiliary Input supports bipolar 20 mA position signals. None of the standard control programs supports the Auxiliary input, and only the Speed Controller supports LVDT1. To use it, the Daughter Board Jumper (see page 51) must configure it for an LVDT rather than a transducer feedback signal.
Speed Inputs
Three of the six auxiliary PCB speed inputs are supported by the Series 3++ Speed Controller, none of the other control programs support any. They can read the frequency signals from either active or passive magnetic pickups: • If active pickups are used, the controller can read any speed that produces at least a 5 Hz signal. The corresponding minimum speed depends on the number of teeth on the exciter and shaft ratio. For example, a 60-tooth gear mounted on the main shaft would generate a 5 Hertz signal at 5 rpm. • If passive pickups are used, the minimum detectable speed is that at which the voltage of the MPU signal meets the minimum listed on the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]. This can be determined from the electrical specifications for your MPUs. In addition to physically connecting them to the MPUs, these inputs must also be enabled (see below) and configured to compensate for both the number of teeth on the MPU gear and its shaft ratio (see Speed Scaling on page 80). You enable the speed input for each installed MPU by setting its selection parameter to On: MPU 1: Speed Input 1 [MODE:S ANIN 1] MPU 2: Speed Input 2 [MODE:S ANIN 2] MPU 3: Speed Input 3 [MODE:S ANIN 3] If more than one MPU is enabled, the controller uses the following rules to decide which one to use as the speed control variable: • If there are three good input signals, the median speed is selected. • If there are two good input signals, the higher of those two speeds is selected. • If there is only one good input signal, that speed is selected. • If all MPUs fail, an emergency shutdown (ESD) is initiated.
August 2007
UM3300/H (1.1.0)
80
Chapter 4: Configuration and Operation Turbine Shaft
Speed Gear
Figure 4-3 Speed Scaling
Auxiliary Shaft
Magnetic Pickup
MPU Signal Varies With Speed, Shaft Ratio, and Tooth Count As shown in Figure 4-3, each MPU is positioned near a balanced gear on the turbine’s main or auxiliary shaft, and transmits a pulse to the controller each time a gear tooth rotates past. The frequency of the MPU signals depends not only on the speed of the turbine, but also on the number of teeth on the speed gear and the ratio of the auxiliary and turbine shaft speeds. Thus, the following function is used to calculate the turbine speed from the number of pulses received during each scan:
N = (C ⋅ P ⋅ Rs ) ⁄ T where C= N= P= Rs = T=
scan rate (scans per minute) rotational speed (in rpm) pulse count (pulses/scan) Shaft Speed Ratio [MODE:S ANIN 6] Gear Tooth Count [MODE:S ANIN 5]
Set the Gear Tooth Count equal to the number of teeth on the speed measuring gear and the Shaft Speed Ratio equal to the number of turbine revolutions required to rotate that gear once. For example, AN IN 6 should be 1.000 if the gear is on the turbine’s main shaft. If it’s on an auxiliary shaft that turns half as fast as the turbine, AN IN 6 should be 2.000. If at all possible, the speed gear should be mounted on the turbine’s main shaft.
Note:
August 2007
It is important to properly match the pickups to the design of the gear that excites them. Otherwise, high-speed operation may not allow enough time for their signals to decay between the passage of adjacent teeth. If a sufficiently high speed was then reached, the measured speed would suddenly fall to zero and the controller would shut down the turbine!
UM3300/H (1.1.0)
Series 3++ Hardware Reference MPU Tests
81
Two factors affect the minimum speed that can be read by the controller’s frequency / magnetic pickup (MPU) inputs: • An MPU signal frequency below 5 Hertz can not be read. The corresponding minimum speed depends on the gear tooth count and shaft ratio. For example, a 60-tooth gear mounted on the main shaft would generate a 5 Hertz signal at 5 rpm. • An MPU signal voltage below the minimum required by the speed inputs can not be read. This is normally an issue only for passive pickups (for which the voltage is a rising function of the speed). If active (constant voltage) pickups are used, the controller can measure any speed above that corresponding to a 5 Hertz signal. This can be determined by comparing the electrical specifications of your MPUs to those listed on the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]. MPU failures are determined by comparing the speed from each input to the Control Threshold [COND:S ALARM 1]. An input fails this test if it is below that level.
Note:
The Control Threshold is stored as a percentage of and thus must be set after the Maximum Control Speed [COND:S DISPLAY HIGH]. If all three speed inputs are enabled, the highest and/or lowest will also be considered to have failed if it has differed from the median speed by more than a user-defined tolerance for at least eight consecutive scan cycles:
Median – Tol < N < Median + Tol where Median = median of the speeds calculated from the three inputs Tol = MPU Tolerance [MODE:S ANIN 4] A failure of either type generates an “MPU# Fail” alarm. If all of the enabled speed inputs fail, the turbine is shut down. For example, assume all three inputs are enabled and the tolerance is 91 rpm. If MPU 1 indicates 3600 rpm, MPU 2 indicates 3650 rpm, and MPU 3 indicates 3700 rpm, the acceptable speed range is 3650 ± 91 (3559 to 3741) rpm. Because all three signals are in this range, all three are judged to be valid. However, if the MPU 3 signal was greater than 3741 rpm, an “MPU3 Fail” alarm would be indicated.
August 2007
UM3300/H (1.1.0)
82
Chapter 4: Configuration and Operation Actuator Control Signal Yes | Act – Outt | > 5%?
OutF
Outt Signal Scaling
Loopback Scaling
Out1 Output Circuitry
Outa Loopback Input
I1
I1
To Valve Actuator
Figure 4-4
High-Current Analog Output
High-Current Output Functional Diagram For turbine controllers, OUT1 is provided by an auxiliary PCB circuit that can generate almost any current-loop signal from –200 to +200 mA. Because this greatly exceeds the usual 4 to 20 mA range, this circuit is usually called the high-current output. It includes: • a digital-to-analog converter (DAC) that generates an intermediate 0 to 5 Vdc signal, • circuitry that converts that voltage into a current signal with a jumper-selectable maximum magnitude of 20, 60, or 200 mA, • a phase inverter that can be turned on by the auxiliary PCB’s CPU when reverse current flow is needed, and • an analog-to-digital converter (ADC) that measures the loopback value of this signal. As shown in Figure 4-4, the high-current output signal and its loopback measurement are calibrated by setting their scaling gains and biases, which can also restrict this signal to a portion of the range selected by the Maximum Output Jumpers (see page 51): • The output signal’s range is specified by setting its calibration gain and bias (see Output Circuit Calibration on page 85). • The loopback measurement is scaled to match by setting its gain and bias (see Loopback Circuit Calibration on page 87). However, those procedures are not meant as routine maintenance tasks—the usual practice is to set the calibration parameters only when the controller is first installed.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Unipolar Output
Bipolar Output
100%
100%
Output to DAC
Output to DAC
0%
0% 0%
Control Signal
On Phase Inverter Off 200 mA Output to Valve –200 mA
Figure 4-5
83
100%
0%
Control Signal
100%
On Phase Inverter Off 200 mA Output to Valve –200 mA
Operation of Bipolar Output Once you have determined the range of the actuator control signal, you should calculate its ideal, minimum, and maximum acceptable values at 5, 50, and 95 percent of span and record them in a table similar to Table 4-1. The recommended tolerance is ±0.25 percent of the maximum output (for example, ±0.15 mA for a 60 mA output). Table 4-2 gives the recommended ranges for several of the most commonly used actuators. The Signal Values Test [MODE TEST 4] can be used to view the raw loopback measurement (Outa in the figure, displayed as AD3) and its calibrated value (Outt in the figure, displayed as AD5).
Note: Caution: Bipolar Operation
August 2007
When checking or changing the calibration of the output or loopback circuits, record any parameter changes you make and restore the original values of all but the scaling parameters when you are done. Calibrate this circuit only while the turbine is shut down or under some alternate form of control. The high-current output of a Speed Controller can be configured for bi-directional operation (for example, –200 to +200 mA) by enabling its Bipolar Output [COND:D OUT 1 –] parameter. The speed board’s CPU then calculates the magnitude of that signal as shown in the top right panel of Figure 4-5, and turns the phase inverter on when a negative current flow is needed.
UM3300/H (1.1.0)
84
Chapter 4: Configuration and Operation Table 4-1
Expected Output Readings Actuator Range (mA): Measured Current (mA) OUT Display
Ideal
Minimum
Maximum
5.0 % 50.0 % 95.0 %
Table 4-2
Expected Output Readings for Common Actuators Measured Current (mA) OUT Display
Ideal
Minimum
Maximum
Actuator Range: 4 to 20 mA 5.0 %
4.80
4.75
4.85
50.0 %
12.00
11.95
12.05
95.0 %
19.2
19.15
19.25
Actuator Range: 20 to 160 mA 5.0 %
27.00
26.60
27.40
50.0 %
90.00
89.60
90.40
95.0 %
153.0
152.6
153.3
Actuator Range: –20 to +20 mA 5.0 %
1.00
0.95
1.05
50.0 %
10.00
9.95
10.05
95.0 %
19.00
18.95
19.05
Actuator Range: –35 to +35 mA 5.0 %
1.00
0.95
1.05
50.0 %
10.00
9.95
10.05
95.0 %
19.00
18.95
19.05
Actuator Range: –60 to +60 mA
August 2007
5.0 %
3.00
2.85
3.15
50.0 %
30.00
29.85
30.15
95.0 %
57.00
56.85
57.15
UM3300/H (1.1.0)
Series 3++ Hardware Reference Output Circuit Calibration
85
The Output Scaling Gain [COND:D GAIN 1] and Output Scaling Bias [COND:D BIAS 1] both calibrate and restrict the range of the high-current output signal. Thus, you should first enter nominal (ideal) values for those parameters based only on the desired range restriction, and then adjust them to precisely calibrate this signal. This circuit is set up to generate a maximum current (Imax ) of 20, 60, or 200 mA by setting the Maximum Output Jumpers (see page 51). Its range is then matched to that of the actuator by calculating the final output as a percentage of twice that maximum (see Figure 4-4):
I 1 = Ou t 1 ⋅ ( I max ⋅ 2 ) Act ⋅ Gai n 1 Ou t 1 = ------------------------------- + Bias 1 100 where: Act = Bias1 = Gain1 = I1 = Imax = Out1 =
actuator control signal, in percent the Output Scaling Bias the Output Scaling Gain high-current output, in mA maximum high-current output (20, 60, or 200 mA) calculated output signal (decimal)
Because the actuator control signal must be between zero and 100 percent, the actual output can never be less than (Imax · 2 · Bias1), nor more than [Imax · 2 · (Gain1 + Bias1)]. Because I1 can not exceed Imax , the sum of Gain1 and Bias1 should not exceed 0.50. The nominal values of this gain and bias should be calculated as:
I high – I low Gai n 1 = 0.5 ⋅ --------------------------I max
and
I low Bias 1 = 0.5 ⋅ ----------I max
where: Ihigh = 100 percent value of actual high-current output (mA) Ilow = 0 percent value of actual high-current output (mA) For bipolar outputs, Ilow (and thus the nominal bias) must be zero. Negative signals are generated as positive currents which are then reversed by the phase inverter. If Ilow is not zero, there will be a gap around the zero point of the output! To configure a 4 to 20 mA signal, for example, set JP4 and JP5 for a 20 mA maximum signal, so Ihigh = Imax = 20, Ilow = 4, and the nominal Bias1 to 0.1 and the nominal Gain1 to 0.4:
Gai n 1 = 0.5 ⋅ ( 20 – 4 ) ⁄ 20 = 0.4 Bias 1 = 0.5 ⋅ 4 ⁄ 20 = 0.1 August 2007
UM3300/H (1.1.0)
86
Chapter 4: Configuration and Operation Use the following procedure to fine-tune the nominal gain and bias or to recalibrate this output signal: Step 1: Disconnect the control element from the OUT1 terminals on the FOM or back panel and connect an ammeter in its place. Step 2: Disable the Bipolar Output [COND:D OUT 1 –], Positioning Loop [MODE:D fC 1], and Output Reverse [MODE:S REV 1] features (if they exist and are enabled). Step 3: Manually adjust the controller output to 5, 50, and 95 percent. Compare the resulting ammeter readings to the ranges recorded in your Expected Outputs Table (see Table 4-1). If all of them are acceptable, skip to step 10. Step 4: Manually set the output to 25 percent and record the ammeter reading as OUTlow. Step 5: Manually set the output to 75 percent and record the ammeter reading as OUThi. Step 6: Use the following formula to calculate a new gain value: 0.5 ⋅ Span Gain 1 = Gai n p ⋅ ---------------------------------------- Out hi – Ou t low where Gain1 is the new value, Gainp is the previous value, and Span is the span of the output range (for example, 16 for a 4 to 20 mA output). Set the Output Scaling Gain [COND:D GAIN 1] equal to this new value. Step 7: Set the output to zero (0) percent and adjust the Output Scaling Bias [COND:D BIAS 1] until the meter reading agrees with the desired minimum output signal (generally, add the error divided by twice Imax to the bias). If that signal is zero, make sure it rises with even a slight increase of the intended output. Step 8: Recheck the accuracy of the signal at 5 and 95 percent and repeat steps 4 to 7 until satisfactory results are obtained. Step 9: Manually adjust the output to 50 percent. If the resulting meter reading is not in the acceptable range, the Auxiliary PCB should be replaced. Step 10: Disconnect the ammeter, reconnect the control element, and restore the original values of any parameters you changed.
Note:
August 2007
If the controller reverts to automatic operation during this test, it is probably because a limiting loop or manual override was triggered. Determine which feature is responsible and disable it.
UM3300/H (1.1.0)
Series 3++ Hardware Reference Loopback Circuit Calibration
87
The Loopback Scaling Gain [COND:D GAIN 2] and Loopback Scaling Bias [COND:D BIAS 2] calibrate and adjust that measurement to the actual range of the high-current output signal. As with the output scaling parameters, you should first enter nominal (ideal) values for these parameters based only on the desired range restriction and then adjust them to precisely calibrate this measurement. If valve positioning is supported and enabled, this gain and bias are not used and need not be set. Otherwise, they scale the internal measurement of the actual high-current output for comparison to its intended value (see Figure 4-4):
Ou t t = 100 ⋅ ( Ou t a + Bias 2 ) ⋅ Gai n 2 where: Outa = raw loopback measurement, expressed as a decimal fraction of the maximum high-current output (Imax ) Outt = scaled measurement for loopback test (in percent) Bias2 = the Loopback Scaling Bias Gain2 = the Loopback Scaling Gain The nominal values of this gain and bias can be calculated as: – I low Bias 2 = -----------I max
and
I max Gai n 2 = -------------------------I high – I low
where Ilow and Ihigh define the intended range of the output signal. For example, consider an ideal 4 to 20 mA output:
I low = 4 –4 Bias 2 = ------ = – 0.20 20
I high = I max = 20 20 Gai n 2 = ---------------- = 1.25 20 – 4
If the high-current output is accurately calibrated, you can use the following procedure to fine-tune the nominal loopback scaling or to recalibrate this measurement: Step 1: Make sure the First Output Assigned Variable [COND:D OUT 1] is set to OUTL and the Bipolar Output [COND:D OUT 1 –] and Positioning Loop [MODE:D fC 1] are disabled. Step 2: Use the Signal Values Test [MODE TEST 4] to display the scaled loopback signal (AD 5) on the Engineering Panel. Step 3: Observe the AD5 value while you manually vary the displayed output from zero to 100 percent. Although they can differ by up to 5 percent without triggering a loopback failure, they should match as closely as possible. If the calibration is satisfactory, skip to step 11. Step 4: Set the displayed output to 25.0 percent and record the displayed value of AD5 as Inlow . August 2007
UM3300/H (1.1.0)
88
Chapter 4: Configuration and Operation Step 5: Set the displayed output to 75.0 percent and record the displayed value of AD5 as Inhigh . Step 6: Press CLEAR to terminate the Signal Values Test. Step 7: Calculate and enter a new Loopback Scaling Gain [COND:D GAIN 2] using the following formula:
Gain 2 = Gai n p ⋅ 50 ⁄ ( In high – In low ) where Gain2 is the new value and Gainp is the previous value. Step 8: Press MODE TEST 4 8 and then the decimal key (several times) to again display AD5 on the Engineering Panel. If necessary, adjust the output so AD5 is not zero. Step 9: Subtract the new value of AD5 from the displayed output and record that error. Step 10: Press CLEAR to again terminate the Signal Values Test. Step 11: Calculate and enter a new Loopback Scaling Bias [COND:D BIAS 2] using the following formula:
error Bias 2 = Bias p + ------------------------------100 ⋅ Gain 2 where Bias2 is the new value and Biasp is the previous value. Step 12: Set the displayed output to 0.00 and redisplay AD5. If it is zero, increase the bias enough to give AD5 a slight positive value (zero or less is always treated as a loopback failure). Step 13: Repeat until satisfactory results are obtained, then restore the original values of any parameters you changed.
Note: Output Loopback Test
August 2007
It the loopback alarm activates unnecessarily when the output is at its minimum value, make the Bias slightly less negative. If it comes on at maximum output, slightly lower the Gain. If the First Output Assigned Variable [COND:D OUT 1] is set to ActL or ActP, an output failure is indicated if its readback and intended values differ by more than 5.0 percent of span for a minimum time defined by the Output Failure Delay [COND:D CONST 2].
UM3300/H (1.1.0)
Series 3++ Hardware Reference
PV SP
ALT
LIMIT 2
LIMIT 3
OUT
89
Control Loop Readouts and Buttons
Controller Type
Fault Alarm
Mode RUN Tran OutF Alarms Com1&2 24V ACK
MENU
AUTO
SCROLL
MAN
∆
Tracking Limit
TEST
A
Figure 4-6
Engineering and Front Panel Operation
Status LEDs, Screen and Buttons
ENTER
Control LEDs and Keys
∇
#
General Layout of Series 3++ Front Panel The microprocessor on the engineering panel PCB runs an embedded program that displays information from the main CPU on the front panel and its own readout and sends back codes identifying the currently-pressed front and engineering panel keys and buttons. Chapter 2 provided an operational description of the engineering panel. Chapter 6 describes the maintenance features of the front panels, which (as shown in Figure 4-6) have three main sections: • The upper section has a three-digit control response readout, five-digit controlled variable and set point readouts, and three buttons that select the feature whose data is displayed. • The middle section provides the Status Screen and Menu System Buttons (see page 90), Fault LED (see page 105), and Alarm LED (see page 106). • The lower section has eight control keys and twelve LEDs, three of which are embedded in associated keys, plus a Test key that displays the engineering panel firmware revision and activates the front-panel User Preferences and LED Tests.
August 2007
UM3300/H (1.1.0)
90
Chapter 4: Configuration and Operation
Status Screen and Menu System Buttons
The various information screens that can be displayed by the 4-line by 10-character status screen are organized into menu groups and selected by pressing the MENU and SCROLL buttons. However, the operation of the compressor and turbine controller menu systems differ somewhat: • The top line of each compressor controller screen displays the current operating state. Pressing the MENU key displays the most recently viewed screen from the next menu / group. You can then cycle through the screens in that group by repeatedly pressing the SCROLL key. • The top line of each turbine controller screen identifies the selected menu. Pressing the MENU key displays the first screen from the next group, which only displays the menu name (for Speed Controllers, it also displays the date and time). You can then display that menu’s first and subsequent data screens by repeatedly pressing the SCROLL key. Turbine controllers also provide Menu and Scroll discrete input functions that can be used to remotely select the active menu and screen. The internal clock of a Speed Controller can be reset using the Set Clock [MODE TEST 9] engineering panel procedure.
User Preferences and LED Tests
Holding down the TEST key displays the installed front-panel firmware version (left-most screen): Display Testing & Options Ver. #.##
LCD Contrast Adjustment Use ¨Î
LED Brightness Adjustment Use ¨Î
LED Test
• Pressing the SCROLL button while continuing to press TEST would then display a prompt (second screen above) indicating that the contrast of the LCD status screen could be adjusted by pressing the Raise or Lower key. • Pressing SCROLL again would display a prompt (third screen above) indicating that the brightness of the control loop readouts could be adjusted by pressing the Raise or Lower key. • Pressing SCROLL a third time would display the right-most screen above and light every readout and indicator LED on both the front and engineering panels. Holding down the SCROLL button and pressing the Raise or Lower key will ramp the beep frequency higher or lower.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference UM3300/H
Chapter 5
91
Series 3++ Hardware Referencemanual
Redundant Controllers
This chapter tells how to set up and operate redundant controllers. Controlled Process Main Controller .000 SP
Controller Inputs
DEV
9.3 ALT
LIMIT 2
LIMIT 3
OUT
Controller Outputs
Antisurge Controller
Fault Alarm
Controller Inputs REDUNDANT CONTROL SELECTOR
Mode RUN TotlB=10.3 SrgCnt=001 ACK
MENU
AUTO
SCROLL
MAN
TEST
ENTER
Controller Outputs
SP
Fault
MAIN
Fault Relays
Switch to Back-Up
Tracking Input
BACK-UP
Alarm
Fault Relays
LIMIT 2
LIMIT 3
OUT
Mode RUN TotlB=10.3 SrgCnt=001 ACK
MENU
SCROLL
MAN
Tracking Input
Switch to Main GREEN ACTIVE
DEV
9.3 ALT
AUTO
∇
#
.000
Antisurge Controller
SURGE RESET
∆ A
Backup Controller
Selected Outputs
RED TRACK
SURGE RESET
∆ TEST
A
ENTER
∇
#
Serial Port 1 Application Tracking Communications
Figure 5-1
Overview
Redundant Controller Data Flow Series 3++ Controllers can be installed in a dual-redundant, paired configuration. The main controller in each pair will normally regulate your process while its “hot” backup monitors it via serial Port 1 so it can instantly take over if the main controller should fail. Each controller pair is connected by a Redundant Control Selector (see page 94) or other switching device that: • clears the Tracking discrete input of the active controller and connects the final control elements to its outputs, and • asserts the Tracking discrete input of the redundant controller and excludes the final control elements from its output circuits. Each controller is configured to track the operating state and outputs of the other only when its own tracking input is asserted by setting its Redundant Tracking [MODE:D fE 1] parameter to true. Switching is triggered by the main controller’s fault relay, possibly wired in series with additional relays set up to be de-energized by other switching conditions. Each of the application manuals listed at the bottom of page 3 describes its available relay functions.
August 2007
UM3300/H (1.1.0)
92
Chapter 5: Redundant Controllers
Switching Logic
Typically, the switching circuitry for redundant Series 3++ Controllers provides Main and Backup buttons for manually activating either controller (provided it is healthy) and relay logic that automatically activates the backup controller if it is healthy and its main counterpart fails. Once the backup has been activated, however, control is not automatically returned to the main controller (that must be done by pressing the Main button while that controller is healthy). Figure 5-2 shows a hardware implementation of this logic, which selects the backup controller when the SR relay is energized: • If both controllers are healthy and neither button is pressed, the M and B relays would both be energized while S and R would both be de-energized: • Failure of the main controller or pressing the Backup button would energize S, thus selecting the backup controller by completing and latching the SR circuit. • Pressing the Main button would energize the R relay, thus selecting the main controller by de-energizing S and SR. • If the backup controller was unhealthy, it could not be activated because pressing its button would not energize S. If the main controller then failed, SR would remain de-energized. • If the main controller was unhealthy, it could not be activated because pressing its button would not energize R. • Failure of the backup controller while active would not break the SR circuit even if the main controller was healthy.
Tracking Input Circuits
One function of the redundant switching device is to energize the tracking input of the tracking controller. For compressor controllers, that is always discrete input D1. For turbine controllers, it must be assigned to an input provided by the CPU/IO PCB (DI-1 through DI8), but never to an auxiliary PCB input (DI-9 through DI-16). Figure 5-2 shows how the tracking inputs of redundant controllers should be connected to their own 24 volt transmitter power terminals through normally-open and -closed switching relay contacts.
Analog Output Switching
Another function of the redundant switching device is to connect control elements to the output signals of only the active controller. Current-loop outputs must also be connected in a way that maintains their continuity when not connected to the field device: • Figure 5-2 shows how this can be done using normally-open (NO) and -closed (NC) contacts of the switching relay (SR). • Figure 5-4 shows the corresponding RCS terminal connections.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Main Controller
Backup Controller
CR1 1 2
S
M
R
B
Backup
93
M
CR1 1 2
Main
SR M
B
S
SR
OUT 1 +
SR
R
OUT 1 +
+
FY –
SR SR
Main Controller
SR SR
Backup Controller
Current-Loop Outputs
DISCRETE IN D1
DISCRETE IN
D
SR
D1
SR
24VDC – +
24VDC – +
R
B
Backup
M
Main
SR
Main Active Backup Unhealthy
S
Figure 5-2
August 2007
Backup Active Both Healthy
M
Tracking Discretes
S
M
R
B
Backup
M
Main
SR S
Backup Controller
S
M
R
B
R
Backup
M
Main
SR
R
S
Backup Active Main Unhealthy
Main Active Both Healthy
Main Controller
S
D
S
M
R
B
R
Backup
M
Main
SR S
R
Typical Redundant Switching Circuitry
UM3300/H (1.1.0)
94
Chapter 5: Redundant Controllers
Redundant Control Selector
Redundant controllers require an independent device to sense main controller failures and automatically transfer control to its backup. Our Redundant Control Selector (RCS) fills that need by providing: • two fault-sensing circuits that connect to the fault and/or other appropriate control relays of the main and backup controllers, • sixteen isolated relay contacts that connect field devices to the main or backup controller’s analog outputs and control relays based on the states of the fault relay circuits, • LEDs and discrete outputs that indicate which controller’s outputs are connected to the process, and • buttons for manually selecting that controller. Hardware specifications for the RCS can be found on the Series 3++ Redundant Control Selector data sheet [DS3300/R].
Operation
Each RCS consists of an Operator Panel that is usually mounted between the front panels of the redundant controllers and a Switching Unit mounted in a less accessible location.The switching unit contains a latched master relay that controls four slave relays: • When de-energized, they connect the main controller to the field and energize the TB6 Main Active discrete output. The Main LED is green and the Backup LED is red. Only the backup controller lights its green Tracking LED. • When energized, they connect the backup controller to the field and energize the TB6 Backup Active discrete output. The Main LED is red and the Backup LED is green. Only the main controller lights its green Tracking LED. The switching unit routes 24 Vdc power through the fault relay of the main controller at all times. As long as that circuit is closed and control has not been manually transferred to the backup controller, the switching relays will be de-energized. If that circuit opens or the Switch to Backup button is pressed, those relays will energize if the backup controller’s fault relay circuit is closed. Once control has been passed to the backup controller, the relays will remain energized until the Switch to Main button is pressed while the main controller’s fault relay circuit is closed. Control of the process can never be transferred to a failed controller and is never automatically transferred to the main controller, even if it is healthy and the backup is not.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Main Controller
RCS Switching Unit
95
Backup Controller
To Transducer: – +
OUT 1 +
OUT 1 +
CR1 1 2
CR1 1 2
DISCRETE IN D1
DISCRETE IN
D
D1
24VDC – +
D
24VDC –
TB6
TB6
Figure 5-3
Fault Relay Connections
Typical Redundant Control Selector Connections Connect the TB6 main and backup controller Fault terminals to the CR1 fault relays of the corresponding controllers. If desired, other relays that would open to indicate additional switching conditions can be connected in series with the fault relay: • For turbine controllers, the auxiliary PCB fault relay (CR9) should be set for normally-open operation and wired in series with CR1, so an automatic switch to the backup controller will occur if either of them de-energizes. • All controllers offer a General Failure relay function that is primarily for redundant switching. These circuits are powered by the RCS, so its terminals indicate a polarity while the dry-contact controller relays do not.
Note: Tracking Input Connections
Field Output Module fault relay circuits connected to an RCS must be set up as dry contacts. Connect each controller’s tracking input (D1 for compressor and assignable for turbine controllers) to the 24 Vdc transmitter power outputs of both via a single switching relay contact (see Figure 5-3): • Connect the 24 Vdc of each controller to its own discrete return terminal and through a diode to the RCS Common terminal. • Connect the main controller input to the Track terminal. • Connect the backup controller input to the Run terminal. Each controller’s tracking input will then be asserted only when its peer is selected/active.
August 2007
UM3300/H (1.1.0)
96
Chapter 5: Redundant Controllers Backup
OUT 1 +
Main
OUT 1 +
RUN
TRACK COMMON
A B C D A B C D A B C D
FY
1 2 3 4 5 6 7 8 9 10 11 12
OUT 1 +
OUT 1 +
FY
Main Selected
1 2 3 4 5 6 7 8 9 10 11 12
OUT 1 +
OUT 1 +
FY
Backup Selected
1 2 3 4 5 6 7 8 9 10 11 12
Figure 5-4
Analog Output Connections
Connecting Current-Loop Outputs to an RCS The current-loop output circuits of redundant controllers must be connected to the switching device in a manner that maintains the continuity of both circuits while including the transducer in only one (so neither controller will indicate an output failure). The upper panel of Figure 5-4 shows how to do so using normally-open (NO) and closed (NC) contacts controlled by a single RCS switching relay. The other panels show how the signals are routed when each controller is selected: • When the main controller is selected (middle panel), its OUT1 circuit includes the transducer (red lines) while the backup controller’s circuit is closed by the relay (gray lines). • When the backup controller is selected (lower panel), its OUT1 circuit includes the transducer (red lines) while the main controller’s circuit is closed by the relay (gray lines).
Power Connections
August 2007
The RCS switching unit provides connectors for two independent external power supplies and automatically powers its circuits from the highest-voltage source. Connect one to a regulated 24 Vdc power converter and the other to a battery pack, with the converter adjusted to provide a voltage slightly above that of the batteries. Power will be drawn from the batteries if the power converter fails, but they will not be recharged when that source is restored.
UM3300/H (1.1.0)
Series 3++ Hardware Reference RCS Power Failure
97
If power to the RCS failed, the slave relays would de-energize and connect the main controller to the field. However, the latched master would remember which controller had been selected: • If the main controller was in control, it would remain so when power was restored (unless it had faulted in the meantime). • If the backup controller was in control, it would resume control when power was restored (even if it had faulted or the main controller had been repaired in the meantime). When a Speed or Extraction Controller RCS is connected to two power supplies, each controller can be set up to alarm the failure of one of them by wiring a discrete input assigned the -RS24 function in parallel with the RCS and one of its power supplies. That controller would then energize any +RS24 relays and signal an “RS24V Fail” alarm if that input was cleared, generally indicating a total failure of the corresponding power supply. If the RCS was without power, both controllers would indicate an RS24V failure.
Unswitched Connections
Input and communication signals must be connected to both controllers in such a way that both can monitor the process and either can be disconnected without affecting the signals to the other.
Discrete Input Connections
With the exception of the tracking input signals (see page 92), all redundant controller discrete inputs should be connected in parallel (rather than through the switching relay). Both controllers can then read them and the removal of either will not affect the other’s inputs.
Analog Input Connections
The analog inputs of redundant controllers should be configured to accept voltage signals (see Analog Input Switches on page 49). They can then be connected in parallel to 5 Vdc transmitters or across 250 ohm dropping resistors connected in series with 20 mA transmitters, so disconnecting either controller would not affect the input of the other. For redundant turbine controllers equipped with FTAs, this can be done by installing the dropping resistors across pins C and D of the FIM jumper blocks (see FIM Analog Input Circuits on page 59): B
A C E G
66 E
C 50 mA
24 VDC
A
August 2007
+
H
F
D
D
68
CH G
B D F H
67
Xmtr –
CH 68
–
+
67
50 mA C
69
UM3300/H (1.1.0)
98
Chapter 5: Redundant Controllers If the FIMs are configured to obtain their onboard 24 Vdc power from a source other than the controllers (see page 57), such a circuit can be powered from either FIM by: • jumpering its pin A to B and connecting its B terminal to the transmitter’s positive terminal, and • jumpering its pin G to H and connecting its H terminal to the other controller’s D terminal: B
A C E G
E
C 50 mA
24 VDC
A
91
CH G
B D F H
92
H
F
D
93
+
Xmtr –
92
50 mA C
CH 93
D
94
The same approach should be taken for the auxiliary current-loop input, but the resistors would have to be installed across their FIM terminals because no configuration block is provided for that circuit.
Serial Ports
If Modbus While Tracking [MODE:D LOCK 0] is Off, the main and backup controllers can be given the same Computer ID Number [MODE:D COMM 0 •]. Write requests will then be implemented by both but only the active controller will respond to read requests. Redundant controllers with Modbus While Tracking enabled must either be connected to different Modbus master serial ports or be assigned unique Computer ID Numbers so both can be remotely accessed via the same master port. Both controllers in each redundant pair must be connected to the same inter-controller serial communication networks. The backup controller does not transmit over Port 1, but does use it to track its active counterpart. Similarly, only the active controller responds to Port 2 requests. Because that port’s address is set by the Computer ID Number, redundant controllers will also have the same Modbus RTU ID. Thus, you must disable Modbus While Tracking or connect the controllers to separate host ports. If your hosts need to know which controller is active, hard wire one of the main controller’s otherwise unused discrete inputs so that it is always asserted. The corresponding discrete input bit or variable will then be cleared only when the backup unit is active.
Ethernet Ports
If Modbus RTU/TCP converters are used, there is no way they can communicate as a duplex pair because each port has to have a unique IP address. Each pair of controllers should be identified by giving them a common Computer ID Number and Modbus While Tracking should enabled even in load-sharing applications. Modbus TCP clients can tell which of the controllers is active by monitoring their Tracking discrete inputs.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference UM3300/H
Chapter 6
99
Series 3++ Hardware Referencemanual
Maintenance and Repair
This chapter discusses controller maintenance and troubleshooting.
Overview
Although Series 3++ Controllers are designed to run continuously for years without requiring any maintenance, hardware problems will occasionally be encountered: • Some developing problems can be detected by routinely reviewing various controller health variables (see Monitoring Controller Health on page 100). • The controller will indicate internal and field element problems as discussed in the sections on Problem Indicators on page 104 and Troubleshooting on page 112. • Most internal problems are resolved by replacing the controller or one or more of its main components (see Replacement Procedures on page 123). Although the turbine controller High-Current Analog Output (see page 82) could be routinely recalibrated, there is usually no reason to do so. No other field calibration is possible. Whenever a malfunctioning controller or CPU/IO PCB is replaced, the original CPU’s control program and configuration parameters must be restored. Both can be downloaded from a PC running the Configurator program (see Support Software Packages on page 27), provided you have ready access to that program and: • the downloadable file for the currently-installed version of each controller’s application software, and • an up-to-date configuration parameter set file. Those files are discussed in the Configurator documentation.
Note:
Port 4 must be set for 19,200 baud and odd parity in order to replace the machine control program. In addition, you should keep records of each controller’s installed program version and checksum, parameter set checksum, and Modbus port settings and ID number. These can be determined using the following engineering keyboard sequences: • • • • • •
August 2007
Program Version [MODE TEST 2] Program Checksum [MODE TEST 8] Parameter Checksum [MODE LOCK 4] Port 3 Baud Rate [MODE:D COMM 3] Port 4 Baud Rate [MODE:D COMM 4] Computer ID Number [MODE:D COMM 0 •] UM3300/H (1.1.0)
100
Chapter 6: Maintenance and Repair
Fault Alarm
Mode RUN Power: AB 24V = 24.0 15V = 14.7 MENU
Figure 6-1
SCROLL
Controller Status Screen and Menu Buttons
Monitoring Controller Health
The CPU/IO PCB temperature and power supply voltages and most field I/O signals can be monitored via the front-panel status screen and/or computer communications.
Internal Conditions
Each compressor controller’s main menu includes two screens that display the CPU/IO PCB component power voltages. Turbine controllers provide those screens via a separate Diagnostic menu:
Diagnostic Power: AB 24V = 24.0 15V = 15.0
then
Diagnostic 5.0V = 5.0 3.3V = 3.3 1.2V = 1.2
Table 6-1 lists the minimum CPU/IO PCB voltages needed for the controller to operate. If the internal 24 Vdc falls below its limits, correct the input voltage or replace the power supply assembly. If any converted voltage deteriorates, replace the CPU/IO PCB. That table also lists the acceptable input voltage ranges and the minimum 24 Vdc output voltage required by the analog outputs (any field devices connected to those terminals might require a higher voltage). If the input power is acceptable but the transmitter 24 Vdc output is not, replace the power supply assembly.
Table 6-1
Acceptable Voltages
PSA
Range
CPU/IO PCB
Minimum
AC Input
96 - 264 Vac
1.2 Vdc
1.15
CPU core
DC Input
21 - 32 Vdc
3.3 Vdc
3.00
RAM/clock chip
Xmtr Out
19.0 Vdc min.
5.0 Vdc
4.50
discrete I/O, serial ports, front panel
15 Vdc
14.25
analog I/O, Auxiliary PCB
24 Vdc
22.0
power converters for above voltages
August 2007
Used By
UM3300/H (1.1.0)
Series 3++ Hardware Reference
101
Scrolling past the second voltage screen displays the CPU/IO PCB’s temperature (measured near the hottest part of that board), which will generally be 20 to 25 degrees Celsius higher than that outside of the controller sleeve (controllers that have an auxiliary PCB run about five degrees hotter than those that do not):
Diagnostic Board Temp 050. degC Although temperature-related problems should not occur unless that temperature exceeds 90°C, additional ambient cooling should be provided if it routinely exceeds 80°C.
Field I/O Screens
Most field I/O signals can be monitored via the Main menu of a compressor controller or In/Out menu of a turbine controller.
Compressor Controller I/O Signals
In addition to any application specific screens, the Main menus of all three compressor controllers include the following I/O screens:
Mode RUN Digitals In:_2___6_ Out:1__4_ The above screen displays the states of all seven digital inputs and all five digital outputs (digits indicate inputs and outputs that are set). The 1 for fault relay CR1 will appear unless it (and possibly CR2) are de-energized by CR1’s assigned function. The above example indicates that only the D2 and D6 inputs are set and only the fault relays and CR4 should be energized. The next two presses of the SCROLL button would then display the intended and measured values of the analog outputs:
Mode RUN Analog Out Out1 =##.# Out2 =##.#
then
Mode RUN OutReadbck Out1= ##.# Out2= ##.#
If their accuracy deteriorates significantly, measure the voltage of the transmitter power circuit (which can indicate PSA malfunctions, bad input voltages, or excessive transmitter power demands). If it is okay, the controller or its CPU/IO PCB should be replaced (these outputs cannot be field calibrated). An output failure alarm would be indicated if any output used to drive a valve or other control element deviated from its intended value by more than five percent.
August 2007
UM3300/H (1.1.0)
102
Chapter 6: Maintenance and Repair Turbine Controller I/O Signals
The first In/Out menu screen of a Speed Controller lists the enabled speed readings, in rpm (Extraction Controllers skip this screen). The label for the selected input is displayed in all uppercase letters (SPD3 below), the labels for the others are capitalized (Spd#):
In/Out Spd1 4969 Spd2 5001 SPD3 4983 SCROLLing that menu then displays the digital inputs and outputs:
In/Out Digital In Î:1_34___8 ¨:9_BC_E_G
then
In/Out DigitalOut Î:_23__67_
Each digit or letter (A for input 10, G for 16) appears if that circuit is asserted or energized, otherwise it is replaced by an underscore. The digits for fault relays appear only if they are de-energized by the assigned relay function. The next two presses of the SCROLL button display the intended and read-back values of the analog outputs (if the optional positioning loop is enabled, the OUT1 readback is replaced by the LVDT1 valve position measurement):
In/Out In/Out In/Out Out1 =##.# RdBk1=##.# LVDT1=##.# Out2 =##.# then RdBk2=##.# or RdBk2=##.# Out3 =##.# RdBk3=##.# RdBk3=##.# If reverse action is enabled for an output, the displayed value will be the complement of the variable it represents: • If Out1 and RdBk1 differ significantly, try recalibrating the HighCurrent Analog Output (see page 82) and its loopback. If that fails, replace the auxiliary PCB. • Out2 and 3 cannot be recalibrated. If their accuracy deteriorates significantly, you should measure the voltage of the transmitter power circuit (which can indicate PSA malfunctions, bad input voltages, or excessive transmitter power demands). If it is okay, the controller or its CPU/IO PCB should be replaced. An output failure would be indicated only if the high-current output’s loopback test was enabled and RdBk1 differed from Out1 by more than five percent (5.0%) of span for a configured minimum time.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Analog In Menu
103
Each controller provides an Analog In menu, whose screens display the scaled, measured variable values and testing status of userspecified Analog Inputs (see page 75): • For compressor controllers, these screens also identify the current operating state:
Mode RUN Analog In 2:D Press 250. psig
or
Mode RUN Analog In 2:D Press 0. Fail
• Their turbine controller counterparts do not:
Analog In 1:V1 Press 250. psig
Analog In or
1:V1 Press 0. Fail
The word “Fail” is displayed after the value if the input’s unscaled value is not within its acceptable range, in which case a transmitter failure is indicated (see Analog Input Problems on page 118). The percent-of-range signal variable value of each analog input can be viewed using the engineering panel Signal Values Test [MODE TEST 4] key sequence. To determine if a specific input is being read correctly, disable its Offset Zero Input [MODE:D ANIN #] parameter and compare the TEST 4 value to a volt or ammeter measurement of the corresponding input signal.
August 2007
UM3300/H (1.1.0)
104
Chapter 6: Maintenance and Repair
Compressor Controllers
Turbine Controllers
Mode RUN Alarms Tran OutF Com1&2 24V
Alarms Com1 Error
Fault Alarm
MENU
Figure 6-2
Problem Indicators
Fault Indicators
SCROLL
Fault Alarm
ACK
MENU
SCROLL
Front-Panel Status LEDs and Alarm Menu Series 3++ Controllers provide various indications of internal and some external control system hardware problems: • Microprocessor and some power problems are indicated by the Fault Indicators (see below). • More specific problems are indicated by the Alarm System (see page 106) and optional External Alarms (see page 108). • Problems that are indicated by beeping can be investigated using the Engineering Panel (see page 110). • A redundant controller pair’s Tracking Indicators (see page 110) will signal the activation of the backup peer. • Speed Controller problems that trigger emergency shutdowns are recorded in the Shutdown Log (see page 111). Microprocessor and some power problems are indicated by the front-panel Fault LED, the CPU/IO Fault Relay, and/or the Speed Board Fault Relay. Because each is controlled by a different PCB, they do not convey the same information. Although various main CPU and RAM/clock chip problems would de-energize the PCB/IO fault relay and also light the fault LED, a total loss of power to the controller or failure of the internal 24Vdc power would only de-energize the fault relays (the LED obviously could not light under those circumstances). In most systems, each controller’s fault relays are connected to external logic circuits that will automatically shut down or transfer control of the compressor or turbine to a backup device when any such relay de-energizes. You can then identify and correct the cause of that action.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Fault LED
105
The front-panel Fault LED is lit if the engineering panel is receiving 5Vdc power and: • it is unable to communicate with the main CPU, in which case the status screen will display “No Comms with Main CPU” and all other LEDs and readouts will be blank/off; or • the CPU is unable to communicate with the Auxiliary PCB, in which case the other LEDs, control loop readouts, and status screen will continue to operate.
CPU/IO Fault Relay
CR1 is hard-wired as a normally-energized fault relay, and CR2 can be set to only de-energize when CR1 does (see CPU/IO Control Relay Switches on page 48). It/they will de-energize if the 3.3 Vdc power falls below its fault threshold or the control program does not periodically reset the watchdog timer. In either case, the main CPU is also reset (see page 77): • If the CPU is able to restart, it will reset the watchdog timer and re-energize the fault relays. The speaker will beep and the engineering panel will display “Reset”. • Some problems allow the CPU to restart but eventually prevent it from resetting the watchdog timer. The fault relay(s) will then toggle off and back on and the controller will beep repeatedly. Although there is a slight chance that powering the controller down and back up would correct this condition, it is almost always indicative of a failed power converter or other component on the CPU/IO PCB. This relay will also de-energize if the trigger condition for its relay assigned function is detected (see Relay Functions on page 108), in which case the CPU is not reset.
Speed Board Fault Relay
The auxiliary PCB’s fault relay is controlled by its watchdog timer: • If that timer is not regularly reset by that board’s CPU, it will de-energize CR9 and reset that CPU. CR9 will not re-energize unless that restart succeeds. • CR9 will also de-energize if the 15 Vdc power converter on the CPU/IO PCB fails. In either case, the main CPU will be unable to communicate with its counterpart on the speed board. A Speed Controller will then light its Fault LED and initiate an emergency shutdown of the turbine, while an Extraction Controller will only indicate an “Aux. Board” alarm.
August 2007
UM3300/H (1.1.0)
106
Chapter 6: Maintenance and Repair
Alarm System Alarm Relays Alarm Discrete and OPC Variable Alarm LED Alarms Menu ACK Button
The meaning of the front-panel Alarms LED, Modbus and OPC Alarm variables, and any relays given the Alarm function depends on the type of controller: • Compressor controllers light their Alarm LEDs, energize any Alarm relays, and set their Modbus/OPC Alarm variables when there are uncorrected controller hardware problems. They do not automatically display the Alarms menu when new problems are detected, and provide no way to acknowledge uncorrected alarms (the ACK button is not used). All current alarm conditions are indicated via the third and fourth lines of a single Alarms screen that you should manually display (by repeatedly pressing the MENU button) whenever the Alarm indicators are set:
Mode RUN Alarms Tran OutF Com1&2 24V • “Tran” indicates one or more analog inputs are beyond their testing ranges (see Analog Input Problems on page 118). • “OutF” indicates the loopback reading for an analog output that is being used to drive a control element differs from its intended value by more than five percent (see Analog Output Problems on page 118). • “Comm1”, “Comm2”, or “Com1&2” indicates expected transmissions are not being received from companion controllers via the corresponding serial ports (see Communication Problems on page 115). • “24V”, “15V”, “5V”, or “3V” means the corresponding CPU/IO PCB voltage is unacceptably low (see Power Problems on page 113). The Alarm LED remains lit and Alarm relays remain energized until all such problems have been corrected.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
107
• Turbine controllers light or flash their Alarm LEDs whenever there are unacknowledged and/or uncorrected alarm conditions, but they energize relays assigned the Alarm function and set the Modbus/OPC Alarm variables only if there are unacknowledged problems (corrected or not). Each screen of their Alarms menus list one of up to eight such conditions:
Alarms Com1 Error
The Alarm LED will flash if the currently-displayed alarm has not been acknowledged, which can be done either by pressing the ACK button or asserting a Reset discrete input. If a new problem is detected, the Alarm menu screen displays automatically (thus causing the LED to flash). Acknowledging that alarm or scrolling to a previously-acknowledged one would cause the LED to stop flashing, but it would remain lit as long as any alarms were uncorrected and would resume flashing if you scrolled to one that had not been acknowledged. Those indicators are used to signal both process and controller problems (only the latter will be covered here): • “Aux. Board” means the main CPU cannot communicate with the auxiliary PCB (see Speed Board Problems on page 121). • “Com1 Error” or “Com2 Error” indicates the corresponding serial port is not receiving expected companion controller data (see Communication Problems on page 115). • “FD24V Fail” indicates a field device power supply failure (see Power Problems on page 113). • “MPU# Fail” indicates a failure of the corresponding (#) speed input (see Speed Input Problems on page 121). • “OutputFail” indicates the high-current output loopback reading differs from its intended value by more than five percent (see Analog Output Problems on page 118). • “Pwr Supply” indicates an internal power supply problem (see Power Problems on page 113). • “PosFeedbck” indicates an unacceptable deviation of a hydraulic control element’s actuator positioning pressure (see Positioning Problems on page 122). • “RS24V Fail” indicates a redundant control selector power supply failure (see RCS Power Failure on page 97). • “Tran# Fail” indicates the corresponding (#) analog input is beyond its transmitter testing range (see Analog Input Problems on page 118). August 2007
UM3300/H (1.1.0)
108
Chapter 6: Maintenance and Repair
External Alarms
In addition to its front-panel Alarms menu, each controller also provides relay functions and Modbus variables that indicate individual or collective hardware problems.
General Failure
All Series 3++ Controllers provide a general failure relay function and Modbus/OPC variables that can be triggered by any of several conditions that would warrant switching to a backup controller: All Controllers: output loopback or internal voltage failure Speed Controllers: valve positioning failure, or the failure of all speed inputs Extraction Controllers: auxiliary PCB failure Each of these problems is also indicated by other relays and variables. Redundant controller fault relays are often assigned this Fail function (see Fault Relay Connections on page 95 and Tracking Indicators on page 110).
Relay Functions
Each controller’s relay outputs can operate external indicators (lights, horns, etc.) for or communicate various problems to a DCS.
FD24
This turbine controller function indicates a transmitter power test failure (see Power Problems on page 113).
OutF
The turbine controller OutF function indicates either an excessive readback deviation of the high-current analog output (see Analog Output Problems on page 118) or an excessive deviation of the position feedback signal (see Positioning Problems on page 122). Compressor Controllers have separate OutF and PosF functions for indicating those problems.
PosF
PSF
This turbine controller function indicates a low CPU/IO PCB voltage. For compressor controllers, such problems are indicated by a Fail not accompanied by an OutF (see Power Problems on page 113).
RS24
This turbine controller function indicates a redundant control selector power problem (see RCS Power Failure on page 97).
SerC
This function indicates the controller has failed to detect an expected transmission on its Port 1 or 2 communication network (see Communication Problems on page 115).
Tran
The Tran function indicates at least one analog input signal is not within its valid range (see Analog Input Problems on page 118). All relays will de-energize if the 5 Vdc power to their coils fails.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
109
Modbus/OPC Variables
A TrainTools or other operator workstation can indicate the following problems when the corresponding Modbus/OPC variables are set.
Aux. Board Fail
This turbine controller discrete indicates the main CPU is unable to communicate with its counterpart on the Auxiliary PCB (see Speed Board Problems on page 121).
FD 24V Fail
This turbine controller discrete indicates a transmitter power test failure (see Power Problems on page 113).
Low Voltage
This discrete indicates a low CPU/IO PCB voltage (see Power Problems on page 113).
MPU # Fail
Each of these Speed Controller discretes indicates the corresponding MPU has failed (see Speed Input Problems on page 121).
Output Fail
This discrete indicates an excessive readback deviation for the analog output used to manipulate the control element (see Analog Output Problems on page 118).
Port # Fail
Each of these discretes indicates the controller has failed to detect an expected transmission on the corresponding serial communication network (see Communication Problems on page 115).
Position Fail
This turbine controller discrete indicates an excessive deviation of the position feedback signal (see Positioning Problems on page 122). Compressor Controllers test that signal only if a relay has been assigned the PosF function, in which case this problem would be indicated by the corresponding CR State discrete.
RS 24V Fail
This turbine controller discrete indicates a redundant control selector power problem (see RCS Power Failure on page 97).
TranFail TranFail#
August 2007
The Tran discrete indicates one or more analog input signals are out of their valid ranges, in which case the corresponding TranFail # discretes would also be set (see Analog Input Problems on page 118).
UM3300/H (1.1.0)
110
Chapter 6: Maintenance and Repair
Engineering Panel
Each time an engineering panel key is pressed, the controller will beep and (unless you pressed the CLEAR key) the engineering readout will display a message. If not, see the section on Front and Test Panel Problems on page 114. The controller will also beep if any key is “stuck”, the CPU reboots or a low-level serial communication error is detected. The engineering panel readout will then display one of the following: Com# POF: indicates a low-level (Parity, Overrun, or Framing) error was detected by the serial port identified by the fourth character (see Communication Problems on page 115). CS= XXXX: indicates an unreasonable parameter value has been detected and changed. If this message is accompanied by repeated beeping, the parameter memory is probably defective (see CPU/IO Board Problems on page 117). Error! indicates an invalid engineering key sequence. If accompanied by repeated beeping, the cause is usually a failed keypad (see Front and Test Panel Problems on page 114). Reset: indicates a CPU Reset (see page 77). This might indicate a power cord or connector problem (see Power Problems on page 113). However, it usually means an internal hardware or software problem is aborting the controller reset sequence (see CPU/IO Board Problems on page 117). Although occasional errors will not affect control of your compressor or turbine, frequent or repeated beeping should be investigated.
Tracking Indicators Tracking LED Redundant Control Selector LEDs
When a redundant pair of controllers is installed, the front-panel Tracking LED of the active peer will be off, that of the inactive peer will be continuously lit. The active controller’s Modbus/OPC Tracking discretes will also be cleared, those of its peer will be set. In addition, the operator panel of our Redundant Control Selector (see page 94) will indicate which controller’s outputs are connected to your field elements: • When the main controller is active, the Main LED is green and the Backup LED is red. • When the backup controller is active, the Main LED is red and the Backup LED is green. Thus, any problem that triggers an automatic switch to the backup controller will be indicated by the lighting of the main controller’s Tracking LED and the RCS Main LED turning red. To diagnose such a switchover, you need to know which controller relays trigger them and the functions assigned to them (see Fault Indicators on page 104 and Relay Functions on page 108).
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Shutdown Log
111
Speed Controller problems that trigger emergency shutdowns of the turbine are recorded and can be viewed by repeatedly pressing the Menu key until the status screen’s shutdown log menu appears.
SD Log 14:12:39 12/25/06
then
SD Log 1 WatchDogSD 13:52:11 12/25/06
Pressing SCROLL once displays the cause of the most recent turbine shutdown and the time and date at which it occurred: • Overspd SD indicates the turbine was shut down because it exceeded a configured trip speed. • MPULoss SD indicates the turbine was shut down because all of its speed inputs failed (see Speed Input Problems on page 121). • Breaker SD indicates a turbine-driven generator was shut down when the generator breaker unexpectedly opened. • DGI SD ## indicates the shutdown was initiated by Stop or ESD input number ##. • OperatorSD indicates the shutdown was initiated from the front panel or via computer communications. • FailsafeSD indicates a start-up aborted when the turbine failed to reach a configured minimum speed quickly enough. • WatchdogSD indicates a power loss or controller failure caused a hard reset of the CPU, thus tripping the turbine (see CPU/IO Board Problems on page 117). • Shutdown indicates the auxiliary PCB failed (see Speed Board Problems on page 121) or that this controller took control after a shutdown and cannot determine its cause. Each subsequent press of the SCROLL key displays the same information for the next older of the last eight shutdowns:
SD Log 8 OperatorSD 19:43:52 01/02/05 If the controller has shut down the turbine fewer than eight times, the second line of the as-yet-unused log screens will display a line of dashes. You can also determine the reasons for the most recent shutdown by reading the Modbus Last ESD register, or the last three by reading the corresponding OPC Last ESD# OPC variables.
August 2007
UM3300/H (1.1.0)
112
Chapter 6: Maintenance and Repair
Troubleshooting
This section suggests appropriate responses to various hardware problems (whose indicators were discussed in the previous section): • • • • • • • • • • •
Power Problems (see page 113) Front and Test Panel Problems (see page 114) Communication Problems (see page 115) CPU/IO Board Problems (see page 117) Analog Input Problems (see page 118) Analog Output Problems (see page 118) Discrete Input Problems (see page 119) Discrete Output Problems (see page 120) Speed Board Problems (see page 121) Speed Input Problems (see page 121) Positioning Problems (see page 122)
Unless the problem is clearly external to the controller, you should replace it or its internal circuit boards and/or front-panel (see Replacement Procedures on page 123) to return it to service as quickly as possible. You can then return all replaced hardware to CCC for repair, or isolate and return only the failed components. If you have removed a controller from service, it is usually easiest to replace suspect components one at a time until the malfunctioning one becomes obvious. Additional information or assistance can be obtained by contacting the Technical Service Department at Compressor Controls.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Power Problems
113
If the controller appears to be “dead” (all display elements are off, all control relays are de-energized, all analog outputs are 0.0, and all serial communication has ceased), check the voltage across the field power output. If it is not zero, either: • one of the CPU/IO board’s power converters has failed, or • the power supply is not providing 24 Vdc power to that board. Either replace both assemblies, or replace one at a time so you can identify and replace only the one that actually failed. You should also check the field power voltage if the standard analog outputs fail but the controller otherwise seems to be okay (a turbine controller might also indicate a “FD24V Fail” alarm and energize any FD24 control relays). If it is not zero, the power supply assembly is not providing 24 Vdc field power and must be replaced. In addition, you should replace the power supply if the controller indicates the 24 Vdc to the CPU/IO board is failing, or the CPU/IO board if any of its power converters is failing (see Internal Conditions on page 100 and Alarm System on page 106). If the controller appears to be dead and there is no voltage across the field power terminals, disconnect the power cord from the back panel and test the voltage (see Table 6-1) across the pins for the installed power supply (see Figure 3-24). If that cable is “live”, either the power supply assembly or the back panel has failed and must be replaced. If the cable is not live, figure out why not. If the engineering panel intermittently beeps and displays a “Reset” message, one of the power cord connections might be loose or worn (or the controller reset sequence is being aborted by a hardwired or software problem, see CPU Reset on page 77 and CPU/IO Board Problems on page 117). You can check the power-cord and backpanel connectors by connecting a different cord to the problematic controller and/or the same cord to a different controller. Depending on the result, replace the back panel or power cord.
August 2007
UM3300/H (1.1.0)
114
Chapter 6: Maintenance and Repair
Front and Test Panel Problems
Front and engineering panel problems will not prevent a controller from continuing to control and protect your process equipment. So, if you suspect such a problem but are able to monitor and operate the controller from a computer workstation or remote operator panel, you might decide to delay correcting it. If you suspect an LED or readout is not working, or want to verify that all of them are, hold down the TEST key and press the SCROLL button three times (see User Preferences and LED Tests on page 90). Doing so will display “LED Test” on the top row of the status screen and light every readout and indicator LED on both the front and engineering panels. If any LED or readout segment does not light, replace the corresponding (front or engineering) panel. If you suspect a front panel key or button is not working, invoke the engineering panel Signal Values Test [MODE TEST 4], press the minus (–) key, and then press the key you want to test to verify that its code is being sent (see page 147). If not, replace the front panel.
Caution:
Pressing a key to verify it is working might affect the operation of the controller. If possible, you should first switch to an alternate method of controlling your process. If an engineering panel key is stuck on, the controller will usually beep at 0.4 second intervals and display “Error!” on the engineering panel readout. However, if the CLEAR key is stuck, the beeping will be accompanied by a blank readout. If the PID, MODE, COND, or SPEC RESP key is stuck, pressing the CLEAR key will neither elicit a beep nor clear the corresponding confirming message. If you suspect an engineering panel key is not working, press it. The controller should beep and display the corresponding message. If any engineering panel key is faulty, replace that panel. If all front panel display elements are unlit/blank but the fault relay is not de-energized or you otherwise know the controller is running: 1. Open the front panel and determine whether the engineering panel is working (pressing any key should elicit a beep). If not, replace it and reinstall the front panel. If the new engineering panel does not work, the CPU/IO circuit that powers the engineering panel is probably bad. That would necessitate replacement of the CPU/IO PCB assembly. 2. Make sure the ribbon cable between the front and engineering panels is connected and undamaged. If not, reseat or replace it. 3. Replace the front panel assembly if it is still unlit.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Communication Problems
115
If the controller beeps and the engineering panel shows a message of the following form:
Com4 POF the port indicated by the number in the fourth field (1 through 4) is detecting serial data it is unable to decode. The P, O, and/or F will appear only when the corresponding type of error occurs: • The P will appear if a parity error was detected. This indicates that the number of set bits (ones) in a received character did not agree with the defined parity for the serial port it arrived on. Continuous parity errors usually indicate that the parity settings of the transmitting and receiving devices are different. • The O will appear if an overrun error occurred. This means that the controller failed to read an incoming character before the next one arrived. • The F will appear if a framing error was detected. This indicates the controller was unable to decode an incoming character due to a synchronization error. Continuous framing errors usually indicate the baud rates of the host and slave disagree. If such errors are occurring continuously, make sure all devices on the problem network are set for the same baud rate and parity and have unique Controller (Port 1) and Computer (Ports 2, 3 and 4) ID numbers. Downloading a different control program (for example, changing a Performance into an Antisurge Controller) will frequently produce misconfigurations that trigger continuous reception errors. For Port 3 or 4, make sure only one Modbus master is connected and is configured to use one start, one stop, and eight data bits. Some Modbus hosts, particularly older PLCs, might experience frequent synchronization errors at high baud rates. Such problems can thus be solved by reducing that setting in both the host and the controllers. Because the communication protocols employed by the controller reject faulty messages (and often provide for their re-transmission), isolated reception errors rarely affect the operation of the controller. Frequent but not continuous errors can indicate poor connections or electromagnetic interference.
August 2007
UM3300/H (1.1.0)
116
Chapter 6: Maintenance and Repair If a controller fails to receive expected information from another via Port 1 or Port 2, it will set its Port 1 or Port 2 Fail Modbus discrete input and OPC variable, display “Comm1”, “Comm2”, or “Com1&2” in the lower left corner of its alarms screen while energizing any SerC relays (compressor controllers), or indicate a “Com1 Error” and/or “Com2 Error” alarm (turbine controllers). Such indications can result from: • the failure of a controller to transmit information expected by its companions, due to misconfiguration, failure of its serial port circuit, or a more general fault; • the failure of the receiving controller’s serial port circuit; or • line breaks, noise, or other network problems. In general, a transmission or line problem will cause several controllers to indicate such problems, while reception failures are indicated only by the problem controller. Several controller features can prove useful when troubleshooting such problems: • Any controller’s Port 1 Test [MODE COMM – 3] will identify the companion controllers it is receiving data from via Port 1. • The Port 2 Slave Test [MODE COMM – 2] of any load-sharing Performance, Antisurge, Dual-Loop A/P, or Extraction Controller will indicate whether it is detecting any communication on the Port 2 load-sharing network. • A Station Performance Controller’s Port 2 Master Test [MODE COMM – 1] will identify the load-sharing slaves that it is communicating with. • The Serial Port Activity Test [MODE TEST 3] elicits a dynamic display that reveals whether a specified serial port is transmitting or receiving data (Port 3 in this example): 3 MODE
TEST
2
PT2 R-T_
The R will be followed by a hyphen if the port is receiving a transmission, otherwise an underscore. Similarly, the T will be followed by a hyphen only when that port is transmitting. In the above example, Port 2 is receiving but not transmitting: A lack of communication activity on ports that are connected to active networks usually indicates a serial port failure. Such failures (which are rare) usually result from extreme voltage surges or the failure of the 24-to-5 volt power converter. Either problem requires replacement of the CPU/IO PCB.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
CPU/IO Board Problems
117
Any of the following symptoms can indicate that the CPU/IO PCB should be replaced: • a de-energized main fault relay (CR1), unless: • the controller is powered down, • cycling the controller off and back on re-energizes CR1, or • the digital I/O status screen shows an underscore in the first relay position, thus indicating it was de-energized by that assigned condition, which does not indicate a CPU/IO PCB failure (see External Alarms on page 108):
Mode RUN Digitals In:_2___6_ Out:_2__5
or
In/Out DigitalOut Î:_23__67_
• a lit Fault LED or non-functional engineering and front panels that remain so even after those panels have been replaced; • periodic beeping accompanied by a “Reset” engineering panel message (see CPU/IO Fault Relay on page 105), provided the power cord is securely connected at both ends and its backpanel connector is not loose or otherwise failing; • repeated beeping accompanied by a “CS=” message on the engineering panel readout (this usually indicates the parameter memory is defective); • any unacceptable power converter voltage (15, 5.0, 3.3, or 1.2), provided the 24 Vdc is good, or an excessive or unusually high difference between the internal and ambient temperatures (see Internal Conditions on page 100); • failure of the standard analog output circuits, provided external causes have been ruled out and the transmitter power supply has not failed; • failure of any analog input or discrete I/O circuit, provided external causes have been ruled out
Note:
August 2007
I/O circuit failures are often caused by voltage transients that can also damage power supply PCB circuit traces (especially those for analog inputs, which provide their over-voltage protection).
UM3300/H (1.1.0)
118
Chapter 6: Maintenance and Repair
Analog Input Problems
Transmitter fail alarms indicate that at least one analog input is below its configured low (or above its specified high) alarm limit, as discussed under Analog Inputs on page 75. They, or any obvious analog input failures, usually indicate: • externally open or shorted circuits • blown fuses (such as those on a turbine controller field input module, see FIM Analog Input Circuits on page 59) • induced currents • failed or miscalibrated transmitters • damaged analog input circuit components • failure of the CPU/IO PCB’s 24-to-15 volt power converter • misconfigured circuits (see Analog Input Switches on page 49) The problematic input(s) can be identified using the status screen’s Analog In Menu (see page 103), provided their measured variable displays are enabled (see page 75). If you suspect the problems are internal, the simplest thing to do is replace the CPU/IO PCB and power supply assemblies (damage to the CPU/IO PCB analog input circuitry is often caused by extreme voltage surges that would also damage the protective circuits on the power supply PCB). To determine if such a problem is internal, connect a test signal in place of the transmitter and use the Signal Values Test [MODE TEST 4] to compare the supplied signal and resulting reading. Keep in mind that an input value reported by that procedure is in percent of span (rather than range), as specified by its Offset Zero Input [MODE:D ANIN #] setting. If that parameter is enabled, the TEST 4 value is determined using a 20 percent offset zero (00.0 for 4 mA or less, 50.0 for 12 mA, A0.0 for 20 mA or higher). If the controller is reading an input correctly but seemingly ignoring it, check to make sure none of its Input Lockout (MODE LOCK 6) parameters have been enabled.
Analog Output Problems
An output loopback deviation or alarm indicates that the controller is unable to maintain the intended voltage or current in a final control element’s analog output circuit. This can be caused by: • field element problems • poor connections or open circuits • blown fuses (such as those on a turbine controller field output module, see FOM Analog Outputs on page 62) • CPU/IO or auxiliary PCB component failures • excessive loads on or failure of the transmitter power circuit (which also powers the CPU/IO PCB analog outputs) • miscalibration of the high-current output or its loopback circuit
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
119
You can determine the magnitude of the problem by using the status screen to view the intended and measured output values (see Compressor Controller I/O Signals on page 101 or Turbine Controller I/O Signals on page 102). Unless the deviation indicates an open circuit or is too large for the control loop to adjust to, such problems rarely require immediate correction. To determine if the cause is internal or external: • transfer control to another device—if it is unable to maintain the intended current or voltage, the problem is probably external to the controller; or • connect a test load in place of the field element and disconnect the transmitter power output—if the controller is still unable to maintain the intended current or voltage, the problem is most likely internal. An internal high-current output problem should be addressed by first trying to recalibrate it. If that fails, replace the auxiliary PCB. Internal standard output problems should be addressed by replacing the power supply and CPU/IO PCB assembly. To isolate the problem further, connect a test load and then replace those components one at a time.
Discrete Input Problems
If you suspect a discrete input circuit is malfunctioning, you can determine whether the input signal is being properly read by comparing its displayed state (see Field I/O Screens on page 101) to the voltage between its back-panel or FIM terminals (see page 53 or page 58). The signal should be greater than 10 Vdc if the input is asserted, or less than 2 Vdc if it is cleared. You should also compare that voltage to the state of the connected signal source to determine whether it is malfunctioning or if there might be a line break or blown fuse—especially for FIM Discrete Input Circuits (see page 58). If you use solid-state relays to control such inputs, keep in mind that they can be problematic. Ground-loop problems can also alter the effective voltages in such inputs. If the controller is reading an input correctly but seemingly ignoring it, check to make sure none of its Input Lockout (MODE LOCK 6) parameters have been enabled.
August 2007
UM3300/H (1.1.0)
120
Chapter 6: Maintenance and Repair
Discrete Output Problems
If you suspect a discrete output/control relay malfunction, you can temporarily alternate the assigned function between On and Off to determine if the connected device responds accordingly. If it does not, check any fuse included in the suspect circuit (such as those on a turbine controller field output module, see FOM Control Relay Circuits on page 63) To directly test a relay’s operation, compare its intended coil state (energized or de-energized, see page 101) to the resistance across its back-panel or FOM terminals (see page 53 or page 63): Step 1: Note the position of its NO/NC switch (see page 48). Step 2: For basic I/O controllers, disconnect the field devices from the CR# circuits by unplugging their terminal blocks from the back panel. For FTA-equipped controllers, it is easiest to connect a spare FOM or FIOM. Alternately, you could disconnect the field wiring from the FTA or temporarily replace the top half of the connectors (which are secured with screws). Step 3: For compressor controllers, set MODE:D RA 1 to OFF and RA 2 through 5 to ON (be sure to note their original settings). This should energize all five relays. For turbine controllers, set MODE:D RA 1 (and RA 9, if present) to +OFF and all other RA parameters to +ON. Step 4: The resistance measured across each relay’s field terminals should be nearly zero for each normally-open relay and nearly infinite for each normally-closed relay. Step 5: For compressor controllers, set MODE:D RA 1 to ON and RA 2 through 5 to OFF. This should de-energize all five relays. For turbine controllers, set MODE:D RA 1 (and RA 9, if present) to +ON and all other RA parameters to +OFF. Step 6: The resistance measured across each relay’s field terminals should be nearly zero for each normally-closed relay and nearly infinite for each normally-open relay. Step 7: Restore the original values of any MODE:D RA parameters you changed in step 3 or 5. Step 8: Restore the original field wiring connections. If the resistance measured across a given relay was the same in both step 4 and step 6, that relay is probably not energizing or deenergizing, or else its contacts are not opening or closing properly. In either case, the CPU/IO PCB will need to be replaced.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Speed Board Problems
121
Unless the CPU/IO PCB’s 24-to-15 volt power converter has failed, any of the following symptoms generally indicates that the auxiliary PCB assembly (speed board) should be replaced: • the speed board fault relay (CR9) de-energizes • the Fault LED lights while other LEDs and readouts are lit • an excessive deviation of the high-current analog output loopback test, provided external causes have been ruled out (see Analog Output Problems on page 118) • an “Aux. Board” alarm If a Speed Controller exhibits any of those symptoms, that assembly must be immediately replaced. If an Extraction Controller does, the immediacy of the problem depends on which auxiliary I/O circuits are in use and how important they are to control of the turbine.
Speed Input Problems
MPU failure alarms are usually caused by the loss of a frequency signal due to misaligned magnetic pickups, broken leads, or high temperatures. When operating with only one healthy MPU, its failure would trigger an MPULoss shutdown. However, such a shutdown could also occur if: • passive MPU’s are used and the speed falls below the minimum needed to generate a measurable signal; or • the pickups are not properly matched to the gear that excites them and the speed exceeds the maximum above which their signals cannot decay between the passage of adjacent teeth. In either case, all of the MPUs would appear to have failed. As an aid to troubleshooting, these controllers provide two ways to display the value of each speed input: • The signal to each input can be displayed (in rpm) by the status screen’s In/Out menu. • The engineering panel’s Signal Values Test [MODE TEST 4] will display each such signal as a percentage of the Maximum Control Speed [COND:S DISPLAY HIGH]. Either value will be accurate only if the input has been properly configured. If the inputs appear to be miscalibrated, check the configuration parameters to make sure you have correctly entered the number of teeth on the exciter gear and the speed ratio between the gear and turbine shafts.
August 2007
UM3300/H (1.1.0)
122
Chapter 6: Maintenance and Repair
Positioning Problems
An Antisurge, Performance, or Speed Controller can be configured to indicate a final control element positioning problem if it detects an excessive deviation between its intended control element position and a predefined or configured analog input signal (which might be an actual position measurement or a hydraulic / pneumatic actuator control pressure). Unless that problem is caused by a concurrent output failure, the problem is external to the controller. Check for wiring problems, or miscalibration or failure of the control element or an intermediate I/H or I/P converter.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Replacement Procedures
123
Series 3++ Controllers contain no user-serviceable parts. Suspect units or components should be replaced with identical spares and returned to CCC for diagnosis and repair. You can: • replace one or more internal components, without dismounting the case and back panel (see Component Replacement); or • replace the entire controller with a new one having the same hardware configuration, without disturbing the field wiring (see Controller Replacement). Either way, you might need to change the front panel (see Front Panel Replacement on page 125) or update, change, or reconfigure the installed application software (see Programming and Configuration on page 126).
Spare Parts
If your chosen maintenance strategy is to replace malfunctioning units, at least one controller with identical components should be stocked for every five in use, along with a selection of front panels. On the other hand, if you choose to do board-level troubleshooting and replacement, you should stock spare assemblies at the same one-to-five level. One or more complete, spare controllers should also be stocked for use while troubleshooting suspect units.
Warning!
To prevent damage from static-electric discharges, all spare circuit boards should be stored and transported in static-resistant pouches. The Series 3++ Controller Parts List [DS3300/P] lists the assemblies you might wish to stock. Your spare parts inventory should be based on the total number of controllers using each assembly.
Return Procedure
To return any item for repair, call CCC at 515-270-0857 and ask to talk to the Return Goods Coordinator. You will be asked to identify your controller model (for example, a Series 3++ Performance Controller), provide its serial number, and describe the problem you are experiencing. He or she will then schedule your repair and assign a return material authorization (RMA) number. Package the items carefully (appropriate packing materials can be sent to you if needed) and ship them prepaid and insured to: Compressor Controls Corporation ATTN: Service Department 4725 121st Street Des Moines, IA 50323 U.S.A. The RMA number should be clearly displayed on all cartons and noted in all correspondence. The equipment will usually be repaired and shipped back within five days of its arrival at the factory.
August 2007
UM3300/H (1.1.0)
124
Chapter 6: Maintenance and Repair
Component Replacement
Most controller malfunctions can be fixed by replacing some or all of the internal components from the front of the case:
Warning!
Disconnect the power cable before disassembling a controller.
Caution:
Never disassemble a controller or handle its components without taking steps to prevent static discharge. Step 1: Transfer control of your process to the malfunctioning controller’s online backup or other alternate device. Step 2: Disconnect the power cable from the rear of the controller. Step 3: Loosen the screw at the bottom of the front panel, pull its left side forward about an inch, then swing it out and to the left. Step 4: Separate the engineering panel assembly by removing the four galvanized screws at its corners and pulling it forward to disengage it from the CPU/IO PCB and case. Step 5: Pull the internal components from the case. Step 6: Decide which components to replace, obtain them from your company stores, and verify their switch and jumper settings (see page 48, page 49, and page 51). Step 7: To separate the auxiliary PCB, remove the four screws that attach it to the standoffs on the CPU/IO PCB, then disengage the pins on its rear side from their CPU/IO PCB connector. Step 8: To replace only the CPU/IO PCB or power supply, remove the two clips from the connector joining them, replace the defective assembly, and re-install the clips. Step 9: To reinstall or replace the auxiliary PCB, align the pins on its rear side with the corresponding connectors on the CPU/IO PCB, then press them together. Reinstall the screws. Step 10: Slide the internal components into the case (the CPU/IO PCB and PSA fit into the left-most set of grooves). Press fairly hard until you feel the PSA “pop” back into its connector. Step 11: Align the tabs on the sides of the engineering panel’s mounting brackets with the grooves in the case, then slide it back into the connector on the front of the CPU/IO PCB. Secure this assembly by reinstalling the four screws at its corners. Step 12: Reinstall or replace the front panel with one having the same overlay as the original (see page 125). Step 13: Reconnect the power cable to the back panel. Step 14: Verify or reload the control program, then reload its configuration parameters (see page 126). Step 15: Transfer control of the process to the reassembled unit.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
Controller Replacement
125
If you suspect the inside of the back panel or case are corroded or contaminated with foreign materials, use the following procedure to replace the entire controller rather than just its internal components: Step 1: Transfer control of your process to the controller’s online backup or other alternate device. Step 2: Unplug the power cable from the controller’s back panel. Unplug the field wiring terminal strips or FTA cables (rather than disconnecting individual wires). Step 3: Loosen and remove the slide clamps from the case, remove the slides and pull the controller forward from the panel cutout. Step 4: Obtain a spare unit having the same hardware configuration from your company stores. Step 5: Verify that all of the replacement unit’s internal switches and jumpers are set the same as in the controller being replaced (see Internal Settings on page 47). Step 6: Remove the slide clamps from the replacement controller, then slide it into the panel cutout. Reinstall its slides and slide clamps and tighten the pressure screws. Step 7: If needed, replace the front panel with that of the original controller or a new one having the same overlay (see below) Step 8: Reconnect the FTA data cables or back-panel terminal strips and power cable. Step 9: Verify or reload the control program and configuration parameters (see Programming and Configuration on page 126). Step 10: Transfer control of your process to the new controller.
Front Panel Replacement
To replace a front panel that has failed or no longer matches a newly-installed control program: Step 1: Loosen the screw at the bottom of the front panel, pull its left side forward about an inch, then swing it out and to the left. Step 2: Unplug the cable connecting the front panel to the engineering panel. Step 3: Squeeze the top and bottom of the wire hinge together until you can pull it away from the engineering panel. Step 4: Insert either end of the new panel’s wire hinge into its hole in the engineering panel’s mounting bracket, then squeeze the top and bottom of the hinge together until you can insert the other tang into its hole. Step 5: Plug the ribbon cable from the engineering panel into the connector on the back of the front panel. Step 6: Close the front panel after completing any needed configuration or other engineering procedures.
August 2007
UM3300/H (1.1.0)
126
Chapter 6: Maintenance and Repair
Programming and Configuration
Whenever you replace a controller or its CPU/IO PCB, you must make sure the control program and configuration parameters of the new CPU match those of the original: Step 1: Retrieve the needed program information and serial communication settings from your records (see Overview on page 99). Step 2: Enter the Enable Reconfiguration [MODE LOCK 5 1] key sequence from the engineering panel, then assign the original values to the following parameters: • Computer ID Number [MODE:D COMM 0 •] • Port 3 Baud Rate [MODE:D COMM 3] • Port 4 Baud Rate [MODE:D COMM 4]. Step 3: Connect a PC running the Configurator program. Step 4: Use the Program Version [MODE TEST 2] test to determine if the replacement is running the desired control program. If not, reload it (see Reloading the Control Program on page 71).
Note:
Port 4 must be set for 19,200 baud and odd parity in order to replace the machine control program. Step 5: Download a saved copy of the original parameter set and verify the resulting parameter checksum. Step 6: Disconnect the Configurator program. Step 7: Use the Set Clock [MODE TEST 9] key sequence to set the internal date and time (Speed Controllers only).
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
127
Series 3++ Hardware Referencemanual
UM3300/H
Appendix A Configuration Parameters This appendix describes each configuration or tuning parameter discussed in the body of this manual, including: • its functional name and a description of that function, • the range of values it can be given, • the sequence of keys you must press to view or change it from the engineering panel (often used as an alternate name), • its confirming display prompt, • any restrictions on the order in which it must be entered, and • cross-references to the sections of this manual in which the parameter is discussed. Keyboard Entry
As discussed in Chapter 2, pressing the indicated keys will produce the listed confirming display, which consists of a prompt followed by the current value. For array parameters, that prompt will include a “#” representing the digit corresponding to the array element. Values that are selected from a list by pressing the decimal key are shown as “Value” or “Valu”. OFF/ON or OFF/HIGH/LOW choices are shown as such and are selected by pressing the corresponding key (0, 1, HIGH, or LOW). Values that are entered by pressing one or more numeric keys are shown as a series of “#” symbols representing digits, possibly including an automatically-placed decimal point. The space before a negative value is replaced by a “–”. A hexadecimal ten leading digit is entered by pressing HIGH and displays as “A” (100.0 is entered as HIGH 0 0 and displays as A0.0).
August 2007
UM3300/H (1.1.0)
128
Appendix A: Configuration Parameters
COND:A f(X) 2 # and X 2 #
These parameters characterize an Antisurge Controller’s reported flow measurement in multisection compressor applications.
Reported Flow Characterizer
Range: 0.00 to 9.99 percent [X] 0.00 to 9.99 percent [f(X)] Display: X2# #.## [X] Y2# #.## [f(X)] Reference: Numeric Parameters . . . . . . . . . . . . . . . . . . . 41
COND:D BIAS 1 Output Scaling Bias
For controllers equipped with an auxiliary PCB, this parameter sets the bias used to scale and calibrate the high-current output signal. Range: .0000 to .9999 Display: B1 .#### Reference: Output Circuit Calibration . . . . . . . . . . . . . . . . 85
Note: COND:D BIAS 2 Loopback Scaling Bias
BIAS 1 and 2 can only be changed via the Engineering Panel. For controllers equipped with an auxiliary PCB, this parameter sets the bias used to scale and calibrate the high-current output’s loopback input signal. Range: –.9999 to .9999 Display: B2 .#### Reference: Loopback Circuit Calibration . . . . . . . . . . . . . 87 MODE TEST 4 . . . . . . . . . . . . . . . . . . . . . . . 146
COND:D CONST 2 Output Failure Delay
This parameter defines the number of seconds the output or position feedback test deviation can be above its threshold before the corresponding alarm is signaled. Range: 0.00 to 9.96 seconds (multiples of .04) Display: CO2 #.## Reference: Output Loopback Test . . . . . . . . . . . . . . . . . . 88
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
COND:D DISPLAY 0# Measured Variable Display
COND:D DISPLAY 0#– Measured Variable Name and Units
COND:D DISPLAY 0 # HIGH Measured Variable Maximum
COND:D DISPLAY 0 # LOW Measured Variable Minimum
COND:D DISPLAY 0#• Measured Variable Decimal
August 2007
129
Each of these parameters determines whether or not the corresponding measured variable can be viewed via the status screen’s Analog In menu. Range:
Off variable cannot be displayed On variable can be displayed Display: D0# OFF/ON Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 Each of these parameters defines the name and engineering units shown when the corresponding measured variable is viewed. Range: up to eight name and five units symbols Display: AAAAAAAA, then EU:AAAAA selected symbol (A) flashes press • to select, then ENTER for each Reference: Label Parameters . . . . . . . . . . . . . . . . . . . . . . 39 Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 Each of these parameters defines the value the Analog In menu would display for the corresponding measured variable if the value of its signal variable was 100.0 percent. Range: –9999 to 9999 Display: 0#H #### Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 Each of these parameters defines the value the Analog In menu would display for the corresponding measured variable if the value of its signal variable was zero. Range: –9999 to 9999 Display: 0#L #### Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 Each of these parameters defines the position of the decimal point in the corresponding measured variable display. Range:
0 #### (no decimal) 1 ###. (trailing decimal) 2 ##.# 3 #.## 4 .### (leading decimal) Display: 0#. 4321 (selected digit is replaced by •) Reference: Enabling Parameters . . . . . . . . . . . . . . . . . . . 36 Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75
UM3300/H (1.1.0)
130
Appendix A: Configuration Parameters
COND:D GAIN 1 Output Scaling Gain
For controllers equipped with an auxiliary PCB, this parameter sets the gain used to scale and calibrate the high-current output signal. Range: .0000 to .9999 Display: G1 .#### Reference: Output Circuit Calibration . . . . . . . . . . . . . . . . 85
Note: COND:D GAIN 2 Loopback Scaling Gain
GAIN 1 and 2 can only be changed via the Engineering Panel. For controllers equipped with an auxiliary PCB, this parameter sets the gain used to scale and calibrate the high-current output’s loopback input signal. Range: 00.00 to 99.99 Display: G2 ##.## Reference: Loopback Circuit Calibration . . . . . . . . . . . . . 87 MODE TEST 4 . . . . . . . . . . . . . . . . . . . . . . . 146
COND:D IN ## Discrete Input Assigned Function
For turbine controllers, each of these parameters selects the function assigned to the corresponding discrete input. If the value is positive, the input is asserted by raising its voltage above the neutral zone. If it is negative, the input is asserted by lowering that voltage below the neutral zone. Range: see UM3307 and UM3308 Display: ##+Value (press HIGH or LOW to select sign, then press • to select function) Reference: Discrete I/O . . . . . . . . . . . . . . . . . . . . . . . . . . 74
COND:D OUT 1 First Output Assigned Variable
This parameter selects the signal from which the high current output signal is calculated and enables or disables the current and position feedback tests. Range:
Act actuator control signal, no tests ActL Act plus current Loopback test only ActP ActL plus position feedback test Off constant, minimum signal Display: OT1 Valu Reference: Loopback Circuit Calibration . . . . . . . . . . . . . 87 Output Loopback Test . . . . . . . . . . . . . . . . . . 88
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
COND:D OUT 1 – Bipolar Output
131
For controllers that support valve positioning via the high-current output, this parameter determines whether that output is generated as a unipolar or bipolar electrical signal. Range:
Off unipolar output On bipolar output Display: OT1- OFF/ON Reference: Bipolar Operation . . . . . . . . . . . . . . . . . . . . . . 83 Output Circuit Calibration . . . . . . . . . . . . . . . . 86 Loopback Circuit Calibration . . . . . . . . . . . . . . 87
COND:S ALARM 1 Control Threshold
This parameter defines the minimum rotational speed below which the signal from a magnetic pickup is considered unreliable. Range: Display: Enter After: Reference:
COND:S DISPLAY HIGH Maximum Control Speed
00000 to Maximum Control Speed A1 ##### COND:S DISPLAY HIGH
MPU Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
This parameter serves as a reference value for converting the absolute speeds (in rpm) obtained from the speed inputs and displayed on the front-panel readouts to the percent-of-range values the controller uses internally. It should be set equal to or slightly greater than the maximum rotational speed your turbine could ever reach. Range: 00000 to 64000 rpm Display: HI ##### Reference: MPU Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
MODE:D ANIN LOW Transmitter Failure Limit
August 2007
For a Dual-Loop A/P Controller, this parameter defines the minimum value for any offset-zero input’s analog-to-digital variable, below which that input is considered to have failed. Range: 00.0 to 99.9 percent Display: ANL ##.# Reference: Numeric Parameters . . . . . . . . . . . . . . . . . . . . 40 Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 MODE:D ANIN – . . . . . . . . . . . . . . . . . . . . . . 141
UM3300/H (1.1.0)
132
Appendix A: Configuration Parameters
MODE:D ANIN # Offset Zero Input
Each of these parameters identifies the zero level of the corresponding analog input signal (relative to its hardware configuration). Range:
Off actual zero (for example, 0 to 5 Vdc) On 20 percent offset zero (e.g., 4 to 20 mA) Display: A# OFF/ON Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 Analog In Menu . . . . . . . . . . . . . . . . . . . . . . 103 MODE TEST 4 . . . . . . . . . . . . . . . . . . . . . . . 145
MODE:D ANIN # HIGH Analog Input High Alarm Limit
MODE:D ANIN # LOW Analog Input Low Alarm Limit
MODE:D COMM 0 Controller ID Number
Each of these parameters defines the maximum value for the corresponding analog input’s analog-to-digital variable, above which that input is considered to have failed. Range: 00.0 to 102.4 percent Display: A#H ##.# Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 MODE:D ANIN – . . . . . . . . . . . . . . . . . . . . . 141 Each of these parameters defines the minimum value for the corresponding analog input’s analog-to-digital variable, below which that input is considered to have failed. Range: 00.0 to 102.4 percent Display: A#L ##.# Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 75 MODE:D ANIN – . . . . . . . . . . . . . . . . . . . . . 141 This parameter identifies the controller in the network connected to its serial Port 1. With the exception of redundant controllers, this ID must be unique within that network. Range: 1 to 8 Display: Ctrl# # Reference: Configuring Communications . . . . . . . . . . . . . 73 Engineering Panel . . . . . . . . . . . . . . . . . . . . 110
Note:
August 2007
COMM 0 and 0 • can only be changed via the Engineering Panel.
UM3300/H (1.1.0)
Series 3++ Hardware Reference
MODE:D COMM 0 • Computer ID Number
133
This parameter identifies the controller in the networks connected to its serial Ports 2, 3, and 4. With the possible exception of redundant controllers, this ID must be unique within each of those networks. Range: 01 to 64 Display: Comp# ## Reference: Configuring Communications . . . . . . . . . . . . . 73 Serial Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Programming and Configuration . . . . . . . . . . 126
MODE:D COMM 2 Port 2 Baud Rate
This parameter defines the data transmission rate for the Port 2 serial communication channel. Range: 2400, 4800, 9600 Display: PT2 Valu (press • to select, then ENTER) Reference: List Parameters . . . . . . . . . . . . . . . . . . . . . . . 37 Configuring Communications . . . . . . . . . . . . . 73
MODE:D COMM 3 Port 3 Baud Rate Port 3 Parity Port 3 Scaling
MODE:D COMM 4 Port 4 Baud Rate Port 4 Parity Port 4 Scaling
August 2007
These parameters define the data transmission rate, parity setting, and Modbus register scaling for the Port 3 communication channel. Range: 4800, 9600, 19k2 (baud) Even, Odd, None (parity) 4000, 4095, 64k (100% value) Display: PT3 Valu (press • to change, then ENTER) PT3 Valu (press • to change, then ENTER) PT3 Valu (press • to change, then ENTER) Reference: Configuring Communications . . . . . . . . . . . . . 73 Programming and Configuration . . . . . . . . . . 126 These parameters define the data transmission rate, parity setting, and Modbus register scaling for the Port 4 communication channel. Range: 4800, 9600, 19k2 (baud) Even, Odd, None (parity) 4000, 4095, 64k (100% value) Display: PT4 Valu (press • to change, then ENTER) PT4 Valu (press • to change, then ENTER) PT4 Valu (press • to change, then ENTER) Reference: Configuring Communications . . . . . . . . . . . . . 73 Programming and Configuration . . . . . . . . . . 126
UM3300/H (1.1.0)
134
Appendix A: Configuration Parameters
MODE:D fC 1 Positioning Loop
This parameter enables or disables the optional valve positioning loop and the display of its input signal value (LVDT1). Range:
Off valve positioning disabled On valve positioning enabled Display: fC1 OFF/ON Reference: Output Circuit Calibration . . . . . . . . . . . . . . . . 86 Loopback Circuit Calibration . . . . . . . . . . . . . 87
MODE:D fD 1 Mass Flow Input
This parameter selects the analog input for the flow signal (∆Po) used to compute a Performance Controller’s measured total flow. Range:
Off measured total flow not calculated 1 to 8 selects corresponding analog input Display: fD1 OFF/# Reference: Enabling Parameters . . . . . . . . . . . . . . . . . . . 36
MODE:D fE 1 Redundant Tracking
This parameter determines whether the controller will operate in its redundant mode when a Track discrete input is asserted. Range:
Off redundant tracking disabled On redundant tracking enabled Display: fE1 OFF/ON Reference: Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
MODE:D LOCK 0 Modbus While Tracking
If redundant controllers are given the same Computer ID Number [MODE:D COMM 0 •], this parameter must be disabled so that only one of them will respond to Modbus data requests to that address. If they are given different ID numbers, enabling this parameter allows the Modbus host to monitor both controllers. Range:
Off host cannot monitor tracking controller On host can monitor tracking controller Display: LOC0 OFF/ON Reference: Serial Ports . . . . . . . . . . . . . . . . . . . . . . . . . . 98
MODE:D LOCK 2 Modbus Write Inhibit
This parameter defines the level of access (read/write or read-only) that a host device has to the controller’s coils and holding registers. Range:
Off read and write access On read access only Display: LOC2 OFF/ON Reference: Enabling Parameters . . . . . . . . . . . . . . . . . . . 34 Configuring Communications . . . . . . . . . . . . . 73
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
MODE:D RA # Relay Assigned Function
135
Each of these parameters selects the conditions under which the corresponding discrete output is triggered. If the assigned function is positive, the relay will be energized when the associated condition exists. If the value is negative, the relay will de-energize. Range: see chapter 3 of each configuration manual Display: RA#±Valu (press HIGH or LOW to select sign, then press • to select function) Reference: List Parameters . . . . . . . . . . . . . . . . . . . . . . . 38 Discrete I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
MODE:E LOCK 6 Auxiliary PCB Lockout
An Extraction Controller that does not use the high-current analog output or discrete inputs of it auxiliary PCB assembly can be configured to ignore or operate without it by enabling this parameter. Range:
Off functioning auxiliary PCB required On auxiliary PCB ignored (if present) Display: LOC6 OFF/ON Reference: Speed Board Operation . . . . . . . . . . . . . . . . . 78 Alarm System . . . . . . . . . . . . . . . . . . . . . . . . 106
MODE:S ANIN 1 Speed Input 1
This parameter specifies whether the controller calculates a speed from the frequency of the first magnetic pickup input signal. Range:
Off MPU1 not read On MPU1 enabled Display: P1 OFF/ON Reference: Speed Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 79
MODE:S ANIN 2 Speed Input 2
This parameter specifies whether the controller calculates a speed from the frequency of the second magnetic pickup input signal. Range:
Off MPU2 not read On MPU2 enabled Display: P2 OFF/ON Reference: Speed Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 79
MODE:S ANIN 3 Speed Input 3
This parameter specifies whether the controller calculates a speed from the frequency of the third magnetic pickup input signal. Range:
Off MPU3 not read On MPU3 enabled Display: P3 OFF/ON Reference: Speed Inputs . . . . . . . . . . . . . . . . . . . . . . . . . 79
August 2007
UM3300/H (1.1.0)
136
Appendix A: Configuration Parameters
MODE:S ANIN 4 MPU Tolerance
When all three magnetic pickup inputs are enabled, this parameter defines their maximum acceptable deviation from the median speed. Any input that deviates from the median by more than this amount is considered to have failed. Range: 01 to 99 rpm Display: WIN ## Reference: MPU Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
MODE:S ANIN 5 Gear Tooth Count
This parameter defines the number of speed input pulses the controller will expect to receive per revolution of the MPU gear shaft. Range: 000 to 999 teeth Display: GR ### Reference: Speed Scaling . . . . . . . . . . . . . . . . . . . . . . . . 80
MODE:S ANIN 6 Shaft Speed Ratio
This parameter defines the number of times the MPU gear shaft rotates per revolution of the turbine. Range: 0.000 to 9.999 Display: Ri #.### Reference: Speed Scaling . . . . . . . . . . . . . . . . . . . . . . . . 80
MODE:S REV 1 Output Reverse
This parameter matches the direction of the actuator control signal to that of your steam control valve. Range:
Off signal-to-open valve On signal-to-close valve Display: REV1 OFF/ON Reference: Output Circuit Calibration . . . . . . . . . . . . . . . . 86
MODE:S SS 3 Alternate MW Input
This parameter specifies how a Speed Controller’s megawatt droop algorithm selects its analog input (signal variable SV7 or SV8). Range:
Off always select SV7 High select highest of two signals Low select lowest of two signals Display: SS3 OFF/HIGH/LOW Reference: Enabling Parameters . . . . . . . . . . . . . . . . . . . 35
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
137
Series 3++ Hardware Referencemanual
UM3300/H
Appendix B Controller Test Sequences This appendix describes the controller test procedures that can be executed from the engineering panel of a Series 3++ Controller. As described in Chapter 2, each such key sequence begins with a data group key that selects the function of the second key. Unlike the key sequences used to enter configuration parameters, most of these procedural key sequences are not assigned to specific data pages. A data page letter is indicated only when you must press the data group key as many times as needed to display the letter at the end of the first step confirming display. For example, the Transmitter Status Test [MODE:D ANIN –] is assigned to the Device page, as indicated by the MODE:D notation and its “MODE: D” first step confirming display. Pressing the CLEAR key will terminate any of these procedures and clear the display. Otherwise, they time out and automatically clear the display after 45 seconds of keyboard inactivity.
LIMIT LOWER CPU Loading
The Machine Control Program (see page 70) scans the controller’s inputs and outputs every five milliseconds, and ideally executes the control loop after every eighth I/O scan (in other words, at 40 millisecond intervals). That loop is interrupted by serial communication tasks and subsequent I/O scans, but should complete before the next eighth such scan. To display the number of I/O scans that are being run between control loop executions on the engineering readout, press the following Front Panel keys (for Dual-Loop A/P and Speed Controllers, the first key is instead labelled ALT or LIMIT): LIMIT 2
∇
Lp
5
If a control loop execution takes more than the allotted eight I/O scans, the displayed Lp will be zero. The CPU will then reset if the loop takes more than 120 more milliseconds to complete. To display the number of I/O scans (out of 16) that remained before that would have happened, press the following front panel keys (for Dual-Loop and Speed Controllers, the first key would be LIMIT or POWER): LIMIT 3
August 2007
∇
Wp
16
UM3300/H (1.1.0)
138
Appendix B: Controller Test Sequences
MODE LOCK 5 1 Enable Reconfiguration
To enable alteration of the controller’s configuration and tuning parameters from the engineering panel, press the following keys: 5 MODE
1
LOCK
LOC5 ON
ENTER
If you make a mistake entering this sequence, the controller will beep and display an Error! message on the confirming display. When you finish reconfiguring your controller, enter the Disable Reconfiguration [MODE LOCK 5 0] sequence to disable further changes (otherwise, reconfiguration will be automatically disabled after thirty minutes of keyboard inactivity):
MODE LOCK 5 0 Disable Reconfiguration
To disable alteration of the controller’s configuration and tuning parameters from the engineering panel, press the following keys: 5 MODE
LOCK
0
LOC5 OFF
ENTER
If you make a mistake entering this sequence, the controller will beep and display an Error! message on the confirming display.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
MODE LOCK 3 • Store Alternate Parameters
139
This procedure copies the controller’s current parameters into any of its three alternate sets. To initiate this procedure, which you can abort at any time by pressing CLEAR, press the following keys: 3 MODE
•
Store1?
ENTER
LOCK
This display indicates which alternate set the current parameters will be copied into. To select a different set, press the decimal (•) key: •
Store2?
Pressing ENTER will then copy the current parameters to the indicated alternate set and briefly display that set’s new checksum:
CS= F882
ENTER
MODE LOCK 3 • • Recall Alternate Parameters
This procedure copies any of the three alternate parameter sets into the controller’s current set. To initiate this procedure, which you can abort at any time by pressing CLEAR, press the following keys: 3 MODE
•
• ENTER
LOCK
Recall1?
This display indicates which alternate set will be copied into the working memory. To select a different set, press the decimal (•) key: •
Recall2?
Pressing ENTER will then initiate a recall of the selected alternate parameter set. If it is valid, it is copied into the current set and the controller executes a soft reset. If the selected set is invalid (which probably means it was never defined), “No Match” is displayed to inform you that the recall has been aborted: ENTER
or
August 2007
Reset No Match
UM3300/H (1.1.0)
140
Appendix B: Controller Test Sequences
MODE LOCK 4 Parameter Checksum
This procedure displays the checksum values of the controller’s various parameter sets. You can determine which (if any) of the alternate parameter sets is currently in use by comparing the checksum of the present and long-term sets to those for the alternate sets. You can also tell if any of these parameter sets agree with those recorded on a parameter worksheet by comparing these checksums to those recorded on that worksheet. To view the parameter checksums, press the following keys: 4 MODE
LOCK
CS= A3C2 P = A76F
or
If the confirming display beings with CS, the present parameter set is the same as that stored in long-term memory. If that display begins with P, the two sets differ and the checksum shown is for the present set. In that case, you can display the long-term parameter checksum by pressing the decimal key: •
L = A3C2
If the two parameter sets are different, you should use the Disable Reconfiguration [MODE LOCK 5 0] procedure to disable reconfiguration. The controller will then correct any errors that occur in the present parameter set. To display the alternate parameter set checksums, continue to press the decimal (•) key: •
•
•
CS1=B94A CS2=632E CS3=44FC
You can cycle through the displays of all four (or five) checksums by continuing to press the decimal (•) key as many times as you want.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
MODE:D ANIN – Transmitter Status Test
141
This procedure can be used to identify which analog input signal(s) triggered a transmitter failure alarm, which is indicated by lighting the front panel’s Alarm LED and displaying “TranFail” on its Alarms status screen. To initiate this test, press the following keys: repeat
MODE
until you see –
AN IN
MODE:
D
AN1 GOOD
or
AN1 HIGH
or
AN1 LOW
The digit in this display is the analog input channel number (AN1). HIGH indicates that signal is above its Analog Input High Alarm Limit, LOW indicates it is below its Analog Input Low Alarm Limit, or GOOD indicates it is between those limits. For a Dual-Loop Controller only, the inputs are checked against a common Transmitter Failure Limit and only test as GOOD or LOW. You can determine the status of each consecutive input signal by pressing the • key: •
AN1 GOOD
or
AN1 HIGH
or
AN1 LOW
This allows you to repetitively cycle through all the inputs. The status of the displayed input is updated continuously. With previous versions, the conditions of all eight inputs were checked only at the instant that this test was initiated and not updated thereafter.
MODE COMM Reset Controller
To restart the control program without initializing its operating state and variables, press the following keys: MODE
COMM
ENTER
Reset
Doing so will increment both the CPU Reset Count [MODE TEST 6] and the Front-Panel Reset Count [MODE TEST 7].
August 2007
UM3300/H (1.1.0)
142
Appendix B: Controller Test Sequences
MODE COMM – 1 Port 2 Master Test
A Station Controller periodically requests information from each Load-Sharing Performance Controller. To determine whether or not those controllers are responding, press the following keys: – MODE
1
COMM
-08 GOOD -08 BAD
or
where the number following the minus sign is the first designated load-sharing controller’s Computer ID Number (08 in the above example). The confirming display will be GOOD if that controller is responding to Station Controller requests, or BAD if it is not. Pressing the decimal key then advances this display through the list of designated Load-Sharing Controllers, in the following order: 08 16 24 32 40 48 56 64
decrementing to decrementing to decrementing to decrementing to decrementing to decrementing to decrementing to decrementing to
01 09 17 25 33 41 49 57
The confirming display The End will appear after the status of all the designated secondary controllers has been reviewed.
MODE COMM – 2 Port 2 Slave Test
To determine if the controller has detected any Port 2 serial communications activity within the past second, press the following keys: – MODE
or
COMM
2
-2
GOOD
-2
BAD
where the confirming display will be GOOD if a serial transmission has been received during the previous second.
Note:
August 2007
Unless this port is used for performance or extraction load-sharing, it is usually not even connected to any other controllers and a BAD result for this test is of no consequence.
UM3300/H (1.1.0)
Series 3++ Hardware Reference
MODE COMM – 3 Port 1 Test
143
Each controller can be configured to expect Port 1 transmissions from other Series 3++ Controllers by enabling any of several features (for example, redundant controller tracking). This procedure reveals whether or not this controller is receiving Port 1 transmissions from the associated controllers. To identify the companion controllers from which Port 1 transmissions are being received, press the following keys: – MODE
3
COMM
-1
GOOD
-1
BAD
where the digit is a controller ID number. GOOD indicates data is being received from that controller, BAD indicates it is not. Subsequently pressing the decimal key displays the same information for the next possible companion controller. You can cycle through all eight possible ID numbers (including this controller’s own) by pressing that key as many times as you like: •
•
Note: MODE TEST 3 Serial Port Activity Test
-8
BAD
-1
GOOD
Although transmissions are normally received from all controllers connected to Port 1 (including this one), only those from specified companion controllers are normally of any concern. To view a dynamic display of a specified serial port’s communications activity, press the following keys: 3 MODE
TEST
#
PT# R-T_
where # is the numeric key corresponding to the port number. The bar after the R will be in the high position if that port is currently receiving a transmission, otherwise it will be low. Similarly, the bar after the T will be high only when that port is transmitting. The port in the above example is receiving but not transmitting. You can then check for communications activity on any other port by pressing the corresponding numeric key (for example, press 4 to view Port 4’s activity): 4
August 2007
PT4 R-T_ UM3300/H (1.1.0)
144
Appendix B: Controller Test Sequences
MODE TEST 2 Program Version
This procedure displays the installed control program and the FPGA and auxiliary PCB firmware revision numbers. To determine which revision of the control program is installed in your controller, press the following keys: 2 MODE
TEST
1061-001
If the confirming display is blank, production software has not yet been loaded into this controller. Pressing the decimal key (•) will then display the installed version of the FPGA or auxiliary PCB firmware: •
FPGA0202
or
SPBD-010
or
--------
The SPBD (speedboard/auxiliary PCB) version is displayed only by Speed and Extraction Controllers with installed auxiliary PCBs, while the line of dashes is displayed by turbine controllers that are not so equipped. In either case, pressing the decimal key (•) a second time would then display the FPGA firmware version.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
MODE TEST 4
145
Signal Values Test
This procedure can display the current values of the analog, speed (frequency), position, and discrete input signals, the intended states of the control relays, and the currently-pressed front-panel buttons and control keys.
Note:
The internal analog inputs for the output loopback measurements, CPU/IO board power supply voltages and temperature can only be monitored via the via the front-panel status screen. To initiate this test, press the following keys: 4 MODE
TEST
Inputs
To display the measured value of any analog input, press the corresponding numeric key. For example, pressing 1 displays the current value of the CH1 input: 1
CH1 45.8
where the number in the display is the corresponding signal variable (values above 99.9 percent display as A0.0). Or, you can display the value of each consecutive input by pressing the decimal key (•). To determine if an input is being read accurately, disable its Offset Zero Input [MODE:D ANIN #] parameter and compare the resulting TEST 4 value to a volt or ammeter measurement of the corresponding input signal.
Note:
The engineering-units value of each enabled input can be displayed via the Analog In menu of the front-panel status screen. To display a turbine controller’s speed/frequency inputs (MPUs), press the decimal key to scroll past the CH8 input display:
CH8 50.8 •
PU1 00.0
Each input is displayed as a percentage of the defined maximum speed for the corresponding turbine shaft. Because the Extraction Controller does not use these inputs, their values are meaningless.
Note:
August 2007
The revolutions-per-minute value of each enabled speed input can be displayed via the In/Out menu of the front-panel status screen.
UM3300/H (1.1.0)
146
Appendix B: Controller Test Sequences To display the auxiliary PCB’s valve position and output loopback signals (see Loopback Circuit Calibration on page 87), scroll past the display for MPU 3:
PU3 00.0 •
•
•
•
LV1 35.2 AD3 50.3 AD4 00.0 AD5 01.1
These values represent: LV1 unscaled LVDT1 input, displayed as a percentage of its maximum range AD3 raw value of the output loopback signal, in percent of 200 mA. AD4 auxiliary analog input (00.0 = -20, A0.0 = +20 mA) AD5 output loopback value, after applying the Loopback Scaling Bias and Loopback Scaling Gain To determine the status of the discrete inputs, press zero (0). Pressing the decimal key (•) then repeatedly toggles the display between inputs 1 to 8 and 9 to 16: 0
•
•
_2__5___ _A__DE__ _2__5___
Each character will be the input number if that input is asserted or an underscore if it is not. Digits above nine are shown in a modified hexadecimal notation (A=10, B=11, …, G=16). The above examples show only inputs DI2, 5, 10 (A), 13 (D), and 14 (E) are asserted.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
147
To determine which discrete outputs are energized, press nine (9): 9
1__4____
where each character will be either the relay number (if that relay is energized) or an underscore (if it is not). The 1 for fault relay CR1 will appear unless it (and possibly CR2) are de-energized by CR1’s assigned function. In the above example, only relays CR1 and CR4 should be energized.
Note:
The status of the Auxiliary PCB Fault relay (DO9) cannot be viewed via this procedure. To display a group of digits indicating which front-panel keys and buttons are pressed, press the minus (–) key: –
12__5___
If no keys are pressed, a line of eight underscores is displayed. If a single key is pressed or stuck, one of the following unique groups of digits will appear (for example, the group 1/2/5 shown above would indicate that only the Menu button is pressed or stuck down): 1356 12456
Caution:
August 2007
8
4
125
5
235
346
6
12346
127
1
237
7
2
This procedure does not disable the normal operation of the front panel keys and buttons, so pressing them to verify that they are working can affect the operation of the controller.
UM3300/H (1.1.0)
148
Appendix B: Controller Test Sequences
MODE TEST 6 CPU Reset Count
Resetting the main CPU restarts its control program. This occurs when the controller is powered up, a hardware or software fault causes a watchdog time out, critical parameters are changed or alternate parameter sets are recalled, the controller is reconfigured from a workstation, or the Reset Controller [MODE COMM] procedure is executed. This procedure checks the controller’s parameters to make sure they are reasonable, resets its serial ports and analog inputs, and begins a new scan cycle. Most controllers always execute a soft reset, which does not change the operating state or analog output. However, a Speed Controller will execute a hard reset (which trips the turbine) when it powers up or detects a fault. To display the number of times the control program has restarted since this count was last zeroed, press the following keys: 6 MODE
TEST
Z80 ####
where #### is the hexadecimal reset count, which can then be reset by pressing the zero key: 0
MODE TEST 7 Front-Panel Reset Count
Z80 0000
To display the number of times the front-panel microprocessor has reset since this count was last zeroed, press the following keys: 7 MODE
TEST
Mot ####
where #### is its current hexadecimal value, which can then be reset by pressing the zero key: 0
Mot 0000
Resetting or powering up the controller will usually increment this count by two.
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
MODE TEST 8 Program Checksum
149
This procedure initiates the calculation and display of a four-digit, hexadecimal (for example, 1AF4) checksum for the controller’s internal binary operating instructions. It is used primarily to verify the successful downloading of a new operating program. To initiate this test, press the following keys: 8 MODE
TEST
CRC BusY
This message indicates the controller is calculating the requested checksum. After a brief pause, it will be replaced by:
CRC #### where #### is the hexadecimal checksum for the installed software. The correct CRCs for the standard releases of each control application are listed on its revisions data sheet {DS33##/V].
MODE TEST 9 Set Clock
This procedure sets a Speed Controller’s clock to a specified month, day, year, hour and minute, which it displays in that order. As the current value of each field is displayed, you can: • press the decimal key (•) to leave it unchanged and display the next field’s value, • enter a new value by pressing the corresponding two numeric keys and then the ENTER key, or • press the CLEAR key to terminate this procedure. If you make a mistake while specifying a new value, press the CLEAR key once to start over or twice to abort this procedure and leave the original value unchanged. If you specify an invalid value and then press ENTER, the procedure aborts after briefly displaying an “Error!” message. Once you have entered a change, making an error or aborting the procedure will not undo it. To initiate this procedure, press the following keys to display the current month-of the-year setting (01≤##≤12): 9 MODE
TEST
Month?##
Either pressing the decimal key (•) or entering a new month will then display the current day-of-the-month (01≤##≤days in month): #
ENTER
August 2007
#
Month?## Day?
##
UM3300/H (1.1.0)
150
Appendix B: Controller Test Sequences where each numeric key used to specify the new month is represented as # (you must press the leading zero for most months). Either pressing the decimal key (•) or entering a new day will then display the current year (20##): #
#
Day?
##
Year? ##
ENTER
Either pressing the decimal key (•) or entering a new year will then display the current hour-of-the-day (00 ≤ ## ≤ 59): #
#
Year? ## Hour? ##
ENTER
Pressing the CLEAR key or entering a new minute (00 ≤ ## ≤ 59) will then terminate this procedure. Entering a new minutes value will also set the seconds counter to zero: #
#
Minut?##
ENTER
MODE TEST HIGH Auxiliary PCB Error Count
For Speed and Extraction Controllers, this procedure dynamically displays the number of times the auxiliary PCB has failed to respond to the main CPU since this count was last zeroed. To display this count, press the following keys: HIGH
MODE
TEST
332=####
where #### is the communication error count, which can then be reset by pressing the zero key: 0
August 2007
332=0000
UM3300/H (1.1.0)
Series 3++ Hardware Reference
151
Series 3++ Hardware Referencemanual
UM3300/H
Glossary/Index This combined glossary and index defines and references various topics discussed in this manual. Alarms
Alternate Parameter Set
Analog Input
August 2007
are undesirable control system conditions indicated by the front-panel Alarms LED, Modbus and OPC Alarm variables, and any control relays assigned the Alarm function. Reference: Compressor Controllers . . . . . . . . . . . . . . . . . . . 106 External Alarms . . . . . . . . . . . . . . . . . . . . . . . . . 108 Turbine Controllers . . . . . . . . . . . . . . . . . . . . . . . 107 is one of three sets of configuration and tuning parameter values that the controller can store in addition to its primary (working) set. Recalling an alternate parameter set causes a Controller Reset. Reference: Alternate Parameter Set . . . . . . . . . . . . . . . . . . . . 28 Displaying Checksums . . . . . . . . . . . . . . . . . . . . 140 Parameter Memory Procedures . . . . . . . . . . . . . . 43 Storing and Recalling . . . . . . . . . . . . . . . . . . . . . 139 is a circuit that measures the electrical signal from a process variable transmitter, or the value of such a signal. Reference: Auxiliary PCB Assembly . . . . . . . . . . . . . . . . . . . . 20 Back Panel Connections. . . . . . . . . . . . . . . . . . . . 55 CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . . . . 18 Current/Voltage Switch Settings . . . . . . . . . . . . . . 49 FIM Connections. . . . . . . . . . . . . . . . . . . . . . . . . . 59 Measured Variable Screens . . . . . . . . . . . . . . . . 103 Measured Variable Value . . . . . . . . . . . . . . . . . . . 76 Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Redundant Controllers . . . . . . . . . . . . . . . . . . . . . 97 Signal Values Test . . . . . . . . . . . . . . . . . . . . . . . 145 Signal Variable Value . . . . . . . . . . . . . . . . . . . . . . 76 Transmitter Status Test . . . . . . . . . . . . . . . . . . . 141 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 118 see also: Position Input, Transmitter Failure
UM3300/H (1.1.0)
152
Glossary/Index Analog Output
is a circuit that generates an electrical signal that is used to manipulate a final control element, or the value of such a signal. Reference: Auxiliary PCB Assembly. . . . . . . . . . . . . . . . . . . . .20 Back Panel Connections . . . . . . . . . . . . . . . . . . . .55 CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . . . . .18 Current/Voltage Switch and Jumper . . . . . . . . . . .50 FOM Connections . . . . . . . . . . . . . . . . . . . . . . . . .62 General Operation . . . . . . . . . . . . . . . . . . . . . . . . .76 Monitoring Intended and Actual Signals. . . . 101–103 Redundant Controllers . . . . . . . . . . . . . . . . . . . . . .92 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . .118 see also: High-Current Output, Output Loopback Failure
Auxiliary PCB
is a circuit board that provides the High-Current Output, Position Inputs, Speed Inputs, and Discrete Inputs 9 to 16. Reference: Auxiliary PCB Assembly. . . . . . . . . . . . . . . . . . . . .19 Failure Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . .107 Fault Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105 General Operation . . . . . . . . . . . . . . . . . . . . . . . . .78 Jumper Settings . . . . . . . . . . . . . . . . . . . . . . . . . . .51 Program Version Test . . . . . . . . . . . . . . . . . . . . .144 Replacement Procedure . . . . . . . . . . . . . . . . . . .124 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . .121
Back Panel
is one of several different assemblies that can be used to provide the power cord and field wiring or Field Termination Assembly connections. Reference: Back Panel Assemblies . . . . . . . . . . . . . . . . . . 23–24 Component Configuration . . . . . . . . . . . . . . . . . . .16 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 53–56 Ethernet Converters . . . . . . . . . . . . . . . . . . . . . . . .23 Serial Port Connections . . . . . . . . . . . . . . . . . . . . .64
Baud Rate Beep Frequency
Bipolar Output Brightness, Readouts Buttons Cable Length
August 2007
see: Serial Port is the frequency of the beep sound, which can be varied by pressing the Raise or Lower Key while holding down the Scroll button. Reference: User Preferences . . . . . . . . . . . . . . . . . . . . . . . . . .90 is a feature of the High-Current Output that can generate bi-directional (forward and reverse) current flows. see: LED Brightness see: Control Keys, Control Loop Buttons, Menu System Buttons is the total of the lengths of all cables within any given RS-485 serial communication network. Reference: Serial Communication Networks . . . . . . . . . . . . . .64
UM3300/H (1.1.0)
Series 3++ Hardware Reference Calibration
Case Mounting Slides
Checksum
153
is only possible for the high-current output circuit of the Auxiliary PCB. All CPU/IO PCB I/O signals are permanently calibrated at the factory. Reference: High-Current Output . . . . . . . . . . . . . . . . . . . . 85–88 are slides along top and bottom of controller case that pull its front flanges back against the panel, thus holding it rigidly horizontal. Reference: Controller Mounting . . . . . . . . . . . . . . . . . . . . . . . 46 Controller Replacement . . . . . . . . . . . . . . . . . . . 125 see: Parameter Checksum, Program Checksum
Circuit Isolation
see: Isolation
Communication Error
is an error in the reception of information from a companion Series 3++ Controller or a Modbus host. Reference: Compressor Controller Alarm . . . . . . . . . . . . . . . 106 External Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Modbus/OPC Alarm Bit. . . . . . . . . . . . . . . . . . . . 109 Serial Port 1 Test . . . . . . . . . . . . . . . . . . . . . . . . 143 Serial Port 2 Test . . . . . . . . . . . . . . . . . . . . . . . . 142 Serial Port Activity Test. . . . . . . . . . . . . . . . . . . . 143 Serial Port Troubleshooting . . . . . . . . . . . . . . . . . 72 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 115 Turbine Controller Alarm. . . . . . . . . . . . . . . . . . . 107
Component Replacement
is the repair of a malfunctioning controller by replacing only circuit boards that are believed to be malfunctioning. Reference: CPU Program and Configuration . . . . . . . . . 99, 126 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Internal Circuit Boards . . . . . . . . . . . . . . . . . . . . 124 Return Procedure . . . . . . . . . . . . . . . . . . . . . . . . 123 see also: Controller Replacement, Spare Parts Stocking
Compressor Controller Configuration
is a hardware configuration that does not include an Auxiliary PCB. Reference: Component Configuration. . . . . . . . . . . . . . . . . . . 16
Compressor Controllers
August 2007
are Series 3++ Controllers (Antisurge, Performance, Dual-Loop A/P) that control and protect a centrifugal or axial compressor. Reference: Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
UM3300/H (1.1.0)
154
Glossary/Index
Computer Communications and Control
is the monitoring and control of a Series 3++ Controller by a Modbus host or a client of the Series 3 OPC Server Program. Reference: Ethernet Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 Limiting Modbus Access . . . . . . . . . . . . . . . . . . . .73 Operational Overview. . . . . . . . . . . . . . . . . . . . . . .69 Ports 3 and 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66 Problem Indicator Variables . . . . . . . . . . . . . . . . .109 Redundant Controllers . . . . . . . . . . . . . . . . . . . . . .98 Serial Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . 18, 72 see also: Ethernet Port, Remote Control, Serial Port
Computer ID Number
is a number between 1 and 64 that identifies a Series 3++ Controller over it Port 2, 3, and 4 communication networks. see: Ethernet Port, Serial Port
Configuration
is the adaptation of a Series 3++ Controller to a specific application by setting its Configuration Parameters. Reference: Alternate Parameters . . . . . . . . . . . . . . . . . . . . . .139 CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . . . . .17 Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . .44 Enabling and Disabling . . . . . . . . . . . . . . . . . . . .138 Key Sequence Examples . . . . . . . . . . . . . . . . . 34–42 Key Sequence Illustration . . . . . . . . . . . . . . . . . . .34 Parameter Memory Procedures . . . . . . . . . . . . . . .43 Planner and Worksheet Forms . . . . . . . . . . . . . . .30 Viewing and Changing Parameter Values . . . . . . .32 see also: Alternate Parameter Set, Engineering Panel, Parameter Checksum
Configuration Parameters
are a set of numeric and other values that enable, disable, or otherwise adapt a Series 3++ Controller to a specific application. Reference: Parameter Memory . . . . . . . . . . . . . . . . . . . . . . . .28
Configurator
see: Series 3 Plus Configurator Program
Connections
see: Installation
Contrast, LCD
see: LCD Contrast
Control Keys
are areas of the front panel with raised white outlines, which can be pressed to initiate various process control actions. Reference: Signal Values Test . . . . . . . . . . . . . . . . . . . . . . . .147 see also: Control Loop Buttons, Menu System Buttons
Control LEDs
are the light emitting diodes in the left-lower portion of the Front Panel and embedded in the top row of Control Keys, which generally indicate the status of process control features. see: Status LEDs
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
155
Control Loop Buttons
are raised, labelled areas in the upper portion of the Front Panel that can be pressed to change the data displayed by the Control Loop Readouts. Reference: Signal Values Test . . . . . . . . . . . . . . . . . . . . . . . 147
Control Loop Readouts
are the numeric LED readouts (PV or DEV or RPM, SP, and OUT) in the upper portion of the Front Panel, which generally display the control variable, set point, and response of a primary or limiting control loop selected by pressing one of the Control Loop Buttons.
Control Program
is a Series 3++ Controller’s (Antisurge, Performance, Dual-Loop, Speed, or Extraction) machine control application software, which is stored in the CPU/IO PCB’s EEPROMs. Reference: Controller Replacement . . . . . . . . . . . . . . . . . . . 125 General Operation . . . . . . . . . . . . . . . . . . . . . . . . 70 Main CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Program Checksum Test . . . . . . . . . . . . . . . . . . 149 Program Version Test. . . . . . . . . . . . . . . . . . . . . 144 see also: Program Version
Control Relay
is a relay that can be included in an external circuit and energizes or deenergizes to indicate the state of an internal variable or condition that can have one of two values. Reference: Assigned Functions . . . . . . . . . . . . . . . . . . . . . . . 74 Auxiliary PCB Assembly . . . . . . . . . . . . . . . . . 19, 78 Back Panel Connections. . . . . . . . . . . . . . . . . . . . 53 CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . . . . 18 FOM Connections. . . . . . . . . . . . . . . . . . . . . . . . . 63 Monitoring Intended State. . . . . . . . . . . . . . 101–103 Signal Values Test . . . . . . . . . . . . . . . . . . . . . . . 147 Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 120
Controller Conversion Controller Disassembly Controller Faults Controller ID Number
see: Model Conversion see: Disassembly see: Fault is a number between 1 and 8 that identifies a Series 3++ Controller on its Port 1 serial communication network. see: Serial Port
Controller Installation
see: Installation
Controller Mounting
see: Installation
Controller Removal
see: Deinstallation
August 2007
UM3300/H (1.1.0)
156
Glossary/Index Controller Replacement
is the installation of a functionally identical controller in place of one that is malfunctioning. Reference: Dismounting Old and Mounting New . . . . . . . . . .125 Programming and Configuration . . . . . . . . . . 99, 126 Return Procedure. . . . . . . . . . . . . . . . . . . . . . . . .123 see also: Component Replacement, Spare Parts Stocking
Controller Reset
is a sequence of actions the controller executes when it is powered up, detects a Fault, or is reconfigured using the Series 3 Plus Configurator Program, or when critical parameters are changed from the Engineering Panel, an Alternate Parameter Set is recalled, or the MODE COMM key sequence is entered. Reference: CPU Reset Count. . . . . . . . . . . . . . . . . . . . . . . . .148 CPU/IO Fault Relays . . . . . . . . . . . . . . . . . . . . . .105 Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . .44 Reset Procedure . . . . . . . . . . . . . . . . . . . . . . . . .141
Controller Troubleshooting
see: Troubleshooting
Converter
see: Ethernet Port, Serial Port
CPU/IO PCB
is a circuit board that includes the controller’s central processing unit, serial ports, and basic field inputs and outputs. Reference: CPU Reset Count. . . . . . . . . . . . . . . . . . . . . . . . .148 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Fault Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105 Machine Control Program . . . . . . . . . . . . . . . . . . .70 Monitoring Voltages . . . . . . . . . . . . . . . . . . . . . . .100 Parameter Memory . . . . . . . . . . . . . . . . . . . . . . . .28 Replacement Procedure . . . . . . . . . . . . . . . . . . .124 Startup and Operation . . . . . . . . . . . . . . . . . . . . . .70 Switch Settings. . . . . . . . . . . . . . . . . . . . . . . . . 47–50 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . .117
Cyclic Redundancy Checksum
is a four-digit hexadecimal number calculated by applying a standard mathematical function to a group of numbers. see: Parameter Checksum, Program Checksum
Data Groups
are configuration and tuning parameter subsets identified by the first key in the associated key sequence. Reference: Data Groups and Pages. . . . . . . . . . . . . . . . . . . . .29
Data Pages
are basic categories of configuration and tuning parameters that roughly correspond to the type of feature (hardware or control algorithm) they govern. Reference: Data Groups and Pages. . . . . . . . . . . . . . . . . . . . .29
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Deinstallation
157
is accomplished by removing the slide clamps and case slides and pulling the case out from the front of the control panel. Reference: Controller Replacement . . . . . . . . . . . . . . . . . . . 125
Diagnostic Menu
are the status screens Turbine Controllers use to display power converter voltages, internal temperatures, and output loopback measurements. Compressor Controllers include those screens in their main menus. Reference: Internal Conditions . . . . . . . . . . . . . . . . . . . . . . . 100
Disassembly
of a panel-mounted controller can be accomplished without removing the case from the control panel. Reference: Disassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Discrete Input
is a signal from another device that can have one of two values, or a circuit that determines the state of such a signal. Reference: Associated Functions . . . . . . . . . . . . . . . . . . . . . . 74 Auxiliary PCB Assembly . . . . . . . . . . . . . . . . . 19, 78 Back Panel Connections. . . . . . . . . . . . . . . . . . . . 53 CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . . . . 18 FIM Connections. . . . . . . . . . . . . . . . . . . . . . . . . . 58 Monitoring State . . . . . . . . . . . . . . . . . . . . . 101–103 Redundant Controllers . . . . . . . . . . . . . . . . . . . . . 97 Signal Values Test . . . . . . . . . . . . . . . . . . . . . . . 146 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 119
Discrete Output Engineering Panel
Environmental Requirements Ethernet Port
August 2007
see: Control Relay is an assembly that provides a keyboard and alphanumeric display for controller configuration, tuning, and troubleshooting. Reference: Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . 44 General Operation . . . . . . . . . . . . . . . . . . . . . . . . 89 Key Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . 31 Operational Overview . . . . . . . . . . . . . . . . . . . . . . 69 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Problem Messages . . . . . . . . . . . . . . . . . . . . . . . 110 Replacement Procedure . . . . . . . . . . . . . . . . . . . 124 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 114 Using. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30–44 see also: Configuration Series 3++ Controllers are intended to be permanently mounted in a dry environment that minimizes static electrical discharges and conforms to specified temperature and humidity restrictions. is a converter that allows Modbus TCP clients to communicate with a Series 3++ Controller’s Modbus RTU serial ports (3 and 4). Reference: Back-Panel LEDs . . . . . . . . . . . . . . . . . . . . . . . . . 67 Connecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 Controller Back Panels . . . . . . . . . . . . . . . . . . . . . 23 Redundant Controllers . . . . . . . . . . . . . . . . . . . . . 98 UM3300/H (1.1.0)
158
Glossary/Index
Extended I/O Turbine Controller
is a controller equipped with an Auxiliary PCB, CPC Back Panel, Field Input Module and Field Output Module.
External Alarms
are control system conditions indicated by control relays assigned the corresponding functions. Reference: Relay Functions . . . . . . . . . . . . . . . . . . . . . . . . . .108
Fault
is an internal malfunction that causes the Fault LED to light and the fault relays to de-energize. Reference: Auxiliary PCB Fault Relay . . . . . . . . . . . . . . . . . .105 CPU/IO Fault Relays . . . . . . . . . . . . . . . . . . . . . .105 Discrete Output Switches. . . . . . . . . . . . . . . . . . . .48 Fault Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . .104 Fault LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105 Fault Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Field Input Module
is an external module that provides wiring terminals for turbine controller field input signals, used in combination with the CPC Back Panel. Reference: 24 Vdc Bus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 Analog Input Connections . . . . . . . . . . . . . . . . . . .59 Discrete Input Connections . . . . . . . . . . . . . . . . . .58 Field Termination Assemblies . . . . . . . . . . . . . . . .24 Position Input Connections . . . . . . . . . . . . . . . . . .61 Speed Input Connections. . . . . . . . . . . . . . . . . . . .61 see also: DS3300/T
Field Input/Output Module
is an external module that provides wiring terminals for compressor controller field I/O signals. It is not available for new Series 3++ but can be retained when upgrading from Series 3 Plus Controllers. Reference: Field Termination Assemblies . . . . . . . . . . . . . . . .24
Field Output Module
is an external module that provides wiring terminals for turbine controller field output signals, used in combination with the CPC Back Panel. Reference: 24 Vdc Bus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62 Analog Output Connections . . . . . . . . . . . . . . . . . .62 Control Relay Connections . . . . . . . . . . . . . . . . . .63 Field Termination Assemblies . . . . . . . . . . . . . . . .24 Serial Port Connections . . . . . . . . . . . . . . . . . . . . .64 see also: DS3300/T
Field Programmable Gate Array
is the microprocessor on the CPU/IO PCB, which has been programmed to duplicate the computational, I/O logic, and serial communication features of the Series 3 Plus Controller’s CPU and analog PCB assemblies. Reference: CPU/IO PCB Processor . . . . . . . . . . . . . . . . . . . . .70 Firmware Revision . . . . . . . . . . . . . . . . . . . . . . . .144
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference
159
Field Termination Assembly
is a generic term for any external module that provides wiring terminals that augment or replace those on the controller Back Panel. Reference: Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 57–63 see also: Field Input Module, Field Output Module, Field Input/Output Module.
Firmware Version
is the revision level (for example, FPGA0202) of the stored programs that govern the operation of the Engineering Panel, Field Programmable Gate Array, and the optional Auxiliary PCB. Reference: Auxiliary PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Engineering Panel . . . . . . . . . . . . . . . . . . . . . . . . 90 Field Programmable Gate Array . . . . . . . . . . . . . . 70 Program Version Test. . . . . . . . . . . . . . . . . . . . . 144 see also: Program Version
Frequency, Beep
see: Beep Frequency
Frequency Inputs
see: Speed Input
Front Panel
is an assembly that provides the Control Keys, Control LEDs, Control Loop Buttons, Control Loop Readouts, Menu System Buttons, Status LEDs, and Status Screen. Reference: Fault LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105 Front Panel Assembly. . . . . . . . . . . . . . . . . . . . . . 21 Front-Panel Reset Count . . . . . . . . . . . . . . . . . . 148 General Operation . . . . . . . . . . . . . . . . . . . . . . . . 89 Operational Overview . . . . . . . . . . . . . . . . . . . . . . 69 Preferences and Tests . . . . . . . . . . . . . . . . . . . . . 90 Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 114
Front Panel Overlay
is a label that covers the Front Panel and identifies the functions of its LEDs, keys, buttons and readouts.
Grounding
is accomplished by connecting the power cable ground conductor and one or both shield pigtails of any High-Density Interconnect Cable to an earth ground. Reference: Power Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Serial Ports 1 and 2 . . . . . . . . . . . . . . . . . . . . . . . 65 Serial Ports 3 and 4 . . . . . . . . . . . . . . . . . . . . . . . 66 see also: Isolation
High-Current Output
is the Auxiliary PCB Analog Output, which can generate uni- or bi-polar current-loop signals up to 200 mA. Reference: Auxiliary PCB Assembly . . . . . . . . . . . . . . . . . . . . 20 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . 85–88 High-Current Analog Output . . . . . . . . . . . . . . . . . 82
August 2007
UM3300/H (1.1.0)
160
Glossary/Index High-Density Interconnect Cable
ID Numbers
Indicator Lights Installation
Interface Preferences Internal Clock
Internal Conditions Isolation
August 2007
is a cable for connecting a Field Termination Assembly to a controller Back Panel. Reference: Back Panel Assemblies . . . . . . . . . . . . . . . . . . . . .23 Field Termination Assemblies . . . . . . . . . . . . . . . .24 Mounting Configuration . . . . . . . . . . . . . . . . . . . . .15 are parameters that identify a Series 3++ Controller to other devices on a serial communications network. see: Serial Port see: Ethernet Port, Status LEDs is the mounting of a controller and connection of its I/O terminals to the corresponding field devices. Reference: Back Panel Connections . . . . . . . . . . . . . . . . . 53–56 Controller Mounting . . . . . . . . . . . . . . . . . . . . . . . .46 Ethernet Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 FTA Connections . . . . . . . . . . . . . . . . . . . . . . . 57–63 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45 Power Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68 Serial Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64–67 Switch and Jumper Settings. . . . . . . . . . . . . . . 47–52 see also: Analog Input, Analog Output, Discrete Input, Discrete Output, High-Current Output, Position Input, Serial Port, Speed Input see: Beep Frequency, LCD Contrast, LED Brightness is an auxiliary function of the CPU/IO board’s random access memory (RAM) chip that keeps track of the current date and time, which is used to timestamp entries in the Speed Controller Shutdown Log. Reference: CPU/IO PCB Components . . . . . . . . . . . . . . . . . . .17 Speed Controller Set Clock Procedure . . . . . . . .149 see: Output Loopback Failure; Temperature, Internal; Voltages, Internal is the use of magnetic, optical, and capacitive techniques to prevent interactions between electrical circuits. Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75 Analog Output Installation . . . . . . . . . . . . . . . . . . .50 Discrete I/O Installation . . . . . . . . . . . . . . . . . . . . .53 Serial Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64, 72 Speed Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 see also: Grounding
UM3300/H (1.1.0)
Series 3++ Hardware Reference
161
Jumper Settings
are hardware options that are selected by installing small electrical connectors on one of the controller’s circuit boards. Reference: Auxiliary PCB Assembly . . . . . . . . . . . . . . . . . . . . 51 Back Panel Assembly . . . . . . . . . . . . . . . . . . . . . . 50 see also: Switch Settings
Key Sequence
is an Engineering Panel procedure for examining or changing a configuration or tuning parameter or executing a controller test. Reference: Key Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . 31 Key Sequence Examples . . . . . . . . . . . . . . . . 34–42 Key Sequence Illustrations . . . . . . . . . . . . . . . . . . 34
Keyboard Test
is a diagnostic procedure that can be run by entering an associated Key Sequence from the Engineering Panel. Reference: Configuration and Testing. . . . . . . . . . . . . . . . . . . 27 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 114
Keys LCD Contrast
LED LED Brightness LED Test
Linear Variable Differential Transformer LVDT Input
see: Control Keys, Control Loop Buttons, Engineering Panel, Menu System Buttons is the adjustable difference between the light and dark areas of the Status Screen’s liquid crystal display element. Reference: User Preferences . . . . . . . . . . . . . . . . . . . . . . . . . 90 see: Alarms, Control LEDs, Ethernet Port, Fault, Status LEDs is the adjustable brightness of the Control Loop Readouts. Reference: User Preferences . . . . . . . . . . . . . . . . . . . . . . . . . 90 is the ability to turn on all LEDs and alphanumeric readout segments on the Front and Engineering Panels to see if any are not working. Reference: User Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 is a device for measuring the linear displacement of an object (such as the head of a valve stem) from some reference position. is an input for a Linear Variable Differential Transformer signal. see: Position Input
Machine Control Program
see: Control Program
Magnetic Pickup
is a device that generates a frequency signal proportional to the speed of a rotating shaft. see: Speed Input
Maintenance Strategy
August 2007
is a user’s basic response to controller malfunctions, which is usually to either replace them completely or to identify and replace only their malfunctioning component assemblies. Reference: Maintenance and Repair Overview. . . . . . . . . . . . 99 Maintenance Strategies . . . . . . . . . . . . . . . . . . . 123 UM3300/H (1.1.0)
162
Glossary/Index Measured Variable
is a scaled representation of an Analog Input signal that can be displayed by the Status Screen. Reference: Analog Input Processing . . . . . . . . . . . . . . . . . . . .76
Menu System Buttons
are raised, areas (labelled ACK, MENU and SCROLL) in the center of the Front Panel that can be pressed to change the information displayed by the Status Screen. Reference: General Operation . . . . . . . . . . . . . . . . . . . . . . . . .90 Signal Values Test . . . . . . . . . . . . . . . . . . . . . . . .147
Modbus
is a protocol that allows master devices to read and write variables within Series 3++ Controllers and other slave devices via serial (Modbus RTU) or ethernet (Modbus TCP) communication networks. Reference: Serial to Ethernet Converters. . . . . . . . . . . . . . . . .23 see also: Computer Communications and Control
Model Conversion
Mounting Mounting Configuration
Operator Panel Output Loopback Failure
Panel Mounted Controller Parameter Checksum
Parity August 2007
is the transformation of one Series 3++ Controller model into another by replacing its Front Panel, Control Program, and perhaps altering the hardware configuration. see: Installation is the mounting of a controller’s CPU/IO, Auxiliary, and Power Supply Assemblies within an extruded case or on a flat plate (usually within a NEMA rated enclosure). Reference: Controller Components . . . . . . . . . . . . . . . . . . 15–16 see: Front Panel is an excessive deviation of an analog output signal’s measured and intended values. Reference: Compressor Controller Alarm. . . . . . . . . . . . . . . .106 External Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . .108 High-Current Analog Output. . . . . . . . . . . . . . . . . .88 Internal Loopback Inputs . . . . . . . . . . . . . . . . . . . .76 Loopback Circuit Calibration . . . . . . . . . . . . . . . . .87 Modbus/OPC Alarm Bit . . . . . . . . . . . . . . . . . . . .109 Turbine Controller Alarm . . . . . . . . . . . . . . . . . . .107 is one whose internal components are contained in an aluminum case for mounting in a control panel. Reference: Mounting Configuration . . . . . . . . . . . . . . . . . . . . .15 is a Cyclic Redundancy Checksum calculated from the controller’s Configuration Parameters. Reference: Controller Mounting . . . . . . . . . . . . . . . . . . . . . . . .45 Parameter Checksum . . . . . . . . . . . . . . . . . . . . . .30 Test Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . .140 see also: Configuration see: Serial Port UM3300/H (1.1.0)
Series 3++ Hardware Reference
163
Plate Mounted Controller
is one whose internal components have been mounted on a plate or wall or within an enclosure other than the standard panel-mounting case. Reference: Mounting Configuration. . . . . . . . . . . . . . . . . . . . . 16
Position Input
is the Auxiliary PCB’s LVDT Input or Analog Input, one of which might be used to measure the position of a control valve. Reference: Auxiliary PCB Assembly . . . . . . . . . . . . . . . . . . . . 20 Daughter Board Jumpers . . . . . . . . . . . . . . . . . . . 51 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 External Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . 108 FIM Connections. . . . . . . . . . . . . . . . . . . . . . . . . . 61 Input Signal Values. . . . . . . . . . . . . . . . . . . . . . . 146 Modbus/OPC Alarm Bit. . . . . . . . . . . . . . . . . . . . 109 Positioning Alarm . . . . . . . . . . . . . . . . . . . . . . . . 107 Troubleshooting Positioning Problems . . . . . . . . 122 see also: Output Loopback Failure
Power Cable Power Supply Assembly
Program Checksum
is the cable that supplies electrical power to the controller. Reference: Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 is a circuit board that provides regulated 24 Vdc power to the controller’s other circuit boards. Other needed component power voltages are generated by converters on the CPU/IO board. Reference: Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Monitoring Voltage . . . . . . . . . . . . . . . . . . . . . . . 100 Replacement Procedure . . . . . . . . . . . . . . . . . . . 124 is a Cyclic Redundancy Checksum calculated from the controller’s Control Program. Reference: Controller Mounting . . . . . . . . . . . . . . . . . . . . . . . 45 Program Checksum Test . . . . . . . . . . . . . . . . . . 149
Program Version
is the revision level (for example, 1061-001) of the Control Program loaded in a Series 3++ Controller. Reference: Controller Mounting . . . . . . . . . . . . . . . . . . . . . . . 45 Controller Replacement . . . . . . . . . . . . . . . . . . . 126 Machine Control Program. . . . . . . . . . . . . . . . . . . 70 Program Version Test. . . . . . . . . . . . . . . . . . . . . 144 see also: Firmware Version
Reassembly
is usually accomplished by installing new or repaired internal components into a still-mounted case from the front of control panel. Reference: Reassembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
August 2007
UM3300/H (1.1.0)
164
Glossary/Index Redundant Controllers
are Series 3++ Controllers installed in pairs in which one serves as an online backup to the other. Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97 Analog Output Connections and Switching . . . . . .92 Discrete Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . .97 Ethernet Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . .98 General Failure Relays . . . . . . . . . . . . . . . . . . . .108 Modbus Communication . . . . . . . . . . . . . . . . . . . .98 MPU Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91 Redundant Control Selector. . . . . . . . . . . . . . . 94–97 Serial Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98 Switching Logic . . . . . . . . . . . . . . . . . . . . . . . . . . .92 Tracking Indicators. . . . . . . . . . . . . . . . . . . . . . . .110
Remote Control
is the monitoring and operation of a controller via electro-mechanical and/or electronic indicators, readouts, potentiometers, and switches connected to some of its analog and discrete inputs and outputs. Reference: Operational Overview. . . . . . . . . . . . . . . . . . . . . . .69 Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .108 see also: Computer Communications and Control
Removal Replacement Resetting Controller Return Procedure
Rotary Variable Differential Transformer Rotational Speed
see: Deinstallation see: Controller Replacement, Component Replacement see: Controller Reset tells how to return a malfunctioning controller or assembly to CCC for repair or replacement. Reference: Return Procedure. . . . . . . . . . . . . . . . . . . . . . . . .123 is a device for measuring the angular displacement of an object (such as a guide vane linkage) from some reference position. see: Speed Input
Safety Considerations
All wiring and maintenance must be performed by qualified personnel in conformance with all applicable safety codes.
Serial Communication Error
see: Communication Error
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference Serial Port
Series 3 OPC Server Program Series 3 Plus Configurator Program
Shutdown Log
165
is a circuit used to exchange digital information with other devices. Reference: Baud Rate and Parity . . . . . . . . . . . . . . . . . . . . . . 73 CPU/IO PCB Assembly . . . . . . . . . . . . . . . . . 17, 18 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . 64–67 Network Cable Lengths . . . . . . . . . . . . . . . . . . . . 64 Redundant Controller ID Numbers . . . . . . . . . . . . 98 Redundant Controllers . . . . . . . . . . . . . . . . . . . . . 98 RS-232 Converters . . . . . . . . . . . . . . . . . . . . . . . . 67 Setting ID Numbers . . . . . . . . . . . . . . . . . . . . . . . 73 Station Controller Port 2 Test . . . . . . . . . . . . . . . 142 Surge Suppression . . . . . . . . . . . . . . . . . . . . . . . . 64 Termination Resistors Not Needed. . . . . . . . . . . . 64 see also: ID Numbers is a TrainTools program that provides OPC online data access to a superset of the Modbus data from Series 3, 3 Plus, and 3++ Controllers. see: Series 3 OPC Server user manual [UM5503] is a PC program that can read, edit, and replace a Series 3* Controller’s configuration parameter set and update or change a Series 3 Plus or 3++ Controller’s control program via its Modbus communication ports. Reference: Configuration and Testing. . . . . . . . . . . . . . . . . . . 27 Controller and Component Replacement . . . 99, 126 is a Speed Controller Status Screen menu that displays the time, date, and cause of the last eight turbine shutdowns.
Signal Isolation
see: Isolation
Signal Variable
is an internal variable representing the percent-of-range value of an Analog Input signal. Reference: Analog Input Processing. . . . . . . . . . . . . . . . . . . . 76
Slide Clamps
Software Checksum Software Version Spare Parts Stocking Speed Board
August 2007
are adjusting screws mounted behind the case mounting slides that push them against the control panel, thus pulling the controller back. Reference: Controller Mounting . . . . . . . . . . . . . . . . . . . . . . . 46 Controller Replacement . . . . . . . . . . . . . . . . . . . 125 see: Program Checksum see: Program Version is simplified and reduced by the use of a standard hardware platform for all Series 3 Controller models. Reference: Spare Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 see: Auxiliary PCB
UM3300/H (1.1.0)
166
Glossary/Index Speed Input
Standard Turbine Controller Status LEDs Status Screen
Surge Suppression Switch Settings
Temperature, Internal
is an input circuit used to measure the frequency of the signal from a Magnetic Pickup speed sensor. Reference: Auxiliary PCB Assembly. . . . . . . . . . . . . . . . . . . . .20 Back Panel Connections . . . . . . . . . . . . . . . . . . . .56 Configuration and Operation . . . . . . . . . . . . . . . . .79 FIM Connections . . . . . . . . . . . . . . . . . . . . . . . . . .61 Modbus/OPC Alarm Bits . . . . . . . . . . . . . . . . . . .109 MPU Fail Alarm . . . . . . . . . . . . . . . . . . . . . . . . . .107 MPU Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81 Scaling and Normalization . . . . . . . . . . . . . . . . . . .80 Signal Values Test . . . . . . . . . . . . . . . . . . . . . . . .145 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . .121 is a turbine controller that is not equipped with the CPC Back Panel, Field Input Module and Field Output Module, and thus has fewer field I/O channels than an Extended I/O Turbine Controller. are front-panel indicator lights for controller and process conditions. is the ten-character by four-line liquid crystal display element in the center of the Front Panel, which displays a set of controller status variables or operator prompts selected by pressing the Menu System Buttons. Reference: Changing Contrast . . . . . . . . . . . . . . . . . . . . . . . . .90 General Operation . . . . . . . . . . . . . . . . . . . . . . . . .90 is the protection of the controller’s electronic components by shunting high voltage transients to ground. Reference: Modbus Serial Ports. . . . . . . . . . . . . . . . . . . . . . . .64 are hardware options that are selected by position small switches on one of the controller’s circuit boards. Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49 Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . .50 Control Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . .48 see also: Jumper Settings Is the temperature inside the controller case, as measured by a sensor on the CPU/IO PCB. Reference: Internal Analog Input . . . . . . . . . . . . . . . . . . . . . . .76 Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100
Termination Resistors
are installed at the ends of high-frequency electrical buses in order to keep reflected signals from disrupting communication signals. Series 3++ serial communication networks rarely if ever need them. Reference: Serial Ports. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Testing
see: Fault, Keyboard Test, Output Loopback Failure, Transmitter Failure, Troubleshooting
August 2007
UM3300/H (1.1.0)
Series 3++ Hardware Reference TrainTools
Transmitter Failure
Troubleshooting
167
is a group of PC software packages whose programs can be used to monitor and maintain CCC Controllers. Reference: Updating and Configuring Controllers. . . . . . . . . . 17 see also: TrainTools Product Overview and Setup manual [UM5500] is an alarm condition that is indicated when any analog input signal is not within user-specified limits or exceeds the 21.0 mA smart-transmitter fail signal specified by the Namur NE 43 recommendation. Reference: Compressor Controller Alarm . . . . . . . . . . . . . . . 106 External Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . 108 Input Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Modbus/OPC Alarm Bits. . . . . . . . . . . . . . . . . . . 109 Transmitter Status Test . . . . . . . . . . . . . . . . . . . 141 Turbine Controller Alarm. . . . . . . . . . . . . . . . . . . 107 is the investigation of controller problems in order to identify and correct the cause. Reference: Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 118 Auxiliary PCB . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Communication Errors . . . . . . . . . . . . . . . . . . . . 115 CPU/IO Board Problems. . . . . . . . . . . . . . . . . . . 117 Discrete Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . 119 Discrete Outputs . . . . . . . . . . . . . . . . . . . . . . . . . 120 Front and Engineering Panel . . . . . . . . . . . . . . . 114 Positioning Problems . . . . . . . . . . . . . . . . . . . . . 122 Speed Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 see also: Analog Input, Analog Output, Discrete Input, Discrete Output, High-Current Output, Position Input, Power Supply Assembly, Serial Port, Speed Input
Turbine Controller Configuration Turbine Controllers User Preferences Valid Speed Range
August 2007
is a hardware configuration that includes the Auxiliary PCB. Reference: Component Configurations . . . . . . . . . . . . . . . . . . 16 are Series 3++ Controllers (Speed, Extraction, Fuel) programmed to control and protect a steam or gas turbine. Reference: Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 see: Beep Frequency, LCD Contrast, LED Brightness the minimum and maximum rotational speeds that can be read by the controller’s frequency / magnetic pickup (MPU) inputs. Reference: MPU Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 Scaling and Normalization . . . . . . . . . . . . . . . . . . 80
UM3300/H (1.1.0)
168
Glossary/Index
Voltages, Internal
Watchdog Time Out
August 2007
are the internally-monitored component power voltages from the Power Supply Assembly and the CPU/IO PCB voltage converters. Reference: Compressor Controller Alarm. . . . . . . . . . . . . . . .106 External Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . .108 Internal Analog Inputs . . . . . . . . . . . . . . . . . . . . . .76 Modbus/OPC Alarm Bit . . . . . . . . . . . . . . . . . . . .109 Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100 Turbine Controller Alarm . . . . . . . . . . . . . . . . . . .107 is a feature that forces a Controller Reset if a power interruption or certain internal errors are detected. see: Fault
UM3300/H (1.1.0)
Series 3++ Compressor Controllers Hardware Specificationssheet
DS3300/C
U
# Compressor Controllers Hardware Specifications This data sheet specifies the physical and operating characteristics of Series 3++ Controllers that do not include the optional Auxiliary PCB Assembly (Speed Board).
2.96 75.2
2.68 68.1
1.0 26
6.00 153
19.04 484
5.50 140
dimensions in inches and millimeters
Figure 1
General Specifications Mounting Dimensions Weight Ambient Conditions
Ratings and Certifications Design Life Design MTBF Program Updating and Configuration
August 2007
Controller Dimensions This section lists various general characteristics of this device, whose dimensions are illustrated in Figure 1. Cutout Width: 2.70 in. (68.6 mm), +0.02 in. (0.5 mm)/–0.00 Cutout Height: 5.60 in. (142.2 mm), +0.03 in. (0.8 mm)/–0.00 Cabinet Depth: 22 in. (56 cm) from front of panel 5.0 lb (2.3 kg) Operating Temperature: -4 to 140°F (-20 to 60°C) Storage Temperature: -22 to +185°F (-30 to +85°C) Relative Humidity: 0 to 95% (if free from condensation) see: Agency Certifications for Series 3++ Controllers [TN41]
15 years (continuous operation) 45 years Front panel swings out to expose configuration and testing panel. Optional PC software can load, configure, and tune control program.
Page 1 of 4
DS3300/C (1.1.0)
AC Cable
Cable
Controller
– (Black) Ground (White)
Line (Black)
+ (Red)
Ground (Green)
DC Cable
Neutral (White)
Figure 2
Power Supplies
Cable
Controller
Power Cable Connector Configurations The internal power supply PCB mounts twin third-party 24 Vdc power modules that separately power the internal circuitry and external transmitters. AC conversion or DC regulation modules can be specified, either option requires a back panel with a matching power cable connector:
Input Voltage
21 to 32 Vdc or 96 to 264 Vac, 50 to 60 Hz
Output Power
24.0±1.2 Vdc, 6.0W maximum, isolated and regulated
Maximum Power Consumption
30W (includes 6W output power)
Power Cable
One 14 ft. (4.3 m) cable with AWG 18 (0.8 mm2) conductors is supplied per pair of controllers. Both ends are plug-compatible with the specified PSA. Custom length cables are available.
Power Failure Protection
Configuration data stored in non-volatile EEPROM Process data stored in RAM with a backup battery (minimum battery life is 1 year @ 70 °C).
Communication Ports
Two serial ports for communicating with other CCC controllers • Port 1: three-wire, EIA RS-485 • Port 2: five-wire, EIA RS-485 Two Modbus RTU or TCP ports (3 and 4) for communicating with support PCs or third-party supervisory systems: • RTU: five-wire serial ports are EIA RS-422/485 compatible • TCP: RJ45 ethernet ports are IEEE 802.3 10/100Base-T compatible (see the Series 3++ Modbus TCP Ethernet Options data sheet [DS3300/N])
Table 1 Baud Rate Parity Start/Data/Stop Bits Cable Length Transceivers (1) 1 Up
Serial Communication Formats Port 1 38400 Even 1/8/2 One
Port 2 Ports 3 and 4 2400, 4800, 9600 4800, 9600, 19200 Even odd, even, none 1/8/2 1/8/1 up to 4000 feet (1200 meters) Two
to 32 transceivers can be connected to each RS-485 network
August 2007
Page 2 of 4
DS3300/C (1.1.0)
CH 1 + –
CH 2 + –
CH 3 + –
CH 4 + –
OUT 1 +
OUT 2 +
CH 1 + –
CH 2 + –
CH 3 + –
CH 4 + –
OUT 1 +
OUT 2 +
CH 5 + –
CH 6 + –
CH 7 + –
CH 8 + –
CR1 1 2
CR2 1 2
CH 5 + –
CH 6 + –
CH 7 + –
CH 8 + –
CR1 1 2
CR2 1 2
CR3 1 2
CR4 1 2
CR5 1 2
DISCRETE IN D1 D2 D D3 D4 D5
CR3 1 2
CR4 1 2
CR5 1 2
DISCRETE IN D1 D2 D D3 D4 D5
PORT 1 TX/RX 1 + –
PORT 2 TX2 RX2 + – 2 + –
NOT USED
PORT 1 TX/RX 1 + –
PORT 2 TX2 RX2 + – 2 + –
24VDC DISCRETE + – D6 D7
PORT 4 TX4 RX4 4 + – + – PORT 3
PORT 3 TX3 RX3 3 + – + –
24VDC DISCRETE + – D6 D7
96-264 VAC 21-32 VDC PORT 4
TB6 MADE IN USA
Figure 3
I/O Circuits Terminals Scan Time Static Protection Analog Input Channels
August 2007
96-264 VAC 21-32 VDC
N GRD H 35 W max
N GRD H 35 W max
MADE IN USA
Back Panel Terminal Blocks All wiring terminals are located on the Back Panel (see Figure 3). Removable back-panel compression terminals accept AWG 18 to AWG 14 (0.8 to 2.0 mm2) wire. Inputs are sampled every 5 milliseconds. Outputs are updated every 40 milliseconds. design protection to 4,000 volts, lab tested to 7,000 volts Eight 0.1% accuracy analog inputs, each switch-selected as: Extended I/O controller has eight and standard controller has four 0.1% accuracy analog inputs, each internally switch-selected as: • 20 mAdc (100 Ω impedance), 30 Vdc over-voltage protection; or • 5 Vdc (400 kΩ impedance), 300 Vdc over-voltage protection Floating-ground isolation to 270 Vdc (adjacent channels), 540 Vdc (lowest to highest channel). Each signal is tested against Namur NE 43 high failure (21 mA) and independently-configurable high and low alarm limits.
Page 3 of 4
DS3300/C (1.1.0)
Analog Outputs
Two isolated, internally-verified, factory-calibrated outputs. Each is independently switch-selectable for either: • 20 mAdc signals (0 to 750 Ω impedance) • 5 Vdc signals (2 kΩ minimum impedance)
Discrete Inputs
Seven 2.2 kΩ discrete inputs with common return • Energized state: +10 to +30 Vdc • De-energized state: 0 to +2 Vdc.
Discrete Output Control Relays
Five single-pole electromechanical relay circuits rated 1 A at 30 Vdc, each switch-selectable as normally-open or normally-closed: • CR1 is hard-wired to always indicate hardware faults. • CR2 can be switch-configured to also indicate faults.
August 2007
L Printed in U.S.A.
Page 4 of 4
DS3300/C (1.1.0)
COMPRESSOR CONTROLS CORPORATION 4725 121st Street, Des Moines, IA 50323, USA Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
Series 3++ Turbine Controllers Hardware Specificationssheet
DS3300/T
U
# Turbine Controllers Hardware Specifications This data sheet specifies the physical and operating characteristics of Series 3++ Controllers that do include the optional auxiliary PCB assembly (speed board).
2.96 75.2
2.68 68.1
1.0 26
6.00 153
19.04 484
5.50 140
dimensions in inches and millimeters
Figure 1
General Specifications Mounting Dimensions Weight Ambient Conditions
Ratings and Certifications Design Life Design MTBF Program Updating and Configuration
August 2007
Controller Dimensions This section lists various general characteristics of this device, whose dimensions are illustrated in Figure 1. Cutout Width: 2.70 in. (68.6 mm), +0.02 in. (0.5 mm)/–0.00 Cutout Height: 5.60 in. (142.2 mm), +0.03 in. (0.8 mm)/–0.00 Cabinet Depth: 22 in. (56 cm) from front of panel 5.5 lb (2.5 kg), not including FTAs Operating Temperature: -4 to 140°F (-20 to 60°C) Storage Temperature: -22 to +185°F (-30 to +85°C) Relative Humidity: 0 to 95% (if free from condensation) see: Agency Certifications for Series 3++ Controllers [TN41]
15 years (continuous operation) 45 years Front panel swings out to expose configuration and testing panel. Optional PC software can load, configure, and tune control program.
Page 1 of 8
DS3300/T (1.1.0)
AC Cable
Cable
Controller
– (Black) Ground (White)
Line (Black)
+ (Red)
Ground (Green)
DC Cable
Neutral (White)
Figure 2
Power Supplies
Cable
Controller
Power Cable Connector Configurations The internal power supply PCB mounts twin third-party 24 Vdc power modules that separately power the internal circuitry and external transmitters. AC conversion or DC regulation modules can be specified, either option requires a back panel with a matching power connector:
Input Voltage
21 to 32 Vdc or 96 to 264 Vac, 50 to 60 Hz
Output Power
24.0±1.2 Vdc, 6.0W maximum, isolated and regulated
Maximum Power Consumption
30W (includes 6W output power)
Power Cable
One 14 ft. (4.3 m) cable with AWG 18 (0.8 mm2) conductors is supplied per pair of controllers. Both ends are plug-compatible with the specified PSA. Custom length cables are available.
Power Failure Protection
Configuration data stored in non-volatile EEPROM Process data stored in RAM with a backup battery (minimum battery life is 1 year @ 70 °C).
Communication Ports
Two serial ports for communicating with other CCC controllers • Port 1: three-wire, EIA RS-485 • Port 2: five-wire, EIA RS-485 Two five-wire, RS-422/485 compatible Modbus RTU serial ports for communicating with support PCs or third-party distributed control and supervisory systems.
Table 1 Baud Rate Parity Start/Data/Stop Bits Cable Length Transceivers (1) 1 Up
Serial Communication Formats Port 1 38400 Even 1/8/2 One
Port 2 Ports 3 and 4 2400, 4800, 9600 4800, 9600, 19200 Even odd, even, none 1/8/2 1/8/1 up to 4000 feet (1200 meters) Two
to 32 transceivers can be connected to each RS-485 network
August 2007
Page 2 of 8
DS3300/T (1.1.0)
I/O Circuits
Terminals Static Protection Frequency Inputs
Extended I/O Turbine Controllers provide terminals for every input and output circuit on external Field Termination Assemblies (see page 5). Standard Turbine Controllers provide back-panel terminals (see Figure 3) for most but not all I/O circuits. Removable back-panel compression terminals accept AWG 18 to AWG 14 (0.8 to 2.0 mm2) wire. Design protection to 4,000 volts, lab tested to 7,000 volts. Extended I/O controller has six frequency inputs for 0-to-30 kHz magnetic pickup speed signals, standard controller has three: • minimum 1.5 V peak-to-peak signal for passive pickups • minimum 8.0 V peak-to-peak signal for active pickups • impedance: 100 kΩ nominal, 20 kΩ minimum @ 1 kHz
Analog Input Channels
Extended I/O controller has eight and standard controller has four 0.1% accuracy analog inputs, each internally switch-selected as: • 20 mAdc (100 Ω impedance), 30 Vdc over-voltage protection; or • 5 Vdc (400 kΩ impedance), 300 Vdc over-voltage protection Floating-ground isolation to 270 Vdc (adjacent channels), 540 Vdc (lowest to highest channel). Each signal is tested against Namur NE 43 high failure (21 mA) and independently-configurable high and low alarm limits.
Position Inputs
Extended I/O controller has one five-wire LVDT and one bipolar 20 mA, 250 Ω position input. Standard controller has neither.
Analog Outputs
OUT1: Current-loop driver that can be configured to generate any needed signal up to 200 mA OUT2 and OUT3: independently switch-selectable for either: • 20 mAdc signals (0 to 750 Ω impedance) • 5 Vdc signals (2 kΩ minimum impedance) All three circuits provide internal reliability tracking
Discrete Inputs
Extended I/O controller has sixteen inputs: DI 1 to 8 have individual grounds, DI 9 to 16 share a common return. Standard controller has nine such inputs, all of which share a common ground. • Energized state: +10 to +30 Vdc • De-energized state: 0 to +2 Vdc • Resistance: 2.2 kΩ Input functions are user-defined and can be redundant.
Discrete Output Control Relays
Extended I/O controllers have nine single-pole, electromechanical control relays, standard controllers have eight (all but CR8): • 1 to 8: switch-selectable as normally-open or normally-closed; rated 1A at 30 Vdc • 9: jumper-selectable as normally-open or normally-closed; rated 1A at 30 Vdc CR1 and CR9 are hard-wired to always indicate hardware faults. CR2 can be switch-configured to also indicate faults.
August 2007
Page 3 of 8
DS3300/T (1.1.0)
+
CH 1 –
CH 2
+
–
CH 3
+
CH 4
–
+
–
OUT 1
+
OUT 2 +
MADE IN USA
1 OUT 3 +
CR1 1 2
CR2 1 2
CR6 1 2
CR7 1 2
CR9 1 2
PORT 1 1 TX/RX + –
CR3 1 2
CR4 1 2
4
CR5 1 2
INPUTS (J1) 60
63
1
4
DISCRETE IN D1 D2 D D3 D4 D5
PORT 2 TX2 RX2 + – 2 + –
24VDC DISCRETE +
–
D6 D7
OUTPUTS (J2)
DISCRETE PORT 3 PORT 4 TX4 RX4 TX3 RX3 D8 D9 3 4 + – + – + – + – 60
FREQ1 + –
FREQ2 + –
FREQ3 + –
63
96-264 VAC 21-32 VDC 21-32 VDC
N
TB6
G
H
96-264 VAC
MADE IN USA
Figure 3
Figure 4
August 2007
N GRD H 35 W max
35 W max
Standard and Extended I/O Back Panels 3.25" (82 mm)
3.0" (76 mm)
DIN EN 50 035 (TS 32)
DIN EN 50 022 (TS 35)
FTA Mounting Options
Page 4 of 8
DS3300/T (1.1.0)
Field Termination Assemblies
Extended I/O controllers are supplied with two rail-mounted Field Termination Assemblies that connect to the controller using HighDensity Interconnect Cables (HDICs) with CPC-23/63 connectors: • The field input module (FIM) provides the analog, discrete, frequency, and position input terminals. • the field Output Module (FOM) provides the analog output, control relay, and serial communication port terminals.
Mounting Options
DIN EN 50 035 or EN 50 022 (see Figure 4)
Field Terminals
Compression terminals accepting AWG 18 (0.8 mm2) to AWG 12 (3.3 mm2) wire.
Jumper Blocks
Jumper blocks use soldered-in AWG 22 jumper wires.
Fuses Weight
Plug-in, 125 V microfuses (Littel Fuse PN 273-XXX or equiv.). Field Output Module: 2.0 lb (0.9 kg). Field Input Module: 2.5 lb (1.1 kg).
Cable Length
Standard HDICs are 10 ft. (3 m) long. Custom cables can be made in any length up to 100 ft. (30 m).
24 Vdc Power Options
The FIM’s analog and discrete input circuits can be powered from an internal bus that draws power either from the controller or an external source connected to terminals 1 and 2. If an external source is connected, remove the CD jumper from the 24 Vdc jumper block or the corresponding fuse: 24 VDC
24 VDC
(to I/O circuits)
(to I/O circuits)
A C E G
B D F H
A
C
E
G
A
C
E
G
B
D
F
H
B
D
F
H
1.0 Amp
1.0 Amp 1
(in controller)
2
1
2
(in controller)
The FOM’s control relay circuits can be powered from an internal bus that draws power from an external source connected to terminals 29 and 30: 24 VDC
24 VDC
(from controller)
(to I/O circuits)
26
27
28
29
30
The controller’s transmitter power output (terminals 26 and 27) does not have sufficient capacity to drive the relay circuits and should not be connected to these terminals.
August 2007
Page 5 of 8
DS3300/T (1.1.0)
Discrete Input Circuits
Each FIM discrete input circuit has a configuration block, 50 mA fuse, and two field wiring terminals (labelled as + and – on page 7): A B C DI
A
D
B
E
C
F
– +
24 Vdc 50 mA
D E F
Configuration block options are discussed in the FIM Discrete Input Circuits section in Chapter 3 of UM3300/H.
Analog Input Circuits
Each FIM analog input circuit has a configuration block, 50 mA fuse, and five field wiring terminals (labelled as B, C/E, D/F, H, and S on page 7): B
A C E G
B E
C 50 mA
24 Vdc
A
G
B D F H
C/E
CH F
D/F
D
H
H
S
Configuration block options are discussed in the FIM Analog Input Circuits section in Chapter 3 of UM3300/H.
Control Relay Circuits
Each FOM control relay circuit has a configuration block, 1.0 amp fuse, and two field wiring terminals (labelled as + and – on page 8): A C E G
B
A 1.0 A +
CR
B D F H
C
H
D
G
–
24 Vdc
Configuration block options are discussed in the FOM Control Relay Circuits section in Chapter 3 of UM3300/H. Terminal polarity markings must be observed only for circuits powered by the FOM.
Analog Output Circuits
Each FOM analog output circuit has dedicated positive, negative, and shield terminals: • OUT1 is a current-loop signal with a configurable range. • OUT2 and OUT3 have CPU PCB switches that select currentloop or voltage operation. If an output is set for 20 mA operation, its parallel redundant terminals can only be connected to a highimpedance voltmeter.
August 2007
Page 6 of 8
DS3300/T (1.1.0)
4.3" 10.9 cm
Terminal Blocks TB2 Discrete Input 7 + Discrete Input 7 – Discrete Input 8 + Discrete Input 8 – Discrete Input 9 + Discrete Input 9 – Discrete Input 10 + Discrete Input 10 – Discrete Input 11 + Discrete Input 11 – Discrete Input 12 + Discrete Input 12 – Discrete Input 13 + Discrete Input 13 – Unused
46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
Unused Unused Unused Do Not Use Do Not Use LVDT 1 Exc + LVDT 1 Exc – LVDT 1 Ret + Do Not Use LVDT 1 Ret – Frequency Input 5 – Frequency Input 5 + Frequency Input 4 – Frequency Input 6 + Frequency Input 4 +
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75
Input Channel 7 B Input Channel 7 C/E Input Channel 7 D/F Input Channel 7 H Shield Input Channel 8 B Input Channel 8 C/E Input Channel 8 D/F Input Channel 8 H Shield Auxiliary Input – Auxiliary Input + Shield LVDT 1 Common Earth Ground
91 92 93 94 95 96 97 98 99 100 101 102 103 104 105
Input Channel 4 B Input Channel 4 C/E Input Channel 4 D/F Input Channel 4 H Shield Input Channel 5 B Input Channel 5 C/E Input Channel 5 D/F Input Channel 5 H Shield Input Channel 6 B Input Channel 6 C/E Input Channel 6 D/F Input Channel 6 H Shield
TB1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
24 VDC In + 24 VDC In – Discrete Input 1 + Discrete Input 1 – Discrete Input 2 + Discrete Input 2 – Discrete Input 3 + Discrete Input 3 – Discrete Input 4 + Discrete Input 4 – Discrete Input 5 + Discrete Input 5 – Discrete Input 6 + Discrete Input 6 – Unused
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
Discrete Input 14 + Discrete Input 14 – Discrete Input 15 + Discrete Input 15 – Discrete Input 16 + Discrete Input 16 – Frequency Input 1 + Frequency Input 1 – Shield Frequency Input 2 + Frequency Input 2 – Shield Frequency Input 3 + Frequency Input 3 – Shield
TB4
50 mA
2 4 50 mA
6 8
10 12
9 11
TB3 50 mA
14 16
13 15 50 mA
1.0 Amp
24 Vdc Jumpers
1.0 Amp
The Shield terminals are tied to the Earth Ground terminal, which should be connected to an external earth ground. Frequency Input 6 – is on Field Output Module.
Analog Input Jumpers and Fuses 50 mA
2
1 50 mA
TB7
August 2007
5 7 50 mA
TB5
Figure 5
1 3
16.0" 40.7 cm
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
Discrete Input Jumpers and Fuses
TB6 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90
4
Input Channel 1 B Input Channel 1 C/E Input Channel 1 D/F Input Channel 1 H Shield Input Channel 2 B Input Channel 2 C/E Input Channel 2 D/F Input Channel 2 H Shield Input Channel 3 B Input Channel 3 C/E Input Channel 3 D/F Input Channel 3 H Shield
3 50 mA
6
5 50 mA
8
7
Field Input Module Dimensions and Terminals
Page 7 of 8
DS3300/T (1.1.0)
4.3" 10.9 cm
Terminal Blocks TB2 6 7 8 9 10
Port 4 Tx + Port 4 Tx – Port 4 Common Port 4 Rx + Port 4 Rx –
16 17 18 19 20
Do Not Use Do Not Use No connection Do Not Use Do Not Use
26 27 28 29 30
+ 24 VDC (Out) – 24 VDC (Out) Unused + 24 VDC (In) – 24 VDC (In)
TB1 1 2 3 4 5
Port 1 Tx/Rx + Port 1 Tx/Rx – Port 1 Common Unused Unused
11 12 13 14 15
Port 2 Tx + Port 2 Tx – Port 2 Common Port 2 Rx + Port 2 Rx –
21 22 23 24 25
Port 3 Tx + Port 3 Tx – Port 3 Common Port 3 Rx + Port 3 Rx –
TB4
TB3
TB6
TB5
Control Relay Jumpers and Fuses 1.0 Amp
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
Analog Output 2 + Analog Output 2 – Shield Analog Output 3 + Analog Output 3 – Shield Current Output 1 + Current Output 1 – Shield Analog Output 2+ Analog Output 2– Shield Analog Output 3 + Analog Output 3 – Shield
61 62 63 64 65 66 67 68 69 70 71 72 73 74 75
Control Relay 8 + Control Relay 8 – Control Relay 9 + Control Relay 9 – +15 VDC Ground – 15 VDC Frequency Input 6 – Spare – Shield Diagnostic Port + Diagnostic Port – Shield Earth Ground Earth Ground
Both sets of terminals for analog output 2 or 3 can be connected only if its PCB switch is set to V position. The Shield terminals are tied to the Earth Ground terminals, which should be connected to an external earth ground. The Ground terminals are tied to the controller digital ground.
August 2007
L Printed in U.S.A.
1 1.0 Amp
3
5
4 1.0 Amp
TB8 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
2 1.0 Amp
Commons for Ports 1 to 4 are isolated.
TB9
Figure 6
12.8" 32.5 cm
TB7
7
Control Relay 1 + Control Relay 1 – Control Relay 2 + Control Relay 2 – Control Relay 3 + Control Relay 3 – Control Relay 4 + Control Relay 4 – Control Relay 5 + Control Relay 5 – Control Relay 6 + Control Relay 6 – Control Relay 7 + Control Relay 7 – Unused
6 1.0 Amp
9
8
Field Output Module Dimensions and Terminals
Page 8 of 8
DS3300/T (1.1.0)
COMPRESSOR CONTROLS CORPORATION 4725 121st Street, Des Moines, IA 50323, USA Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
DS3300/P Series 3++ Controller Parts List
U Assembly
# Controller Spare Parts List Part Number
Assembly
Part Number
Complete Electronics Assembly (note 1): CPU/IO PCB and AC Power Supply . . . . 15-500000-002 CPU/IO PCB and DC Power Supply. . . . 15-500010-002
Engineering Panel: Assembly with Keypad . . . . . . . . . . . . . . .15-500400-001 Keypad only . . . . . . . . . . . . . . . . . . . . . . .50-002551-001
Auxiliary PCB (Speed Board): Assembly with Daughter Card . . . . . . . . 15-300600-C01
Field Termination Assemblies, Turbine (note 2): Field Input and Output Modules. . . . . . . .50-203130-148 Fuse, 50 mA . . . . . . . . . . . . . . . . . . . . . .20-401830-500 Fuse, 100 mA . . . . . . . . . . . . . . . . . . . . .20-401830-101 Fuse, 250 mA . . . . . . . . . . . . . . . . . . . . .20-401830-251 Fuse, 1.0 A . . . . . . . . . . . . . . . . . . . . . . .20-401830-102 Fuse, 5.0 A . . . . . . . . . . . . . . . . . . . . . . .20-401830-502 HDIC (note 3) . . . . . . . . . . . . . . . . . . . . .18-002830-210
Back Panel, Compressor Controller (note 2): AC, serial Modbus. . . . . . . . . . . . . . . . . . 15-300500-002 AC, wired ethernet . . . . . . . . . . . . . . . . . 15-300500-006 DC, serial Modbus . . . . . . . . . . . . . . . . . 15-300500-D02 DC, wired ethernet . . . . . . . . . . . . . . . . . 15-300500-D06 Back Panel, Turbine Controller (note 2): AC, Back-panel terminals . . . . . . . . . . . . AC, Back-panel terminals, plate mount. . AC, for FIM & FOM . . . . . . . . . . . . . . . . . DC, Back-panel terminals . . . . . . . . . . . . DC, for FIM & FOM . . . . . . . . . . . . . . . . .
15-300500-004 15-300500-005 15-300500-003 15-300510-004 15-300510-003
Back Panel Terminal Block (note 2): 6 terminals . . . . . . . . . . . . . . . . . . . . . . . 20-002568-F06 12 terminals . . . . . . . . . . . . . . . . . . . . . . 20-002568-F12 Case: Assembly with Slides and Clamps . . . . . 15-300300-001 Mounting Slide . . . . . . . . . . . . . . . . . . . . 50-002422-001 Slide Clamp . . . . . . . . . . . . . . . . . . . . . . 50-002420-001 CPU/IO PCB (note 1) . . . . . . . . . . . . . . . . . 18-211656-001
Front Panel Assembly (without overlay): with hinge. . . . . . . . . . . . . . . . . . . . . . . . .15-500200-003 hinge only . . . . . . . . . . . . . . . . . . . . . . . .50-002431-001 Front Panel Overlays: Antisurge Controller . . . . . . . . . . . . . . . . .50-001280-005 Performance Controller . . . . . . . . . . . . . .50-001290-005 Dual-Loop A/P Controller. . . . . . . . . . . . .50-001291-005 Speed Controller . . . . . . . . . . . . . . . . . . .50-001270-005 Extraction Controller . . . . . . . . . . . . . . . .50-001271-005 Power Cables (note 4): for AC Power Supply . . . . . . . . . . . . . . . .18-002542-120 for DC Power Supply . . . . . . . . . . . . . . . .18-002542-024 Power Supply Assembly: 21-to-32 Vdc . . . . . . . . . . . . . . . . . . . . . .18-211657-1DC 96-to-264 Vac. . . . . . . . . . . . . . . . . . . . . .18-211657-1AC
1. Series 3++ CPU/IO PCB includes all field I/O circuits but not the power supplies (unlike Series 3 Plus, the analog circuits are not on a separate PCB but the 24 Vdc power supplies or regulators are). 2. Detachable terminal blocks are included with complete controllers and all FTAs, but not with replacement back panels. 3. Standard high-density interconnect cable is 10 feet long with two right-angle connectors. Two are required for each turbine controller (one for FIM, one for FOM). Custom lengths will be quoted on request. 4. Standard power cables are 14 feet long with two back-panel connectors, which will yield one long or two short cables. Longer cables will be quoted on request.
August 2007
Page 1 of 2
DS3300/P (1.1.0)
Side Views of Series 3++ Controller Showing Locations of Major Assemblies
Case
Mounting Slide
Front Panel Assembly Engineering Panel Assembly
CPU/IO PCB Assembly
August 2007
L Printed in U.S.A.
Slide Adjuster
Back Panel Assembly Power Supply Assembly
Auxiliary PCB Assembly (optional)
Page 2
Auxiliary PCB Daughter Card
DS3300/P (1.1.0)
COMPRESSOR CONTROLS CORPORATION 4725 121st Street, Des Moines, IA 50323, USA Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
Series 3++ Modbus TCP Ethernet Optionsdata sheet
DS3300/N
U
# Modbus TCP Ethernet Options This data sheet specifies the built-in Modbus TCP/RTU converter options for Series 3++ Controllers. Connection and configuration instructions can be found in Chapter 4 of the Series 3++ Modbus Reference manual [UM3300/M] or Appendix B of the Series 3 OPC Server user manual [UM5503]. CH 1 + –
CH 2 + –
CH 3 + –
CH 4 + –
OUT 1 +
OUT 2 +
CH 5 + –
CH 6 + –
CH 7 + –
CH 8 + –
CR1 1 2
CR2 1 2
CR3 1 2
CR4 1 2
CR5 1 2
DISCRETE IN D1 D2 D D3 D4 D5
PORT 2 TX2 RX2 + – 2 + –
24VDC DISCRETE +
–
D6 D7
PORT 3
PORT 1 1 TX/RX – +
PORT 4
96-264 VAC 21-32 VDC
MADE IN USA
Figure 1
Overview
N GRD H 35 W max
Ethernet Back Panel Series 3++ Compressor Controllers can be purchased with two Digi Connect ME ethernet to serial port converters built into their back panels, which allow Modbus TCP clients (masters) to communicate directly with their Modbus RTU serial ports (3 and 4). No built-in option is currently available for Turbine Controllers, but they can be similarly connected using external converters that are available from numerous vendors. For example, the Digi One IA and IAP are Digi International’s rail-mounted equivalents to the Connect ME, and they also offer modules with multiple serial ports.
August 2007
Page 1 of 2
DS3300/N (1.0.0)
Modbus TCP
Each converter can service simultaneous requests from multiple clients, each communicating via either the transmission control or user datagram protocol (TCP or UDP). Such requests are queued for a configurable maximum time, after which they are flushed. Each converter’s Modbus node number is configurable, and the Modbus TCP exception responses (0A and 0B) can be disabled.
Bandwidth
The data transfer capacity of each converter is limited to that of the 19200 baud, odd-parity Modbus RTU controller port it connects to, (approximate maximum is 1700 data bytes per second).
IP Settings
Compatible with Internet Protocol versions IPv4 and IPv6. Default static IP addresses and subnet masks can be changed, or modules can be set to obtain them from a DHCP server.
Status LEDs
Configuration and Maintenance
Security Options
Lower, yellow LED lights when electrically connected. Upper, green LED flashes three times while converter is booting, then intermittently to indicate data communication. Each converter can be configured, monitored, and/or updated using a web browser or the Series 3 OPC Server program. Each converter has a recessed reset switch, and can also be rebooted via its configuration interface. Secure Sockets Layer/Transport layer Security (SSL/TLS) HTTP configuration interface can be disabled, or its default user name and password can be changed.
Regulatory Approvals
Ambient Conditions
August 2007
L Printed in U.S.A.
The following certifications have been obtained by the converter’s manufacturer (Digi International): • FCC Part 15 Class B, EN 55022 Class B • EN 61000-3-2 and EN 61000-3-3 • ICES-003 Class B, VCCI Class II, AS 3548 • FCC Part 15 Sub C Section 15.247 • IC RSS-210 Issue 5 Section 6.2.2(o) • EN 300 328, EN 301 489-17 • UL 60950-1, EN60950 (EU) • CSA C22.2, No. 60950 • EN 55024 Relative humidity: 5 to 90% (non-condensing) Temperature limits exceed those of Series 3++ Controllers
Page 2 of 2
DS3300/N (1.0.0)
COMPRESSOR CONTROLS CORPORATION 4725 121st Street, Des Moines, IA 50323, USA Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
DS3300/R
U
Series 3++ Redundant Control Selectordata sheet
# Redundant Control Selector This data sheet specifies the Redundant Control Selector for duplex Series 3++ Control Systems. For usage information, see Chapter 5 of the Series 3++ Hardware Reference manual [UM3300/H].
Overview and Operation
Each Redundant Control Selector (RCS) has two main components: • an operator panel that is usually mounted between the operator panels of a redundant pair of controllers, and • a switching unit that can be mounted in an inaccessible location. The switching unit includes a latched master relay that controls four 4PDT slave relays: • When de-energized, the slave relays connect their COMMON and RUN terminals, thus selecting the main controller. • When energized, they connect their COMMON and TRACKING terminals, thus selecting the backup controller. Both the operator panel and switching unit have LEDs that indicate which controller is currently selected and buttons for transferring control of the process to the other. In addition, the master relay is connected to the fault (and possibly other) relays of the main and backup controllers. If each of those circuits is set up to open when the corresponding controller should not be in control: • Either healthy controller can be manually selected by pressing one of the corresponding buttons. • If the main controller is selected and the backup is healthy, control is transferred to the backup if the main controller faults or the Switch to Backup (or Trip) button is pressed. • If the backup is selected and the main controller is healthy, control can be transferred to the main controller only by pressing the Switch to Main (or Reset) button. Note that control of the process can never be transferred to a failed controller and is never automatically transferred to the main controller, even if it is healthy and the backup is not. If power to the RCS failed, the slave relays would de-energize, thus selecting the main controller. However, the latched master would remember which controller had been selected and return control to it when power was restored.
July 2007
Page 1 of 4
DS3300/R (1.0.0)
REDUNDANT CONTROL 3.125 79.4
.63 16 +24V Trip Reset Backup Main Ground
SELECTOR 5.25 133.4
MAIN
6.0 152.4
Switch to Back-Up
1.25 31.8
BACK-UP Switch to Main
1.0 25.4 GREEN ACTIVE
2.00 50.8
1.0 25.4
2.96 75.2
Figure 1
RED TRACK
dimensions in inches and millimeters
1.3 33.0
Operator Panel Dimensions and Connector Pinouts
7.25 184
6.75 171
4.25 108
Figure 2 July 2007
2.8 71 8.75 222
dimensions in inches and millimeters
Switching Unit Dimensions Page 2 of 4
DS3300/R (1.0.0)
General Specifications
The dimensions of the operator panel and switching unit are shown in Figure 1 and Figure 2.
Switching Relays
Four 4PDT electro-mechanical slave relays controlled by a magnetically-latched master relay. Slave relay contacts are rated at: 3 A. @ 28 Vdc (resistive) or 3 A. @ 120 Vac
Discrete Outputs
Either the Main or the Backup discrete output is connected to the supplied power when the corresponding controller is selected.
Status LEDs
Main and Backup LEDs on operator panel and switching unit are green when corresponding controller is active, otherwise red. The switching unit also has five red LEDs, one for each slave relay and one that lights when the main controller faults.
Operator Panel Switches
Momentary-contact, push-button switches for selecting the main or backup controller are shrouded to prevent inadvertent operation.
Wiring Terminals Maximum Separation Weight
Removable compression terminals accept AWG 18 (1.0 mm) to AWG 14 (1.6 mm) wire. Cable connecting operator panel to switching unit can be up to 300 ft. (90 m) in length. Switching Unit: 2.75 lb (1.25 kg) Operator Panel: 0.25 lb (0.11 kg)
— (Black or Brown Ground (White) + (Red or Orange)
Cable Connector
Figure 3
Power Inputs Required Voltage
End-Panel Connector
Power Connector Pinouts The switching unit has connectors for two independent external power supplies and automatically powers its circuits from the source providing the highest voltage. 24 Vdc (± 10%)
Protective Features
Each power supply circuit includes a 2.0 A., slow-blow fuse and surge-suppression circuitry.
Pass-Through Power
Two pass-through power circuits are provided on terminal block TB5. Total pass-through load should not exceed 5 W.
Power Consumption Power Cable
July 2007
7 W, excluding pass-through loads One 14 ft. (4.3 m.) cable with AWG 18 (0.8 mm2) conductors is supplied per pair of controllers. Both ends are equipped with compatible connectors as shown in Figure 3. Custom length cables are available.
Page 3 of 4
DS3300/R (1.0.0)
Terminal Block TB6
Terminal Block TB5
Manual Selection Switches
Main LED Backup LED Fuses
Power Cord Connectors Terminal Block TB1 Terminal Block TB2
to Backup Fault Main Active DO
+ – + –
Figure 5
July 2007
L Printed in U.S.A.
TB6
isolated spares
1 2 3 4 5 6 7 8 9 10 11 12
Backup Active DO
+ – + –
1 2 3 4 5 6 7 8 9 10 11 12
to Main Fault
TB5
pass-through grounds isolated spares pass-through +24 Vdc
1 2 3 4 5 6 7 8 9 10 11 12
operator panel connections
+24V Trip Reset Backup Main Ground
Switching Unit Components
TB1 through TB4
Figure 4
Terminal Block TB3 Terminal Block TB4
D C B A D C B A D C B A
COMMON terminals (to field devices) TRACK terminals (to backup controller outputs) RUN terminals (to main controller outputs)
Switching Unit Terminal Blocks
Page 4 of 4
DS3300/R (1.0.0)
COMPRESSOR CONTROLS CORPORATION 4725 121st Street, Des Moines, IA 50323, USA Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
DS3301/V. Series 3++ Controller Hardware Revisionsdata sheet
U
# Controller Hardware Revisions
This data sheet describes the new and modified hardware changes documented by the corresponding release of the Series 3++ Hardware Reference manual [UM3300/H].
Manual Version 1.1.0
This release of the hardware reference manual incorporated the changes described below.
Modbus TCP Option
The optional Modbus TCP Back Panel for compressor controllers replaces the Port 3 and 4 terminal blocks of the Modbus RTU Back Panel with built-in ethernet-to-serial port converters (see page 23, page 67, page 98, and the Series 3++ Modbus TCP Ethernet Options data sheet [DS3300/N]).
Hardware Specifications
The communication port, analog input over-voltage, and maximum power consumption specifications were revised (see the Series 3++ Compressor Controllers Hardware Specifications sheet [DS3300/C] and the Series 3++ Turbine Controllers Hardware Specifications sheet [DS3300/T]).
August 2007
Page 1 of 2
DS3301/V (1.1.0)
August 2007
L Printed in U.S.A.
Page 2 of 2
DS3301/V (1.1.0)
COMPRESSOR CONTROLS CORPORATION 4725 121st Street, Des Moines, IA 50323, USA Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
TN41Agency Certifications for Series 3++ Controllerstechnical note
U
Agency Certifications for Series 3++ Controllers This document documents the current agency certifications for Controllers and related components, which have been determined to be compliant with the following safety, environmental, and EMC standards.
Technical Note
Electrical Safety
A/D
Note:
AM
TN41 (1.0)
Industrial Process Measurement and Control Compliant Standard
Certification Level
EN 61010-1 IEC 1010-1 (2005) (Low-Voltage Directive)
Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory use – General Requirements
Other agency certifications are in process and will be added to this publication when certificates are issued.
Environmental Industrial Process Measurement and Control Compliant Standard
Certification Level
IEC 60654-1 (2003) (IEC 654, Part 1)
Operating Conditions for Industrial Process Measurement and Control Equipment, Part 1: Temperature, Humidity, and Barometric Pressure
IEC 60654-2 (2001) (IEC 654, Part 2)
Operating Conditions for Industrial Process Measurement and Control Equipment, Part 2: Power
MIL-PRF-28800F (1996) (Class 3 and 4)
Equipment for use with Electrical and Electronic Equipment, General Specifications for Navy Ship Systems – Vibration
April 2007
Agency Certifications for Series 3++ Controllers
Electromagnetic Capability (EMC) European Union: 73/23/EEC Low Voltage Directive and 89/336/EEC Electromagnetic Compatibility Directive Compliant Standard
Certification Level
IEC 61326 A3:2003
Electrical Equipment For Measurement, Control, and Laboratory Use -- EMC Requirements.
BS EN 55011 A2:2002
(CISPR 11 (2004)) (FCC part 15 subpart B)
Industrial, scientific and medical (ISM) radio-frequency equipment emissions – Electromagnetic disturbance characteristics – Limits and methods of measurement
IEC 61000-4-2 (2001)
Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques Section 2: Electrostatic Discharge Immunity Tests
IEC 61000-4-3 (2002)
Electromagnetic Compatibility (EMC), Part 4-3: Testing and Measurement Techniques - Radiated, Radio-Frequency, Electromagnetic Field Immunity Test
IEC 61000-4-4 (2001)
Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques Section 4: Electrical Fast Transient/Burst Immunity Test
IEC 61000-4-5 (2005)
Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques Section 5: Surge Immunity Test
IEC 61000-4-6 (2004)
Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques Section 6: Immunity to conducted disturbances, induced by radio-frequency fields
IEC 61000-4-8 (2004)
Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques Section 8: Power frequency magnetic field immunity test
IEC 61000-4-11 (2004)
Electromagnetic Compatibility (EMC), Part 4: Testing and Measurement Techniques Section 11: Voltage dips, short interruptions, and voltage variations immunity tests
The TTC and impeller logos, Air Miser, Guardian, Recycle Trip, Reliant, Safety On, SureLink, TTC, Total Train Control, TrainTools, TrainView, TrainWare, Vanguard, Vantage, and WOIS are registered trademarks; and the Series 3++ and Series 5 logos, COMMAND, and TrainPanel are trademarks of Compressor Controls Corp. © 2007
Page 2 TN41 (1.0) April 2007
COMPRESSOR CONTROLS CORPORATION 4725 121st Street, Des Moines, Iowa 50323-2316, U.S.A. Phone: (515) 270-0857 • Fax: (515) 270-1331 • Web: www.cccglobal.com
FM73
U
Documentation Feedback Form Publication Title: Series 3++ Hardware Reference Manual Publication No.: UM3300/H (1.1.0) Publication Date: August 2007
If you have questions or comments concerning the information provided in this user manual or in any of our technical documents please contact CCC’s Technical Documentation Department: E-mail:
[email protected] Which Series of Controllers do you have, and are you using our TrainTools software? Series 3+/3++
Series 4
Series 5
TrainTools
Guardian
Vantage
Air Miser
❒
❒
❒
❒
❒
❒
❒
Some additional information we would like to know:
Printed Online ❒
❒
Yes
No
2. Did you find what you were looking for?
❒
❒
3. Do you require system installation information?
❒
❒
4. Do you require system maintenance information?
❒
❒
5. Do you require system configuration information?
❒
❒
6. Do you require system operation information?
❒
❒
1. How do you prefer to access our documentation?
Please provide the following information if you wish to be contacted: Company: Name: Email: You may also fax your questions or comments to: Fax: (515) 334-2500 ATTN: Manager, Technical Documentation Comments:
May 2006
FM73 (3.0)
a
NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES
BUSINESS REPLY MAIL FIRST CLASS MAIL PERMIT NO. 7515 DES MOINES, IOWA POSTAGE WILL BE PAID BY ADDRESSEE
COMPRESSOR CONTROLS CORPORATION
Technical Documentation Department 4725 121st Street Des Moines, Iowa 50323-9906
Fold Along Dotted Line
Please Fasten Here With Tape — Do Not Staple