Method for bored pile capacity calculationFull description
Full description
Pile capacity caculation as per iRC78
pipe thickness
pipe wall thickness calculationFull description
calculation for wallFull description
formwork
Descripción: c
Full description
Wall thickness calculation based on ASME B31 Code.Description complète
Wall thickness calculation based on ASME B31 Code.
To design a water treatment plant first and foremost thing is calculation/estimation of plant capacity in which plant has to run up to design period without trouble.
To design a water treatment plant first and foremost thing is calculation/estimation of plant capacity in which plant has to run up to design period without trouble.Description complète
Design Calculation of Boundary wall
You simply have to enter details in the red column and get the optimized answer in the relevant tabs.Full description
Oliver
Descripción completa
DOC. NO.
63-INQ09-036-DC-03
DESIGN SHEET 2
SHEET NO.
. T0802
CONTAINMENT CAPACITY WITHIN BUNDWALL COMPOUND CHECK TANK FARM FOR A
T-1414 ~ 1421
NET CAPACITY WITHIN BUNDWALL i) GROSS CONTAINMENT CAPACITY LENGTH OF NEW BUNDWALL (INSIDE DIMENSION) WIDTH OF NEW & EXT'G BUNDWALL (INSIDE DIMENSION) INTERNAL HEIGHT OF EXT'G BUNDWALL NEW CONTAINMENT CAPACITY
Lb1 = W1 = Hb1=
Vg1 = Hb1 * W1 * Lb1 =
LENGTH OF EXT'G BUNDWALL (INSIDE DIMENSION) WIDTH OF NEW & EXT'G BUNDWALL (INSIDE DIMENSION) INTERNAL HEIGHT OF NEW BUNDWALL
Lb2 = W2 = Hb2 =
21.00 m 29.50 m 1.40 m 867.30 m3 42.00 m 29.50 m 1.40 m
Vg2 = Hb2 * W2 * Lb2 =
1,735 m3
Vg =Vg1 + Vg2=
2,602 m3
(T-1420 & T-1421) Dt= Ht1 = Hb1 - Hf = Vt1 =
13.8 m 1.10 m 164.53 m3
EXT'G CONTAINMENT CAPACITY GROSS CONTAINMENT CAPACITY ii) TANK DISPLACEMENTS NEW TANK DIAMETER (OUTSIDE) NEW TANK DISPLACED HEIGHT CAPACITY DISPLACED BY NEW TANK
EXT'G TANK DIAMETER (OUTSIDE) (T-1414 & T-1418) Dt = EXT'G TANK DISPLACED HEIGHT Ht1 = Hb2 - Hf = CAPACITY DISPLACED BY EACH EXT'G TANK Vt2 =
5.7 m 1.10 m 28.07 m3/TANK
EXT'G TANK DIAMETER (OUTSIDE) (T-1415 & T-1416) Dt = EXT'G TANK DISPLACED HEIGHT Ht1 = Hb2 - Hf = CAPACITY DISPLACED BY EACH EXT'G TANK Vt3 =
9.6 m 1.10 m 79.62 m3/TANK
EXT'G TANK DIAMETER (OUTSIDE) (T-1419) EXT'G TANK DISPLACED HEIGHT CAPACITY DISPLACED BY EACH EXT'G TANK
Dt = Ht1 = Hb2 - Hf = Vt4 =
7.555 m 1.10 m 49.31 m3
EXT'G TANK DIAMETER (OUTSIDE) (T-1417) EXT'G TANK DISPLACED HEIGHT CAPACITY DISPLACED BY EACH EXT'G TANK
Dt = Ht1 = Hb2 - Hf = Vt5 =
3.9 m 1.10 m 13.14 m3
Vt = Vt2 + Vt3 +Vt4 + Vt5 =
442 m3
ASSUME ONE NO. OF LARGEST DIA. TANK FAIL, GROSS CAPACITY DISPLACED BY TANK
DOC. NO.
63-INQ09-036-DC-03
DESIGN SHEET 3
SHEET NO.
. T0802
iii) FOUNDATION DISPLACEMENTS ASSUME ALL TANK FOUNDATION HEIGHT Hf = 0.3 m BY ASSUMING ALL TANK FOUNDATION OFFECT 500 MM FROM TANK OUTSIDE DIA. CAPACITY DISPLACED BY NEW TANK (T-1420 & T-1421) Vf1 = 51.61 m3 CAPACITY DISPLACED BY EXT'G TANK (T-1414 & T-1418) Vf2 = 10.58 m3/TANK CAPACITY DISPLACED BY EXT'G TANK (T-1415 & T-1416) Vf3 = 26.47 m3/TANK CAPACITY DISPLACED BY EXT'G TANK (T-1419) Vf4 = 17.24 m3 CAPACITY DISPLACED BY EXT'G TANK (T-1417) Vf5 = 5.66 m3 GROSS CAPACITY DISPLACED BY FOUNDATION Vf = Vf1+ Vf2+ Vf3+Vf4+Vf5= Vp =
50 m3
Vd = Vt+ Vf + Vp =
693 m3
Vn = Vg - Vd =
1,909 m3
Vtank =
1,944 m3
Vfire =
150 m3
ASSUME GROSS CAPACITY OF DISPLACED BY PUMP, PIPERACK STUMP, PIPING & OTHER ACCESSORIES APPROX. iv) TOTAL DISPLACED CAPACITY NET CAPACITY WITHIN BUNDWALL B
200 m3
NET CAPACITY DURING ONE TANK FAILURE THE LARGEST TANK CAPACITY D= H=
13.8 m 13 m
FIRE WATER CAPACITY DURING ONE TANK ON FIRE (APPROXIMATE CAPACITY DURING 30 MIN. FIRE) NET CAPACITY DURING ONE TANK FAILURE
Vmax = Vtank + Vfire =
C
CONTAINMENT CAPACITY CHECK Vn ---------Vmax SINCE 1.4
=
1,909 ---------2,094
=
0.91 < 1, NO GOOD
Vn < Vmax NO GOOD m NEW BUND WALL HEIGHT IS NOT SUFFICIENT