BMS Design
CONTENTS Preface
The The pur purpose ose of th this doc docum ument ent is to to help help th the user users s to und under erst stan and d how how the the ins insttrument entatio ation n of air air-c -con ond ditio ition ning ing system works. There are various types of instrumentation systems such as electric, electronic and direct digital control (DDC) systems, which can be used to control the air handling unit (AHU). This document includes a number of examples with the emphasis placed on electronic and electrical instrumentation. The Appropriate method must be selected after studying the various conditions such as how the system will be used, likely operating conditions, degree of control accuracy required, consistency of all facilities, etc. Contact the Yamatake representatives for further information on actual instrumentation and design.
Part Pa rt I
1. Building Management System 1.1 What is buildin building g managem anagement ent system system? ? ..................... ........... ...................... ....................... ..................... ...................... ...................... ........................ ..................... ....... 1 1.2 The Advant Advantag ages es of Building Building Managem Management System ...................... .......... ....................... ....................... ....................... ....................... ........................ ............ 4
2. Fundamentals of Automatic Control 2.1 2.2 2.3 2.4 2.5 2.6
Gene G eneral ral of Autom Automat atic ic Control Control ...................... ........... ..................... ..................... ...................... ...................... ...................... ..................... ........................ ........................ ............ .. 5 Automat Automatic ic Control Control Method Methodolog ology y ...................... ........... ...................... ...................... ...................... ...................... ....................... ...................... ......................... .................... ..... 7 Applicat Application ion fo Autom Automat atic ic Control Control device device ..................... ........... ..................... ...................... ..................... ..................... ...................... ....................... ..................... ......... 9 BMS & Autom Automat atic ic contr control ol design design genera generall ....................... ........... ....................... ...................... ....................... ....................... ....................... ........................ .............. ..11 Autom Automati atic c Control Control System Design Design Proc P rocedu edure re ..................... .......... ....................... ....................... ....................... ....................... ...................... ..................... .......... 15 Autom Automat atic ic Control Control System System Retrofit Retrofit P lanning lanning P rocedu rocedure re ....................... .......... ........................ ....................... ......................... ........................ ............. ..17
3. Automatic Control Devices 3.1 3.2 3.3 3.4
E lectric lectric Control Control Devices Devices ...................... ........... ...................... ...................... ..................... ...................... ...................... ..................... ........................ ........................ .................... ......... 19 E lectron lectronic ic Control Control Devices Devices ...................... ........... ..................... ...................... ...................... ..................... ....................... ...................... ...................... ....................... ................. ...... 19 DDC (Direct (Direct Digital Digital Control) Control) ....................... ........... ....................... ...................... ...................... ....................... ....................... ....................... ........................ ....................... ........... 21 Int I ntellig elligent ent Componen Componentt ..................... .......... ...................... ...................... ...................... ...................... ...................... ....................... ...................... ....................... ....................... ............ ..24
4. HVAC System generals 4.1 AHU System Systems .................... .......... ...................... ...................... ..................... ...................... ..................... ..................... ...................... ..................... ....................... ........................ ................. ...... 25 4.2 Chiller C hiller P lant Systems ....................... ............ ...................... ....................... ....................... ....................... ....................... ....................... ........................ ....................... .................... ......... 26
5. Control Funct F unctions ions 5.1 HVAC Autom Automatic atic Control Control details details ....................... ............ ...................... ....................... ...................... ...................... ....................... ...................... ....................... .................. ...... 27 5.2 E nergy nergy saving saving applicat application ion ....................... ........... ...................... ..................... ...................... ...................... ...................... ...................... ....................... ....................... ................. ...... 30
6. Typical Instrumentation Examples 6.1 Examples of Automatic Control System Instrumentation entation ......... ............. ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ...... .. 35
Part II
Guide Specification for HVAC
CONTENTS Preface
The The pur purpose ose of th this doc docum ument ent is to to help help th the user users s to und under erst stan and d how how the the ins insttrument entatio ation n of air air-c -con ond ditio ition ning ing system works. There are various types of instrumentation systems such as electric, electronic and direct digital control (DDC) systems, which can be used to control the air handling unit (AHU). This document includes a number of examples with the emphasis placed on electronic and electrical instrumentation. The Appropriate method must be selected after studying the various conditions such as how the system will be used, likely operating conditions, degree of control accuracy required, consistency of all facilities, etc. Contact the Yamatake representatives for further information on actual instrumentation and design.
Part Pa rt I
1. Building Management System 1.1 What is buildin building g managem anagement ent system system? ? ..................... ........... ...................... ....................... ..................... ...................... ...................... ........................ ..................... ....... 1 1.2 The Advant Advantag ages es of Building Building Managem Management System ...................... .......... ....................... ....................... ....................... ....................... ........................ ............ 4
2. Fundamentals of Automatic Control 2.1 2.2 2.3 2.4 2.5 2.6
Gene G eneral ral of Autom Automat atic ic Control Control ...................... ........... ..................... ..................... ...................... ...................... ...................... ..................... ........................ ........................ ............ .. 5 Automat Automatic ic Control Control Method Methodolog ology y ...................... ........... ...................... ...................... ...................... ...................... ....................... ...................... ......................... .................... ..... 7 Applicat Application ion fo Autom Automat atic ic Control Control device device ..................... ........... ..................... ...................... ..................... ..................... ...................... ....................... ..................... ......... 9 BMS & Autom Automat atic ic contr control ol design design genera generall ....................... ........... ....................... ...................... ....................... ....................... ....................... ........................ .............. ..11 Autom Automati atic c Control Control System Design Design Proc P rocedu edure re ..................... .......... ....................... ....................... ....................... ....................... ...................... ..................... .......... 15 Autom Automat atic ic Control Control System System Retrofit Retrofit P lanning lanning P rocedu rocedure re ....................... .......... ........................ ....................... ......................... ........................ ............. ..17
3. Automatic Control Devices 3.1 3.2 3.3 3.4
E lectric lectric Control Control Devices Devices ...................... ........... ...................... ...................... ..................... ...................... ...................... ..................... ........................ ........................ .................... ......... 19 E lectron lectronic ic Control Control Devices Devices ...................... ........... ..................... ...................... ...................... ..................... ....................... ...................... ...................... ....................... ................. ...... 19 DDC (Direct (Direct Digital Digital Control) Control) ....................... ........... ....................... ...................... ...................... ....................... ....................... ....................... ........................ ....................... ........... 21 Int I ntellig elligent ent Componen Componentt ..................... .......... ...................... ...................... ...................... ...................... ...................... ....................... ...................... ....................... ....................... ............ ..24
4. HVAC System generals 4.1 AHU System Systems .................... .......... ...................... ...................... ..................... ...................... ..................... ..................... ...................... ..................... ....................... ........................ ................. ...... 25 4.2 Chiller C hiller P lant Systems ....................... ............ ...................... ....................... ....................... ....................... ....................... ....................... ........................ ....................... .................... ......... 26
5. Control Funct F unctions ions 5.1 HVAC Autom Automatic atic Control Control details details ....................... ............ ...................... ....................... ...................... ...................... ....................... ...................... ....................... .................. ...... 27 5.2 E nergy nergy saving saving applicat application ion ....................... ........... ...................... ..................... ...................... ...................... ...................... ...................... ....................... ....................... ................. ...... 30
6. Typical Instrumentation Examples 6.1 Examples of Automatic Control System Instrumentation entation ......... ............. ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ ...... .. 35
Part II
Guide Specification for HVAC
1 Buildi Bui lding ng Manage Management ment System
1 Building Au to mat ion io n
1.1 What is Bui ldi ng Management Management System? Building Management System (BMS) is comprehensive comprehensive system for controlling and managing various facilities in a building. Central monitoring system monitors the operating status and errors of building facilities such as air handling, chiller plant, utilities and power facilities. With the advent of computer technology and improvement in digital communication technology, the automatic control equipment of air handling can now be integrated with centralized equipment resulting in centralized monitoring and control of all the facilities in a building. Centralized equipment is now called an Integrated BA System, which monitors an expanding number of facilities, from lighting, elevator facilities, fire control facilities, and security facilities such as access control or intrusion monitoring from user terminals. It has also expanded into a system called a Intelligent Building Management System which controls information on the entire building and its facilities and ensures their effective operation. A BMS can be classified into the following four categories.
agreed with utility companies will not be exceeded. The The syst system em can can be upgrad raded to the BMS, in which the information managed by the BMS can be displayed on user's user's P C monitors and users can operate each facility. (3) Security/fire control system
The The sec secu urit rity syst system em cont contro rols ls acce access ss to to build uildin ing gs or individual rooms using a mechanized system, features intrusion monitoring to detect intruders in buildings, and issues alarms and video monitoring. There are two types of access control system: using a key management box, and using a card reader. These systems assure not only the safety of buildings but allow users 24-hour access. The The fire ire con control syst system em for detec etectting ing fire ire in buildings and for preventing the spread of fire can display alarms or stop AHU by establishing a receiver specified by laws and by incorporating the signals into the integrated BA system. (4) Intellig Intellig ent Build ing Management Management System
(1) (1) Automatic control system
The The aut automatic atic con control syst system em prov rovides ides continuous, sequential and energy-saving control of process values (physical values) related to air handling, chiller plant and Utilities, etc. In air handling systems, control of temperature or humidity in air handling units (AHU) which carry out cooling/heating or ventilation is included. In chiller plant facilities, a number of operating unit controls and pressure controls for heat pump chillers, refrigerators and pumps are included. In Utilities, control of water tank level and pumps operation which supply clean water in buildings or waste water treatment are included in the automatic automatic control system s ystem..
The The Int Intelli ellig gent ent build ilding ing manag anagem ement ent syst system em collects, stores and processes information on a variety of facilities in buildings and operating data to help building managers with maintenance control work, maintenance work, tenant billing and energy management and helps building owners with maintenance cost management. For example, software is included that supports equipment ledger management, performance management, maintenance schedule management, metering and billing. Vertical integration of functions ⋅ Vertical decentralization of systems ⋅
1
Building Management System
Monitoring / operation
Central control
(2) Building Management Management System
The The Buil Build ding ing Mana Manag gement ent Syst System em monit onitor ors s the the operating status and identifies any malfunctions of the equipment in building at the fundamental level. It carries out display of functions, keeps a log and operates the system. It also controls system-wide facilities such as power or air handling systems. For example, it features scheduled operating controls to operate equipment according to a set schedule, and power demand control to operate each facility and all equipment so that the power demand
Information management
IBMS
Automatic control system Local control
l a n r i o ) t m r a e C v t P e r ( l e E s U
g n i t h g i L
⋅ ⋅
Figure 1
r e w o P
g n i l d n a h r i A
t n a l p r e l l i h C
g n i b m u l P
l o r t n o c s s e c c A
g n i r o t i n o m n o i s u r t n I
m r a l a e r i f c i t a m o t u A
l o r t n o c e k o m S
Horizontal integration of target facilities Horizontal decentralization of system
Conceptual rendering of Intelligent Building Management System
1 Building Management System
Intelligent Building Facility Reservation
Lift/Escalator System
Fire Alarm
IBMS Server
Ethernet Integration Data Server
BEMS Building Energy Management System
BACnet IP
Energy Data Server
System Management Serve
Client PC
System Core Server
LonTalk
Infilex ZM
Paramatrix Chiller Plant Controlle
SAnet
Infilex AC
Infilex GD
Infilex VC Infilex FC ACTIVAL
ACTIVAL PLUS
VAV BOX
ACTIVAL MINI Neoplate
Neopanel
Intelligent Component Series
Building Management Figure 2
Sample automatic control system of air-conditioning and Sanitary facilities
2
1 Building Management System
IBMS Management System Help Desk
Facility Management
Asset Management
Multimedia Public Display
Security Security System OPC Data Storage Serve
Security Data Server
Server
BACnet IP Access Core Controller
Wiegand 3rd Party
Electric Lock
LonTalk Infilex GC
IR Passive Sensor
Devices
CCTV
Proximity Card Reader
Lighting System ACTIVAL
CO2 Concentration Transmitter Pipe Insertion Temperature Sensors
Room Temperature Humidity Sensor Duct Insertion Temperature Humidity Sensors
Operator Panel
BMS
Modbus
Devices
Interface PLC Power meter
System Figure 3
3
BACnet
Sample integrated BA syst em
1 Building Management System
1.2 The Adv antages of Bui ldi ng Management System The advantages of introducing a Building Management System to users of buildings include the provision of a comfortable, safe and convenient environment. The advantages to owners and managers include reduction of operating costs by means of energy conservation and labor-saving over the entire building as well as better maintenance, leading to improvement of the value of property. The BMS clearly affords a variety of
(1) Labor-savin g, efficient management
Since integration allows comprehensive control of large amounts of data, operation of building and facilities can be carried out by a smaller number of people. More sophisticated management can be realized through effective use of the information.
(2) Maintenance and opti mization of environment
Maintains optimum thermal environment condition, such as temperature and humidity including CO2 and dust requirements, as well as lighting levels for individual users or production facilities.
benefits. In particular, the automatic air-conditioning control system allows the creation of the most comfortable environment for users, prevents wastage of energy by optimum control and continuously maintains these advantages. Introducing BMS. The detailed benefits of introduction are as follows:
(4) Ensur es a variety of safety features
By concentrating all information about building facilities into the central unit, you can easily identify the status of facilities, operate the facilities and take correct countermeasures in the event of power failure or outbreak of fire. By integration with the security system, you can assure the safety of building users and confidential information with no loss of convenience. (5) Improve convenience for building users
By integrating each facility, services and convenience to individual users can be improved. For example, 24-hour free safe access to buildings, simple and user-friendly setting and adjustment of temperature or operating time and identification of outdoor air temperature, weather status and building management information. The following pages illustrate a sample automatic control system for air-conditioning and utilities, and a sample integrated BA system.
(3) Resource/energy savin g
Utilizing natural energy effectively and limiting unnecessary use of resources or energy, using the methods like controlling and maintaining a desired temperature setting accurately, or by employing only outdoor air necessary to carry out control in response to the load placed in the building.
4
2 Fundamentals of Automatic Control This section describes the mechanism of automatic control, important factors in air handling control including temperature, humidity, pressure, flow rate, response, methods and how to read the implementation diagrams as well as notes for designing automatic control systems.
2.1
Please note that to make the descriptions in this document simpler and easier to understand, some non-technical expressions may be used in the sections describing the theory of automatic control.
General of Automatic Control
Figure 4 shows an example of manual adjustment and Figure 5 shows an example of automatic control. As you can see in Figure 5, an automatic control system consists of a sensing element, a controller and a final control element. The sensing element is an alternative to human vision, the controller which makes comparisons and judgments is an alternative to the brain and the final control element is a substitute for the hands and feet. Automatic control systems always compare the actual temperature with the desired temperature and work to eliminate the difference between them. To a control system, changes in outdoor air load such as outdoor air temperature or solar radiation and changes in room load such as number of occupants are added as disturbance. If there is no change in internal or external conditions, once a valve (final control element) is set to the optimum position, the temperature is held constant. However, loads fluctuate with changing external and internal conditions, making automatic control necessary. As the figure on the right shows, when there are
changes in setting e r temperature or u t a Necessary changes r changes of e of temperature p m disturbance, a e T delay occurs in the system until control action is (appearance) (appearance) Dead time Time constant taken and the Dead tim e & Time constant actual room temperature starts changing. This is called dead time. The time taken from start of changes in room temperature to re-establishment of set temperature is called the time constant. The quality required for automatic control in such systems is quick response and stability. Quick response means to achieve the target value as soon as possible. Stability means to keep the system which achieved the target constant. To design automatic control, function and quality must be determined in line with the characteristics of the applicable control and budget.
Room temperature 20°C
Steam
a)Manual adjustment of room temperature
Desired value 25°C
20°C In manual adjustment you look at the current room temperature, compare it with the desired value, decide whether to open or close the valve and manually set the valve to change the flow rate of steam. As the result, the supply air temperature and room temperature change and you visually confirm the result. b) Flow (temperatures in the diagram are examples)
Figure 4
Temperature controller
Manual adjustm ent Outdoor air temperature Infiltration, solar radiation Change in number of occupants
Thermostat Control differential
Motorized valve
Steam
+Comparison
Set point (Temperature setting)
a)Automatic control of room temperature
25°C
Amount of control (room temperature) Issues signals to controller to reduce control differential.
Motorized valve
AHU
(Room)
20°C
Starts operation at the signal from the controller and changes the temperature of the control target
Detects room temperature 20°C b) Flow (temperatures in the diagram are examples)
Figure 5
5
Automatic control
2 Fundamentals of Automatic Control
2.2
Automatic Control Methodol ogy
There are various methods for operating the controller of automatic control equipment. These are selected and adopted according to the
Control
characteristics of the control target, the required degree of control accuracy and the budget available. This section describes a typical control response used in automatic control of air-conditioning.
Two-position (ON/OFF) control
Item
Proportional (P) Control Setting dial
Setting dial
Mechanism (electric control device)
Diaphragm
Diaphragm Increase in temperature
Increase in temperature
Snap switch
Differential
Potentiometer
Proportional band
・ The position of the target value
varies depending on the controller
Action diagram (heating)
n o i t i s o P
n o i t i s o P
Fully closed (Temperature) Amount of control
(Temperature) Amount of control Target value
Target value
Amount of control
Response (response when the system is loaded in progressive stages.)
・ The position of the target value
varies depending on the controller
Fully open
Amount of control
e u l a v t e g r a T
l a i t n e r e f f i D
m o o e r r u n t i a n r o e i t p a m u t t e c u l F
e u l a v t e g r a T Offset Time
Time
m e t s y s l o r t n o c d e d n e m m o c e R
t n e m e l e l o r t n o C e c n a b r u t s i D
Dead time
Short
Short to medium
Time constant
Medium to long
Medium to long
Size
Small
Small to medium
Speed
Low
Low to medium
Features
Applications
・Select either of the two fixed amounts control signal. ・ The setting is just a target value. It does not achieve the exact set point. ・If the differential is too large, the fluctuation increases; if it is too small, it turns on and off repeatedly, an effect called 'hunting.' ・Relatively small and stable system. ・Room temperature control, where it is OK if the temperature varies around the target value (differential).
d n a b l a n o i t r o p o r P
・ The amount of operation is proportional to the current value of the action signal. ・ The setting is just a target value. An offset (remaining differential) remains, since no action is made to achieve the exact set point. ・If the proportional band is wide, the offset is large; if it is too small, hunting occurs. ・Control target with minimum disturbance and lag. ・Room temperature control, where a high degree of accuracy is not required.
Figure 6.1 Actio n of automati c cont rol (1)
6
2 Fundamentals of Automatic Control
Control
Floating Control
Item
Proportional +Integral (PI) Control
Increase in amount of operation
Action diagram (heating)
m g a r h p a i D
Off
Decrease in amount of operation (Temperature) amount of control
n o i t a r e p o f o t n u o m A
(Temperature) Amount of control
Dead band Set point
Target value
Proportional band
d n a b d a e D
t n Dead e m time e l e l o r t Time n o constant C e c n a b r u t s i D
(Temperature) Amount of control Set point
d n a b l a n o i t r o p o r P
t n i o p t e S
Time
Time
Short
Short to medium
Short to long
Short
Short to long
Short to long
Size
Small to large
Small to large
Small to large
Speed
Low
Low to medium
Low to high
Features
Applications
Proportional band
Amount of control
d n a b l a n o i t r o p o r P
t n i o p t e S
Time
m e t s y s l o r t n o c d e d n e m m o c e R
n o i t a r e p o f o t n u o m A
Amount of control
Amount of control
Response (response when n o disturbance is added in i t i the systems loaded in s o P progressive stages.)
Proportional +Integral + Derivative (PID)Control
・When an action signal exceeds a ・Adds the integral action to the ・Adds a derivative function to the certain range(dead band),it proportional action to eliminate offset PI control. Provides a faster increases/decreases the amount of and keeps the control target at or response. operation at a certain speed. very near the set point ・ The setting is just a target value. It does not achieve the exact set point.
・System with minimum lag and time ・Systems with large disturbance constant ; disturbance can be large. ・Room temperature control or pressure control where supply air ・ Tank level control, etc. temperature control or high degree of accuracy is required.
・System where there are significant load changes and a high degree of accuracy is required. ・Special constant temperature and constant humidity control, pressure control, etc.
Notes:P: Proportional I : Integral D: Derivative
Figure 6.2 Acti on of Autom atic Contro l (2)
7
2 Fundamentals of Automatic Control
2.3
Applic ation for Automatic Control Device
According to its principle and structure, the automatic control equipment for air handling is classified as follows: (See Figure 7 on the next page). Electric Electronic Pneumatic Electro-pneumatic Direct Digital Cont rol (DDC)
These methods are chosen for their specific characteristics (Figure 7, next page). With the recent digitalization of products, it is getting more difficult to categorize these methods simply according to their operating principle and structure. Please note that in this document some devices are regarded as electronic due to how they are applied, even if they use built-in digital circuits. The structure, operating principle and type of each device is explained in Section 3.
In J apan, compared with America and Europe, pneumatic/electro-pneumatic methods using pneumatic pressure as the input signal are found in only a few applications, such as chiller plant control or explosion-proof systems, where large valves are used, or hospitals, where many valves are used. In electric control devices, mechanical elements such as diaphragms or nylon tapes are used and sensing elements and a controller are included in a single unit. These devices are commonly used as they are convenient to handle and feature low cost. However, it is expected that these devices will be replaced by electronic digitized products with a similar appearance. Microprocessors are increasingly being mounted on electronic devices, but DDC is becoming even more widespread. Further details on DDC are given in Section 3.3. Here, DDC is categorized as a product that obtains various function and benefits by communicating with main building management system. In this regard, it is different from electronic devices with micro processors.
8
2 Fundamentals of Automatic Control Electric Sensing & Control Element
Pneumatic Sensing & Control Element
Electronic Sensing Element
Sensing Element
Electro-pneumatic Sensing Element Remote setting
Remote setting
Diagram temperature Case: Temperature control
Sensing Element Communication with central system Controller Central F/O unit
Converter
Final Control Element
・Physical
Principle
Controller
Controller
Controller
DDC
dispositions of bellows, bimetal diaphragms or nylon tapes are used. ・ The sensing element and controller are integrated in a single unit.
Final Control Element
Final Control Element
Final Control Element
・Air pressure balancing method
using nozzles and flappers. ・ Two types available: sensing element and controller integral type and separate type. ・High accuracy types for industrial use are also available.
・Resistance temperature
device Bridge circuit Electronic circuits are used ・ Transmit by current, voltage signal. ・Microcomputer mounted types and sensing element and controller integral types are available.
Final Control Element
・Sensing element
and controller are electronic control. ・Final control element uses pneumatic control. Attains advantages of both control.
Final Control Element
・Digital circuits
(microcomputer) are used. ・Digital signal ・Realize excellent performance by mutual communication with central monitoring unit
Source of power
Electricity
Air
Electricity
Electricity / Air
Electricity
Accuracy Sensing Transmission Response Actuator Response Speed
Moderate
Moderate
Accurate
Accurate
Accurate
Moderate
Moderate
Fast
Fast
Fast
Moderate ・ Two-position ・Proportional
Moderate ・Proportional ・Compensation
・ Two-position ・Proportional ・PID ・Cascade ・Compensation
Moderate ・ Two-position ・Proportional ・PID ・Cascade ・Compensation
computing control ・Comfortable environment control ・Energy-saving control ・Indication ・Central monitoring
・Indication ・Central monitoring
・Central monitoring
・Central monitoring
・ Temperature ・Humidity ・Pressure ・Dew point temperature ・Flow rate ・Others
・ Temperature ・Humidity ・Pressure ・Dew point
・ Temperature ・Humidity ・Pressure ・Dew point
・Flow rate ・Others
・Flow rate ・Others
measurement
Function
setting
・ Temperature ・Humidity ・Pressure
・ Temperature ・Humidity ・Pressure
Control Element
Flameproof
Cost efficiency
measurement setting
temperature
temperature
Very Easy
Easy
Moderate
Moderate
Moderate
Very Easy
Easy
Easy
Moderate
Easy
Not Applicable
Applicable
Applicable with Flame proof device (Install flameproof equipment)
Low cost, provided the instrumentation is simple.
Low cost, provided the instrumentation is simple. (air source equipment is required)
More expensive than an electric control system.
General air handling Simple instrumentation
For flameproof When large valves are used (relatively low cost)
For constant temperature and constant humidity Remote setting indication
Applications
Figure 7
9
+
・Various complex
Control Method
Ease of handling Ease of installation
・ Two-position ・Proportional ・PID ・Cascade ・Compensation
Control methods comparis on table
Applicable with Flame proof device (Install flameproof equipment) Comparatively low cost in instrumentation with many valves. Constant temperature and constant humidity Remote setting indication Control target with rapidly changing disturbance When large valves are used
Applicable with Flame proof device (Install flameproof equipment) Less expensive than an electric control system if it is used with central monitoring unit Intelligent building Energy-saving instrumentation Complex instrumentation
2 Fundamentals of Automatic Control
2.4 BMS & Aut omatic Cont rol Design General At first glance, diagrams of automatic controls for air-handling look confusing and off-putting. However, it is possible to understand the drawing more easily if you learn a few rules. (Different manufacturers
tend to use slightly different rules). Normally, drawings of BMS including central monitoring and automatic controls are composed of the following items.
1. Automatic c ontrol Drawing 2. Legend Table for automati c co ntrol devices 3. Valve s ize tabl e 4. Automatic control (remote) panel dimensions table 5. Central monitoring system bloc k di agram 6. Central monit oring system s pecifications 7. Central monit oring system di mension diagram 8. Central monitoring system I/O hardware interface wiring circuit diagram 9. Central monitoring system input and output list I/O table 10.BMS & Automatic co ntrol f low wi ring plan
Work segment diagram and central monitoring system diagrams may be added to these drawings. In particular, instrumentation diagrams in which the functions and systems of automatic control are entered with an overview of facilities enable the viewer to fully understand the automatic control system. This section contains an explanation of the symbols used in this diagram.
In addition, some typical examples of instrumentation diagrams of air-conditioning facilities are shown in Section 6. Figure 8 shows a table of typical symbols, Figure 9 shows the legends used in instrumentation diagrams and Figure 10 gives an explanation using an instrumentation example of an air handling unit control.
10
2 Fundamentals of Automatic Control
Note : The • symbol in floor plans is intended for use in measurements.
Symbol Instrumentation diagram
Abbreviations
Remarks
T,H
Room temperature (humidity) controller
Electric thermostat/humidity controller
TE,HE,THE
Room temperature (humidity) sensor (transmitter)
Electronic sensor
TD
Duct temperature controller
Electric thermostat
TED,DTE
Duct (dew-point) temperature sensor (transmitter)
Electronic sensor
TW
Pipe insertion temperature controller
Electric thermostat
TEW
Pipe insertion temperature sensor
Electronic sensor
CO2
CO2 density sensor
PE
Pressure transmitter
dPE
Differential pressure (static pressure) transmitter
dPS
Differential pressure switch
FM
Flow meter
⎯
SW
(Toggle) Switch
⎯
QM
Set point device
⎯
R/TM/Other
Relay/timer/converter
⎯
TC,TIC,HIC
Temperature (humidity, others) (indicating) controller
⎯
TR,AT
Transformer
⎯
DDC,PMX
DDC controller
MD(MDF/MDE)
Motorized damper actuator
MV
Motorized two-way valve
MVT
Motorized three-way valve
BFV/BV/SV
Motorized butterfly valve/ball valve/electromagnetic valve
⎯
⎯
Central monitoring panel
⎯
CP/RS
Automatic control panel/remote panel
Figure 8
11
Description
Floor plan
Typical symbols for automatic control drawings
The symbol shown in ( ) is used to represent panel mounted device.
2 Fundamentals of Automatic Control
Legend
Power (1∅100/200 V AC, devices inside panel are omitted.) Power (24 V AC, connected to transformer secondary side) Unshielded cable (diagonal lines show the number of cables) Shielded cable (diagonal lines show the number of cables) Coaxial cable (diagonal lines show the number of cables) Air piping Fan interlock signal (52X contact) ON/OFF signal (
Shows Mg.SW)
Air source (main air) Devices mounted inside the field mounted panel Devices mounted inside the monitoring panel Devices mounted inside field mounted box (relay, transformer boxes, etc.) signal to/from monitoring panel communication cable (EIA 568 complied category 3 to 5∅ 0.5 × 4P)
General work segments 1. Power supply for automatic cont rol Supplied from a Distribution board (or power panel). Piping and wiring work is included in the automatic control work.
2. Interloc k This work involves piping and wiring up to the target devices such as power panels. Interlocking inside the power panel is included in the power work.
3. Central monitoring input and output Piping and wiring between the power panel, high voltage panel , distribution board and remote station (RS) panels are included in this work. Auxiliary relays and contacts required for remote control of power, lighting, etc. are installed inside the respective power panel. (See the input and output interconnection diagram)
4. Fan c oil Piping and wiring between fan coil local operation switch and the main unit is included in this work.
5. Variabl e Air Volu me (VAV) Power supply for VAV (24 V AC) is supplied from the instrumentation panel (CP ). Piping and wiring between CP panel and VAV are included in this work.
Figure 9
Legend and example of work segment
12
2 Fundamentals of Automatic Control
The symbols with shading lines represent the devices mounted in panel
Communication with BMS Communication interface
Shows contact (digital) output
Abbreviation for Direct Digital Controller
COM I/F
DDC
DO DI
AO AI
Shows contact (digital) input
The symbols without shading lines represent the devices mounted in field/room
Shows number of cables
Shows analog signal input
1
Shows branching of signal lines Shows analog signal output
Shows 24V AC output 2
R
R.A dPS
MV1
MV1
C
H
MV2
THE
BAV
Shows the product abbreviation specified in the device list
1
Return air duct
O.A
FAN
Outdoor air duct
C
MDF
Supply air duct
S.A
C TD
See valve selection table for flow details of coil and humidification unit
1
Shows panel power AC input
Shows 24V AC output
TR 2
AT
Control items 1. Room temperature control Chilled water valve and hot water valve shall be controlled (Modulating control by PI action) by room temperature to keep set point. Chilled water valve
Hot water
g n i n e p o
(%) valve 100
g n i n e p o e v l a V
Chilled water valve
Hot water
(%) valve (reheat) 100 g n i n e p o e v l a V
0
0
Set point
Humidity
Set point
Temperature
3. Start-up control
e v l a V
Outdoor air damper remains closed for pre-cooling or preheating for a predetermined time after AHU is started.
0 Set point
Temperature
2. Room humidity control Humidification (winter) : Proportional humidification valve shall be controlled by room humidity to keep set point. Dehumidification (summer) : Proportional chilled water valve shall be controlled as dehumidification by room humidity to keep set point. Under processing dehumidification, room temperature shall be compensated by reheat valve control.
Figure 10
13
Chilled water valve
Humidification
(%) valve 100
4. Interlock control Devices are interlocked with AHU status and season's information. Devices : O.A damper, 2-way valves, humidification valve.
5. Defect alarm of humidification valve Humidification valve defect is detected by the temperature inside AHU when AHU is off.
6. Communication with BMS
Example of Autom atic Control Diagram
2 Fundamentals of Automatic Control
2.5
Autom atic Control System Design Procedure
Since automatic control plays the important role of being the 'nervous system' of buildings or facilities, sufficient consideration must be paid to the design stage of the buildings.
This section explains the system-wide plan of automatic control made at the planning stage of the building or facilities and examples of procedures of instrumentation and design of individual facilities at the actual design stage.
System-wide plan Identify the various characteristics o f the building
Identify overview of building facilities
Identify the area, use, scale, methods of management and operation, concept and budget of the building. The importance of control changes depending on the area or use. For example, some areas may need frost-protection control.
Identify the concept, method, system and number of units of the building facilities.
Determine the con ditions for the plan
Determine the concept, effect of introduction, required quality (required accuracy, etc.) and environmental conditions of the automatic control system. For example, determine which is of primary importance: temperature/humidity conditions, energy conservation, system reliability, etc.
Determine control items and functions
Determine the control target, items to be controlled, monitored, operated and over all function for each facility. See Sections 5 and 6.
Select th e system and control method
Select the system-wide configuration and control method to match the required function. For example, optimum start/stop control of the air handling unit can be carried out at the central monitoring unit and the other AHU controls can be performed by DDC.
Check consis tency with facility systems
Check whether the selected control function and control method are consistent with the facility system. Review of the building or facilities may be necessary for the required function for automatic control.
Check whether the plan is in line with the budget.
Check budget
14
2 Fundamentals of Automatic Control
Instrumentation design for individual facility Identify f acility drawing
Check cont rol item and function
Check the device table of the facility, distribution diagram or floor plan and identify the position of the respective facility.
Check the control items, functions and accuracy required for control of the respective facility system while planning the instrumentation.
Identify f acility system
Identify devices, duct and piping systems related to the respective facility and check whether they are consistent with the control items. For example, return air fans, exhaust air fans, duct systems, and piping systems for air handling units.
Check final control elements
Check whether the operable valves, dampers, humidifiers, inverters, etc. related to the respective facility are connected to the locations consistent with the control items.
Determine locations of sensors
Select the contr ol method
Design contr ol logic
Select the control devices
Select the control valves
Determine your control method based on what it is you want to control, the required conditions of quality, the driving source, need for measurement, setting and display, position, operating method, and method of management. With consideration given to the elements added so far, set up the control logic based on the required control loop, how it is planned to work, the relationship between each loop, interlock, the transmission points for central monitoring, etc. An overview of the control logic system is described in the instrumentation diagram with an explanation of what each part does. Select control devices in line with control logic, input/output signal, circuits and budgets.
Select the appropriate type and size of control valves based on the liquid, flow rate, inlet pressure, pressure drop (ÆP), and pressure rating. Check whether the pressure, shut-off and flow rate is within the allowable range of the valve. For details, see our separate document, "Valve Selection and Sizing"
Create instrumentation diagram
Create your instrumentation diagram, automatic control device table and valve size table.
Calculate th e autom atic control panel s ize.
Based on the devices installed inside the respective automatic control panel, calculate panel size and create size table.
Create your floor plan
Create a detailed budget 15
Determine the types of sensors and installation locations (rooms, return air ducts, etc.) to ensure that the sensors required for control items accurately detect the load on the control targets. Also take into account the space design and ambient environments.
Create your floor plan for automatic control based on the positions of facility equipment, piping, ducts, power and distribution boards work segments, and wiring routes and your existing instrumentation diagram. Identify the quantity of devices, panels, piping, wiring and installation work and calculate the budget, including the costs of devices and panels, adjustment costs, engineering costs and instrumentation work costs.
2 Fundamentals of Automatic Control
2.6
Automatic Control System Retrofi t Planning Procedure
As with facilities, it is also important to identify the problems and needs of the owners, users and building managers and solve them successfully and reliably when fitting automatic controls.
The course of action for retrofitting is distinctly different from that for installation of systems in new buildings. An example of planning procedure and retrofitting of air handling unit controls is given below.
Planning pr ocedure for retrofit buil ding Investigation of current conditions
Identify current problems. It is important to precisely identify current problems and solve them reliably to make retrofit plans successful. Therefore, 1. Precisely identify the problems and needs of owners, building users and building managers. 2. Objectively determine the need for retrofitting based on a diagnosis of the facilities, etc. 3. Investigate the current system and devices to identify the operating conditions of each function. 4. Investigate the availability of parts necessary for troubleshooting.
Narrow down the problems by means of these investigations.
Basic plan
Clarify the reason for renewal In a basic plan, it is import ant to clarify t he benefits t o owners, users and managers. 1. Clarify the motives (problems, etc.) of owners, users or managers and propose improvements, describing their effects. 2. Propose correct methods and measures to satisfy their needs. 3. Ask about the potential motives and needs of owners, users and managers and propose solutions.
It is import ant to clarify t he reason to identify the intended effects of retrofitting.
Investigation f or implementation
Implementation plan
Installation plan
Installation
Operation
Carry out detailed investigation to realize solutions. Retrofit buil ding is subject to various constraints and detailed on-site investigation is required before formulating an im plementation plan. (1) Building constraints such as space available, type of structure, etc. (2) Operational constraints of building users or managers. (3) Consistency with existing facilities.
Plan installation so as not to interfere with the day-to-day operation of the building. A d etai led in st all ati on pl an i s r equ ir ed b efo re em bar ki ng on ret ro fi tt in g a building while it is in use. (1) Consider the method of shifting to a new work system to minimize down time. (2) Prepare "shift procedures" to ensure a successful shift from the old system to the new system. (3) Determine construction time periods taking care not to cause inconvenience to building users. (4) Make plans for material movement with consideration given to the use of the building.
Improve training for the new system. The managing engineer must be able to adapt quickly to the new system. Set up a training plan for the new building management system. (1) Training before switch over to the new system. (2) Follow-up training after switch over to the new system.
It is necessary to prepare the plan according t o the new management controls and implement the same.
Measuring the effects of the new system
Comparison and verification of co st effectiveness A c om par is on of eff ect s b efo re an d af ter ret ro fi t i s r equ ir ed. (1) Set up in advance the method of effect measurement and comparison. (2) Effects must be checked after retrofitting.
16
2 Fundamentals of Automatic Control
Retrof it examples of air handling unit c ontrol The method of retrofit varies depending on the current control method. These are cases of replacing the existing control method with DDC. From pneumatic to DDC (Install an electro-pneumatic converter and leave the air source equipment in place) Procedures ⋅ Replace the existing pneumatic controllers with DDC. ⋅ Replace sensors ⋅ Connect the existing pneumatic final control elements to a DDC via an electro-pneumatic converter Adv ant ages ⋅ The benefits of pneumatic control can be retained. ⋅ Existing final control elements can be effectively used. ⋅ The down time of air handling units due to replacement can be reduced.
Measurement (to Central)
From pneumatic to DDC (Eliminate all pneumatic control devices) Procedures ⋅ Replace existing pneumatic controllers with DDC. ⋅ Replace all sensors and final control elements. Adv ant ages ⋅ Elimination of air source equipment saves space ⋅ Costs are higher than when using the electro-pneumatic converter, since all devices are replaced. From electric to DDC Procedures ⋅ Replace existing electric controllers with DDC. ⋅ Replace all sensors and final control elements. Adv ant ages ⋅ Better fine control and energy-saving control can be done as compared with electric control ⋅ Existing wiring (for sensors) can be used if it is in satisfactory condition.
From electronic to DDC Procedures ⋅ Replace existing electronic controllers with DDC. ⋅ Existing sensors and final control elements can be used if they are still in good condition. Adv ant ages ⋅ Existing devices can be used effectively. ⋅ This approach features the lowest cost of the four methods combined with the benefits of DDC.
Figure 11
17
Measurement (to Central)
Cooling/heating
changeover
Measurement (to Central)
Measurement (to Central)
Retrofit example of air handling unit cont rol
3 Automatic Control Devi ces
3. Automatic Control Devices
3.1 Electri c Contr ol Devices The sensing element, controller and set point device are built into a single unit. This method monitors changes in temperature and humidity via bellows or diaphragms as mechanical displacements and directly controls final control elements such as motorized valves, motorized dampers, humidifiers, compressors, etc. Electricity is used to transmit signals or as a source of power for mechanical movements. Both room mounted types and insertion types are used that are installed in ducts or piping to detect temperature, humidity, pressure, and other variables. The
structure is simple and easy to handle. Therefore, the work is simple and can be carried out at comparatively low cost. This method is used in applications where a high degree of accuracy is not required. This circuit produces either a two-position action (output signal: SPST or SPDT, etc.) or a proportional action (output signal: 0 to 135 Ω potentiometer). Integral (I) or differential (D) actions are not supported. A power supply of 100/200 V AC or 24 V AC is used.
Temperature cont roller Neostat TY900
Motorized valve
Actuator MY 5320 Three-way valve VY5303
Return air
Outdoor air
Supply air
Air handling unit Chilled/hot water
Figure 12
3.2
Sample instrumentation drawing for electric control
Electron ic Control Devices
In electronic control devices, the sensing elements and controllers are at a distance from each other. Controllers are usually placed in a control panel in mechanical room. Since an electronic controller uses electronic circuits (digital circuits), it accepts various measured values, such as temperature, humidity, pressure, flow rate, CO2, density, etc. and provides highly accurate control and indications and allows remote setting of measured values. Since the outputs are general-purpose signals, converters such as high/low select* or ratio bias* or auxiliary devices can be used and electronic control devices can accommodate flexible instrumentation such as selective controls or limited controls.
∗High / low select : A device which selects the
larger (or smaller) signal from two input signals and outputs. Ratio bias : A device which issues outputs, changing the start and end points or rate of change of input signals.
18
3. Automatic Control Devices The principal actions of controllers and types of input and output signals are as follows: Input signal types
Element
Actions
Resistance temperature device (Pt100)
Current
0 to 20mA DC 4 to 20mA DC
Voltage
0 to 10mV DC - 10 -+10mV DC 0 to 100mV DC 1 to 5V DC 0 to 5V DC
Output signal types
Two-position Time proportioning
Relay contact (SPDT) Open collector (voltage) Position proportional contact +feedback potentiometer
•P(Proportional) •PI •PID
Current
4 to 20mA DC
Voltage
0 to 10V DC 1 to 5V DC 2 to 10V DC
Temperature sensors for air handling systems include room, duct, pipe and ceiling mounted types. Temperature sensing elements take the form of resistance temperature devices. Resistance temperature sensors are Pt100 made of platinum. Pt100 is specified by J IS and used in air handling controls with constant temperature and constant humidity and chiller plant control where a high degree of accuracy is required. Humidity sensors are classified into room- and duct- mounted types. The measurement values are either relative humidity, dew point temperature and dry-bulb temperature. Sensing elements comprise the high polymer thin film type, which is compact and ensures high stability and quick response. An external power supply is required for high polymer thin film sensors. They have electronic circuits inside the sensors and transmit voltage or current signals. Final control elements are damper motors, motorized valves, humidifiers, etc. It also uses inverter or thyristors with current input.
Temperature characteristics of platinum resistance temperature Sensors
Temperature indicating controller R36
Return air
Room temperature sensor Neosensor TY7043
Motor driver RN796A Motorized two-way valve Actival VY5117
Supply air Outdoor air
Chilled water
Figure 13
19
Hot water
Air handling unit
Sample instrumentation drawing of electronic control
3. Automatic Control Devices
3.3 DDC (Direct Digital Contr ol) According to the definition of the J apan Electric Measuring Instruments Manufacturers' Association, DDC is defined as "Control in which the functions of a controller are performed by means of a digital device." However, in this document, DDC indicates "a controller in which an automatic control system and a remote station of central monitoring are integrated, which applies digital processing using a microprocessor." The features of DDC, its sample configuration, and comparison with electronic controller are shown below. Features of DDC {Digital
setting, display and calculation eliminate errors in transmission and calculation, allowing highly accurate control and measurement. {All input and output signals can be transmitted to the central monitoring unit. More precise and detailed management is possible. {DDC allows distributed control and management of each unit, not only for air handling units but also for fan coil units (FCU),VAV(Variable air volume)units and Chiller P lant equipment.
{ Transmission
functions are integrated. Only one sensor is required to carry out control and measurement. components and self-diagnosis {Common functions enable quick response when a problem occurs. {LCD display set point devices and wireless sensors can be connected, for convenience and better design. {Programs can be easily added and or modified onsite to cope with changes in room layouts, such as movement of partitions. {Control functions and remote station function for central monitoring are included in the controller saving space in panels. {Easy upgrade and retrofitting since it utilizes the same sensors and final control, other type, The digital transmission of input and output signals of sensors and final control elements is also possible.
Exhaust air Central system
Return air
Multipurpose Controller Infilex GC WY5111
Damper Actuator MY6050 QY9010
Room temperature/ humidity sensor HTY7043
Damper Actuator MY6050 QY9010
Motorized Two-Way Valve VY5118 Motorized two-way valve Actival VY5117
Steam
Supply air
Outdoor air
Insertion temperature sensor TY7803
Damper Actuator MY6050 QY9010
Air handling unit Chilled/hot water
Figure 14
Sample inst rumentati on drawing of DDC
20
3. Automatic Control Devices
Building Management System savic-net series
Central monitoring unit
o s n e s y t i d i m u h / e r u t a r e p m e T
Setting device for engineering
o s n e s y t i d i m u h / e r u t a r e p m e T
r o s n e s y t i s n e d 2 O C
n a f r i a y l p p u s U H A
n a f r i a n r u t e r U H A
e r u s s e r p l a i t n e r e f f i d r e t l i F
e n i l n o i s s i m s n a r t l a t i g i D
⋅Call point ⋅ON/OFF, setting, status, alarm ⋅Real time/totalized data ⋅Program data
To other DDC controllers (peer communication)
Input interface e l i f g n i t t e s a t a D
e l i f n o i t a c i n u m m o C
Control calculation unit
Output interface
User terminal
Fan coil unit e v l a V
Figure 15
21
e t e p r m e a v n D I
r e e i f i p d i m a m D u H
n a f r i a y l p p u s U H A
n a f r i a n r u t e r U H A
Example of dist ribut ed DDC contr oller conf igurati on
DDC controller
3. Automatic Control Devices
Electronic controller + RS (remote station)
e n i l n o i s s i m s n a r T
Temperature measurement
Humidity measurement Temperature setting
Automatic control panel
Humidity setting
Temperature controller
Fan ON/OFF
Humidity controller
Power panel
Central monitoring unit
Air handling unit
DDC
Transmission line (Digital signal)
Temperature measurement Humidity measurement Temperature setting Humidity setting Fan ON/OFF Controller failure Fan ON/OFF
Power panel
Central monitoring unit
Air handling unit RS: Remote Station DDC: Direct Digital Controller T: Temperature sensor H: Humidity sensor
Figure 16
Comparison of control methods
22
3. Automatic Control Devices
3.4 Intelli gent Compon ent In addition to DDC control, Intelligent Component Series are Intelligent Component Products are the field devices which contains the information of device and control conditions. The features of Intelligent Component Series, its sample configuration are as shown below. Features of Intelligent Compo nent Series { This
product transmits all input and output signals to the central BMS through the dedicated communication line called SA-net. More data transfer than direct wiring is possible. {From room temperature sensor to control valve, major products required for AHU control are available in its lineup.
{ACTIVAL
PLUS is one of the lineup of Intelligent Component Series. This is the motorized control valve with flow rate measurement and control function controls chilled and hot water flow rate by detecting flow rate not by adjusting the valve opening. {ACTIVAL PLUS calculates flow rate by differential pressure detected by built-in pressure sensor times Cv calculated by the valve opening position times the constant. {Wall mounted LCD display is available to indicate measured pressure, temperature, calculated flow rate from ACTIVAL PLUS.
Exhaust air Return air
Damper Actuator MY8040
Central system
Multipurpose Controller Infilex GC WY5111 Room Temperature Sensor HTY7043
Damper Actuator MY8040
Motorized 2-way valve with flow rate measurement and control FVY5160
Motorized 2-way valve Spring Return Type VY516X Steam
Supply air
Outdoor air Damper Actuator MY8040
Air handling unit Chilled/hot water
Figure 17
23
Duct Insertion Temperature Sensor TY7803C
Sample schematic drawing of Intelligent Component Series
4 HVAC System generals 4.1 AHU Systems Air handling is divided into three systems: outdoor air processing, room interiors, or room perimeters, depending on the load each air handling unit is processing.
Appropriate AHUs are adopted for each system. There are various ways of classifying the AHUs. The following ways are amenable to automatic control.
(1) Outdoor AHU In this AHU, only outdoor air is drawn in and processed without any return air from the system. Total heat exchangers are added in some cases. This unit is suitable with the combination of fan coil units, for individual rooms of hotels or hospitals, and AHUs on each floor in office buildings. In this type, controls are performed based on supply air temperature and dew point temperature. However, it is also possible to bypass all heat converters for outdoor air cooling depending on the season. Supply air Outdoor air To indoor AHU
(2) Constant air volume (CAV) AHU This method processes room load (return air) and outdoor air load (outdoor air), or room load only, and distributes constant air volume via ducts. A cooling/heating coil or combination of a cooling coil and a heating coil are used. This method controls zones with fairly constant load characteristics and is used extensively, from large spaces such as theaters or shopping centers, interiors of small to medium sized buildings, to zoned air handling in large buildings and units on each floor. The CAV AHU performs temperature and humidity control of rooms by controlling the amount of return air supplied back to the room. It also performs room temperature and CO2 density control by monitoring the outdoor air load and controlling the intake of outdoor air.
Exhaust air
Outdoor air
(4) Packaged air co ndit ioner This is a room unit incorporating a compressor. There are two types: a cooling compressor + electric heater type and heat pump type. Also there are water source types and multi-type units which need to be installed in multiple rooms. This method is mainly used for air handling of spaces with load characteristics and operating times that differ from other spaces, from computer rooms to stores or small-sized office buildings. In packaged air conditioners, ON/OFF control to determine the number of operating units of compressors in response to room temperature, etc. are carried out.
Supply air
Return air
Exhaust air Outdoor air Outdoor air
(5) Fan coi l un it (FCU) (3) Variabl e air v ol ume (VAV) AHU based on This method further divides zones with similar load tendency, controls these zones using individual VAV units, and reduces the total air volume of AHU using inverters, etc. accordingly. Compared with CAV AHUs, VAV AHUs can control the zones better with respect to the load on each small zone and thus enable energy conservation. This method is suited for medium-to large-sized office buildings with wide air handling areas which place importance on running costs. VAV AHUs control each VAV room temperature and control supply air temperature and fan air volume accordingly. They also controls outdoor air and CO2 condensation in the same way as for CAV AHUs.
25
A compact air conditioner which incorporates a fan, a coil, and a filter, etc. Generally, it does not take in outdoor air or perform humidifying, but simply carries out air circulation. There are floor standing, ceiling-mounted and cassette types. This method is suited for individual rooms in hotels or hospitals or perimeters in office buildings. The FCU controls room or return air temperature by controlling valves individually or in groups (for zones). They can be used to optimize load sharing with air handling units in interior or outdoor air processing air handling units as well as to carry out energy-saving control.
4. HVAC Sys tem g enerals
4.2 Chiller Plant Systems A variety of chiller plant equipment is available, with different operating principles and structures, including absorption chillers, heat pump chillers and boilers. Auxiliary equipment includes chilled/hot water pumps, cooling water pumps, and cooling towers. Classifying chiller plant types are classified as the closed piping method, open piping method, DHC (District Heating and Cooling) receiving method and individual chiller plant types of packaged air conditioners. (1) Closed type piping Single-pump system This method supplies chilled/hot water to the whole building by a combination of chiller plant equipment and chilled/hot water (chilled water or hot water separately) pump. The system is simple and the initial cost is low. It is mainly used for small sized buildings. The single-pump system controls the number of operating chiller plant equipment according to flow rate and control bypass valves to keep the differential pressure at load constant. This system also controls peripherals including cooling towers and heat exchangers.
Air handling unit
Chilled/Hot water pump
Chiller
This document describes the closed method and the open method. The closed method is further classified as constant flow and variable flow method. In constant flow method, chilled/hot water is supplied to the whole building at a constant rate of flow controlled by three-way valves on the load side of the air handling units. In the variable flow method, the chilled/hot water supply flow is varied under the control of the two-way valves at the load side. This section mainly describes the variable flow method, which enables better energy conservation. (3) Open pipi ng Storage tank syst em This system uses double-foundation slabs and tanks as storage tanks, stores chilled/hot water from chiller plant equipment (mainly the motorized type) in tanks and directly supplies the water from the tanks to air handling units, etc. at the load side. Using the off-peak system of utility companies, this system stores heat efficiently by using cheaper off-peak power and halting equipment operation during peak hours in the daytime to reduce running costs and optimize power demand. This can also be used as a backup system for heat recovery or in the event of chiller plant equipment failure. Although this system requires large capital investment for installing water tanks, secondary pump to cope with higher head, as well as anti-corrosion measures, This system saves the running cost. Also it is cheaper, since lower capacity chiller plant equipment can be used. This system is mainly used for large-sized buildings and computer center. The storage tank system controls chiller plant equipment inlet three-way valves to store heat in storage tanks at a fixed temperature, the number of operating secondary pumps, bypass valves and pressure holding valves in the return pipe at load side.
(2) Closed type piping Dual-pump system This method is also called the duplex pump or secondary pump system. The primary pump is controlled within the head of the chiller plant system and the secondary pump shares the load of the head equal to the resistance of the load side. Although the initial cost and installation space is higher than with the single-pump system, energy conservation can be realized by using a separate secondary pump for each chiller plant system and controlling the number of operating units. This method is mainly used for medium to large sized buildings. The dual-pump system controls the number of operating secondary pumps according to flow rate and control bypass valves or inverters according to differential pressure in front and behind the pumps.
Secondary pump
Air handling unit Primary pump Heat pump
Water charging side Chilled water tank Water discharging side (at lower temperature) (at higher temperature)
Air handling unit Secondary pump
Chiller
Primary pump
26
5 Control Functions 5.1 HVAC Aut omati c Contr ol Details This section explains details of control items described in application examples of automatic control in Section 6.1. (1) Room (supply air and return air) temperature control 〈1〉 Chilled water valve and hot water valve control g n i n e p o
e v l a V
(Single coil heating)
•Detects room temperature using temperature
(Single coil cooling)
Chilled water valve
Hot water valve
Room temperature Heating set point
Temperature main set point (double coils)
sensor and provides proportional control of chilled water valves and hot water valves. In electronic DDC methods, integral action is also possible. •In the single coil (dual-pipe) method, the action each valve is within the dotted line of the diagram on the left. • The set point position in the double-coil (four-pipe) method is as shown in the left diagram. In DDC method, main set point, cooling and heating set points can be determined as required.
Cooling set point
〈2〉 Chilled water valve and hot water valve +outdoor cooling control •Detects room temperature by using temperature
g n i n e p o e v l a V
(Single coil heating)
Hot water valve
(Single coil cooling) Chilled water valve
Outdoor air damper
Minimum opening
Room temperature Heating set point
Outdoor air cooling set point
Cooling set point
Temperature main setting (double coil)
sensor and provides proportional control of chilled water valves, hot water valves, outdoor air/return air/exhaust air damper (outdoor air cooling). In electronic and DDC methods, integral action is also possible. •Using natural energy, provides outdoor air cooling control when intake of outdoor air is effective. •When there is a total heat exchanger, the system changes to a bypass duct or operates the rotor intermittently during outdoor cooling. When the outdoor air satisfies the following conditions, intake of outdoor air is effective. i. Outdoor air temperature
<
room temperature (temperature based comparison)
II. Outdoor air enthalpy
<
room enthalpy (energy-based comparison)
III. Outdoor air temperature
>
outdoor air temperature low limit set point (measures against humidification load)
IV. Outdoor air dew point temperature
<
outdoor air dew point temperature high limit set point (measures against dehumidification load)
•Provide a minimum opening for outdoor air
intake to ensure correct design amount of outdoor air or CO2 density.
27
5 Control Functions Expression of o utdoor air intake condition on a psychrometric chart The conditions of I to IV in 〈2〉 of the previous page are expressed on a psychrometric chart as shown on the right.
y t i
d Room i environment m u
Outdoor air intake effective area
h e t u l o s b A
Dry bulb temperature
〈3〉 Temperature control of heat pump package Heating
•Performs ON/OFF control of compressors
Cooling
Compressor
according to room temperature. Compressor
s u t a t S
Temperature Heating set point
Heating/cooling changeover is done manually.
Cooling set point
(2) Room (return air) humidity control 〈1〉 Humidifier control •Provides ON/OF F control of humidifier according
to room humidity. •Mainly used for vaporizing humidifying, water
humidification, ultrasonic humidification and pan humidification.
s u t a t S
Humidity Humidifying set point
〈2〉 Control of humidifying valve and chilled water valve •Provides PI control to humidifying and chilled
Humidifying valve
Chilled water valve
g n i n e p o e v l a V
Humidity Humidifying set point
Dehumidifying set point Humidity set point
water valves according to room (return air) humidity to provide humidifying and dehumidifying reheat control. •For electric control or humidifying only system, the valve action is within the dotted line •For dehumidification, when humidity increases, the chilled water valve opens. As a result, the heating coil (hot water coil) reheats to compensate for the decrease in room (supply air, return air) temperature. •Proportional control of humidification achieved by applying steam humidification or steam generator •In steam humidification applications, the supply air dew point temperature can be used as the control.
28
5 Control Functions (3) Supply air temperature cascade control
Changes supply air temperature set point to control supply air temperature based on the control output of room temperature and room temperature set point. Due to this, the impact of process lag and disturbances can be reduced. (4) Supply air temperature limit control
This function controls supply air temperature within high and low limits. This prevents overheating during heating, temperature stratification and condensation at outlet during cooling. (5) Supply air temperature set point optimization control
In a variable air volume air handling unit, calculates optimum supply air temperature set point based on air volume of VAV and room temperature to prevent insufficient ventilation and heat output. (6) Supply air vo lume cont rol b y VAV air volum e
Adds up air volume of all VAVs and CAVs to output the speed of rotation in line with the fan speed characteristics of the AHU. Controls the fan speed in stages based on VAV opening. Sets minimum fan speed to ensure minimum outdoor air volume for ventilation. (7) Warming up control
During warming up of air handling unit (pre-cooling/preheating), the following controls are achieved. The time between the start of AHU till start of occupancy is called as warming up period. The length of the warming up period is determined by calculation in the central monitoring unit or delay timer. [1] Outdoor air intake disabled (outdoor air/exhaust air/outdoor air bypass/exhaust air bypass damper: fully closed, return air damper: fully open) To reduce outdoor air load, the outdoor air intake is disabled. This reduces warming up time and reduces power consumption by the fans. However, when outdoor air cooling is effective, outdoor air intake is performed. [2] A humidific ation disabled During warming up, there is a change in temperature, room relative humidity tends to be unstable, and the control does not stabilize. In order to prevent condensation in the supply air duct, humidification is disabled by interlock (Humidifier OFF or humidifying valve fully closed).
29
[3] Total heat exch anger off Turn off total heat exchanger because outdoor air is not taken in.
(8) Interlock control while AHU fan is off [1] Disable humidification [2] Chilled/hot w ater v alve fully c losed [3] Outdoor air/exhaust air/outdoor air bypass/exhaust air by pass damper fully closed [4] Return air damper fully open [5] Total heat exch anger off [6] VAV fully open
(9) Communication w ith central monit oring system
In case of DDC system, input and output signals and calculation values can be transmitted to the controller as required, except the following typical items. [1] ON/OFF of fan, status failure monitoring [2] Filter differential pressure alarm m onitoring [3] Room (return air, supply air) temperature and humidity measurement [4] Room temperature and humidity setting [5] Warming up command [6] Monitoring of DDC controller failure
(10)Control of chiller plant system
This controls the number of operating pumps or chiller plant equipment for generating and supplying the heat required by the load AHU. [1] Number of operating pumps control In response to changes in load, it controls the differential pressure between headers in the single pump system, and controls the number of operating secondary pumps and bypass valves according to the flow rate in the double-pump system. Uses PID control of bypass two-way valves to maintain output pressure to load constant. [2] Number of operating chiller/hot water generators contr ol In dual pump system, it controls number of operating chilled/hot water generators depending on the load by measuring return header temperature. This improves response to the change in required flow rate of secondary side (air handling units), supply water temperature to the secondary side, return temperature and flow rate.
5 Control Functions
5.2
Energy Saving Applic ations according to the predefined level. When power is restored, the control carries out operation and control so that each piece of equipment returns to normal taking account of the passage of time.
(1) Power/lighting management, control function
For effective and safe usage of power, it measures power, current, power factor to monitor, control and report power reception status, relay status, occurrence of ground fault/leakage of electricity and operating status of generators. [1] Power demand control Predicts power consumption and controls operation of facility equipment so that the power contract with the utility company does not exceed. Since priority can be set to control targets such as air handling units, exhaust air fans or chillers to be stopped in peak periods, it is possible to control contract power without having a significant impact on the environment.
Predicted power Target power Shedding level Power consumption
Current
[2] Power factor control This control eliminates the reactive power generated by the reduction elements of power factor, such as motors for air handling, by adding and shedding the power factor compensator. This enables to accept power factor adjustment discount of utility company as well as to eliminate loss of power energy. The rotational or sequential addition/shedding method can be selected according to the combination of power factor compensators with equal/different capacitance.
Reactive power Control effective low limit
Power factor compensator shedding level (TX) If power factor leads up to here, compensators are shed.
Active power Power factor compensator add level (CX) Target power factor low limit (PFL) (If power factor delays up to here, compensators are added.)
Shedding area
No shedding or addition is carried out
[4] Lighting schedule control Reduces lighting intensity to half or turns off lighting near windows or during lunchtime.
(2) Comfortable environment control, energy-saving contr ol
In addition to local automatic control, carries out central control using a schedule related to the entire building and data such as season, outdoor air temperature and humidity. Realizes compatibility with energy conservation and comfort by eliminating waste (coordination control), total optimization of rooms, distribution, chiller plant systems (conjunction control) and optimum operation based on load prediction (prediction control). [1] Tenant calendar control / time schedule control Sets calendar (specification of holidays) for building management system to perform changeover of scheduled patterns including air handling operation and scheduled operation of power or lighting. [2] Optimum start and stop control So that the room temperature becomes the set point at the start time of the occupation of the office, calculates the warming up time and activates air handling units automatically. When it stops, this control turns off air handling units at the optimum time within the range where the stop of the air handling units does not have an impact on the office environment. The chiller plant equipment can be started automatically a certain time before the air handling unit with the earliest start time is activated.
Temperature setting Start/stop target temperature
Target value Room temperature Operation of air handling unit
Optimum start Calculate so that the power factor is within a certain range based on the set point by adding and shedding power factor compensators.
Room occupied
Room occupation start
Optimum stop Room occupation end
[3] Power failure/power restoration contr ol, generator load distribution control In case of power failure, generators are activated to operate emergency equipment. If generator capacity remains, ordinary equipment is added
30
5 Control Functions [3] Zero energy band control Allows latitude in setting temperature and humidity within the range of comfortable environment and individually sets target values of cooling, heating and dehumidification. This type of control prevents waste of energy due to overcooling, overheating and mixing loss of cooling and heating, as well as the hunting effect in which the chilled water valve and hot water valve repeat opening and closing alternatively to maintain a comfortable environment without consuming extra energy. for setting the target value refer to the thermal environmen environmental tal index such as P MV. •Explanation •Zero energy band and action of chilled
Zero energy band of humidity
e v l a v g n i y f i d i m u H
Zero energy band of temperature
Temperature
Heating set point
Radiant temperature on window
Comfort zone Room temperature setting
temperature
n o i t a c i f i d i t n i m o u p h t e e D s
t n i o p t e s g n i y f i d i m u H
Cooling coil valve
Cooling set point
[4] Radiant temperature control This This cont control rol measu easure res s radia adiant nt tem tempera peratture ure in a space such as the perimeters of buildings where the thermal sense (perceived temperature) of human beings cannot be only detected by room temperature sensors only since the change in solar gain is large. This control changes the room temperature set point based on the radiant temperature. The radiant temperature sensor is used for measurement. The sensor is installed on the ceiling and measures radiant heat from walls or windows without contact with walls or windows. Responding to the changes in the environment caused by solar radiation or changes in the weather, it maintains a comfortable environment in the perimeter zones.
31
Perceived tem eratures eratures
Detects radiant temperature instantly and carries out compensation. Therefore, the perceived temperature is held constant.
e v g l n a i l v o l o i o C c
Heating coil valve
Even if the room temperature is within the comfort zone, perceived temperature in the perimeters varies depending on the weather or outdoor air temperature, and may deviate from the comfort zone.
•P erimeter control according to radiant
water/hot water/humidifying valve
y t i d i m u H
•Existing room temperature control
Perceived temperatures
Radiant temperature on window
Comfort zone Room temperature setting
[5] PMV management management pr ogram P revents overcooling and overheating by using an index (the (the P MV index) which which objectively describes human thermal perception (Cold to comfortable to Hot) for management and setting of room temperature and humidity and carries out optimum room temperature setting. This allows compatibility between a comfortable room environment and energy conservation. Select one of the comfort sensor, radiant temperature sensor, room temperature sensor depending on how the building or room is used.
PMV value Environmental element
Hot
Room temperature Radiant temperature Air flow Humidity
Warm n o i t a l u c l a c V M P
Slightly warm Comfortable Slightly cool
Human elements Activity level Clothing level
Cool Cold
5 Control Functions [6] Variable water volume supply pressure setting control (VWV (VWV control) While terminal pressure or output pressure is held constant in the existing variable water flow control, this control reduces power for pumps responding to the air handling load by reducing the pressure
set point during air handling low load (with low demand for cooling or heating) and decreasing the speed of rotation of pumps by inverter control. Compared with the constant terminal pressure control, annual energy conservation of about 30 % can be achieved realized.
Pressure Pressure KP a
Pressure KPa
Valve nearly fully open
Close valve Inverter
Inverter
Flow rate
L / min
Flow rate
Existing constant supply water pressure control
[7] Air handing load prediction control Based on the actual air handling load up to the previous day, predicts consumption load for the next day to carry out optimum start and stop of chiller plant equipment in advance. ARIMA (Auto-Regressive Integrated Moving Average) models are used as the process for predicting the load. By carrying out optimum operation control, it is possible to minimize operating costs. The predicted air handling load can be used for heat storage target of heat storage tanks and the predicted power load can be used for power demand control. [8] CO2 outdoor intake control Based on the detected value of the CO 2 gas gas sensor, controls the outdoor air damper to change the intake of outdoor air according to the number of occupants. It is recommended to use VAV units for outdoor air dampers or to carry out outdoor air volume control using air velocity sensors to ensure sufficient outdoor air.
L / min
VWV control
[9] Duty cycle control Saves power consumption of air handling facilities by operating air handling units intermittently while maintaining comfort. It is also possible to change the stop interval.
Tempera peratu ture compensa pensati tion on control Duty cycle Average load operating mode (When temperature is within target values)
[10]Enthalpy [10]Enthalpy co ntrol Tak Takes es in out outdoor door air air by open openin ing g dam damper pers and and uses ses natural energy effectively when the outdoor air enthalpy/temperature is lower than the room enthalpy/temperature; outdoor air can be used for cooling. If a DDC is used, the DDC carries out the calculation. Outdoor air intake by enthalpy decision (Outdoor air cooling decision)
Outdoor air
Enthalpy Outdoor air intake effective area
Room conditions 25°C 60%RH)
Room temperature Dry bulb temperature
32
5 Control Functions (3) Building Energy Management Management System
The The build ilding ing ener energ gy manag anagem ement ent syst system em composed of the following items; Energy Data Server, Energy Saving Applications, and Intelligent series control control products. products. Those Thos e works together to realize the evaluation cycle of energy consumption. [1] Energy Data Server Server Energy Data Server (EDS) collects and stores measured data such as temperature, humidity, power consumption, energy, flow rate, and device status through savic-net FX building management system. Displays the measured data as the individual or the combination of graphs such as bar, line, laminated, spread, status, and circle to visualize the energy consumption pattern for easy building performance evaluation.
- Duct insertion humidity transmitter - Duct insertion dew point temperature sensor - Damper actuator - Motorized control valve (for water) - Motorized control valve (for steam; spring return) - Motorized control valve with flow measurement and control function (for water) Intelligent Component Series uses SA-net communication line to send and receive signal and data. The major benefit is the reduction of wiring and installation costs. Refer to page XX for more details.
(4) Security Security System
The The secu securrity ity syst system em com comprise rises s an acce access ss control system to automate passkeys, an intrusion monitoring system to detect and report intruders, an image monitoring system to monitor intruders and important facilities and an inter-phone system as an auxiliary system for access control. The BMS manages the information generated by these systems as a single unit and interlocks with other facilities. Signal exchange. [1] Secure status status mo nitoring Monitors the access/secure status of each room and zone as well as the storage status of keys. [2] Intrusion monitoring Detects intruders via security sensors and detects and monitors broken glasses and system tampering, tampering, etc. [3] Card information management Manages a variety of information on cards used for access control. [4] Access/intrusion history information management Stores information related to access control and intrusion monitoring to carry out history management.
[2] Energy Saving Applications Various types of Energy Saving Applications are used to improve energy consumption based on the result of building performance evaluation through E nergy Data S erver. Refer to “5.2 E nergy Saving Applications” (pages from 28 to 30) for more details. [3] Intelligent Component Series Products The int intelli ellige gent nt com compone ponent nt seri series es prod produ ucts cts is a sensing and control device designed especially for Energy management. The product lineup are - Room temperature sensor, - Room humidity transmitter, - Duct insertion temperature sensor,
33
[5] Air handling and and lighting interlock cont rol According to information of access control, turns on and off the air handling facilities or lighting fixtures as per occupancy status to save energy and improve convenience. The intruder alarm turns on lighting automatically to warn intruders that they have been detected. [6] Elevator Elevator non-stop control Enhances safety by controlling elevators so that they do not stop on unoccupied floors, using the information of access control
5 Control Functions
34
6 Typical ypi cal Instrumenta Instru mentatio tion n Examples
6. Typical Instrumentation Examples
6.1 6.1
Examples Examples of Automatic Contro Contro l Systems Instrumentation
(1) Air Handling Unit Cont rol(VAV) rol(VAV) sets CO2
MDF,QP
Ex.A
VAV
THED
R.A
FAN
VSD
Communication among DDC controllers COM I/F DO
2
DDCV
2
DDC DI
AO
AI 1
MDF,QP
UT
TE R dPS
MV
BV
VSD DDCV
HC
S.A FAN
O.A
TED
VAV
C
MDF,QP
1
TR 2
AT
1. Supply air temperature control Chilled/hot water valve and outdoor damper shall be controlled to keep supply air temperature set point. Heating Chilled/hot
Outdoor air damper
(%) 100 water valve
g n i n e p o e v l a V
Cooling ( ) 100 Outdoor
g n i n e p o e v l a V
Outdoor air cooling Min. opening 0
Set point
Min. opening 0
Set point
Temperature ure
2. Return air humidity control Humidification (winter) : ON/OFF humidifier shall be controlled to keep return air humidity set point. s u t a t S
ON OFF
Humidity
Set point 3. Start-up control Outdoor air damper and exhaust air damper are fully closed and return air damper is fully opened, humidifier is off during pre-cooling or preheating. 4. Interlock control Devices are interlocked with AHU status and season's information. Devices : dampers, 2-way valve, humidifier. 5. Outdoor air cooling control Outdoor air damper shall be controlled to keep supply air temperature set point when outdoor air intake is available. 6. CO2 control Outdoor air damper shall be controlled to keep CO2 concentration set point. g n i n e p o r e p m a D
Outdoor air damper
P roduct No.
Transformer Transformer
ATY72Z ATY 72Z
BV
VY630 VY 6300 0 CY8100C
DDC
Motorized ball valve Insertion CO2 CO 2 concentration concentration transmitter Digital controller for OHU
DDCV
Digital controller for VAV
WY520 WY 5206 6
dPS
Differential Differential pressure switch
PY Y-604
MDF
Damper actuator actuator
MY605 MY 6050 0 VY 5117
Set point CO2
7. Supply air volume control Necessary air volume is calculated by summing up the set point of each VAV through DDCV communication. Supply air fan VSD shall be controlled to supply necessary air volume as shown below.
WY51 WY 5111
MV
Motorized Motoriz ed 2-way valve
TE
Roomtem tempera peratu ture re sensor sensor
TY7043 TY7043
TED
Inser Inserti tion on tempera peratture ure sen sensor sor
HY7803
THED
Inser Inserti tion on tempera peratture ure sen sensor sor
HTY7803
QP
Auxiliary potentiometer
QY 9010 9010
R
Relay
⎯
TR
Tran Transfo sform rmer
AT72-J 1
UT
Digital user terminal
QY 7205 7205
t u p t u O
Min, rotation frequency Necessary air volume
8. Load reset control of supply air temperature Supply air set point is adjusted automatically according to control status of each VAV and AHU. 9. Communication with BMS 1. Room temperature control VAV shall be controlled to keep room temperature set point. Heating
0
35
Description
AT
CO2 Chilled/hot water valve
air cooling
Temper Temperatu ature
Abbreviation
Cooling
(%) 100
( ) 100
e
e
m u l o v r i A
Min. air volume
0
m u l o v r i A
Min. air volume 0
Set point
Temperature ure
Set point
Temperature
6. Typical Instrumentation Examples (2) Outdoor Air Handling Unit Control Communication with BMS
COM I/F DO
DDC DI
AO
Starts chilled water pump forcibly (individual wiring)
AI 1
R
dPS
1
MV1
MV1
C
H
MV2
BAV 2
O.A
S.A FAN MDF TED
TDED C
C TD
1
TR 2
AT
1. Supply air temperature control Chilled water valve and hot water valve shall be controlled to keep supply air temperature set point. ( ) Hot water valve g100
n i n e p o e v l a V
Chilled water valve
0
Set point
Temperature(°C)
2. Supply air dew point temperature control Humidification (winter) : Humidification valve shall be controlled to keep supply air dew point temperature set point. Dehumidification (summer) : Chilled water valve shall be controlled as dehumidification to keep supply air dew point temperature set point. Under dehumidification process, reheat control shall be activated to keep supply air temperature set point. ( ) g100
n i n e p o e v l a V
Humidification valve
Description
Product No.
AT
Transformer
ATY72Z
BAV
Motorized bore valve
VY6091
DDC
Digital controller for OHU
WY5111
dPS
Differential pressure switch
PY Y-604
MDF
Damper actuator
MY6050
MV1
Motorized 2-way valve
VY 5117
MV2
Motorized 2-way valve
VY 5118
TD
Insertion thermostat controller
TY6800
TDED
Insertion dew point temperature sensor
HTY7903T
TED
Insertion temperature sensor
HY7803
R
Relay
⎯
TR
Transformer
AT72-J 1
0
Set point ( ) Hot water valve 100
g n i n e p o e v l a V
Chilled water valve
Abbreviation
Dew point temperature( °CDP) Chilled water valve
(reheat)
0
Set point
Temperature(°C)
3. Interlock control Devices are interlocked with OHU status and season's information. Devices : O.A damper, 2-way valves, humidification valve. 4. Defect alarm of humidification valve Humidification valve defect is detected by the temperature inside OHU when OHU is off. 5. Antifreezing control Chilled water valve is fully opened when the temperature inside outdoor air duct is lower than the preset temperature. (Starts chilled water pump forcibly if it is OFF) 6. Communication with BMS
36
6. Typical Instrumentation Examples (3) Air Handling Unit Control (CAV) Communication with BMS
COM I/F DO
DDC DI
AO
AI 1
R
R
R dPS
MV
MV
C
H
BV
MDF,QP
S.A
O.A FAN
1
TED C
MDF
C 2
MDF,QP Ex.A
R.A
MDF
FAN
1
THED MDF,QP
1
TR 2
AT
1. Supply air temperature control Chilled water valve, hot water valve and outdoor air damper shall be controlled to keep supply air temperature set point. Outdoor air damper
Hot water
(%) valve g100
n i n e p o e v l a V
Chiller water valve
Outdoor air cooling Min. opening
0
Set point
Temperature
2. Return air humidity control Humidification (winter) : ON/OFF humidifier shall be controlled to keep return air humidity set point. Dehumidification (summer) : Chilled water valve shall be controlled as dehumidification to keep return air humidity set point. Under dehumidification process, reheat control shall be activated to keep supply air temperature set point.
s u t a t S
ON
Chilled water valve
Humidifier
(%) 100
g n i n e p o e v l a V
OFF 0
g n i n e p o e v l a V
Set point Hot water valve (%) (reheat) 100
Humidity Outdoor air damper
Chiller water valve
Outdoor air cooling Min. opening 0
Set point
Temperature
3. Start-up control Outdoor air damper and exhaust air damper are fully closed and return air damper is fully opened, humidifier is off during pre-cooling or preheating.
37
Abbreviation
Description
Product No.
AT
Transformer
ATY72Z
BV
Motorized ball valve
VY6300
DDC
Digital controller for OHU
WY5111
dPS
Differential pressure switch
PY Y-604
MDF
Damper actuator
MY6050
MV
Motorized 2-way valve
VY 5117
QP
Auxiliary potentiometer
QY 9010
R
Relay
⎯
TED
Insertion temperature sensor
HY7803
THED
Insertion temperature sensor
HTY7803
TR
Transformer
AT72-J 1
4. Interlock control Devices are interlocked with AHU status and season's information. Devices : dampers, 2-way valves, humidifier. 5. Outdoor air cooling control Outdoor air damper shall be controlled to keep supply air temperature set point when outdoor air intake is available. 6. Heat exchanger control Intermittent timer control shall be activated when outdoor air intake is available. 7. Communication with BMS
6. Typical Instrumentation Examples (4) Fan Coil Unit Contr ol (zone contro l)
CHS CHR MV
HC
Communication with BMS
FAN
HC
HC
FAN
FAN
C
C
C
DDCF
LAN cable
R (x3)
UT
・Display ・Setting ・ON/OFF ・Air volume
TE
TR
changeover
Abbreviation
Description
Product No.
DDCF
Temperature controller
WY5205
MV
Motorized 2-way valve
VY5120
R
Relay
⎯
TE
Roomtemperature sensor
TY7043
TR
Transformer
AT72-J 1
UT
Digital user terminal
QY7205
1. Room temperature control 2-way valve shall be controlled to keep room temperature set point. 2. Fan ON/OFF operation ON/OFF operation of fan coil unit is done by user terminal (UT ). 3. Interlock control Devices are interlocked with FCU status. Devices : 2-way valve. 4.Heating/cooling changeover Heating/cooling changeover command comes from BMS. 5. Communication with BMS
(5) Fan Coil Unit Control (DDC) Abbreviation
Description
Product No.
DDCF
Temperature controller
WY5205
MVV
Motorized 2-way valve
VY5502 +MY5560C
TE
Roomtemperature sensor
TY7043
UT
Digital user terminal
QY7205
HR HS CR
Communication with BMS CS
DDCF DDCF MVV
MVV C
H
C
C
FAN
MVV
C
H
C
C
MVV
FAN
LAN cable
TE
UT
・Display ・Setting ・ON/OFF ・Air volume
changeover
1. Room temperature control 2-way valve shall be controlled to keep room temperature set point. 2. Fan ON/OFF operation ON/OFF operation of fan coil unit is done by user terminal (UT ). 3. Interlock control Devices are interlocked with FCU status. Devices : 2-way valves. 4. Fan coil unit interlock by network communication Group operations of fan ON/OFF, valve control and air volume changeover are done by network communication. 5. Communication with BMS
38
6. Typical Instrumentation Examples (6) Heat Pump Package Control (water humi difi cation)
Communication with BMS
S.A
COM I/F DO
Description
Product No.
AT
Transformer
ATY72Z
BV
Motorized ball valve
VY6300
DDC
Digital controller for package
WY5111
MDF
Damper actuator
MY6050
THE
Room temperature and humidity sensor
HTY7043
TR
Transformer
AT72-J 1
R
Relay
⎯
DDC DI
AO
AI
FAN 2
1. Room temperature control ON/OFF compressor shall be controlled to keep room temperature set point. 2. Room humidity control ON/OFF humidifier shall be controlled to keep room humidity set point. 3. Start-up control Outdoor air damper is fully closed and humidifier is off during pre-cooling or preheating. 4. Interlock control Devices are interlocked with PAC status and season's information. Devices : O.A damper, humidifier. 5. Communication with BMS
THE
BV
R.A
Abbreviation
R 1
O.A H.P
1
MDF
TR 2
AT
(7) Package Control (steam humidification) Communication with BMS
S.A
COM I/F DO
DDC DI
AO
Abbreviation
Description
Product No.
AT
Transformer
ATY72Z
DDC
Digital controller for package
WY5111
LT
Limit controller
L4029E
MDF
Damper actuator
MY6050
THE
Room temperature and humidity sensor
HTY7043
TR
Transformer
AT72-J 1
R
Relay
⎯
AI
2
FAN THE LT Humidifier
R.A
E
H
SCR
R C
1
DX
O.A COMP
MDF
1
TR 2
AT
39
1. Room temperature control ON/OFF compressor and proportional SCR shall be controlled to keep room temperature set point. 2. Room humidity control Steam humidifier shall be controlled to keep room humidity set point. 3. Interlock control Devices are interlocked with PAC status and season's information. Devices : O.A damper, SCR, steam humidifier. 4. Overheat protection of heater Electric heater is forced off if the temperature in PAC casing increases abnormally. 5. Communication with BMS
6. Typical Instrumentation Examples (8) Chiller Plant System Control (1-pump s ystem) Communication with BMS
HC
COM I/F
C
DO
PMX DI
AO
AI
TEW
FM dPEW TEW
TEW
MV
Temperature Chiller TEW
TEW Temperature Chiller
TEW
TEW Temperature Chiller
TEW
TEW Temperature Chiller
TEW
TEW
TR
:Monitored by BMS
1. Sequence control of chiller (1)Chiller number control Number of chiller is calculated according to load flow rate and sequence control is done followed with setting table as shown below diagram.
Abbreviation
Description
Product No.
DC
DC 24V power supply
RY Y792D
dPE W
Differential pressure transmitter
J TD
Electromagnetic flow meter
MGG10C/ MGG11
MV
Motorized 2-way valve
VY 5113J
PMX
Digital controller for chiller plant system
WY2001Q
TEW
Pipe insertion temperature sensor
TY7830B
TR
Transformer
AT72-J 1
FM d e t a r e p o r e l l i h c f o . o N
NO.1,2,3,4
NO.1,2,3
NO.1,2
NO.1
NO.1 rated capacity NO.1,2,3 rated capacity NO.1,2 rated capacity
Flow rate
(2)Rotation control Rotation function shall be incorporated in this sequence control to equalize running time of chiller. (3)Skip control Defected chiller shall be excluded from sequence control by automatically. (4)Number calculation compensation Running number of chillers shall be adjusted by supply temperature (above set point) and return header temperature (below set point).
2. Header bypass valve control Proportional header bypass valve shall be controlled as shown below, to keep constant the differential pressure between headers. (However, bypass valve is fully opened when the pumps are all off.) To avoid sudden increase in pressure, bypass valve is forced open before the batch ON command or the increase in number of operating equipment. g n i n e p o e v l a V
Bypass valve opening
0 SP
Differential pressure
3. Communication with BMS
40
6. Typical Instrumentation Examples (9) Chiller Plant System Control (2-pump s ystem) HC
C
Communication with BMS COM I/F
TEW PEW
DO
Communication with BMS COM I/F
PMX DI
AO
DO
AI
VSD (x4)
PMX DI
AO
AI
FM MV TEW TEW
Temperature Chiller TEW
TEW
Temperature Chiller TEW
TEW
Temperature Chiller TEW
TEW
Temperature Chiller TEW
TEW
TR
:Monitored by BMS VSD
1. Sequence control of chiller (1)Chiller number control Number of chiller is calculated according to load energy and sequence control is done followed with setting table as shown below diagram. d e t a r e p o r e l l i h c f o . o N
NO.1,2,3,4
Description
DC
DC 24V power supply
RY Y792D
FM
Electromagnetic flow meter
MGG10C/ MGG11
MV
Motorized 2-way valve
VY 5113J
Pressure transmitter
J TG
PMX
NO.1,2
PMX
NO.1
NO.1 rated capacity NO.1,2,3 rated capacity NO.1,2 rated capacity
Load energy
(2)Rotation control Rotation function shall be incorporated in this sequence control to equalize running time of chiller. (3)Skip control Defected chiller shall be excluded from sequence control by automatically. (4)Number calculation compensation Running number of chillers shall be adjusted by supply temperature (above set point) and return header temperature (below set point). 2. Sequence control of secondary pump (1)Secondary pump number control Number of secondary pump is calculated according to load flow rate and sequence control is done followed with setting table as shown below diagram. d e t a r e p o r e l l i h c f o . o N
Abbreviation
PE W
NO.1,2,3
:Communication with BMS
Product No.
Digital controller for chiller plant system Digital controller for dual-pump system
TEW
Pipe insertion temperature sensor
TY7830B
TR
Transformer
AT72-J 1
(2)Rotation control Rotation function shall be incorporated in this sequence control to equalize running time of pump. (3)Skip control Defected pump shall be excluded from sequence control by automatically. 3. Pressure control of supply water VSD and bypass valve shall be controlled by supply water pressure as shown below. VSD output(%) 100
Bypass valve
100
0
0 SP
Pressure
NO.1,2,3
SP of pressure
NO.1,2 NO.1
41
WY2001P
4. Estimated end pressure control during low load operation Set point of supply water pressure is adjusted automatically by load flow rate, in order to reduce conveyance power during low load operation.
NO.1,2,3,4
NO.1 rated capacity NO.1,2,3 rated capacity NO.1,2 rated capacity
WY2001Q
Load flow rate
0
Flow rate Rated water volume of 1 pump Rated water volume of 2 pumps 5. Communication with BMS
6. Typical Instrumentation Examples (10) System Configu ration Diagram Building Management System MS LCD User PC
KB CLP
PC P
SMS
DSS
IPv4/v6 Network (BACnet)
SCS
Converter (Ethernet/RS-485 conversion)
SCS
RS-485
NC-bus/LC-bus
NC-bus/LC-bus Individual Wiring Substation
RS
Sensor
Power Panel
Controller, Power Meter
Flow meter
PMX
Valve Chiller Plant Control
Individual Wiring RS
Other Manufacturer's BACnetDevices
DDC
Sensor・Setter Valve AHU C ontrol
Individual Wiring Distribution Panel
RS
ZM
UT
RS
SC-bus
Individual Wiring Auxiliary Panel
Lighting System Interface
Sensor・Setter
DDCF
Valve FCU Control Sensor・Setter
DDCV UT
VAV VAV C ontrol
Building Multi System Interface
BMIF
RS-232C
RS-232C
HVAC ・Plumbing・Electricity
A C/ GC V A Individual grounding (class D)
Primary power failure alarm Battery low alarm Failure Fire AlarmPanel Substation, generator
Power supply to ※
Distribution Circuit
UPS kVA
P
mark
Power supply to ※ mark To SCS
Relay Circuit RS
Fire Signal
Relaytimercircuit for power failure/ restoration judgment
Power supply status Switching breaker of generator-commercial power Electric work
To SCS(Power supply status of AC/GC and generator)
SystemControl Panel
Referential Outlook and Dimension
3kVA Backup 10 minutes 400
700 SP
SP
0 0 8
220
KB
530
MS
0 0 5
1400 0 5 9 1
CLP LCD
PC
0 0 7
0 5
42
6. Typical Instrumentation Examples Buil ding Management Syst em Hardw are Specific ations (1/2) Symbol PC
LCD (PC)
Name Client PC
Color Graphic Display
Description Display and operation of system management information, setting and changing of various programs are done through Web browser. A mouse is used for screen selection and operation.
As the main display unit, LCD displays various lists and graphics. It can display graphics, data simultaneously with multi windows.
Specifications CPU Main storage capacity HDD CD-ROM drive Power OS Web browser J AVAvm1.4 embedded SVG Viewer3.0 and above embedded・XGA support Adobe Reader 6.0 and above embedded Mouse(MS)
Size Display colors Display characters Resolution
DSS
Data Storage Server
Performs the overall system management,periodical data collection, data storage, data processing, etc. It also controls input/output of peripheral devices.
CPU Main storage capacity OS HDD Max. data points Power
SMS
System Management Server
Performs display, setting and operation of theoverall system management information (graphics, points, programs, etc.) through web browser software of the client PC.
CPU Main storage capacity OS HDD Max. data points Power Number of graphics
SCS
System Core Server
Performs data transmission with RS and DDC, manages point data and schedule control. It also stores trend data.
CLP
Color Printer
Prints various data as follows. 1. daily, monthly and yearly reports 2. trend data 3. various lists (alarm dashboard) 4. maintenance messages 5. screen
IPv4/v6 Network
Backbone network of BMS for data transmission. It has transmission protocols such as IEIEj/p BACnet, HTTP, etc.
UPS
Uninterruptible Power System
NC-bus
New Controller Bus
43
Provides uninterruptible power to client PC, servers and other necessary terminal transmitters.
Transmits data between BMS and terminal transmitters.
: P entium4 3.0GHz and above : 512MB and above : 40GB and above : 24-speed and above : AC100/200V +/-10%, 50/60Hz : WindowsXP : IE6.0
: optical
: 17 / 19 inch type : 16190000 colors and above : Alphanumeric, Kana, Hiragana, Kanji (J IS level 1st& 2nd), symbols and drawings : 1024x768 / 1280x1024 pixels : 32-bit : SDR AM 256MB : Linux : 40GB (24-hour run) : 2000/5000/10000/20000/ 30000 objects : AC100/200V +/-10%, 50/60Hz, 50VA : 32-bit : SDR AM 256MB : Linux : 40GB(24-hour run) : 2000/5000/10000/20000/ 30000 objects : AC100/200V +/-10%, 50/60Hz, 50VA : graphics
CPU Main storage capacity OS Max. data points Communication line Power
: 32-bit : SDR AM 128MB : Linux : Max. 1000 objects/unit : 4 lines/unit : AC100/200V +/-10%, 50/60Hz, 70VA
Printing method Printing color Paper size Power Temperature condition Connection
: S emiconductor laser : Full color : A4 : AC100/200V +/-10%, 50/60Hz : 10-35℃ : IPv4/v6 network
Communication method Communication speed Wiring Input Output Time backup Battery type Backup method Communication method Communication speed Wiring
: Ethernet, TCP/IP protocols, IPv4 or IPv6 : 10Mbps, 100Mbps : 100BASE-TX, 100BASE-FX : AC/GC V A : AC V A : minutes : Compact size sealed lead-acid : Online power system : Private communication : 4800bps : IPEV-S 0.9-1P (twisted pair cable)
6. Typical Instrumentation Examples Buil ding Management Syst em Hardware Specificati ons (2/2) Symbol
Name
Description
Specifications
LC-bus
LonTalk Protocol Controller Bus
Transmits data between BMS and terminal transmitters.
Communication method Communication speed Wiring
: Lon-Talk protocol : 78kbps : Lan cable, connector joint (category 3-5 0.5φ*4P in conformity with EIA568)
SC-bus
Sub Controller Bus
Transmits data between ZM and terminal transmitters.
Communication method Communication speed Wiring
: Private communication : 4800bps : Lan cable, connector joint (category 3-5 0.5φ*4P in conformity with EIA568)
Installed in local place and transmits data with BMS. RS and input/output devices are connected with individual wires.
Input/output points Power Communication method
: Refer to point summary : AC100/200V +/-10%, 50/60Hz : Private communication/Lon-Talk
RS
Terminal Transmitter
DDC
AHU Controller
Performs AHU control and transmits data with BMS.
Input/output points Control items Power Communication method
: Refer to point summary : Refer to control diagram : AC100/200V +/-10%, 50/60Hz : Private communication/Lon-Talk
PMX
Chiller Plant Controller
Performs control of chiller plant systemand transmits data with BMS .
Input/output points Control items Power Communication method
: Refer to point summary : Refer to control diagram : AC100/200V +/-10%, 50/60Hz : Private communication/Lon-Talk
Coordinates with BMS to manage DDCV (VAV controller) and DDCF (FCU controller).
Connectable number Power
: 50 units(DDCV, DDCF)/ZM : AC24V +/-15% / AC100V-200V, 50/60Hz : Private communication/Lon-Talk
ZM
Terminal Transmitter
Communication method
BMIF
Building Multi Interface
Communicates between building multi system and BMS, transmits data of ON/OFF command, status, alarm, temperature setting and measurement.
Input Communication method Communication procedure Communication speed Power
: Max. 64 systems : P olling/Selecting method (equal to J ISIIX5002) : 4800bps : AC100/200V +/-10%, 50/60Hz, 20VA
RU-L
Lighting Interface
Communicates between lighting system and BMS, transmits data of ON/OFF command, status, and schedule management.
Input Communication method Communication procedure Communication speed Power
: Max. 64 systems : P olling/Selecting method (equal to J ISIIX5002) : 1200bps : AC100/200V +/-10%, 50/60Hz, 20VA
DDCV
VAV Controller
Performs VAV control and transmits data with BMS.
Power Communication method
: AC24V +/-15% / AC100V-240V, 50/60Hz : Private communication
DDCF
FCU Controller
Performs FCU control and transmits data with BMS.
Power Communication method
: AC100V-240V, 50/60Hz : Private communication
UT
Digital Operating Unit
Communicates with BMS, DDC, etc., transmits data of ON/OFF command, temperature display, setting, overtime running request schedule adjustment. It is possible to restrict on the access by using a password.
Operating target Display Operation Power
: 4 zones/unit : LCD : Touch panel : AC24V +/-15%, 50/60Hz, 1.5VA
44
6. Typical Instrumentation Examples Buil ding Management Syst em Software Specific ations (1/3) 1. System overview Building management system (BMS) is set in ,performs efficient management, monitoring, control of various equipments such as chiller plant, HVAC, plumbing, electricity receiving and transforming, lighting, fire-prevention, etc., in order for laborsaving, energy saving, security and comfortable environment. BMS is a risk distribution system that even a trouble occurs at a part of BMS, the performance of other part is hardly affected. • BMS is composed of BA servers and client PC. OS of the servers is Linux with consideration for stability, capability and better security. • IP v6 network configuration responding to future extension. • Any PC can be man-machine interface (monitor) as long as it has web browser software and appropriate configurations. (Refer to hardware specifications for the details.) • User can modify the graphics easily.
2. Basic functions 2-1. Common functions (1) Operating methods Operating by mouse and keyboard. (2) Operator access control Max. 200 pairs of user ID and password can be registered with various access limitation (operable/display only/undisplayable) to each function. User authentication is not necessary for the client PC assigned a special IP address (3) Segregation name settings Points can be divided up to 32 segregations (by equipment, system, place, building, etc.) with different access limitations on point operation, alarm display, buzzer sound for each user. Screen display and buzzer sound are easy to set. (4) Module status monitoring The status of system modules is monitored constantly. Alarm is notified whenever a trouble occurs. (5) Remote unit status monitoring The status of remote units is monitored constantly. Alarm is notified whenever a trouble occurs. (6) Register maintenance Maintenance-registered points are removed from monitoring, control, schedule targets. An indicator is shown on the screen during maintenance. (7) Alarm transmission Outputs point alarm by contact output. 2-2. Monitoring (1) Status monitoring It is possible for the user to monitor point status, measured value and totalized value constantly. (2) Alarm monitoring It is possible for the user to monitor alarm occurrence, recovery of points and system devices constantly. The latest alarm information is displayed in new alarm area along with indicator blinking, buzzer sound (4 kinds), voice message (90 kinds), forced graphic display and forced guidance display when point alarm occurs. (3) ON/OFF mismatch / status mismatch monitoring Alarm occurs when • Point status does not change when a fixed period has elapsed after the issue of ON/OFF command from BMS. • Point status does not match the ON/OFF command from BMS. (4) High/Low limit monitoring of measured value Alarm occurs when the measured value deviates from the specified range of High/Low limit value. (5) Batch setting on High/Low limit monitoring of measured value It is possible to perform batch setting on the set points of High/Low limit monitoring of multiple measured values. (6) Deviation monitoring of measured value Alarm occurs when the deviation between measured value and set point exceeds the specified value. (7) Batch setting on deviation monitoring of measured value It is possible to perform batch setting on the set points of deviation monitoring of multiple measured values.
45
2-3. Display (1) Multi-window display Max. 3 windows can be displayed simultaneously. (2) Sequential screen display Group list, trend graph, control screen are displayed automatically in a predetermined sequence besides graphics. (Max. 100 screens/sequence, Max. 20 sequences) Time display and screen hardcopy (J PEG format) can beset also. (3) Screen scroll function This function helps to scroll the display of window vertically and horizontally when the range for display exceeds the window size. (4) New alarm display Displaying the latest alarm contents in new alarm display area. (5) Graphic display Graphic displays the point information in the building. Screen size can be enlarged or reduced randomly. Graphic displays the point status by symbol color change, figuration switching, animation at the time of status change or alarm occurrence. The associated graphic is forced to display at the time of alarm occurrence. Live-wire symbol is used for electricity receiving and transforming equipments, etc. • Animation: displays point status and alarm occurrence by symbol motion. • Live-wire: color indication of piping, wiring. Graphic displays measured value・totalized value by numeric value, gradation, meter indication, level symbol, which are updated periodically. • Gradation: color indication of temperature distribution • Meter indication: displays measured value by analog meter • Level symbol: level indication of measured value Graphic can also realize that • Screen transition • Photographic data insertion (6) Graphic modification This function helps to • change the layout and name of the room • change background color • change and plug in various symbols • generate a new graphic (7) Point list display Point information is listed by group, alarm occurrence, ON status, OFF status, maintenance, trouble. It is possible to operate ON/OFF command and setting on multiple points simultaneously in the same list, as well as outputting a list in PDF file and printing. (8) Time program list This function helps to display the ON/OFF time setting of registered time programs in a list. Representative point status (normal/alarm, ON/OFF) can be used to display the status of time program. (9) Point search This function helps to display and print the necessary point information in list format, according to the attribute information of the point. (10)Point guidance This function provides detail comment (such as the treating method or contact address) automatically at the time of alarm occurrence. (11)Point details display Point detail information is displayed from graphic screen directly. It includes point information, point registration, runtime data, trend graph for the past 48 hours, schedule of status and measured value. (12)Screen history display It is used to display the 20 previously displayed screens after login. (13)User menu settings The screens displayed frequently are registered in the user menu for quick selection. The associated screens can be grouped into categories and displayed hierarchically according to equipment type / floor for each user. Furthermore, it is possible to display any 3 screens on the system menu display area as shortcuts. (14)Infilex (IP type) point list screen display I/O information can be displayed on the point list screen by accessing the IP controller directly.
6. Typical Instrumentation Examples Buil ding Management Syst em Software Specific ations (2/3) 2-4. Operation (1) Individual ON/OFF operation・set point change It is possible to operate individual ON/OFF and change set point by selecting a point from associated graphic or list. When multiple ON commands are issued simultaneously, the ON commands will take effect one after the other with a fixed time delay. 3-action operation (operate-confirm-run) is executed for important equipment instead of usual ON/OFF operation (operate-run). The confirmation message gives a caution to operator in the 'confirm' step. (2) Preset of totalized value It is possible to preset the totalized value and runtime. 2-5. Print (1) Screen print It is possible to print and spool the currently displayed screen by using a specified printer.
3. Control functions 3-1. Common (1) Calendar control It is possible to specify normal days, holidays, special days 1 and special days 2 till for 2 years ahead. (2) Time program control ON/OFF operation of the equipment registered in time program is executed automatically in a predetermined schedule. There are 2 kinds of schedules, that is, priority schedule and execution schedule. ON/OFF time is specified for the 4 kinds of calendar days in a priority schedule and the execution schedule for the next 1 week from the current date can be created according to calendar information and priority schedule. ON/OF F time change can be executed on execution schedule. It is possible to set ON/OFF operation up to 8 times a day. (3) Batch setting of time program control It is possible to perform batch setting on multiple priority schedules. (4) S chedule composition This function is used to generate a single time schedule from multiple schedules for the ON/OFF operation of the communal equipment. (5) Interlock control This function helps to operate the target equipment to a desired status (ON/OFF, etc.) with the conditions of point status change or alarm occurrence, etc. (6) Numeric operation This function performs the four arithmetic operations for totalized value and measured value, and outputs the calculation result to a point. (7) Logical operation This function performs the logical operations for the input status of multiple points and outputs the result to a point. (8) Add-subtract operation of totalized value It is possible to perform add-subtract operation on multiple totalized values and output the result to a data point. 3-2. HVAC (1) Seasonal changeover control This function performs the seasonal changeover (mode switching on the season) automatically at the specified date. There are 4 modes which are fan, cooling, heating and cooling/heating. Forced manual changeover operation is also available. (2) Batch setting of seasonal changeover control It is possible to perform batch setting on multiple seasonal changeover. (3) Set point schedule control It is possible to change the set value of the set point automatically according to the schedule per annum. (4) Batch setting of set point schedule It is possible to perform batch setting on multiple set point schedules. (5) OptimumON/OF F control (pre-cooling, pre-warming control) This function estimates the attribute of room temperatureraise/fall to perform the optimum ON/OFF control of AHU. Holiday compensation, consecutive holidays compensation and abnormal data compensation are available. • Holiday compensation: early start of the AHU if it did not work in the previous day. • Consecutive holidays compensation: early start of the AHU according to the days the AHU has been switched OFF. • Abnormal data compensation: learning is not performed when measured input is abnormal.
(6) Chiller optimumON/OFF control This function refers to the estimated optimum ON/OFF time of the AHU, starts the chiller earlier than the optimum start time of the earliest AHU, and stops the chiller earlier than the optimum stop time of the latest AHU within the same chiller system. Earlier start and stop time is up to 120 minutes against target time. (7) Duty cycle control This function calculates the optimumstop time of AHU, etc. to perform duty cycle control while maintaining a comfortable environment. (8) Cold air intake control Proportional control of cold air intake damper is executed when outdoor air cooling is effective, which is evaluated by the comparison of outdoor temperature, return (room) enthalpy and dry-bulb temperature (9) Optimum room temperature setting This function calculates PMV value and change the set point of room temperature automatically for energy-saving. PMV value can be set up according to operating mode (energysaving/normal/comfortable). PMV value is calculated according to room temperature, window radiant temperature (measured value/calculated value), room relative humidity, air draft (set value), activity (set value varying with time), amount of clothing (set value varying with month). (10)Duty cycle program with power demand function This function compares the estimated demand value with the target power to perform duty cycle control of AHU, etc. while maintaining a comfortable environment. It is possible to set different temperature value for normal day and holiday. 3-3. Electricity (1) Power failure control Alarm notification is given through buzzer sound and blinking of the power failure indicator, status mismatch alarm is withheld and general control retention is performed during commercial power failure. However, fire process and manual operation are available. (2) Sequential start control when generator works Startup is output one by one to the registered equipments when detecting startup of the generator. (3) Generator load distribution control This function keeps the power load within the power capacity of the generator. Power is connected to the units in order of priority level (15 levels). (4) P ower restoration control Power restoration control is executed by automatic or manual power restoration command after commercial power restored. ON/OFF command is executed according to point status before power failure and general control retention during power failure. (5) Power demand monitoring Estimating power demand value of 30 minutes interval. Alarm occurs if the estimated power demand or real power demand exceeds the target power with the blinking of indicator. Synchronization with the supply demand meter is based on the external input or screen operation. (6) Power demand control This function estimates the usage of power at intervals, decides the necessity of interruption/recovery of load in order of priority level (15 levels). It is also possible to increase or decrease the analog output ratio of the inverter. (7) Power demand history This function helps to store the power demand control results as history data, display the target value and demand value. • Daily data: past 13 months at 30 minutes interval • Monthly data: past 13 months at 1 day interval History data can be output in CSV format. (8) Power factor improvement control It is the function to improve power factor by recover or interrupt the phase advance capacitor, according to the values of power factor (reactive power) and active power. 3-4. Fire-prevention (1) Fire process Alarm notification is given through buzzer sound, blinking of the fire indicator and display on alarm dashboard with input of fire. It is also possible to stop the associated equipments (AHU, etc.) automatically by the input fire signal. The priority of fire process is higher than other controls at this time. Furthermore, fire cancellation is done only by manual operation.
46
6. Typical Instrumentation Examples Buil ding Management Syst em Software Specific ations (3/3) 3-5. Security (1) Security interlock This is a event program that stops AHU, etc. with the security status of security system automatically.
4. Data management functions 4-1. Data management (1) Runtime monitoring and ON/OFF counting Runtime and on-off cycle count of the equipment are totalized and displayed in the point operation screen. The equipment that exceeds a certain value of runtime/On-Off cycle count is displayed in the list ('Maintenance Notification' in indicator area). In addition, it is possible to output the list in PDF format. (2) Daily report, monthly report, yearly report It is possible to display the measured value and totalized value in the specified format. (Daily report: pages, monthly report: pages, yearly report: pages) The maximum value, minimum value and mean value can also be displayed if necessary. In addition, it is possible to output the report in PDF format automatically or manually. The time range for manual print is shown as below. • Daily report: past 13 months • monthly report: past 10 years • yearly report: past 10 years Point data can also be output in CSV format. (3) Trending Measured value, totalized value and time series change of equipment operation status are stored for a fixed period and can be displayed on trend graph (broken line) and bar graph (bar graph/laminated graph). Trend graph: sheets. 1 sheet can display max. 2/8 points. (Max. 2/8 axes in 1 graph) Trend data is stored as follows. • 1 minute data: past 40 days • 1 hour data: past 13 months • 1 day data: past 10 years • 1 month data: past 10 years (4) Alarm dashboard Alarm dashboard displays the alarm, status change, operation settings, unacknowledged alarm in order of year/month/day/hour/minute/second in a list. It is possible to extract and display part of the list by type filtering. It also supports string search, time search and comment input. In addition, it is possible to output the list in PDF format automatically or manually, as well as CSV format.
47
(5) User data processing This function helps to output the gathered trend data in CSV format automatically or manually. (6) Overtime running This function regulates the overtime running time on client PC. Request operation of overtime running can be performed from the user operable equipment or client P C for each request unit. The log of overtime running request is stored, that is also used for summary process. In addition, it is possible to output the list in PDF format. (7) Meter reading This function collects the meter reading values of power, gas, water supply at the specified date and calculates the monthly or bimonthly consumption, which is used to list and display the meter reading result of each meter, system or tenant. Abnormal value detection according to the comparison with the last consumption ratio and manual modification are available. It is possible to output the list in PDF and CSV formats. • Data points: Max. 200/500/1500 meters In addition, output of a meter reading result file before report print can be used for confirmation. (8) Real time trending This function supports high-speed storage of measured value at 1/2/3/5/10/30 seconds interval and display of time series trend graph. A trend graph can display max. 8 data points. The limitation on the number of analog points, data, graphics is shown as below. • Max. 100 points/P-SCS, Max. 20 points/SCS • Max. 6000 data/point • Trend graph:40/100 sheets (9) Runtime display It is possible to output totalized runtime of the equipment to a data point. (10) Overtime totalization It is possible to output totalized overtime of the equipment to a data point.
6. Typical Instrumentation Examples
48
6. Typic al Instru mentation Examples Point Summary Li st (reference only) (1/2) T N L E O M B P I M Y U S Q E
POINT NAME
L E C I N T A P A L M O O T R T U N A O C
E T C U P R U T O U S O / L T A U P N G N I I S
OPERATION , S F G F N I F U F T O T O A / T / T N E N S O O S
DISPLAY S U T A T S
M R A L A
ANALOG . P M E T
. I M U H
S T R O E T H T O
VCB
1RS-1
LV panel
1
Over current
1RS-1
LV panel
1
Low voltage
1RS-1
LV panel
1
Current
1RS-1
LV panel
1
Voltage
1RS-1
LV panel
1
Power factor
1RS-1
LV panel
1
Power
1RS-1
LV panel
1
Reactive power
1RS-1
LV panel
1
Integral power
1RS-1
LV panel
Auto/manual
1RS-1
LV panel
1
Start/stop
1RS-1
GE panel
1
MCCB
1RS-1
GE panel
Over current
1RS-1
GE panel
1
Over voltage
1RS-1
GE panel
1
Major failure
1RS-1
GE panel
1
Minor failure
1RS-1
GE panel
1
Auto/manual
1RS-1
GE panel
1F lighting
1RS-1
1L-1
20
2F lighting
2RS-1
2L-1
20
1
1
1
R-1,2
Chiller batch ON/OFF
1CP-1
R-1
Chiller No.1
1CP-1
R-1
1
1
R-2
Chiller No.2
1CP-1
R-2
1
1
CP -1
Primary pump No.1
1CP-1
1M-1
1
1
CP -2
Primary pump No.2
1CP-1
1M-1
1
1
Chiller outlet temperature
1CP-1
Sensor
2
Chiller inlet temperature
1CP-1
Sensor
2
Supply header temperature
1CP-1
Sensor
1
Return header temperature
1CP-1
Sensor
1
Return temperature
1CP-1
Sensor
1
Instantaneous flow rate
1CP -1
Flow meter
1CP-1
Flow meter
Totalized flow rate
49
1
1 1
S K R A M E R
6. Typical Instrumentation Examples Point Summary Li st (reference only) (2/2) T N L E O M B P I M Y U S Q E
POINT NAME
L E C I N T A P A L M O O T R T U N A O C
E T C U P R U T O U S O / L T A U P N G N I I S
OPERATION
DISPLAY
ANALOG
, S F G F N I F U F T O T O A / T / T N E N S O O S
T S M . I . S R O U R P T A M M E T A L E U H T H T S A T O
S K R A M E R
OHU-1
OHU-2
Outdoor air handling unit (1F)
1CP-2
1M-2
1
1
Supply air temperature
1CP-2
Sensor
1
Supply air dew point temperature
1CP-2
Sensor
1
Outdoor air duct temperature
1CP -2
Sensor
1
Filter alarm
1CP-2
Sensor
1
Humidification valve defect
1CP-2
Sensor
1
Outdoor air handling unit (2F)
2CP-1
2M-1
Supply air temperature
2CP-1
Sensor
1
Supply air dew point temperature
2CP-1
Sensor
1
Outdoor air duct temperature
2CP -1
Sensor
1
Filter alarm
2CP-1
Sensor
1
Humidification valve defect
2CP-1
Sensor
1
Air handling unit (1F hall)
1CP-2
1M-3
Return air fan
1CP-2
1M-3
Supply air temperature
1CP-2
Sensor
1
Return air humidity
1CP-2
Sensor
1
Return air temperature
1CP-2
Sensor
CO2 concentration
1CP-2
Sensor
Supply air fan VSD speed
1CP-2
1M-3
1
Return air fan VSD speed
1CP-2
1M-3
1
Room temperature
1CP-2
Sensor
Filter alarm
1CP-2
Sensor
1
Humidification valve defect
1CP-2
Sensor
1
VAV
1CP-2
DDCV
10
Fan coil unit (1F)
1CP-2
DDCF
10
Room temperature (1F)
1CP-2
DDCF
Fan coil unit (2F)
1CP-2
DDCF
Room temperature (2F)
1CP-2
DDCF
2CP -1
Sensor
1 1 1
1
1 1 1 1
AHU-1
1
1 1
1 1 1 1
1
1
5
5
10
10
10 10
Outdoor air temperature and humidity
1
1
50
6. Typic al Instru mentation Examples Hardware Interface (1/2) I/O items
ON/OFF, status, alarm Instantaneous contact output
Remote unit (RS) (DDC) (PMX)
ON/OFF, status
Input DI
ON
Instantaneous contact output Input DI
DI
OFF
ON IN
COM
IN
OFF
COM
COM
24VAC/DC
IN
24VAC/DC
Wiring
CX
TX
Local Equipments Electric, HVAC, Plumbing, others
Local
52X
52
TX
Local
Remote
OFF
Operation circuit
CX
51X
ON
TX CX
52
I/O items Remote unit (RS) (DDC) (PMX)
Remote
OFF
Operation circuit
52X
ON
52
52X
52
51
Remarks
52X
TX CX
52X 52X
51
a-a contact 1.Contact for status confirmation uses auxiliary relay(52X). 2.Remote auxiliary relay(CX, TX) has spark killer.
ON/OFF, status
ON/OFF, status(lighting)
Continuous contact output Input
Remote control pulse output
ON/OFF, status, alarm Continuous contact output DI
Input
a-a contact 1.Contact for status confirmation uses auxiliary relay(52X). 2.Remote auxiliary relay(CX, TX) has spark killer.
DI
DI
ON OFF
ON
ON OFF IN
COM
IN
COM
24VAC/DC
COM
IN
OFF DI
24VAC/DC
Wiring White
Red Locals witch
CX
Local Equipments Electric, HVAC, Plumbing, others
52X
Local OFF
Operation circuit
52
51
OFF
CX
Operation circuit 52X
51
Remarks
52X
Local
Remote
ON
52
CX
51X
1.Contact for status confirmation uses auxiliary relay(52X). 2.Remote auxiliary relay(CX) has spark killer.
52
Remote CX
l o r t n o e c m e r t o f o s m e n a r R t
AC 24V 1.5A
OFF
ON
ON Blue 52
52X
51
1.Contact for status confirmation uses auxiliary relay(52X). 2.Remote auxiliary relay(CX) has spark killer.
Blue
l o r t n o c e t o y m a l e e R r
6. Typical Instrumentation Examples Hardware Interface (2/2) I/O items Remote unit (RS) (DDC) (PMX)
Status, alarm
Status
Alarm
TOT(pulse) input
TOT(pulse) input
Contact input
Contact input
Contact input
No-voltage contact pulse
No-voltage contact pulse
DI
IN
DI
DI
IN
COM
COM
COM
IN
COM
TOT
TOT
DI
IN
COM
IN
Wiring Local Equipments Electric, HVAC, Plumbing, others
Remarks
52X
51X
Status contact Alarm contact
1.Input No-voltage a continuous contact 2.Circuit voltage, current DC12V, 10mA
52X
Status contact
51X
Alarm contact
1.Input No-voltage a continuous contact 2.Circuit voltage, current DC12V, 10mA
Totalizing 1.Input 12VDC, 10mA 2.Input condition ON time over 30ms OFF time over 30ms ON+OFF time over 100ms
Totalizing(for water meter) 1.Input 12VDC, 10mA 2.Input condition ON time over 30ms OFF time over 30ms ON+OFF time over 100ms over 30ms over 30ms
over 30ms over 30ms ON
ON
OFF
OFF
over 100ms
I/O items
over 100ms
AI
AI
AI
AO
Temperature input
Current Input
Voltage input
Current Output
Remote unit (RS) (DDC) (PMX) Wiring Local Equipments Electric, HVAC, Plumbing, others
Remarks
Pt100Ω resistance
1.Input Pt100Ω, J Pt100Ω 2.Circuit voltage, current DC1V, 1mA 3.Range 0~50℃, -50~100°C -20~80℃, 50~200℃
Transducer Transmitter
1.Input DC4~20mA 2.Input impedance 300Ω 3.No isolation
4~20mA
1.AIV1 input 1~5VDC Input impedance 500Ω 2.AIV2 input 0~5VDC Input impedance 5K Ω 3.AIV3 input -5~5VDC Input impedance 110K Ω 4.No isolation
1.Output signal 4~20mA DC 2.Output voltage 24V DC 3.Max. resistance 600Ω 4.With isolator
52
6. Typic al Instru mentation Examples Valve Selection Table (reference only) General
This table shows selected valve conditions for all control valves that are installed in a project. Valve selection table
System
Fluid
Flow rate
Pi
Delta P
CV
Bore(A)
Remarks
Chilled water bypass 2-way valve
W2
2000
Chilled water flow meter
W
2000
150.0
113.2
100
Chilled water 2-way valve
W2
300
30.0
38.0
40
2sets
Hot water 2-way valve
W2
120
30.0
15.2
25
2sets
Humidification 2-way valve
S
30
80.0
1.1
15
2sets
Steam shutoff valve
S
15
2sets
150
200.0
Chilled water 2-way valve
W2
200
30.0
25.3
40
Hot water 2-way valve
W2
80
30.0
10.1
25
Humidification 2-way valve
S
15
80.0
0.5
15
Steam shutoff valve
S
200.0
15
Chilled water 2-way valve
W2
20
30.0
2.5
20
20sets
Hot water 2-way valve
W2
20
30.0
2.5
20
20sets
Fluid W2 : Water(2-way valve), W : Water, S : Steam Unit Fluid W2, W : Flow rate[l/m], Delta P[kPa] Fluid S : Flow rate[kg/h], Pi, Delta P[kPa]
Control Panel Table (reference onl y) General
This table shows panel name and size, location, also including controlled subjects by the panel. Control panel table Type
Name
Size for Reference(mm) W
Controlled Subjects
Location
D
System control panel
Stand
700
1950
400
DSS , SMS, etc.
1F security room
1CP -1
Wall mounted
700
1300
250
Chiller plant system control
1F machine room 1
1CP-2
Wall mounted
700
1300
250
OHU-1, AHU-1, FC U
1F machine room 2
2CP -1
Wall mounted
700
1100
250
OHU-2, measurement
2F machine room 1
1RS -1
Wall mounted
700
700
250
Substation and generator monitoring, lighting
1F electric room
2RS-1
Wall mounted
700
700
250
Lighting
2F EP S
W : Width
53
H
H : Height
D : Depth
Guide Specification Building Management System Energy Management System Security System and, Control Devices
1 Guide Specifications for HVAC
1.
GENERAL
Building Management Systems and Instrumentation for HVAC shall comply with the conditions stated in this specification in terms of Hardware, Software, and its installation, test, and commissioning. 1.1.
Scope
A.
Supply all hardware and software necessary to meet the specified project requirements. B. Supply hardware layouts, connections, control loop configuration as control flow diagrams. C. Specify the detailed design for all distributed control system input/output points. D. Design, supply and install all panels, and data communication network cables including all hardware. E. Supply and install all interconnecting cables between control panels, controllers, operator terminals and peripheral devices. F. Prepare entire specifications for all items supplied by the supplier from other purchased products. G. Supply supervisory specialists and engineers at the project site to assist in any phases of system installation, start-up, test and commissioning. H. Prepare necessary operator and technician training programs I. Prepare as-built documentation, software, all DDC control logic and all associated support documentation on approved media which accurately represents the final system. 1.2.
Submittals
System supplier shall submit system control sequence drawings with engineering design to the project. System configuration diagrams. Input/Output point and alarm point list. All system wirings and interconnections between components. Hardware specifications and instructions, Software specifications, and application user guides.
2 Guide Specifications for HVAC
1.3.
References
The latest standards as stated below are followed as references. ASHRAE American Society Conditioning Engineers
of
Heating,
Refrigerating
and
Air
European CE Mark: EMC Directive 2004/108/EC and 89/336/EEC 1.4.
Warranty
Warranty shall include all costs for labor, parts, transportations, expenses within one year from actual completion and acceptance by the owner Warranty shall cover.
3 Guide Specifications for HVAC
2.
PRODUCTS
2.1.
HARDWARE REQUIREMENTS
2.1.1.
General
A Building Management System (BMS) shall be built on a server-client type system architecture. All necessary information and system database are archived in system servers. A PC with web-browsing software installed shall perform as a Client PC, solely for browsing the contents of all archived data as a supervisory terminal. BMS shall use the latest technologies such as IP/Linux/XML/ SVG/J AVA as its platform. 2.1.2.
Server
System Servers shall comprise of several servers on server-client system structure. The number of system servers shall differ depending on the system requirements. Servers shall include Server for System Management and Server for Data Storage. Servers shall be built on the full open platform using Linux system. 2.1.2.1.
Server for System Management
A Server for System Management shall carry out distribution of information for the display, setting, and operations of the management information of the overall system (data point, program, etc.) through the Web browsing software installed in the Client PC. Server shall support access of up to 5 client PCs simultaneously. Server shall be provided with dedicated hardware using full open platform Linux system and come with 32 bit CP U with main storage capacity of SDRAM 256 MB. Auxiliary memory unit HDD shall be 40 GB in 2.5 inch size. Maximum BACnet objects manageable shall be 30,000 objects. Server shall back up data up to 72 hours. 2.1.2.2.
Server fo r Data Storage
A Server for Data Storage shall store necessary database for BMS. The server shall manage the data transmitted from an Advanced Building Controller as BMS databases and provide the data to display or print the historical trending graphs as well as daily, monthly, and yearly reports. Server shall be provided with dedicated hardware using full open platform Linux system and come with 32 bit CP U with main storage capacity of SDRAM 256 MB. Auxiliary memory unit HDD shall be 40 GB in 2.5 inch size. Maximum BACnet objects manageable shall be 30,000 objects. Server shall back up data up to 72 hours.
4 Guide Specifications for HVAC
2.1.2.3
Server for Energy Management
A Server for Energy Management shall store necessary database for the purpose of energy consumption management. 2.1.2.4
Server for Securit y Data
A Server for Security Data store necessary database for the purpose of security. The server shall have the storage capacity of 1 million access history. Server for Security Data shall comply with the specifications as follows: OS: Windows® XP Internet Browser: Internet Explorer 6 or later CP U: Pentium® IV processor, 3 GHz and above Main storage capacity: 512MB and above Loading function: IPv6, J ava® vm 1.4 and above, XGA, Acrobat® Reader, IE6.0 and above - HDD capacity: 40GB and above. -
- CD-ROM: 1 unit 2.1.3.
Server Redundancy
System Servers shall be capable of dual-redundant system. Dual-redundancy shall be configured by setting 2 servers respectively with one to one warm-standby system. The system runs 2 servers simultaneously and when trouble occurred on either one server, another one will backup immediately. Servers carry out the backup of critical data such as Monitoring Data and Historical data. When trouble occurred below measures shall be applied to backup data. Assume there are 2 servers “Server A” and “Server B”. When “Server A” information cannot be browsed from Client PC due to the network trouble, it is judged as “Server A: Down”, and then “Server B” (normally Standby) becomes Active, and the Client PC connection is switched to “Server B” automatically. When network trouble is solved and “Server A” is restored, (Client PC is restored to be able to browse server information), as “Server A: Active”, automatically carry out restorations (acquiring trending data during “Server A” is down from Advanced Building Controller and copying the difference between Client PC settings and data for scheduled copy). After restored as “Server A: Active”, Client PC still maintain the connection to Server B. Operator has to re-login to switch the connection to Server A.
5 Guide Specifications for HVAC
2.1.4.
Client PC
A Client PC shall be the PC with web-browsing software for accessing the database achieved and stored in System Servers. Client PC is basically installed in the supervision room to supervise the whole building. It supervises the following features: -
Monitoring: status, alarms, and measurement of each facility Operation: remote ON/OFF control Data output: operating status, alarm status, and measuring data Data analysis: operating status, alarm status, and measuring data
Up to 5 Client PCs shall be able to access Server simultaneously. Client PC shall comply with the specifications as follows: -
2.1.5.
OS: Windows® XP/Vista Internet Browser: Internet Explorer 6 or later CP U: Pentium® IV processor, 3 GHz and above Main storage capacity: 512MB and above Loading function: IPv6, J ava® vm 1.4 and above, XGA, Acrobat® Reader, IE6.0 and above
Printer
Any type of printer with USB connection available shall be able to connect the network of the system. Printer driver shall be compatible with Windows XP or later. 2.1.6.
Commun icati on Network
BMS shall have the capability of full system integration using BACnet IP, LonTalk, Modbus, or OPC. For the communication network between Client PCs and each server, hyper text transfer protocol (http) shall be used. Uses BACnet IP between each system server and advanced building controller. Internet Protocol version 4 (IPv4) or Internet Protocol version 6 (IPv6) shall be selectable for both communication network depending on the required specifications. LonTalk protocol shall be used for the communication between Advanced Building Controller and the DDC controllers, such as multi-purpose controller. MODBUS protocol shall be used for the network connection with power meters and controllers using RS485 communications. OPC shall be used for the system integration with IBMS. Using PC based OPC server, BMS shall be able to connect with other systems as
6 Guide Specifications for HVAC
IBMS by converting BACnet protocol to the one communicable via OPC. 2.1.7.
Controller
2.1.7.1.
Adv anced Bui ldin g Contr oll er
An Advanced Building Controller shall consolidates the DDC groups and performs different types of integrated control including energy saving. The controller shall be capable of autonomous distributed control to continue the operation even if another part of the system is shut down. Collects various management information from the DDCs and transmits information to Server for System Management. Stores the collected data for forty-eight (48) hours. The controller shall come with 32 bit CPU with main storage capacity of SDRAM 128 MB and Compact Flash® 64MB. Maximum Data points manageable shall be 1,000 points. Uses IP (Ethernet® 10 BASE-T/100BASE-TX) 1 channel to communicate with the higher level of the system. The communication line of controllers consists of LonTalk® protocol Controller bus) 4 lines (2 channels). This controller shall back up the data up to 72 hours. 2.1.7.2.
Direct Digital Contr oller (DDC)
DDC controller shall carry out the controls for each and every device. The control operations shall be self-sustaining to enable the continuous control even if the other parts of the system are down. Data transmission shall be made via the Client PC and the Advanced Building Controller. The Client PC will receive, for example, the changes in setup values, and send back the data of control results. DDC lineups several types as follows: A.
Multi -purp os e Contr oller
the controller designed as a multipurpose controller for several devices. Consists of a basic unit and connectable I/O modules. The number and types of the modules shall be flexibly changeable corresponding to the control or management to fit in various applications. B.
AHU Contro ller
the DDC controller specially designed for AHU control. The controller has inputs and outputs suitable for AHU control and its software shall be freely editable in response to the applications. C.
I/O Modu les
7 Guide Specifications for HVAC
I/O modules consist of the following types: D.
Module with 8 digital inputs Module with 16 digital inputs Module with 8 relay outputs Module with 16 relay outputs Module with 8 relay outputs +8 digital inputs Module with 4 remote control relay outputs Module with 4 totalizer pulse inputs Module with 16 totalizer pulse inputs Module with 2 voltage/current outputs Module with 4 voltage/current outputs Module with 4 voltage/current inputs Module with 4 temperature inputs Module with 2 voltage/current inputs +2 temperature inputs Module with 1 modutrol motor outputs Module with 3 modutrol motor outputs
Zone Manager
A Zone Manager shall carry out the management of VAV controllers, Fan Coil Unit Controllers, and AHU Controllers. Up to 50 controllers are manageable by one unit of Zone Manager. E.
VAV Cont roll er
designed specifically for Variable Air Volume unit control. The VAV controller shall be provided as a damper actuator with DDC controller inside that controls a VAV unit in a building HVAC system. Rated torque of VAV damper actuator shall be selectable from 5Nm of 10Nm depending on the torque required. F.
Fan Coil Unit Contr oller
provides digital control of fan coil units. In addition to start/stop operation, valve control, and fan speed changeover, the controller shall provide setback and interlock operations with outdoor air handler. 2.1.7.3.
Chiller Plant Contr ol Packaged Contr oller
Chiller Plant Control Packaged Controller is a direct digital controller (DDC) specifically designed for sequential control of chiller plant equipment of building HVAC systems. These packaged controllers comprise of 2 types; a pump controller and a chiller controller. Each packaged controller consists of a combination of a control module, a base module, I/O modules, and a LCD operator interface.
8 Guide Specifications for HVAC
The Control module performs arithmetic operations and exerts the chiller/pump controls. The plug-in type I/O modules are the input/output sections of the controller and load communications to connect with the control module. The Base module enables power supply and communication interface to the I/O modules. I/O modules include the followings: - Module with 4-20 mA DC current inputs - Module with 4-20 mA DC current output - Module with one floating output with nominal 135ohm feedback potentiometer - Module with five potential free contact inputs - Module with four potential free contact (normally open) outputs - Module with two potential free contact inputs and one 24VDC voltage instantaneous contact output The Base module supplies power to I/O modules and carries out communication connections and address settings for I/O modules. The base module also functions as a terminal block for the I/O modules. The I/O modules shall be plug-in type, which can be plugged directly into the base module back panel and can be easily detached without disconnecting their wiring. The LCD Operator Interface is a display setting device having a color touch-panel LCD. Users shall be controlled with access levels and passwords. This interface shall also be used as a parameter-setting device by service personnel. 2.1.7.4.
Acc ess Contr oll er
Provide control device for access control equipment of the security system. The controller collects data on access control, monitors operating status of access control equipment, and interfaces with other facilities such as lighting and air conditioning facilities. This device shall use Wiegand protocol for the control of Security card devices. The controller shall be connectable to the security system via 10 BASE-T or 100 BASE-T of Ethernet protocol. Sends access control data to the system, receives commands from the terminal devices as well as from the system to control electric lock, and thus performs security management of a whole building. The controller composed of a basic module and I/O modules such as Modules for Wiegand signal, power supply for electric keys, passive sensors and other devices,
9 Guide Specifications for HVAC
2.1.9.
Field Devic es
2.1.9.1.
Sensors
Supplier shall provide the following types of sensor depending on the specific system requirement. A.
Room Temper atu re Senso r
Uses resistance thermometer sensor for temperature sensing element. Designed suitable for room temperature sensing. The sensing range shall be from 0°C to 60°C with ±0.3°C sensing accuracy. B.
Duct Inserti on Type Temperature Sensor
Uses filterless probe resistance thermometer sensor for temperature sensing element. Designed to be installed to air ducts and suitable for supply or return air temperature detection. The sensing range shall be from 0°C to 60°C with ±0.3°C sensing accuracy. Sensor housing shall be dust-proof and splash-proof (IP54) for higher environmental resistance and installable using dedicated quick-detachable bracket for easy installation. C.
Pipe Mount Type Temperature Sensor
Uses resistance thermometer sensor for temperature sensing element. Detects water temperature of piping. Sensing range of the sensor shall be from -50°C to 200°C with sensing accuracy of ± 0.05 + 0.002 temperature measured. D.
Ceiling Mount Type Temperature Sensor
Uses resistance thermometer sensor for temperature sensing element. Designed to be installed to narrow opening of ceiling. The sensing range shall be from 0°C to 60°C with ±0.3°C sensing accuracy. E.
Room Type Humidi ty Transm itt er
Uses polymer capacitive humidity sensor for humidity sensing element. The sensing range shall be 0%RH to 100%RH with ± 3% sensing accuracy. Designed suitable for room humidity detection. F.
Duct Inserti on Type Humidi ty Transm itt er
Uses polymer capacitive humidity sensor for humidity sensing element. The sensing range shall be 0%RH to 100%RH with ± 3% sensing accuracy. Designed to be installed on air ducts and suitable for supply or return air humidity detection.
10 Guide Specifications for HVAC
Sensor housing shall be dust-proof and splash-proof (IP54) for higher environmental resistance and installable using dedicated quick-detachable bracket for easy installation. G.
Ceili ng Mount Type Humidi ty Transm itt er
Uses polymer capacitive humidity sensor for humidity sensing element. The sensing range shall be 0%RH to 100%RH with ± 3% sensing accuracy. Designed to be installed to narrow opening of ceiling. H.
Dew-poi nt Temperature Sensor
uses a polymer capative humidity sensor for a dew point sensing element. Comes either with or without built-in temperature sensing element. The sensing range is from -40°C to 60°C DP with ± 1°C sensing accuracy. Sensor housing shall be dust-proof and splash-proof (IP54) for higher environmental resistance and installable using dedicated quick-detachable bracket for easy installation. I.
Radiant Temperature Sensor
measures infrared radiation at the perimeter on a wall. The sensing range shall be from 5°C to 50°C with ±2°C sensing accuracy. Output signal shall be 1 to 5 V DC. Uses 1 to 5 V DC as output signal linearly corresponding to 5°C to 50°C. J.
Carbo n Monoxi de (CO) Concentr ation Transm itt er
detects concentration of Carbon Monoxide and sends a real time value. The sensing range shall be 0 to 60 ppm with sensing accuracy of ±5% FS. Uses 4 to 20mA signal as output signal linearly corresponding to 0 to 60 ppm. K.
Duct Insertion Transmitter
Type
Carbon
Dioxicide
(CO2)
Concentration
detects the concentration of CO2 in ducts and other sites using Non-dispersive infrared absorption method and transmits a real time value to other devices. The sensing range shall be 0 to 2000 ppm with sensing accuracy of ±(50 ppm +5% readout). Uses 1 to 5 VDC signal as output signal linearly corresponding to 0 to 2000 ppm. The transmitter shall be installable using simple mounting bracket for easy installation. The device shall be able to calibrate using CO2 service bag containing CO2 zero gas supply.
11 Guide Specifications for HVAC
L.
PMV Sensor
detects the combination of air temperature, mean radiant temperature, and air velocity and converts into the sensor signal by equipped processor. The sensing accuracy shall be ±0.5 PMV. M. Different ial Pressur e Transm itt er
uses silicon diaphragm for its sensing element. Detects deflection of its diaphragm as electrical capacitance. The sensing accuracy shall be ± 1.0% of full span. Uses 4 to 20mA signal as output signal. N.
Pressur e Transm itt er
detects the pressure of chilled/hot water, brine, lubricating oil, steam, air, and other fluids. Converts measured values into 4 to 20 mA DC electric signals. 2.1.9.2.
User Termi nal Devic es
User terminal shall have a temperature sensing element built-in and functions as a sensor and a remote controller. User can set On/Off control of devices, temperature setting, and other controls of air conditioning equipment. LCD display will indicate the status of equipment and setting value and present value of temperature. Use modular connectors for easy installation. This device shall be connectable to DDC controllers such as Fan Coil Controller, VAV unit controller, and AHU controller. 2.1.9.3. A.
Electri c Act uator s and Contr ol Valves Elec tr ic Valv e Act uat or
Actuators for motorized control valve shall support several control signals as follows; B.
Nominal 135 ohm feedback potentiometer Nominal resistance 135 ohm input 4 mA DC to 20 mA DC input 2 V DC to 10 V DC input
Contro l Valve
Supplier shall provide the Control valve with the body materials as stated below; - FC200: Gray cast iron - SCS13A: Stainless steel - FCD450: Ductile cast iron
12 Guide Specifications for HVAC
Diameter nominal size shall range from DN15 to DN150. C.
Motori zed Contr ol Valve
Provide the valve which electric actuator and its valve body shall be integrated in a single unit. D.
Motor ized Contr ol Valve wit h Flow Measur ement and Control Functions
Provide the valve which electric actuator and its valve body shall be integrated in a single unit. The control valve shall control flow rate not by valve opening but by flow rate calculated by the measured value from built-in pressure sensor and Cv. The control valve comes with built-in pressure sensor and temperature sensor. The built-in pressure sensor ranges from 0 to 10 MPa at the accuracy of ±0.1% FS for 7-17°C or 45-65°C and ±0.5% FS for other conditions. The built-in temperature sensor ranges from 0 to 100°C at the accuracy of ±1°C. E.
Electri c Damper Actuator:
A motorized actuator to open and close a damper. The actuator is provided on and off control or floating control in response to a command from a controller. Combined with an auxiliary potentiometer will enable the actuator proportional control in response to a command from a proportional controller. The damper actuator shall have the torque at the rated voltage of 20Nm and holding torque of 16Nm. Operating time is approximately 15 seconds. F.
Electri c Damper Act uator :
A motorized actuator to open and close a damper. The actuator is provided on and off control or floating control in response to a command from a controller. Combined with an auxiliary potentiometer will enable
13 Guide Specifications for HVAC
2.2.
SOFTWARE REQUIREMENTS
2.2.1.
Software Requi rements for BMS
BMS shall include the application software for management, monitoring, and controls. 2.2.2.
User Management
System shall be secured its access by user IDs and passwords. User Management function shall be the one manages the passwords and user IDs. Administrator shall be able to set the access rights of both browsing and operation for each function and the point operation level according to the user ID. This function shall be able to register up to 200 user IDs. Normally, user authentification shall be performed by user ID and password. User shall also be authentificated by registering the IP address of Client PC. It is possible to set up to 4 client PCs for 1 user ID. Password shall be able to set within 36 alphanumeric characters. User shall be able to change the password anytime. Screen access rights to display and operate shall be set by user. Operation level, alarm, and buzzer shall be able to set by segregation. 2.2.2.1.
Log Outpu t
Records and displays all the operating logs carried out by user in list. Items to be recorded and displayed are: -
Date (YYYY/MM/DD) at the time of operation Time (hours, minutes, and seconds) at the time of operation IP address of Client PC User ID
Operation type such as displaying, setting, printing, change of display, and canceling, button name to be clicked, dialog box name to be opened, contents of operation, contents of inputs and setting, device ID, point ID, point name, program name, and operation failed or not. Maximum storable logs are up to 1,000,000 logs. Operation logs shall be able to output in CSV file format and save in Client PC. 2.2.3.
Graphic
Displays the status of each facility targeted for management in graphic formats such as floor plan, cross section and schematic diagram. User is possible to perform the equipment's ON/OFF operation and setpoint change operation, and to display the trending graph and individual
14 Guide Specifications for HVAC
equipment schedule. The graphic displays present the status of each piece of equipment to be controlled in graphical forms such as floor plans, cross sections or schematic diagrams. Starts/stops equipment, changes setting, displays historical trend and individual equipment schedule. The displays can be enlarged and reduced at a desired magnification using SVG supporting magnification at browser. Up to 1,000 graphical displays can be assigned to the system. A dynamic element placed on a static element of equipment or floor indicates the status of a point by changing the color of the symbol or displaying the numerical value of analog/totalizer point. The dynamic element can also lead operators to another graphic display. Up to 200 dynamic elements can be displayed on a screen. The types of dynamic elements (points + screen transition) are shown below: -
Digital color change Digital shape change Analog numerical value display Animation Live wire display Graphic display selection Screen call Screen transition Picture scanner read display
User shall be able to modify or revise the graphic using Graphic Generator software which generates user-defined graphics and gives facility to edit the screen in the event of any change in the application environment such as partition or room name of the building. 2.2.4.
Group Lis t
Lists groups for the user to manage the Points easily. In addition to the system group list that is already listed, there is the user group list that can be set by the user optionally. It is possible to carry out batch ON/OFF command and batch settings change for each group. Servers shall have a capability of redundant system. 2.2.5.
Alarm
If any alarm occurs, the system automatically processes the alarm. The system notifies the alarm via buzzer sounds. BMS shall display the latest alarm and brink indicators. The operation of the latest alarm
15 Guide Specifications for HVAC
display, buzzer sounds and the Alarm Dashboard can be specified by the segregation pattern of the Segregation setting. Four types of alarm sounds are available for each alarm level. The following alarm events are available. - Alarm input - Unmatched command (Failure of start/stop of start/stop points, status - unmatched) - Analog high/low limit alarm - Sensor error - Trouble - Totalized value increase error - Control alarm (Power demand target value exceeded, etc.) - Component alarm (bus trouble, line status, error, remote unit no response) - Power demand alarm, power failure alarm, fire alarm Specify the following alarm level for each alarm point. - Emergency alarm - Major alarm - Moderate alarm - Minor alarm 2.2.5.1.
Alarm Dashbo ard
Displays the information about change of status and alarm occurrence traditionally printed on a message printer. Only the required information can be extracted and displayed by narrowing search to all/alarm/operation setting/unacknowledged alarm records or searching information by a desired text string. Comments can also be entered if any. The accumulated data can be saved to the desired media (hard disk/USB memory, etc.) of a Client PC in a CSV format file. The data shall be displayed in PDF file to realize paper-less operations. The information displayed on the Alarm Dashboard is as follows: -
Point alarm Control alarm Device alarm Remote unit alarm Point operation Point change of status
16 Guide Specifications for HVAC
When an alarm occurs in logged-in status, the alarm is notified by the buzzer sound, updated New Alarm display, and indicator blinking based on the alarm. Also, alarm occurrence and recovery will be recorded in Alarm Dashboard irrespective of login status. Buzzer sound has kinds of tones in each alarm level. Alarm is also given as an appropriate voice announcement when an alarm occurs. 2.2.5.2.
Alarm Noti fic ation via E-mail or SMS
Alarms shall be notified to the PC or mobile terminal of building administrator through E-mail or Short Message Service. Alarm notification supports alarm confirmation operation in places far away from the client PC. 2.2.6.
Device/Remote Unit Status Monit ori ng
Based on the device/remote unit status monitoring function, the status of system servers, system controllers, and filed controllers is constantly monitored. Whenever a trouble is found, and alarm is notified with the buzzer sound, and so on. 2.2.7.
Trending
Trending function graphically displays time-series variation in measured point data such as power and temperature, time series changes of power operation status (ON/OFF), and totalized data are stored for a fixed period of time and displayed on trend graph (broken line) and bar graph (bar graph/laminated graph). User shall also display up to 8 different scales of graph all at once. 4 axes each are displayed on both left and right side of the trending graph. Trend shall be able to display up to 8 points per sheet and 400 sheets maximum. Displayable points are ON/OFF, Status, Measured, Setpoint, and Tantalization. Data of 1 minute cycle shall be able to be displayed for up to 40 days. Data of 1 hour cycle is stored for the past 13 months. Data of 1 day cycle is stored for the past 10 years. Data of 1 month cycle is stored for the past 10 years. Displayable graph types are broken line, bar, laminated, combination of broken line and bar graph, combination of broken line and laminated graph. 2.2.7.1.
Real Time Trend ing
17 Guide Specifications for HVAC
In addition to the trending function, the real time trending shall also be selectable. Collects and stores the data of points that are targeted for real time data collection, and then displays obtained results as broken line graph. The latest data shall be collected all the time. Meanwhile, in “Specific” method, there are two data collection methods, namely a method to collect the point data when status change has occurred on digital point and a method to collect the point data by setting start time/end time. It can be set in either one of these. Collected point data shall be displayed as real time trending graph. It shall be able to display and print the real time trending graph as numeric data. The points targeted for real time data collection and the information about the collection conditions set by the user in client PC will be set in real time data collection file. The real time data collection file reflects the information to Server for System Management and Advanced Building Controller through update function. Minimum data collection cycle for real time trending is 1 second and usual trending collects and displays in 15 minutes interval. 2.2.8.
Report
Measured values and totalized values are displayed on the screen, and the daily report of electricity and air-conditioning operations are prepared. User shall be able to output daily report either automatically or manually in PDF format (print image) which realize paper-less operation. 2.2.8.1.
Daily Repor t
Daily reports for the last 40 days including the current day can be displayed and printed manually. Daily report displayed on the screen can be output in CSV format as well. Printable data are the following 3 data. - Hourly report data contains 1-minute values totalized for 1 hour (totalized value) OR selected value among; max./min./average value of 1-minute values for 1 hour and on-the-hour value (measured value) - Daily report data contains 1-hour values totalized for 1 day (for the current day and for previous day) and load factor (totalized value only) AND max., min., av., and reading values of 1-hour values for 1 day. (Specify the values necessary to print.) - Monthly report data contains 1-day value totalized for 1 month (to the current day of the month from the following day of the previous month, to the current day of the previous month from the following day of the two months previous) and load factor (totalized value only) AND max., min., and av. values of 1-day values for 1 month. (Specify the values necessary to
18 Guide Specifications for HVAC
print. Monthly report data is printed out after the daily report data is printed.) Monthly report can be output either automatically or manually in PDF format (print image). 2.2.8.2.
Monthl y Report
Monthly reports for the last 13 months including the current month can be displayed and printed manually at your convenience. Monthly report displayed on the screen can be output in CSV format as well. Printable data are following 3 data as a monthly report. - Daily report data contains 1-hour values totalized for 1 day and load factor (totalized value only) OR selected value among; max./min./average value of 1-hour values for 1 day. - Monthly report data contains 1-day values totalized for 1 month (for the current month and for the previous month) and load factor (totalized value only) AND max., min., and av. values of 1-day values for 1 month. (Specify the values necessary to print. Monthly report data is printed out after the daily report data is printed.) - Yearly report data contains 1-month values totalized for 1 year (to the current month of the year from the following month of the previous year, to the current month of the previous year from the following month of the two years previous) and load factor (totalized value only) AND max., min., and av. values of 1-month values for 1 year. (Specify the values necessary to print. Yearly report data is printed out after the monthly report data is printed.) Yearly report can be output either automatically or manually in P DF format (print image). 2.2.8.3.
Yearly Report
Yearly reports for the last 10 years including the current year can be displayed and printed manually at your convenience. Yearly report displayed on the screen can be output in CSV format as well. Printable data are the following 2 data as a yearly report. - Monthly report data contains 1-day values totalized for 1 month and load factor (totalized value only) OR selected value among; max./min./average value of 1-day values for 1 month. - Yearly report data contains 1-month values totalized for 1 year (for the current year and
19 Guide Specifications for HVAC
for the previous year) and load factor (totalized value only) AND max., min., and av. values of 1-month values for 1 year. (Specify the values necessary to print. Yearly report data is printed out after the monthly report data is printed.)
2.2.8.4.
Editable Repor t Format
Report format is editable freely by users if required. User shall be able to change, add and delete ruled lines, and insert merged cell to match the requirement of each project. BMS shall switch the report format when locale is changed. 2.2.9.
Runtim e Monit ori ng and On/Off Count ing
This function shall be used to display the equipment that exceeds a certain value of runtime/on-off cycle count, in the Maintenance Notification screen, and activates the judgment of equipment inspection and replacement time. User shall be able to maintain and replace the equipment in the building at regular intervals, prevent the breakdown of the equipment, and thereby control the maintenance cost. It is possible to generate and displays the PDF file as maintenance monitoring report with the information of all equipment or the equipment that exceeds the monitoring targeted value. The PDF file can be printed manually anytime using a printer. Up to 50 groups and 100 points per group shall be monitored and counted. This function counts total time and elapsed time up to 999,999 hours. 2.2.10.
Overtim e Runnin g
Overtime running means the extra running of the equipment based on the operation requested from the user operable equipment or client PC, in other than the time slot (core time) that is set in advance. Receiving of request, count of actual runtime and printing are carried out in the overtime running management. 2.2.11.
Meter Reading
Automatically collects the overtime runtime data and the meter-reading value of meters measuring power, water supply, gas, and so on. Calculates the consumption month wise. In addition, it detects and modifies abnormal value after meter-reading and outputs the list of meter-reading results.
20 Guide Specifications for HVAC
Maximum data points available are 3000 meters including 1,500 actual meters and 1,500 logical meters. Up to 50 types of Meter shall be assignable. This function handles up to 400 tenants. Maximum totalization point shall be 1,500 meters. Overtime runtime is 1,000 request units maximum. Automatic meter-reading shall be able to set once a month. Operator shall read meter manually anytime. Meter reading record shall be saved in CSV format and output anytime operator requests. 2.2.12.
Time Progr am Contro l
Automatically starts or stops the equipment at the preset time. For the weekly schedule (that is the base schedule for each day of the week throughout the year) and the priority schedule (that can be used for holiday settings, etc.), it is possible to set up to 8 times operation and the time a day. Based on the weekly schedule, priority schedule, and calendar*1 settings, the execution schedule for the next 1 week from the current date can be created for starting or stopping the equipment. Further, it is possible for the user to specify name for time programs. Time programs shall be able to display all the on/off time settings of time programs in list. 2.2.13.
Schedule Compos iti on
Interlocks multiple Time Programs into 1 schedule and write it in a specified Time Program. It shall be convenient to create a schedule using this function based on the time program of each tenant, for common utility areas (such as entrance hall) used by many tenants. Compose up to 10 sub-programs per Advanced Building Controller and up to 10 time programs per sub-program. 2.2.14.
Event Prog ram
Automatically performs interlock operation for multiple facilities such as AHU and lighting inside the building, along the predetermined conditions. It is possible to take a common emergency action and reduce the load to run each facility by specifying the link and related operation between multiple facilities, such as run pattern/run sequence of facilities and counter measures during alarm, in advance.
21 Guide Specifications for HVAC
2.2.15.
Energy Saving Appl icati ons
BMS shall have the applications designed for Energy-saving control. The applications include control software such as Optimum Start/Stop Control, Chiller Optimum Start/Stop Control, Duty Cycle Control, P ower Demand Control, VAV Control, and VWV Control.
2.2.15.1. Optim um Start/Stop Contr ol
This function estimates the attribute of temperature raise/fall for HVAC start/stop and performs the optimum start/stop control of Air Handling Units to avoid unnecessary runtime. Up to 50 subsystems shall be able to control under Advanced Building Controller. This function output the optimum timing of start/stop command based on the time program in which measured room temperature and control equipment are assigned. 2.2.15.2. Chiller Optim um Start/Stop Contr ol
This function refers to the estimated optimum start/stop time based on the optimum start/stop control for AHU, and starts the chiller plant "x" minutes earlier than the optimum start time of the earliest AHU and stops the chiller plant "y" minutes earlier than the optimum stop time of the latest AHU, within the same chiller plant system. Up to 4 types of start/stop holding time shall be able to set per subprogram. 2.2.15.3. Duty Cycle Contro l
This function calculates the optimum stop time of Packaged Air Conditioning units etc. while maintaining a comfortable temperature environment, and reduces thermal energy/electrical energy by performing duty cycle control up to 20 subsystems per Advanced Building Controller and up to 20 points per subsystem. This function stops and recovers the equipment based on the measured room temperature. 2.2.15.4. Pow er Demand Cont rol
This function supports 2 types of power contracts; Actual and Demand, to cover a variety of power contract systems that may differ depending on countries. Power demand control function estimates the usage of power at intervals, decides the necessity of interruption/recovery, and interrupts/recovers the equipment according to the capacity required. BMS stores the power demand control results as history and displays the targeted value and demand value.
22 Guide Specifications for HVAC
Further, it is possible to save the day's data and month's data of power demand in the optional media (hard disk, USB memory, etc.) of the client PC, in CSV format. 2.2.16.
Power Failure & Resto ratio n Contr ol
During power failure, if Server for System Management, Server for Data Storage, and Advanced Building Controller are backed up with UP S, alarm notification shall be given through buzzer sound, blinking of the power failure icon, and new alarm display. During this stage, outputs except fire process event program output, power failure event output, and output made by manual operation are withheld. When detecting the startup of the generator, startup is output one by one in the points registered in the generator registration order list. Outputs other than fire process event program output, power failure event output, and output made by manual operation are withheld. Power restoration program shall be able to start up when detecting commercial power restoration. At this time, since output is done for ON/OFF point in the same way as before power failure occurrence and also the output that was withheld during power failure is output, it is possible to move back automatically to the original status. Selecting automatic/manual startup and specifying the point order of power restoration is possible for power restoration program. 2.2.17.
Generator Load Distr ibu tio n Contr ol
When the generator for an emergency purpose is operated during power failure, this function keeps the power load. If the instantaneous value of the generator load exceeds the desired value set beforehand, excess power is cutoff from units in order of low-priority level. On the other hand if it is low, power is connected to the units in order of priority level. 2.2.18.
VAV Cont ro l
Provide the VAV control application which optimizes the supply air temperature and pressure of AHU including VSD control of AHU fan. The application shall have the function to optimize the pressure loss of duct to reduce energy consumption of fan. Provide the function that optimizes supply air temperature to satisfy each zone temperature condition. 2.2.19.
VWV Cont ro l
VWV stands for Variable Water Volume. This application shall be a part of energy saving applications for heating/cooling source delivery
23 Guide Specifications for HVAC
systems. VWV shall control the running speed of secondary water delivery pumps in Chiller P lant to maintain the supply water pressure in certain level by means of all AHUs’ differential pressure. Enables power of the delivery pump to be reduced significantly without the decrease of HVAC performance. VWV control requires motorized control valve with differential pressure sensor to detect the differential pressures of all AHUs. VWV control consists of three programs such as demand calculation per program, pressure setpoint calculation, and energy saving effect calculation. Demand calculation per program calculates the demand level of each program of a maximum of 30 AHUs with the same control level. Setpoint calculation determines the setpoint change request for chiller plant equipment. The pressure setpoint is calculated based on the setpoint change request. Energy saving effect calculation calculates the energy saving effect as a result of VWV control. 2.2.19.
DDC Software
Provide DDC software which freely programmable and modifiable by system engineers. System Engineer shall be able to create or modify control software for multipurpose controller through field engineering tools. By entering necessary parameters and wiring output and input of each software module, control software for certain HVAC applications shall be created. 2.2.20.
Chiller Plant Contr ol Packaged Contr oller
Chiller Plant Control Packaged Controller is a direct digital controller (DDC) specifically designed for sequential control of chiller plant equipment of building HVAC systems. This controller carries out energy-saving control including the optimization of multiple chillers and other chiller plant units in response to the air conditioning load. User can change the setting of control sequence through operator interface equipped with the controller. Not only the pre-programmed sequence, but also the user-determined programmed control is also available for Chiller plant control. Operator shall be able to switch automatic/manual operation by communicating with host system. Manual operation takes highest priority for all the control sequences. Group command is executed by communicating with the host BMS or operating interface. Daytime or nighttime mode can be switched by communicating with host
24 Guide Specifications for HVAC
system. The switchover between daytime and nighttime modes changes the operating sequences, maximum number of running chillers, and load at startup. Operator shall be able o switch cooling/heating mode by communicating with host BMS or operating interface. The switchover between cooling and heating also changes the operating sequences, maximum number of running chillers, and load at startup. Operating sequence has several types such as normal sequence, sequence with base unit changeover, rotation, and operator program. Normal sequence fixes the order of chiller or pump. Sequence with base unit changeover performs the sequential control but base unit is changed so as to avoid too much load for base unit. Rotation mode is a method for averaging each chiller runtime. The operating sequence of he chillers are sequentially shifted so that the chiller which has been stopped for the longest period is started first and the chiller which has been running for the longest period is stopped first. Operator shall be able to program the operation sequence. This method is useful when the capacity of chillers or pumps to be controlled differs; operator is possible to assign desired sequence.
2.2.21
Software Requi rements for Securit y System
Security System shall include the application software for management, monitoring, and controls. 2.2.22
Room Data Proc ess
Room is considered to be the smallest unit in the building, which is segmented to perform the security status changeover (alert/non alert) and access user management in Security System. Multiple registrations of data points required for controlling and monitoring shall be being performed in one room. In this system, each room is registered in Access Controller, and then the controller performs access management control for those rooms. Consequently, when there are several card readers in a single room, access management control will be executed simultaneously for all the card readers in the room. In Figure 1 of “Room setting example”, security changeover can be made from either one of the 2 card readers. 2.2.23
Ac cess User Management
Access user management manages the user information that is used for accessing the buildings and rooms. It includes the operation of user registration, deletion, display based on various search conditions, setting the information and copying the attributes.
25 Guide Specifications for HVAC
User access operation becomes possible by distributing the user information created in the center to the remote. Up to 100,000 users shall be manageable. User information shall include access information and personal information as stated below. Access Information - Department ID - User No. - Card data - Card type - Registration status - Entry allowed room/group - Validity period - PIN - Close rights - 1st entry rights - Last exit rights - Pass back rights. Personal Information - Name - Nickname - Division (up to 2 divisions manageable) - Gender - Date of Birth - Age (calculated automatically from the date of birth) - Notes (up to 5 notes memorable)
2.2.24
Log Outpu t
Records and displays all the operating logs carried out by user in list. Items to be recorded and displayed are: -
Date (YYYY/MM/DD) at the time of operation Time (hours, minutes, and seconds) at the time of operation IP address of Client PC User ID
Operation type such as displaying, setting, printing, change of display, and canceling, button name to be clicked, dialog box name to be opened, contents of operation, contents of inputs and setting, device ID, point ID, point name, program name, and operation failed or not.
26 Guide Specifications for HVAC
Maximum storable logs are up to 1,000,000 logs. Operation logs shall be able to output in CSV file format and save in Client PC. 2.2.25.
Graphic
Displays the status of each facility targeted for management in graphic formats such as floor plan, cross section and schematic diagram. User is possible to perform the equipment's ON/OFF operation and setpoint change operation, and to display the trending graph and individual equipment schedule. The graphic displays present the status of each piece of equipment to be controlled in graphical forms such as floor plans, cross sections or schematic diagrams. Starts/stops equipment, changes setting, displays historical trend and individual equipment schedule. The displays can be enlarged and reduced at a desired magnification using SVG supporting magnification at browser. Up to 1,000 graphical displays can be assigned to the system. A dynamic element placed on a static element of equipment or floor indicates the status of a point by changing the color of the symbol or displaying the numerical value of analog/totalizer point. The dynamic element can also lead operators to another graphic display. Up to 200 dynamic elements can be displayed on a screen. The types of dynamic elements (points + screen transition) are shown below: -
Digital color change Digital shape change Analog numerical value display Animation Live wire display Graphic display selection Screen call Screen transition Picture scanner read display
User shall be able to modify or revise the graphic using Graphic Generator software which generates user-defined graphics and gives facility to edit the screen in the event of any change in the application environment such as partition or room name of the building. 2.2.26.
Group Lis t
Lists groups for the user to manage the Points easily. In addition to the system group list that is already listed, there is the user group list that can be set by the user optionally.
27 Guide Specifications for HVAC
It is possible to carry out batch ON/OFF command and batch settings change for each group. Servers shall have a capability of redundant system. 2.2.27.
Alarm
If any alarm occurs, the system automatically processes the alarm. The system notifies the alarm via buzzer sounds. BMS shall display the latest alarm and brink indicators. The operation of the latest alarm display, buzzer sounds and the Alarm Dashboard can be specified by the segregation pattern of the Segregation setting. Four types of alarm sounds are available for each alarm level. The following alarm events are available. - Alarm input - Unmatched command (Failure of start/stop of start/stop points, status - unmatched) - Analog high/low limit alarm - Sensor error - Trouble - Totalized value increase error - Control alarm (Power demand target value exceeded, etc.) - Component alarm (bus trouble, line status, error, remote unit no response) - Power demand alarm, power failure alarm, fire alarm Specify the following alarm level for each alarm point. - Emergency alarm - Major alarm - Moderate alarm - Minor alarm 2.2.27.1 Securit y Alarm Dashboard
Displays the information about change of status and alarm occurrence traditionally printed on a message printer. Only the required information can be extracted and displayed by narrowing search to all/alarm/operation setting/unacknowledged alarm records or searching information by a desired text string. Comments can also be entered if any. The accumulated data can be saved to the desired media (hard disk/USB memory, etc.) of a Client PC in a CSV format file. The data shall be displayed in PDF file to realize paper-less operations.
28 Guide Specifications for HVAC
The information displayed on the Alarm Dashboard is as follows: -
Point alarm Control alarm Device alarm Remote unit alarm Point operation Point change of status
When an alarm occurs in logged-in status, the alarm is notified by the buzzer sound, updated New Alarm display, and indicator blinking based on the alarm. Also, alarm occurrence and recovery will be recorded in Alarm Dashboard irrespective of login status. Buzzer sound has kinds of tones in each alarm level. Alarm is also given as an appropriate voice announcement when an alarm occurs. 2.2.27.2 Alarm Notifi catio n via E-mail or SMS
Alarms shall be notified to the PC or mobile terminal of building administrator through E-mail or Short Message Service. Alarm notification supports alarm confirmation operation in places far away from the client PC. 2.2.28.
Device/Remote Unit Status Monit ori ng
Based on the device/remote unit status monitoring function, the status of system servers, system controllers, and filed controllers is constantly monitored. Whenever a trouble is found, and alarm is notified with the buzzer sound, and so on. 2.2.29.
Report
Measured values and totalized values are displayed on the screen, and the daily report of electricity and air-conditioning operations are prepared. User shall be able to output daily report either automatically or manually in PDF format (print image) which realize paper-less operation. 2.2.29.1. Daily Report
Daily reports for the last 40 days including the current day can be displayed and printed manually. Daily report displayed on the screen can be output in CSV format as well. Printable data are the following 3 data. - Hourly report data contains 1-minute values totalized for 1 hour (totalized value) OR
29 Guide Specifications for HVAC
selected value among; max./min./average value of 1-minute values for 1 hour and on-the-hour value (measured value) - Daily report data contains 1-hour values totalized for 1 day (for the current day and for previous day) and load factor (totalized value only) AND max., min., av., and reading values of 1-hour values for 1 day. (Specify the values necessary to print.) - Monthly report data contains 1-day value totalized for 1 month (to the current day of the month from the following day of the previous month, to the current day of the previous month from the following day of the two months previous) and load factor (totalized value only) AND max., min., and av. values of 1-day values for 1 month. (Specify the values necessary to print. Monthly report data is printed out after the daily report data is printed.) Monthly report can be output either automatically or manually in PDF format (print image). 2.2.29.2. Monthly Report
Monthly reports for the last 13 months including the current month can be displayed and printed manually at your convenience. Monthly report displayed on the screen can be output in CSV format as well. Printable data are following 3 data as a monthly report. - Daily report data contains 1-hour values totalized for 1 day and load factor (totalized value only) OR selected value among; max./min./average value of 1-hour values for 1 day. - Monthly report data contains 1-day values totalized for 1 month (for the current month and for the previous month) and load factor (totalized value only) AND max., min., and av. values of 1-day values for 1 month. (Specify the values necessary to print. Monthly report data is printed out after the daily report data is printed.) - Yearly report data contains 1-month values totalized for 1 year (to the current month of the year from the following month of the previous year, to the current month of the previous year from the following month of the two years previous) and load factor (totalized value only) AND max., min., and av. values of 1-month values for 1 year. (Specify the values necessary to print. Yearly report data is printed out after the monthly report data is printed.) Yearly report can be output either automatically or manually in P DF format (print image).
30 Guide Specifications for HVAC
2.2.29.3. Yearly Report
Yearly reports for the last 10 years including the current year can be displayed and printed manually at your convenience. Yearly report displayed on the screen can be output in CSV format as well. Printable data are the following 2 data as a yearly report. - Monthly report data contains 1-day values totalized for 1 month and load factor (totalized value only) OR selected value among; max./min./average value of 1-day values for 1 month. - Yearly report data contains 1-month values totalized for 1 year (for the current year and for the previous year) and load factor (totalized value only) AND max., min., and av. values of 1-month values for 1 year. (Specify the values necessary to print. Yearly report data is printed out after the monthly report data is printed.) 2.2.29.4. Edi table Report Form at
Report format is editable freely by users if required. User shall be able to change, add and delete ruled lines, and insert merged cell to match the requirement of each project. BMS shall switch the report format when locale is changed. 2.2.30.
Securit y Card Data Impor t
Provide the function that imports the security card data items in CSV format. -
User No. Card data User Name User Nickname 2 Divisions of organization Gender Birthday 5 Notes All room rights Rights pattern Rights index Rights index for area Rights index for room Close mode privilege
31 Guide Specifications for HVAC
2.2.31.
1st entry privilege Last exit privilege Passback privilege State of registration Start date of valid term End date of valid term Number of card issue Department ID
Securit y Card Data Expor t
Provide the function that exports the security card data items in CSV format. 2.2.32.
User No. Card data User Name User Nickname 2 Divisions of organization Gender Birthday 5 Notes All room rights Rights pattern Access rights index Access rights index for area Access rights index for room Access rights index for room name Close mode privilege 1st entry privilege Last exit privilege Passback privilege State of registration Start date of valid term End date of valid term Number of card issue Department ID Department Name
Personal Photo Image Impor t
Provide the function that imports the photo image of card user, and to display it in the screen. By checking the screen display, it is possible to
32 Guide Specifications for HVAC
confirm the identity of the card holder in case he or she loses the card, etc. The image data can be imported from the media on to the drive connected to the client PC in J PEG image. It is possible to specify the source folder for importing. that exports the security card data items in CSV format. 2.2.33.
Scop e Management
Scope management function is used while registering/changing/deleting or referring to records of the access user information for each department (or tenant). Management range and reference range will be restricted based on the category setup. In other words, administrator of each department (Tenant) can register, delete, refer to access history and perform occupant display, etc. towards only access users whose categories are the same as his or her own category. Accordingly, if log in is performed through the administrator ID and password, subsequent operation and screen display will be automatically restricted by judging the category of the administrator who logged in. 2.2.34.
Loc al Ant i-passback Contr ol
Provide the function of Local Anti-passback Control. This function is used to compare the Card Reader type (Entry Reader or Exit Reader) with occupancy status (IN when the entry reader verification is OK and OUT in case of exit reader verification is OK) and perform access management without any logical discrepancy. With this function, it is possible to prevent the unauthorized access such as "Card sharing" and "Unauthorized accompanying" and manage the occupancy more strictly. Local Anti-passback Control is the control made on a per-controller basis and it cannot perform logical judgment across rooms. To perform controls across multiple doors or rooms, use Global Anti-passback. 2.2.35.
Global Ant i-passback Contr ol
As a result of card reader operation, Global Anti-passback function allows the access if the card actually belongs to that particular zone and disallows the access if it belongs to other zones. In other words, it judges whether the correct individual is residing in the zone and carries out a proper access management without any logical discrepancy. With this function, it is possible to prevent the unauthorized access such as "Card sharing" and "Unauthorized accompanying" and manage the occupancy more strictly. Further, trouble such as system communication failure that affects this control may occur. By considering these cases, it is possible to set in advance, whether the flexibility or security should be given importance like “Allow all users at the time of trouble” or “Emphasize the security even at the time of trouble” in accordance with the operation
33 Guide Specifications for HVAC
level. 2.3.
SYSTEM INTEGRATION
2.3.1.
BACnet Confor mance
BMS and its components shall comply with BACnet IP as its communication protocol for open system integration. System servers shall be able to communicate with third-party BACnet devices. 2.3.2.
Lon Mark Confo rmanc e
BMS shall have the product conformance by LonMark International®. Advanced Building Controller communicates with DDCs using LonTalk protocol. 2.3.3.
Modbus
BMS shall be connectable through Modbus protocol. Equipment such as power meters, power monitoring systems, chillers or lighting systems using Modbus protocol can be monitored by the central BMS.