Basic Indicators Module Replacement System Specific Repair More Information
System Overview – Klystron Solenoid S21 PS Rack
CompactLogix PLC
One PLC per sector, up to eight power supplies Monitors interlocks for power supplies Provides interlock status to MKSU Does NOT control power supplies
• • • •
System Overview – Alcove PLC Alcove Rack 1
FlexLogix PLC
One PLC per MCOR crate and bulk power supply Interlocks the MCORs on bulk ps voltage and ground fault. Remote control for bulk and MCOR reset •
•
•
System Overview – Gallery PLC Gallery Rack
ControlLogix PLC
One PLC for up to 3 bulk power supplies Interlocks MCORs on bulk ps voltage and ground fault Interlocks Intermediate power supplies Remote control of bulk power supplies •
•
• •
System Overview – 6575 Mod PLC 6575 Modulator
CompactLogix PLC
Monitors interlocks and provides status to MKSU Controls modulator and various sub‐systems
• •
System Overview – SPEAR3 HVPS Control Enclosure
SLC 5/03 PLC
Monitors and provides interlocks to/from HVPS and Klystron Controls the HVPS
• •
System Overview – A‐line Bend PS SPANG PS
Monitors interlocks Controls the power supply
• •
SLC 5/03 PLC
Basic Indicators
Basic Indicators •
Processor (everything should be green) –
Run – solid green to be in RUN mode •
–
I/O – solid green means good modules • •
– –
– –
Otherwise put in RUN mode using key switch Otherwise look for absence of green OK LED on module Note that some modules do not have OK LED
Force – off, we do not use forces! RS232 – solid or flashing green, communicating with touch panel BAT – should be green, but generally is not critical OK – must be solid green! Any red means we need to go online to see what the problem is. A power cycle will probably fix it, but we will lose any information on what caused the fault.
Basic Indicators •
Power Supply –
•
OK – green
Network Module –
Link – green, good link to switch
–
Net – flashing green, Ethernet traffic
–
OK – green, module is good
–
Module on the ControlLogix
–
Card on the FlexLogix
–
Built in on the CompactLogix
Module Replacement •
Processor –
May need to reprogram, unless preprogrammed spare available •
•
I/O Module –
•
Currently only Gallery and Alcove PLCs
Direct replacement, no further action needed
Ethernet Module –
May need to configure, unless pre‐configured spare is available •
Currently only Gallery and Alcove PLCs
System Specific Repair •
Klystron Solenoid – –
•
Alcove PLC – –
–
•
Spare chassis in test stand Processor will need reprogramming/configuring Spare chassis in B127 Install appropriate Ethernet card into the processor before using All programs are identical
Gallery PLC – –
–
Spare Chassis in R127 Install appropriate processor and Ethernet module, if replacing chassis All programs are unique
System Specific Repair •
•
•
6575 Modulator PLC –
Identify and replace problematic module
–
Spares not yet available, parts are available if needed
–
All programs will (hopefully) be identical
SPEAR3 HVPS PLC –
Identify and replace the problematic module
–
Spares located in B127
SPANG Bend PS –
Identify and replace the problematic module
–
Spares unknown
More Information • •
Do not hesitate to call Engineering on PLC problems How‐To Documentation –