08 Distance Calculation Sheet
Home
08 Distance Calculation Sheet
okok...
Author:
mahesh
25 downloads
499 Views
44KB Size
Report
DOWNLOAD .PDF
Recommend Documents
Distance Calculation
Distance CalculationFull description
Distance Relay Setting calculation
sample relay setting calculationFull description
08-Presentation Distance Protection
Calculation Sheet
Str calculation
Calculation Sheet
Full description
CSC Distance Relays -Sample Calculation
Sample calculation for Distance relay setting for 132 KV lines
Chimney Calculation Sheet
design
CONVEYOR CALCULATION SHEET draft.xls
Steel Structure Calculation Sheet
SteelFull description
Sump Pit Calculation Sheet
My AECOM PHE Calculation
Transformer Impedance Calculation Sheet
Transformer Impedance Calculation SheetFull description
Trunnion Calculation Sheet[1]
Full description
Pump Sizing Calculation Sheet
Full description
Reactor Sizing (Calculation Sheet)
Reactor sizingFull description
Best Tank Calculation Sheet
tank calculation
Crack Width calculation sheet
crack width calculation for water retaining structures
Scaffold Materials Calculation Sheet
Scaffold Materials Calculation SheetFull description
Best Tank Calculation Sheet
tank calculationFull description
08 - Sheet Metal Work
08 Sheet Metal Work
Classic reference for the home workshop. Still valid today.
08 - Sheet Metal Work
Example Distance Distance ENU
Example Distance Distance ENU
Example Distance Distance ENU
Example Distance Distance ENU
Example Distance Distance ENU
Example Distance Distance ENU
Setting Calculation for Distance Protection Scheme Name os S/S Feeder Name Type of Circuit Type of Conductor
132KV Bhadsahapur 132KV Bhadsahapur - Samayapur Single Circuit Zebra
SYSTEM DATA CT
Primary Secondary
800 Amps 1 Amps
PT
Primary Secondary
132 K Volts 110 Volts
CTR PTR CTR/PTR
800 1200 0.666666667
Positive Sequence Impedance: Ohms/KM/Phase/Ckt: 0.02936+j 0.30716 Zero Sequence Impedance: Ohms/KM/Phase/Ckt: 0.27566+j 1.0715 Parallel Line Mutal Impedance: 0.22806+j 0.6221 Positive Sequence Resistance:R Ohm/Ph/KM R1 Primary 0.02936 Positive Sequence Reactance:X Ohm/Ph/KM X1 Primary 0.30716 Zero Sequence Resistance:R Ohm/Ph/KM Ro Primary 0.27566 Zero Sequence Reactance:X Ohm/Ph/KM Xo Primary 1.0715 Parallel Line Mutual Resistance:R Ohm/Ph/KM Rom Primary 0.22806 Parallel Line Mutual Reactance:X Ohm/Ph/KM Xom Primary 0.6221 Arc Resistance:
10
Ohms
(assumed)
Tower Foot R
15
Ohms
(assumed)
Line Angle
84.53 degree
Length of Protected Line
50 KM
Length of Adjacent Shortest Line
75 KM
Length of Adjacent Longest Line
100 KM
1
Siemens Ltd.,PTD-EA,Gurgaon
D(Z1) D(Z1B) D(Z2) D(Z3) D(Z4)
80 120 100 1.2 25
% of Protected line % of Zone-1 % of Protected line + (Protected Line + Longest Second Line) % of Zone-1
Distance D1 D1B D2 D3 D4
Zone 1 Zone 1B Zone 2 Zone 3 Zone 4
40 48 87.5 180 10
Reactance X1 X1B X2 X3 X4
Zone 1 Zone 1B Zone 2 Zone 3 Zone 4
Resistance R1 R1B R2 R3 R4 Impedance Z1 Z1B Z2 Z3 Z4
KM KM KM KM KM
Forward Forward Forward Forward Reverse
8.191 9.829 17.918 36.859 2.048
Ohms/Ph Ohms/Ph Ohms/Ph Ohms/Ph Ohms/Ph
Forward Forward Forward Forward Reverse
Zone 1 Zone 1B Zone 2 Zone 3 Zone 4
0.783 0.940 1.713 3.523 0.196
Ohms/Ph Ohms/Ph Ohms/Ph Ohms/Ph Ohms/Ph
Forward Forward Forward Forward Reverse
Zone 1 Zone 1B Zone 2 Zone 3 Zone 4
8.228 9.874 17.999 37.027 2.057
Ohms/Ph Ohms/Ph Ohms/Ph Ohms/Ph Ohms/Ph
Forward Forward Forward Forward Reverse
50
% of Adjacent shortest Line
Phase - Phase R1 R1B R2 R3 R4
Settings to be done in Digsi Address 110 112 113 121
Description
Set Value Device Configuation Trip Mode 21 Phase Distance 21 Ground Distance 85-21 Pilot Protn
1/3 Pole Quadrilateral Quadrilateral PUTT(Z1B)
201 203 204 205 206
Power System Data1 CT Star Point Rated Primary Voltage Rated Secondary Voltage Rated Primary Current Rated Secondary Current
Toward Line 400 KV 110 V 1000 A 1A
1105 1110 1111 1116
Power System Data 2 Line Angle x- line Reactance(secondary) Line Length RG/RL
84.53 10.23866667 50 2.77
2
Siemens Ltd.,PTD-EA,Gurgaon
1117 1126 1127
XG/XL RM/RL XM/XL
-0.08 2.589 0.675
21 Distance - Quadrilateral 1301 1302 1303 1304 1351 1352 1353 1354 1311 1312 1313 1314 1321 1322 1323 1324 1331 1332 1333 1334
Operating Mode Z1 R Ph-Ph Z1 X Z1 R G Z1 Operating Mode Z1B R Ph-Ph Z1B X Z1B R G Z1B Operating Mode Z2 R Ph-Ph Z2 X Z2 R G Z2 Operating Mode Z3 R Ph-Ph Z3 X Z3 R G Z3 Operating Mode Z4 R Ph-Ph Z4 X Z4 R G Z4
Forward 4.116 8.191 17.450 Forward 4.273 9.829 17.606 Forward 5.046 17.918 18.379 Forward 6.857 36.859 20.190 Reverse 3.529 2.048 16.862
3
Siemens Ltd.,PTD-EA,Gurgaon
stance Protection Scheme
Earth Compensation Factor: Ko = Angle =
0.308560003 #NAME?
6.666666667 Ohms
Secondary
10 Ohms
Secondary
4
Siemens Ltd.,PTD-EA,Gurgaon
% of Adjacent shortest Line
Phase - Phase 4.116266667 4.272853333 5.046 6.856533333 3.529066667
Phase - Earth R1e R1Be R2e R3e R4e
17.450 17.606 18.379 20.190 16.862
5
Siemens Ltd.,PTD-EA,Gurgaon
6
Siemens Ltd.,PTD-EA,Gurgaon
×
Report "08 Distance Calculation Sheet"
Your name
Email
Reason
-Select Reason-
Pornographic
Defamatory
Illegal/Unlawful
Spam
Other Terms Of Service Violation
File a copyright complaint
Description
×
Sign In
Email
Password
Remember me
Forgot password?
Sign In
Our partners will collect data and use cookies for ad personalization and measurement.
Learn how we and our ad partner Google, collect and use data
.
Agree & close